Turagh Limited Tharmal Report
Turagh Limited Tharmal Report
CONSULTANT:
SAFeTY SOLUTIONSBangladesh
House # 25, Road # 5, Arambagh A/R, Mirpur,Section-07 Dhaka-1216.
E-mail:
Call: +8801722-245473, +8801912524727
SAFeTY
SOLUTIONSBangladesh DON’T LEARN SAFETY WITH ACCIDENT
Table of Contents
01 Instrument Details 02
02 Thermographer details 02
03 Inspection Summary 02
Thermal of analysis
06 06-63
Thermographar details
INSPECTION SUMMARY
For the equipment inspected, we have recorded some Thermographic(s) and/ or daylight photographs document conditions
found during our inspection. These thermograms and/ or photographs appear on the image Pages found at the end of this
report. As a reference, each Image Page contains Evaluation Priority Ratings. Subjective Evaluation Ratings are based upon
the Qualified Assistant’s opinion of the subject item’s importance to the safe and condition operation of the facility.
American National Standards Institute (ANS) has approved a standard for international Electrical Testing Association
(NETA) for performing different testing in the Electrical system named as “STANDARD FOR ACCEPTANCE TESTING
SPECIFICATIONS FOR ELECTRICAL POWER AND SYSTEMS”. Based on Acceptance Testing Specification (ATS)
2009, we have below table to identify hot spots and consequent actions for hot spots.
As per NETA Maintenance Testing Specifications for Electrical Equipment (Tablet: 100.18 )
Delta T between Similar Delta T Over ambient
Priority Components Under Similar Recommend Action
Air Temperature
Load
00 1 to 3 °C 1 to 10°C Possible Deficiency Warrants
Investigation
01 4 to 15 °C 11 to 20°C Indicates Probable Deficiency Repair as
time Permits
02 --- 21 to 40°C Monitor Until Corrective Measures Can
be Accomplished
03 > 15 °C >40°C Major Disarepancey; Repair Immediately
Summary of findings
IR_09109.IS2
IR_09120.IS2
IR_09123.IS2
IR_09124.IS2
IR_09130.IS2
IR_09131.IS2
IR_09133.IS2
IR_09136.IS2
Category-00 Minor IR_09137.IS2 16 6months
IR_09138.IS2
IR_09139.IS2
IR_09140.IS2
IR_09141.IS2
IR_09144.IS2
IR_09149.IS2
IR_09150.IS2
Inspected By:
Inspection Date: 11/22/2020 10:22:46 Location Sub-Station
AM
Equipment Transformer Equipment Name: Transformer
Ambient Air Temp: 30.1°C Wind Speed
Load (%) Adequate Max Rated Load: 630KVA
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 41.3°C
Image Range 30.1°C to 49.9°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:22:46 AM
Calibration Range -20.0°C to 80.0°C
Image Info
Transmission 1.00
Average Temperature 32.3°C
Image Range 30.1°C to 49.9°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:23:48 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 10:26:18 Location Sub-station
AM
Equipment Control panel Equipment Name: Cooling power control
panel
Ambient Air Temp: 32.0°C Wind Speed
Image Info
Transmission 1.00
Average Temperature 36.3°C
Image Range 32.0°C to 51.7°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:26:18 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 10:29:41 Location Sub-station
AM
Equipment SDB Equipment Name: SDB-01
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 40A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 30.7°C
Image Range 29.6°C to 33.9°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:29:41 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 10:30:53 Location Sub-station
AM
Equipment LT Equipment Name: LT-02-UP
Ambient Air Temp: 32.9°C Wind Speed
Load (%) Adequate Max Rated Load: 1000A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 40.5°C
Image Range 32.9°C to 50.4°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:30:53 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 10:31:22 Location Sub-station
AM
Equipment LT Equipment Name: LT-2-Middle
Ambient Air Temp: 30.1°C Wind Speed
Load (%) Adequate Max Rated Load: 1000A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 38.4°C
Image Range 30.1°C to 49.4°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:31:22 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 10:31:48 Location Sub-station
AM
Equipment LT Equipment Name: LT-2 Down
Ambient Air Temp: 29.0°C Wind Speed
Load (%) Adequate Max Rated Load: 1000A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 33.9°C
Image Range 29.0°C to 48.2°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:31:48 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 10:33:59 Location Sub-station
AM
Equipment PFI Equipment Name: PFI-1-UP
Ambient Air Temp: 29.7°C Wind Speed
Load (%) Adequate Max Rated Load: 630A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 34.7°C
Image Range 29.7°C to 48.6°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:33:59 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 10:34:11 Location Sub-station
AM
Equipment PFI Equipment Name: PFI-1-Middle
Ambient Air Temp: 31.0°C Wind Speed
Load (%) Adequate Max Rated Load: 630A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 35.7°C
Image Range 31.0°C to 49.8°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:34:11 AM
Calibration Range -20.0°C to 250.0°C
Inspected By:
Inspection Date: 11/22/2020 10:34:57 Location Sub-station
AM
Equipment PFI Equipment Name: PFI-1-DOWN
Ambient Air Temp: 26.3°C Wind Speed
Load (%) Adequate Max Rated Load: 630A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 31.1°C
Image Range 26.3°C to 50.1°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:34:57 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 10:36:51 Location Sub-station
AM
Equipment COS Equipment Name: COS-1-UP
Ambient Air Temp: Wind Speed
28.7°C
Load (%) Adequate Max Rated Load: 1000A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 33.3°C
Image Range 28.7°C to 48.0°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:36:51 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 10:37:14 Location Sub-station
AM
Equipment COS Equipment Name: COS-1-Middle
Ambient Air Temp: 30.0°C Wind Speed
Load (%) Adequate Max Rated Load: 1000A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 35.9°C
Image Range 30.0°C to 48.6°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:37:14 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 10:37:21 Location Sub-station
AM
Equipment COS Equipment Name: COS-1-down
Ambient Air Temp: 28.9°C Wind Speed
Load (%) Adequate Max Rated Load: 1000A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 34.5°C
Image Range 28.9°C to 46.4°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:37:21 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 10:42:13 Location Sub-station
AM
Equipment PFI Equipment Name: PFI-2
Ambient Air Temp: 29.9°C Wind Speed
Load (%) Adequate Max Rated Load: 800A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 31.1°C
Image Range 29.9°C to 32.6°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:42:13 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 10:43:26 Location Sub-station
AM
Equipment LT Equipment Name: LT-1-left
Ambient Air Temp: 30.5°C Wind Speed
Load (%) Adequate Max Rated Load: 2000ACB
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 31.7°C
Image Range 30.5°C to 45.0°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:43:26 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 10:44:23 Location Sub-station
AM
Equipment LT Equipment Name: LT-1-middel
Ambient Air Temp: 30.6°C Wind Speed
Load (%) Adequate Max Rated Load: 2000ACB
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 33.3°C
Image Range 30.6°C to 46.6°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:44:23 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 10:44:48 Location Sub-station
AM
Equipment LT Equipment Name: LT-1-Right up
Ambient Air Temp: 30.2°C Wind Speed
Load (%) Adequate Max Rated Load: 2000ACB
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 33.0°C
Image Range 30.2°C to 36.7°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:44:48 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 10:44:59 Location Sub-station
AM
Equipment LT Equipment Name: LT-1-Right Down
Ambient Air Temp: 29.9°C Wind Speed
Load (%) Adequate Max Rated Load: 2000A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 32.6°C
Image Range 29.9°C to 37.3°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:44:59 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 10:48:20 Location Sub-station
AM
Equipment COS Equipment Name: COS-2
Ambient Air Temp: 29.9°C Wind Speed
Load (%) Adequate Max Rated Load: 800A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 32.9°C
Image Range 29.9°C to 40.9°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:48:20 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 10:58:24 Location Sub-station
AM
Equipment Generator Equipment Name: Gas Generator-1
Ambient Air Temp: 29.5°C Wind Speed
Load (%) Adequate Max Rated Load: 2000A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 32.1°C
Image Range 29.5°C to 41.1°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:58:24 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 10:59:19 AM Location Sub-station
Image Info
Transmission 1.00
Average Temperature 37.5°C
Image Range 31.0°C to 48.1°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 10:59:19 AM
Calibration Range -20.0°C to 80.0°C
Image Info
Transmission 1.00
Average Temperature 36.6°C
Image Range 30.5°C to 49.2°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:01:55 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:03:25 Location Generator Room
AM
Equipment SDB Equipment Name: SDB-01
Ambient Air Temp: 31.5°C Wind Speed
Load (%) Adequate Max Rated Load: 50A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 33.5°C
Image Range 31.5°C to 49.5°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:03:25 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:07:47 Location 1st Floor
AM
Equipment DB Equipment Name: DB-9
Ambient Air Temp: 29.2°C Wind Speed
Load (%) Adequate Max Rated Load: 250A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 31.2°C
Image Range 29.2°C to 36.8°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:07:47 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:07:57 Location 1st Floor
AM
Equipment SDB Equipment Name: SDB-2
Ambient Air Temp: 27.6°C Wind Speed
Load (%) Adequate Max Rated Load: 32A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 29.6°C
Image Range 27.6°C to 32.3°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:07:57 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:10:40 Location 1st Floor Finishing
AM
Equipment DB Equipment Name: DB-5
Ambient Air Temp: 31.7°C Wind Speed
Load (%) Adequate Max Rated Load: 160A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 37.5°C
Image Range 31.7°C to 49.3°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:10:40 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:12:00 Location 1st Floor
AM
Equipment DB Equipment Name: DB-7
Ambient Air Temp: 29.5°C Wind Speed
Load (%) Adequate Max Rated Load: 63A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 31.6°C
Image Range 29.5°C to 39.5°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:12:00 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:14:28 Location 2nd Floor Sewing
AM
Equipment DB Equipment Name: DB-6
Ambient Air Temp: 30.2°C Wind Speed
Load (%) Adequate Max Rated Load: 63A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 32.6°C
Image Range 30.2°C to 42.6°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:14:28 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:14:54 Location 2nd Floor Sewing
AM
Equipment DB Equipment Name: DB-Ex fan
Ambient Air Temp: 29.4°C Wind Speed
Load (%) Adequate Max Rated Load: 63A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 31.8°C
Image Range 29.4°C to 42.5°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:14:54 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:17:49 Location 2nd Floor Office
AM
Equipment SDB Equipment Name: SDB-3
Ambient Air Temp: 29.3°C Wind Speed
Load (%) Adequate Max Rated Load: 63A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 31.4°C
Image Range 29.3°C to 34.4°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:17:49 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:20:42 Location 3rd Floor Sample
AM
Equipment SDB Equipment Name: SDB-4
Ambient Air Temp: 28.3°C Wind Speed
Load (%) Adequate Max Rated Load: 63A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 29.3°C
Image Range 28.3°C to 31.9°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:20:42 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:23:13 Location 4th Floor Accounts
AM
Equipment SDB Equipment Name: SDB-5
Ambient Air Temp: 29.0°C Wind Speed
Load (%) Adequate Max Rated Load: 63A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 30.7°C
Image Range 29.0°C to 35.3°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:23:13 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:26:20 Location 5th Floor Mersentizzing
AM
Equipment SDB Equipment Name: SDB-6
Ambient Air Temp: 29.3°C Wind Speed
Load (%) Adequate Max Rated Load: 63A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 31.1°C
Image Range 29.3°C to 38.4°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:26:20 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:28:50 Location 6th Floor
AM
Equipment SDB Equipment Name: SDB -7
Ambient Air Temp: 28.1°C Wind Speed
Load (%) Adequate Max Rated Load: 100A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 29.6°C
Image Range 28.1°C to 34.5°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:28:50 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:32:08 Location 7th Floor
AM
Equipment SDB Equipment Name: SDB-8
Ambient Air Temp: 27.5°C Wind Speed
Load (%) Adequate Max Rated Load: 32A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 29.3°C
Image Range 27.5°C to 36.5°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:32:08 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:38:42 Location GF Dyeing
AM
Equipment SDB Equipment Name: SDB-Lighting
Ambient Air Temp: 32.9°C Wind Speed
Load (%) Adequate Max Rated Load: 32A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 34.6°C
Image Range 32.9°C to 38.2°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:38:42 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:38:53 Location GF Dyeing
AM
Equipment DB Equipment Name: DB-1
Ambient Air Temp: 34.5°C Wind Speed
Load (%) Adequate Max Rated Load: 63A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 38.1°C
Image Range 34.5°C to 52.6°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:38:53 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:41:29 Location GF Dyeing
AM
Equipment DB Equipment Name: DB-2
Ambient Air Temp: 31.2°C Wind Speed
Load (%) Adequate Max Rated Load: 125A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 34.6°C
Image Range 32.8°C to 40.5°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:41:29 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:43:30 Location GF Dyeing
AM
Equipment Equipment Name: DB-3
DB
Ambient Air Temp: 31.2°C Wind Speed
Load (%) Adequate Max Rated Load: 100A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 33.0°C
Image Range 31.2°C to 41.4°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:43:30 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:49:02 Location GF Dyeing
AM
Equipment Control board Equipment Name: Ex Fan Control board
Ambient Air Temp: 30.0°C Wind Speed
Load (%) Adequate Max Rated Load: 63A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 32.3°C
Image Range 30.0°C to 40.6°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:49:02 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:54:07 Location GF Boiler Room
AM
Equipment SDB Equipment Name: SDB-2
Ambient Air Temp: 35.9°C Wind Speed
Load (%) Adequate Max Rated Load: 40A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 39.0°C
Image Range 35.9°C to 51.0°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:54:07 AM
Calibration Range -20.0°C to 80.0°C
Image Info
Transmission 1.00
Average Temperature 30.4°C
Image Range 28.8°C to 44.2°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:55:26 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:55:47 Location ETP GF
AM
Equipment DB Equipment Name: DB-7 Left
Ambient Air Temp: 27.6°C Wind Speed
Load (%) Adequate Max Rated Load: 1000A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 30.0°C
Image Range 27.6°C to 32.8°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:55:47 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 11:59:37 Location GF Boiler Room
AM
Equipment DB Equipment Name: New Boiler DB
Ambient Air Temp: 30.9°C Wind Speed
Load (%) Adequate Max Rated Load: 100A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 32.1°C
Image Range 30.9°C to 36.8°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 11:59:37 AM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 12:02:23 Location ETP/GF
PM
Equipment SDB Equipment Name: SDB-1-Left
Ambient Air Temp: 30.6°C Wind Speed
Load (%) Adequate Max Rated Load: 400A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 32.4°C
Image Range 30.6°C to 37.2°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 12:02:23 PM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 12:02:39 Location ETP/GF
PM
Equipment SDB Equipment Name: SDB-1-Middle
Ambient Air Temp: 31.4°C Wind Speed
Load (%) Adequate Max Rated Load: 400A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 34.4°C
Image Range 31.4°C to 50.2°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 12:02:39 PM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 12:03:14 Location ETP/GF
PM
Equipment SDB Equipment Name: SDB-1-Right
Ambient Air Temp: 30.9° Wind Speed
Load (%) Adequate Max Rated Load: 400A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 33.2°C
Image Range 30.9°C to 46.9°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 12:03:14 PM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 12:04:53 Location ETP/GF
PM
Equipment control board Equipment Name: EX-Fan control board
Ambient Air Temp: 29.7°C Wind Speed
Load (%) Adequate Max Rated Load: 32A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 32.8°C
Image Range 29.7°C to 48.4°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 12:04:53 PM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 12:07:23 Location ETP/GF
PM
Equipment SDB Equipment Name: EX-Fan SDB
Ambient Air Temp: 27.7°C Wind Speed
Load (%) Adequate Max Rated Load: 25A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 30.0°C
Image Range 27.7°C to 47.8°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 12:07:23 PM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 12:16:43 Location Canteen /GF
PM
Equipment DB Equipment Name: Canteen DB
Ambient Air Temp: 28.7°C Wind Speed
Load (%) Adequate Max Rated Load: 25A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 30.2°C
Image Range 28.7°C to 34.9°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 12:16:43 PM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 12:22:12 Location Central store/1st
PM
Equipment SDB Equipment Name: SDB-3
Ambient Air Temp: 28.8°C Wind Speed
Load (%) Adequate Max Rated Load: 63A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 30.5°C
Image Range 28.8°C to 36.8°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 12:22:12 PM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 12:23:27 Location Central store/1st
PM
Equipment DB Equipment Name: DB-10
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 1000A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 31.6°C
Image Range 29.6°C to 35.2°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 12:23:27 PM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 12:42:15 Location Sewing/3th floor
PM
Equipment SDB Equipment Name: SDB-3
Ambient Air Temp: 29.4°C Wind Speed
Load (%) Adequate Max Rated Load: 32A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 30.6°C
Image Range 29.4°C to 36.4°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 12:42:15 PM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 12:45:25 Location Sewing/3th floor
PM
Equipment control board Equipment Name: EX-Fan control board
Ambient Air Temp: 30.7°C Wind Speed
Load (%) Adequate Max Rated Load: 40A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 32.1°C
Image Range 30.7°C to 41.4°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 12:45:25 PM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 12:47:33 Location Sewing/4th floor
PM
Equipment control board Equipment Name: EX-Fan control board
Ambient Air Temp: 31.2°C Wind Speed
Load (%) Adequate Max Rated Load: 63A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 33.0°C
Image Range 31.2°C to 46.8°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 12:47:33 PM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 12:49:29 Location Cutting/5th floor
PM
Equipment control board Equipment Name: EX-Fan control board
Ambient Air Temp: 30.5°C Wind Speed
Load (%) Adequate Max Rated Load: 63A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 31.7°C
Image Range 30.5°C to 41.2°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 12:49:29 PM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 12:51:43 Location Cutting/5th floor
PM
Equipment SDB Equipment Name: SDB
Ambient Air Temp: 28.5°C Wind Speed
Load (%) Adequate Max Rated Load: 16A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 29.5°C
Image Range 28.5°C to 30.7°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 12:51:43 PM
Calibration Range -20.0°C to 80.0°C
Inspected By:
Inspection Date: 11/22/2020 12:54:37 Location New Cutting/5th floor
PM
Equipment control board Equipment Name: EX-Fan control board
Ambient Air Temp: 28.3°C Wind Speed
Load (%) Adequate Max Rated Load: 63A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562
Image Info
Transmission 1.00
Average Temperature 30.2°C
Image Range 28.3°C to 44.4°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 11/22/2020 12:54:37 PM
Calibration Range -20.0°C to 80.0°C