You are on page 1of 1

6.

SETTING PROFI

6.1.2e SETTING TEMPERATURE OF COLD JUNCTION T/C

C. J . TEM. Setting temperature of


  cold junction

INPUTS CLEAR READ. /S 23. 0 - range 0…99°C with compensation box


- DEF = 23°C
CHANNE. CONFIG. TYPE
OUTPUT. RTC MODE
SERVIC. EXT. IN. CONECT.
KEYS C. J . TEM.

6.1.2f ZERO OFFSET OF THE MEASUREMENT RANGE RTD OHM

AD. RES. Offset of the beginning of


  the measuring range

INPUTS CLEAR READ. /S 0. 0 - in cases when it is necessary to offset the


beginning of the range by certain value, e.g.
CHANNE. CONFIG. TYPE while using sensor in measuring head
- entered directly in Ohm (0…9999)
OUTPUT. RTC MODE - DEF = 0
SERVIC. EXT. IN. CONECT.
KEYS AD. RES.
LEADS

6.1.2g COMPENSATION OF 2-WIRE CONDUCT RTD OHM

LEADS Compensation of
  2-wire conduct

INPUTS CLEAR READ. /S YES - for measurement accuracy it is necessary to


perform compensation of conduct always in
CHANNE. CONFIG. TYPE case of 2-wire connection
- prior confirmation of the displayed prompt “ YES“
OUTPUT. RTC MODE it is necessary to substitute the sensor at the
end of the conduct by a short-circuit
SERVIC. EXT. IN. CONECT. - DEF = 0
KEYS AD . RES.
LEADS

50 | INSTRUCTIONS FOR USE OM 402UNI

You might also like