Professional Documents
Culture Documents
a r t i c l e i n f o a b s t r a c t
Article history: Although there have been multiple studies on window thermal properties in energy-efficient fenestration
Received 19 April 2012 design, the effects of building geometry factors have been studied much less. The study presented in this
Received in revised form 9 October 2012 paper evaluated the role of geometry factors, such as window orientation, window to wall ratio, and room
Accepted 20 October 2012
width to depth ratio, on building energy performance in a commercial office building. A series of energy
simulations were performed for six climate zones in the United States using a model of a room in a typical
Keywords:
office building created in Design Builder, an energy analysis program, to evaluate total annual energy
Energy-efficient fenestration
consumption. The simulation results were analyzed to find the combination of parameters yielding the
Energy savings
Building energy performance
lowest energy consumption and to define potential energy savings for office buildings located in various
Geometry factors climate zones. The study showed that geometry factors affect energy consumption significantly in hot
Energy simulations climates (Zones 2 and 3) and cold climates (Zones 6 and 7) but only marginally in temperate climates
(Zones 4 and 5). Energy savings were on average 3% and 6% reaching a maximum of 10% and 14% in hot
climates (Zones 2 and 3) and 1% in temperate and cold climates (Zones 4–7).
© 2012 Elsevier B.V. All rights reserved.
0378-7788/$ – see front matter © 2012 Elsevier B.V. All rights reserved.
http://dx.doi.org/10.1016/j.enbuild.2012.10.035
I. Susorova et al. / Energy and Buildings 57 (2013) 6–13 7
Table 1
Minimum thermal properties of a building envelope.
Heat transfer coefficient of steel-framed 0.70 0.48 0.36 0.36 0.36 0.36
exterior wall assembly (W/m2 K)
Heat transfer coefficient of fixed fenestration 4.25 3.68 3.13 3.13 3.13 2.56
(W/m2 K)a
Solar heat gain coefficient 0.25 0.25 0.40 0.40 0.40 0.45
Window to wall ratio 40%
a
Heat transfer coefficient of aluminum frame is 4.70 W/m2 K.
8 I. Susorova et al. / Energy and Buildings 57 (2013) 6–13
Table 3
Total annual energy consumption in an office building in climate Zone 2.
The first evaluated parameter was window orientation; north, area exposed to heat transfer through the facade and the amount of
northeast, east, southeast, south, southwest, west, and northwest received daylight; a room’s depth determines the distance of day-
orientations were tested. Another tested parameter was window light penetration. A wide and shallow room has a good daylight
to wall ratio (WWR) which shows what percentage of an exte- level and light distribution but high heat gain and loss through the
rior wall area is occupied by glazing material. WWR is important large area of its exterior wall. In a narrow and deep room, a daylight
as it affects the amount of available daylight and heat transfer level is lower but heat transfer through the small area of its exterior
between the exterior and interior of a building. Seven WWR val- wall is much lower as well. The office room model tested four val-
ues were tested for the constant window width of 6 m: 20% (0.55 m ues of W/D ratio, 1:1, 1:1.5, 1:2, and 1:2.5, for the fixed room width
high window located 0.75 m above the floor level), 30% (0.8 m of 6 m, which corresponded to room depths of 6 m, 9 m, 12 m, and
high window located 0.75 m above the floor level), 40% (1.1 m 15 m respectively. The selected room depth values were based on
high window located 0.75 m above the floor level), 50% (1.4 m high typical lease spans in office buildings [4].
window located 0.75 m above the floor level), 60% (1.6 m high win-
dow located 0.75 m above the floor level), 70% (1.9 m high window 3. Results and discussion
located 0.15 m above the floor level), and 80% (2.2 m high window
located 0.15 m above the floor level). The maximum recommended It total, 1344 annual energy simulations were performed for 6
value of WWR in commercial buildings according to the ASHRAE climate zones, 8 window orientations, 7 window to wall ratios, and
90.1 Energy Standard is 40% for all climate zones; this value is used 4 width to depth ratios. The simulations modeled lighting, heating,
as the baseline case [9]. Any WWR greater than 40% is allowed cooling, auxiliary (fans and pumps), hot water, and total energy
only if a trade-off is provided showing improvements in energy consumption per year per square meter of office space.
performance over the baseline case. The energy simulations for climate Zones 2 (Houston, TX)
The last parameter evaluated by this study was the ratio of room (Table 3 and Fig. 1) and 3 (Los Angeles, CA) (Fig. 2) demonstrated
width to depth (W/D ratio), an important room geometry parame- that total building energy consumption in a shallow room (room
ter which affects the interrelation between adiabatic interior walls depth 6 m) lowers marginally when the window to wall ratio is
and exterior walls and the distribution of daylight though a room’s increased from 20% to 40% and grows when the window to wall
interior space. The width of a room’s exterior wall determines the ratio is increased from 40% to 80%. Total consumption for other
Fig. 1. Total energy consumption in climate Zone 2 for (a) south and (b) west window orientations.
I. Susorova et al. / Energy and Buildings 57 (2013) 6–13 9
Fig. 2. Total energy consumption in climate Zone 3 for (a) south and (b) west window orientations.
Table 4
Total annual energy consumption in an office building in climate Zone 6.
room depths (9 m, 12 m, and 15 m) steadily lowers as the window to orientations except for south orientation where the effect is only
wall ratio is increased from 20% to 80%. In contrast, in climate Zones marginal. The growth of energy consumption with the increase of
6 (Minneapolis, MN) (Table 4 and Fig. 3) and 7 (Duluth, MN) (Fig. 4), the window to wall ratio is especially noticeable in shallow rooms
total building energy consumption grows steadily and significantly but becomes less significant in deep rooms. In Zones 2, 3, 6, and
as the window to wall ratio is increased for all room depths and 7, for all values of the window to wall ratio, energy consumption
Fig. 3. Total energy consumption in climate Zone 6 for (a) south and (b) west window orientations.
10 I. Susorova et al. / Energy and Buildings 57 (2013) 6–13
Fig. 4. Total energy consumption in climate Zone 7 for (a) south and (b) west window orientations.
Table 5
Total annual energy consumption in an office building in climate Zone 4.
lowers with the increase in room depth from 6 m to 15 m and is affected by varying values for window to wall ratios, room depths
the lowest for south orientation. In climate Zones 4 (Seattle, WA) and orientations.
(Table 5 and Fig. 5) and 5 (Chicago, IL) (Fig. 6), the change in build- In general, the highest reduction in total energy consumption in
ing energy consumption is insignificant and does not appear to be comparison with the baseline case was achieved with the window
Fig. 5. Total energy consumption in climate Zone 4 for (a) south and (b) west window orientations.
I. Susorova et al. / Energy and Buildings 57 (2013) 6–13 11
Fig. 6. Total energy consumption in climate Zone 5 for (a) south and (b) west window orientations.
to wall ratios of 30% (Zone 2), 40% (Zones 3 and 4), and 80% (Zones windows in shallow rooms in which higher heat transfer through
5–7); room depths of 6 m (Zones 2–4) and 15 m (Zones 5–7); and exterior surface is a predominant load on energy consumption. In
north (Zones 2–4 and 7) and northwest (Zones 5 and 6) orientations. such climates, small window area is preferable for north facades
Window to wall ratio has the highest effect on total energy con- while larger area is better for south facades because heat gain from
sumption in deep rooms in hot climate zones (Zones 2 and 3) and the sun can decrease the need for heating. In temperate climates
in shallow rooms in cold climate zones (Zones 6 and 7) while it is (Zones 4 and 5), rooms with medium window area have the best
relatively unimportant in medium-depth rooms. This observation energy performance.
is explained by the fact that in hot climates the need for artificial Room depth (W/D ratio) has a significant effect on total energy
lighting is lower for rooms with large window area. In cold cli- consumption in rooms with small window areas in hot climates and
mates, large window areas contribute to a larger heat loss through in rooms with large window areas in cold climates; width to depth
Table 6
Combinations of window to wall ratio, room depth, and facade orientation parameters showing energy savings.
6m 9m 12 m 15 m
Zone 2 20 – – – –
30 S, SW – – –
50 – All All All
60 – All All All
70 – All All All
80 – All All All
Zone 3 20 – – – –
30 – – – –
50 – All All All
60 – All All All
70 – All All All
80 – All All All
Zone 4 20 – – –
30 N, NE, E, W, NW – – –
50 – All All All
60 – All N, NE, E, SE, S, SW, NW All
70 – N, SE, S N, NE All
80 – SE, S N All
Zone 5 20 N, NE, E, SE, S, SW, NW – – –
30 All W – –
50 – S N, NE, E, SE, S, SW, NW N, NE, SE, S, SW, NW
60 – – N, SE, S, SW All
70 – – S N, SE, S, SW
80 – – S N, SE, S, SW
Zone 6 20 All N, NE, E, W, NW NE, E, W, NW N, NE, E, W, NW
30 All NE, E, W, NW N, NE, E, W, NW N, NE, E, W, NW
50 – S S, SE, SW SE, S, SW
60 – S S SE, S, SW
70 – – S S
80 – – S S
Zone 7 20 N, NE, E, W, NW N, NE, NW, W NE, NW N, NE, NW, W
30 N, NE, E, SE, S, SW, NW N, NE, E, W, NW N, NE, W, NW N, NE, E, W, NW
50 SE, S, SW SE, S, SW SE, S, SW
60 S SE, S, SW SE, S, SW SE, S, SW
70 S S SE, S, SW SE, S, SW
80 S S SE, S SE, S, SW
12 I. Susorova et al. / Energy and Buildings 57 (2013) 6–13
Table 7
Total energy savings for different climate zones.
Ave Max Ave Max Ave Max Ave Max Ave Max Ave Max
6m 0.16 0.19 – – 0.56 0.82 2.04 3.55 2.56 4.80 1.70 3.58
9m 1.59 3.08 3.79 6.76 0.80 1.40 0.24 0.44 0.57 0.96 0.57 1.58
12 m 4.16 7.30 6.44 12.81 0.59 1.77 0.58 1.17 0.30 0.78 0.59 2.02
15 m 5.06 9.95 7.03 14.09 1.59 3.02 0.81 2.08 0.38 1.29 0.57 1.97
Average 2.74 5.75 0.89 0.92 0.95 0.86
[6] V. Motuzienė, E.S. Juodis, Simulation based complex energy assessment of office [8] J. Carmody, S. Selkowitz, E.S. Lee, D. Abasteh, T. Willmert, Windows Systems for
building fenestration, Journal of Civil Engineering and Management 16 (3) (2010) High-Performance Buildings, W. W. Norton & Company, Inc., New York, 2004.
345–351. [9] ASHRAE, Standard 90.1 energy standard for buildings except low-rise residential
[7] R. Johnson, R. Sullivan, S. Selkowitz, S. Nozaki, C. Conner, D. Arasteh, Glaz- buildings, in: American Society of Heating, Refrigeration, and Air-Conditionning
ing energy performance and design optimization with daylighting, Energy and Engineers, 2010.
Buildings 6 (1984) 305–317.