Cable Size: 1x240 mm2 33 kV, Under Ground XLPE Copper Cable
KA
Short circuit current for 1 sec. (kA) Isc =
√t
0.143 x 240.39
=
√1
= 34.3 kA / 1 sec.
Note: This is satisfying that conductor short circuit current is 34.3 kA/1 Sec.
Calculation for Metallic Screen & Armour of withstands required fault current for 1 sec.
Cable Size: 1x240 mm2, 33 kV, Under Ground XLPE Copper Cable
(A) = (0.7854 x 1.02 x 96) + (15 x 0.06) = 75.4 + 0.9 = 76.3 mm2
KxA
Short circuit current for 1 sec. (kA) Isc =
√t
0.143 x 76.3
=
√1
1. Number of Wire = 50
2. Diameter of each wire = 2.5 m m
KxA
Short circuit current for 1 sec. (kA) Isc =
√t
0.084 x 245.44
=
√1
Note: This is satisfying that total Earth Fault short circuit current of this cable is 31.5 kA/1 Sec.