Professional Documents
Culture Documents
EST EST2 v2.0 Signature Series Component Installation Manual PDF
EST EST2 v2.0 Signature Series Component Installation Manual PDF
Component
Installation Manual
Limitation of liability
This product has been designed to meet the requirements of NFPA
Standard 72, 1993 Edition; Underwriters Laboratories, Inc., Standard
864, 7th Edition; and Underwriters Laboratories of Canada, Inc.,
Standard ULC S527 Installation in accordance with this manual,
applicable codes, and the instructions of the Authority Having
Jurisdiction is mandatory. EST shall not under any circumstances be
liable for any incidental or consequential damages arising from loss of
property or other damages or losses owing to the failure of EST
products beyond the cost of repair or replacement of any defective
products. EST reserves the right to make product improvements and
change product specifications at any time.
While every precaution has been taken during the preparation of this
manual to ensure the accuracy of its contents, EST assumes no
responsibility for errors or omissions.
FCC warning
This equipment can generate and radiate radio frequency energy. If this
equipment is not installed in accordance with this manual, it may cause
interference to radio communications. This equipment has been tested
and found to comply within the limits for Class A computing devices
pursuant to Subpart B of Part 15 of the FCC Rules. These rules are
designed to provide reasonable protection against such interference
when this equipment is operated in a commercial environment.
Operation of this equipment is likely to cause interference, in which
case the user at his own expense, will be required to take whatever
measures may be required to correct the interference.
8 7 6 5
SINGLE
INPUT
24 VDC
from
+ SIGNAL
2-CTM
Master Box
MODULE
panel
+ +
2 1
1 3
+
10 9
2
4 3 2 1
DATA IN
1
+ +
Municipal
Circuit
+
DATA OUT Notes
SINGLE
INPUT OPENS.
24 VDC
from
+ SIGNAL
2-CTM
Master Box
MODULE
panel 3 Circuit not supervised for
OPENS and is not power
2 1
1 3
+ + + limited.
+ +
10 9
2
4 3 2 1
DATA IN
1
Description
The City Tie Module (2-CTM) is designed for use with
Signature controllers. The 2-CTM is an interface between a
1 2
Single Input Signal Module or a Dual Input Signal Module and
a Master Box. It provides off premise signal transmission for
systems which must comply with the provisions of the NFPA.
The 2-CTM is used to activate a local energy fire alarm box,
which provides a 24 VDC alarm signal which is current limited
at 200 mA.
2 1
SPECIFICATIONS
INSTALLATION SHEET:
Power Nominal 24 VDC @ 200mA
Municipal Box Operation Nominal 24 VDC 2-CTM
Max. Wiring Resistance 25W City Tie Module
Trip Current 200mA into 14.5 Coil INSTALLATION SHEET P/N: 270496 FILE NAME: 270496.CDR
Max. Current 300mA REVISION LEVEL: 1.2 APPROVED BY: SJ
Standby Current 20mA DATE: 08/22/97 CREATED BY: MR
270 270L
INSTALLATION SHEET
6) Using the two 6-32 x 5/8 in (16 mm) machine screws provided,
mount the pull-station to the electrical box.
T
LIF
7) Pull the glass rod release lever and install the glass rod through Glass rod
the mounting bracket on the front of the pull-station. Set the release
toggle switch to the NORMAL position and snap the cover into its lever
locked position.
WIRING DIAGRAM
Notes
[1] Refer to Signature Loop Controller Installation Sheet for wiring
specifications.
2 All wiring is power-limited and supervised.
Factory
connections:
do NOT alter
Green LED
(normal)
Red LED
(alarm/active)
4 3 2 1
TB1
REAR VIEW CAUTION: Exposing more wire may cause a ground fault. Exposing
of 270 Series less wire may result in a faulty connection.
WARNINGS PULL
IN CASE
OF
This device will NOT operate without electrical power. As fires
frequently cause power interruption, we suggest you discuss further FIRE
safeguards with your local fire protection specialist.
INSTALLATION SHEET
SIGA-270P
2-Stage Fire Alarm Station
the mounting bracket on the front of the pull station. Push the Glass rod
glass rod release lever into its closed position. Set the toggle release
switch to the NORMAL position, and snap the cover into its lever
locked position.
WIRING DIAGRAM
Notes
[1] Refer to Signature Loop Controller Installation Sheet for wiring
specifications.
2 All wiring is power-limited and supervised.
Factory
connections:
do NOT alter
Green LED
(normal)
Red LED
(alarm/active)
4 3 2 1
TB1
REAR VIEW CAUTION: Exposing more wire may cause a ground fault. Exposing
less wire may result in a faulty connection.
Temporal Continuous
Operating Voltage (Note #1) 20 to 24 VDC 20 to 24V FWR 20 to 24 VDC 20 to 24V FWR
Low High Low High Low High Low High
Vol. Vol. Vol. Vol. Vol. Vol. Vol. Vol.
Operating Current (UL 268 Individual alarm) 20mA 44mA 29mA 57mA 20mA 44mA 29mA 57mA
Operating Current (UL 464 Reverse Polarity) 50mA 60mA 55mA 73mA 50mA 60mA 55mA 73mA
Sound Level Output @ 10 ft (3.05 M) Note #2 Low Volume High Volume Low Volume High Volume
Anechoic - Peak @ 24 VDC 99 dBA 99 dBA 104 dBA 99 dBA 104 dBA
Anechoic - Average @ 24 VDC 94 dBA 98 dBA 94 dBA 98 dBA
Reverberant Room per UL 464 @ 24 VDC 79 dBA 82 dBA 79 dBA 82 dBA
Reverberant Room per UL 464 @ 20 VDC 79 dBA 82 dBA 79 dBA 82 dBA
Reverberant Room per UL 268 85 dBA 85 dBA 85 dBA 85 dBA
Synchronization Pulses at temporal rate within 200 ms on common circuit (Note #3)
Compatible Detectors Signature Series Detectors
Operating Temperature 32°F to 100°F (0°C to 38°C)
Operating Humidity 0 to 93% RH
Storage Temperature -4°F to 140°F (-20°C to 60°C)
Construction & Finish High Impact Engineering Polymer, White
Maximum Distance from Ceiling (wall mount) 12 in (305 mm)
Compatible Electrical Boxes North American 4" (101 mm) Square by 2-1/8" (54 mm) deep; mud box (4in x
4in octagonal concrete ring); European 100 mm2
Shipping Weight 1 Lb. (0.45 Kg)
NOTES:
1. The horn must be connected to a continuous voltage when it is set to sound a temporal horn; it may be connected to either a
pulsed or continuous voltage when set to sound a steady tone.
2. For sleeping area installations, the HIGH VOLUME setting must be used.
3. The temporal pattern for the horn is : 1/2s ON, 1/2s OFF, 1/2s ON, 1/2s OFF, 1/2s ON, 1-1/2s OFF, repeat cycle.
4. The base will accept #12 AWG (2.5 mm2 ), #14 (1.5 mm2 ), #16 (1.0 mm2 ), and #18 (0.75 mm2 ) wire. Size #16 and #18
are preferred.
5. Break wire run at each terminal. Do not loop wires around terminals.
6. Rated 32°F to 120°F (0°C to 49°C) when used with model SIGA-PS or SIGA-IS.
7. At power up, units may sound for 10 seconds. Do NOT connect 24 VDC until mapping is complete.
2.13/16 in
(71 mm)
INSTALLATION SHEET:
DATA IN (-)
Listed 24 VDC
Power Supply
Optional SIGA-CR
for disabling/disconnecting Optional SIGA-CR
Signature Signature for disabling/disconnecting
sounder base
Controller Controller sounder base
NOTES
The SIGA-CC1 can be mounted in a North American 2-1/2" (64 mm) deep
2-gang box, standard 4" square 1-1/2" (38 mm) deep box, or European
100 mm square box. The terminal blocks will accept #14, 16 or 18 AWG WARNINGS
wire (1.5 mm 2 , 1.0 mm2 , 0.75 mm2 ). Sizes #16 and #18 are preferred.
1) This module will NOT operate without electrical power. As fires
SYSTEM CONTROLLER COMPATIBILITY frequently cause power interruption, we suggest you discuss
The SIGA-CC1 requires the Signature Loop Controller. The loop further safeguards with your local fire protection specialist.
controller downloads the personality code which determines how the
module will operate. The following personality codes may be 2) This module does NOT support conventional smoke detectors.
downloaded to the SIGA-CC1:
INSTALLATION SHEET:
SIGA-CC1
This module requires transient protection for installations in which
electromechanical bells or horns are connected to the output circuits. Single Input Signal Module
A Bi-Polar Transient Protector (P/N 235196P) MUST be used to protect
the module's electronic circuitry from the effects of electronic transients INSTALLATION SHEET P/N: 387022P FILE NAME: 387022P.CDR
caused by the inductive load of bells or horns. REVISION LEVEL: 6.0 APPROVED BY: LM
The bi-polar transient protector assembly should be connected across DATE: 07/06/98 CREATED BY: MR
the terminals of the bell or horn located electrically closest to the module.
The bi-polar transient protector is not polarity sensitive. GS BUILDING SYSTEMS CORPORATION
A UNIT OF GENERAL SIGNAL
Bells and horns MUST be located a minimum of 6 ft. (1.83 m) from the 6411 Parkland Drive 625 6th Street East
module. GS BUILDING SYSTEMS Sarasota, FL 34243 Owen Sound, Ontario
CORPORATION
USA Canada N4K 5P8
Technical Manuals Online! - http://www.tech-man.com
INSTALLATION INSTRUCTIONS
1) The SIGA-CC1 is shipped from the factory as an assembled
unit; it contains no user-serviceable parts and should NOT be
disassembled.
2) Refer to Technical Bulletin (P/N 270145) for installation
guidelines.
3) Verify that all field wiring is free of opens, shorts, and ground
faults.
4) Make all wiring connections as shown in the wiring diagram.
5) Write the address assigned to the module on the label provided
and apply the label to the module. Peel off the removable serial
number label from the module and apply it to the appropriate
location in the Serial Number Logbook.
6) Using the two 6-32 x 3/8" (9.5 mm) machine screws provided,
mount the module to the electrical box.
7) Using the four 4-24 x 5/16" (7.9 mm) self-tapping screws provided,
mount the wall plate to the module.
NOTE:
1) Wire in accordance with NFPA70-1996, National Electrical Code
Article 760, Section 760-54(a)(1), Exceptions No. 2 and 3.
2 Max. #14 AWG (1.5 mm2 ) wire; Min. #18 (0.75 mm2 )
WARNINGS
The SIGA-CC2 can be mounted in a North American 2-1/2" (64 mm) deep 2-
gang box, standard 4" square 1-1/2" (38 mm) deep box, or European 100
mm square box. The terminal blocks will accept #14, 16 or 18 AWG wire (1.5
mm2, 1.0 mm2, 0.75 mm2 ). Sizes #16 and #18 are preferred. 1) This module will NOT operate without electrical power. As fires
frequently cause power interruption, we suggest you discuss further
SYSTEM CONTROLLER COMPATIBILITY safeguards with your local fire protection specialist.
The SIGA-CC2 requires the Signature Loop Controller. The loop controller
downloads the personality code which determines how the module will 2) This module does NOT support conventional smoke detectors.
operate. The following personality code may be downloaded to the SIGA-
CC2:
Personality Code 7: Riser Selector (Dual Input)
The SIGA-CC2 is factory assigned personality code 7. Personality code 7
configures the SIGA-CC2 as a one of two output Signal Power (24V DC) or Dual Input Signal Module, SIGA-CC2
.Audio Evacuation (25 or 70V) Riser Selector. Each output circuit is
monitored for open or shorted wiring. If a short exists, the control panel
inhibits the activation of the audible/visual signal circuit, so the riser is not
connected to the wiring fault.
INSTALLATION SHEET:
SIGA-CC2
This module requires transient protection for installations in which Dual Input Signal Module
electromechnanical bells or horns are connected to the output circuits.
A Bi-Polar Transient Protector (P/N 235196P) MUST be used to protect the
module's electronic circuitry from the effects of electronic transients caused INSTALLATION SHEET P/N: 387040P FILE NAME: 387040P.CDR
by the inductive load of bells or horns.
REVISION LEVEL: 6.0 APPROVED BY: LM
The bi-polar transient protector assembly should be connected across the
DATE: 07/06/98 CREATED BY: MR
terminals of the bell or horn located electrically closest to the module. The
bi-polar transient protector is not polarity sensitive.
A UNIT OF GENERAL SIGNAL
GS BUILDING SYSTEMS CORPORATION
Bells and horns MUST be located a minimum distance of 6 ft. (1.83 m) from 6411 Parkland Drive 625 6th Street East
GS BUILDING SYSTEMS
the module. CORPORATION Sarasota, FL 34243 Owen Sound, ON, Canada
Technical Manuals Online! - http://www.tech-man.com
INSTALLATION INSTRUCTIONS
1) The SIGA-CC2 is shipped from the factory as an assembled
unit; it contains no user-serviceable parts and should NOT
be disassembled.
2) Refer to Technical Bulletin (P/N 270145) for installation
guidelines.
3) Verify that all field wiring is free of opens, shorts, and ground
faults.
4) Make all wiring connections as shown in the wiring diagram.
5) Write the address assigned to the module on the label provided
and apply the label to the module. Peel off the removable serial
number label from the module and apply it to the appropriate
location in the Serial Number Logbook.
6) Using the two 6-32 x 3/8" (9.5 mm) machine screws provided,
mount the module to the electrical box.
7) Using the four 4-24 x 5/16" (7.9 mm) self-tapping screws
provided, mount the wall plate to the module.
NOTE:
1) Wire in accordance with NFPA70-1996, National Electrical Code
Article 760, Section 760-54(a)(1), Exceptions No. 2 and 3.
Strip 1/4" (6.4 mm) from the ends of ALL wires that connect to the
terminal block of the module.
CAUTION:
Exposing more than 1/4" (6.4 mm) of wire may cause a ground fault.
Exposing less than 1/4" (6.4 mm) of wire may result in a faulty
connection.
The SIGA-CR can be mounted in a North American 2-1/2" (64 mm) deep
1-gang box, or standard 4" square 1-1/2" (38 mm) deep box with 1-gang WARNINGS
cover. The terminal blocks will accept #14, 16 or 18 AWG wire (1.5 mm 2,
1.0 mm 2 , 0.75 mm 2 ). Sizes #16 and #18 are preferred.
SYSTEM CONTROLLER COMPATIBILITY 1) This module will NOT operate without electrical power. As fires
The SIGA-CR requires the Signature Loop Controller. frequently cause power interruption, we suggest you discuss further
safeguards with your local fire protection specialist.
Personality Code 8: Dry Contact Output
The SIGA-CR is factory assigned personality code 8 which configures the 2) Dangerouos voltages may be present at terminals even when
SIGA-CR as an output dry relay contact. power is shut off!!
INSTALLATION SHEET:
SIGA-CR
Control Relay Module
Strip 1/4" (6.4 mm) from the ends of ALL wires that connect to the
terminal block of the module.
CAUTION:
Exposing more than 1/4" (6.4 mm) of wire may cause a ground fault.
Exposing less than 1/4" (6.4 mm) of wire may result in a faulty
connection.
SYSTEM CONTROLLER COMPATIBILITY 1) This module will NOT operate without electrical power. As
The SIGA-CRR requires a Signature Loop Controller to operate. fires frequently cause power interruption, we suggest you
discuss further safeguards with your local fire protection
Personality Code 8: Dry Contact Output specialist.
The SIGA-CRR is factory assigned personality code 8 which
configures the SIGA-CRR as a constant power polarity reversing
device.
SIGA-CRR
INSTALLATION SHEET:
SIGA-CRR
Polarity Reversal Relay Module
Strip 1/4" (6.4 mm) from the ends of ALL wires that connect to the
terminal block of the module.
CAUTION:
Exposing more than 1/4" (6.4 mm) of wire may cause a ground fault.
Exposing less than 1/4" (6.4 mm) of wire may result in a faulty
connection.
Optional SIGA-CR
for disabling/disconnecting
Signature sounder base
SIGA-MP2 Controller
SIGA-CRR Activates ALL Sounders,
Head Operates its Sounder
1 6254A-003
Audible Bases EOL Relay
Listed 24 VDC
Power Supply
The SIGA-CT1 can be mounted in a North American 2-1/2" (64 mm) deep 1- #16 AWG (1.0 mm ) 2
6,225' (1,897m)
gang box, or standard 4" square box 1-1/2" (38 mm) deep with 1-gang cover. 2
The terminal blocks will accept #14, 16, or 18 AWG wire (1.5 mm2 , 1.0 mm2 , #14 AWG (1.5 mm ) 9,900' (3,018m)
0.75 mm2 ). Sizes #16 and #18 are preferred.
IMPORTANT NOTE:
TRANSIENT PROTECTION
INSTALLATION SHEET:
SIGA-CT1
Single Input Module
Strip 1/4" (6.4 mm) from the ends of ALL wires that connect to the
terminal block of the module.
CAUTION:
Exposing more than 1/4" (6.4 mm) of wire may cause a ground fault.
Exposing less than 1/4" (6.4 mm) of wire may result in a faulty
connection.
The SIGA-CT2 can be mounted in a North American 2-1/2" (64 mm) deep 1- #18 AWG (0.75 mm ) 2
3,930' (1,198m)
gang box, or standard 4" square box 1-1/2" (38 mm) deep with 1-gang cover. 2
6,225' (1,897m)
#16 AWG (1.0 mm )
The terminal blocks will accept #14, 16, or 18 AWG wire (1.5 mm2 , 1.0 mm2 ,
0.75 mm2 ). Sizes #16 and #18 are preferred. #14 AWG (1.5 mm ) 2
9,900' (3,018m)
SYSTEM CONTROLLER COMPATIBILITY
The SIGA-CT2 requires the Signature Loop Controller. The loop controller
downloads the personality code which determines how the module will
operate. The following personality codes may be downloaded to the SIGA-
WARNINGS
CT2:
1) This module will NOT operate without electrical power. As fires
Personality Code 1: N/O Alarm Latching (Class B)
frequently cause power interruption, we suggest you discuss further
The SIGA-CT2 is factory assigned personality code 1 to input channels 1
safeguards with your local fire protection specialist.
and 2. Personality code 1 configures the SIGA-CT2 for Class B normally-
open dry contact initiating devices (e.g., pull-stations, heat detectors, etc.).
2) This module does NOT support conventional smoke detectors.
When the N/O input contact of an initiating device is closed, an alarm signal
is sent to the loop controller and the alarm condition is latched at the module.
INSTALLATION SHEET:
SIGA-CT2
Dual Input Module
Strip 1/4" (6.4 mm) from the ends of ALL wires that connect to the
terminal block of the module.
CAUTION:
Exposing more than 1/4" (6.4 mm) of wire may cause a ground fault.
Exposing less than 1/4" (6.4 mm) of wire may result in a faulty
connection.
W W
INSTALLATION SHEET:
The guard is finished in white enamel, and secured with Adapter & Guard 8.875" diameter x 5.5" height
tamper-proof fasteners. (22.54cm x 13.97cm)
Compatible Devices
Detectors SIGA-IPHS XLS-IPHS
SIGA-PS XLS-PS GSA-PS
WARNINGS
1) For proper operation, ONLY the specified detectors should be
used with this mounting plate. A detector that is not rated for the
air velocities produced in air ducts will NOT operate properly and
may result in loss of life. 1) Select the location for the duct housing and apply the adhesive
backed drill template on the duct. Drill out the 4 mounting holes
and the (2) 1 5/8" (41 mm) diameter holes for the air sampling
and exhaust tubes. If the air stream is in the opposite direction
Specifications to that shown, invert the duct housing.
2) Insert the appropriate air sampling tube (not supplied) in the 1
5/8" (41 mm) diameter hole. Orient the tube so that the air flows
Compatible Bases Standard Base, SIGA-SB into the inlet holes along the side of the tube. If the air sampling
Relay Base, SIGA-RB tube is longer than the duct, either cut the end of the tube to fit
Isolator Base, SIGA-IB inside the duct or drill a clearance hole in the opposite duct wall
and allow the tube to protrude outside the duct. Insert the
Compatible Detectors rubber stopper (supplied) into the far end of the sampling tube.
Intelligent Photoelectric Smoke Detector, SIGA-PS 3) Insert the exhaust tube into the red connector on the housing
Intelligent 3D Multisensor Smoke Detector, SIGA-PHS oriented with the slanted edge facing downstream. Tighten the
Intelligent 4D Multisensor Smoke Detector, SIGA-IPHS screw on the connector.
4) Bring the duct housing up to the air sampling tube, keeping the
WARNINGS
1) For proper operation, ONLY the specified detectors should
be used with this mounting plate. A detector that is not rated
for the air velocities produced in air ducts will NOT operate
properly and may result in loss of life.
Control Relay Module
2) The SIGA-DMP is intended for use ONLY in the three (SIGA-CR) mounted
directly to
configurations shown in Installation Options. For other 2 SIGA-DMP.
duct sizes, refer to the appropriate manufacturer's
documentation.
Installation Instructions
1) Refer to Technical Bulletin (P/N 270145) for installation
guidelines.
WARNINGS
CAUTION:
Exposing more than 1/4" of wire may cause a ground fault.
1) This test station will NOT operate without electrical power. Exposing less than 1/4" of wire may result in a faulty connection.
As fires frequently cause power interruption, discuss further
safeguards with your local fire protection specialist.
SIGA-DTS
Table A - Technical Documentation DUCT DETECTOR TEST STATION
P/N Title
PART NO.: P-847550-1739 ISSUE: 2
270144 Signature Series Technical Reference Manual
270186 Installation & Preventive Maintenance Guide EDWARDS SYSTEMS TECHNOLOGY
SARASOTA , FL 800-655-4497 Fax. 941-753-1806
270188 System Operations Guide CHESHIRE, CT 203-699-3000 Fax. 203-699-3075
OWEN SOUND, CANADA 519-376-2430 Fax. 519-376-7258
INTERNATIONAL: CANADA 905-678-6767 Fax. 905-678-9791
Technical Manuals Online! - http://www.tech-man.com
PRODUCT INFORMATION circumstances should heat detectors be relied on as the sole means
of fire protection.
6) Maintenance (Regular or Selected) should be planned in
Description: The Intelligent Fixed-Temperature Heat Detector (HFS) accordance with the requirements of the authority having
is a component of the Signature Series. This intelligent analog device jurisdiction to ensure proper operation. Refer to NFPA 72 and
contains a fixed-temperature heat sensor to detect heat from fire. The ULC Standard CAN 536. See the Technical Bulletin for cleaning
heat sensor monitors the temperature of the air in its surroundings instructions.
and the detector analyzes the data and determines whether an alarm 7) The bright orange-colored dust cover (supplied) MUST remain on
should be initiated. A heat detector by itself, however, does NOT the detector during installation, and then be removed prior to
provide life safety protection. For life safety situations, a heat detector operation. The dust cover is NOT a substitute for removing the
should be used in conjunction with ionization or photoelectric smoke detector during new construction or heavy remodeling.
detectors or a combination thereof.
8) To ensure proper operation, store the detector within the
LEDs: The HFS provides two LEDs that indicate the status of the recommended ranges. Allow the detector to stabilize to room
detector. temperature before applying power.
Normal: Green LED flashes
Alarm: Red LED flashes
Standalone alarm: Green and red LEDs glow continuously
Electronic addressing: The loop controller automatically assigns SPECIFICATIONS
addresses to the detectors. Custom addresses can be assigned to
the detectors via laptop computer. No addressing switches are used.
Operating voltage range: 15.2 - 19.95 Vdc
Stand-alone operation: If isolated from the loop controller, the Normal operating current: 45 mA
detector alarms when heat levels exceed a preset value. See the
Alarm current: 45 mA
applicable control panel manual to verify standalone capabilities.
Standalone alarm current: 18 mA
Self-diagnostics: The HFS contains a microprocessor capable of ULI fixed-temp alarm rating: 135 °F (57 °C)
performing comprehensive self-diagnostic tests and storing results. ULC fixed-temp alarm rating: 140 °F (60 °C)
Details such as hours of operation, last maintenance date, sensitivity Actual alarm point: 130 to 140 °F (54 to 60 °C)
values, and number of alarms and troubles are stored in nonvolatile Operating temperature range: 32 to 100 °F (0 to 38 °C)
memory. These statistics may be retrieved and reviewed as desired. Operating humidity range: 0 to 93 % RH, non-condensing
Storage temperature range: -4 to 140 °F (-20 to 60 °C)
Maximum spacing: 70 ft' (21.3 m) centers
Construction and finish: High impact engineering polymer,white
INSTALLATION INSTRUCTIONS Compatible bases
Standard: SB, SB4
Relay: RB, RB4
1) Push a small screwdriver into the tamper-resist access slot and Isolator: IB, IB4
rotate the detector counterclockwise to remove it. Note: You can Audible: AB4
permanently disable the tamper-resist mechanism by breaking Shipping weight: 7.7 oz (218 g)
and removing the plastic lever arm from the base.
2) See the Technical Bulletin for installation guidelines.
3) Install and wire the base as described in the Installation Sheet
supplied with the base. PRODUCT DIAGRAM
4) Peel off the removable serial number label from the detector and
apply it to the appropriate location in the serial number log book.
5) Connect the detector to the base by rotating the detector
clockwise until it snaps into the locked position.
6) NFPA code requires that a calibrated sensitivity test be performed Tamper-Resist Lever Arm
upon completion of the original installation and following any - Break off to disable -
modifications or additions to the system. The Signature Series (Located on Base)
can perform this test and generate a system sensitivity report.
7) In Canada your installation must meet the requirements of
CAN/ULC-S524-M91: Standard for the Installation of Fire Alarm
Systems, and the local Authority Having Jurisdiction.
Access Slot for
8) Before initial testing, remove the dust cover from the detector and Tamper-Resist Mechanism
notify the proper authorities that the fire alarm system is
undergoing maintenance and will be temporarily out of service.
WARNINGS
INSTALLATION SHEET
1) This detector will NOT operate without electrical power. As fires
frequently cause power interruption, we suggest you discuss SIGA-HFS
further safeguards with your local fire protection specialist. Intelligent Fixed-Temperature
2) This detector will NOT sense fires that start in areas where heat
cannot reach the detector. Heat from fires in walls, roofs, or on
Heat Detector
the opposite side of closed doors may not reach the detector.
3) This detector is intended for use with ionization and/or INSTALLATION SHEET P/N: 387017P FILE NAME: 387017P.CDR
photoelectric smoke detectors. The heat detector by itself does REVISION LEVEL: 7.0 APPROVED BY: R. Right
NOT provide life safety protection.
4) This detector will NOT detect oxygen levels, smoke, toxic gases, DATE: 11DEC98 CREATED BY: D. Chinell
or flames. This device should only be used as part of a broad RELATED DOCUMENTS
based life safety program which includes a variety of information Technical Bulletin (P/N 270145)
sources pertaining to heat and smoke levels, extinguishment
systems, visual and audible devices, and other safety measures. EDWARDS SYSTEMS TECHNOLOGY
5) Independent studies indicate that heat detectors should only be
used when property protection alone is involved. Under no 6411 Parkland Drive 625 6th Street East
TM
Sarasota, FL 34243 Owen Sound, Ontario
USA Canada N4K 5P8
Technical Manuals Online! - http://www.tech-man.com
Technical Manuals Online! - http://www.tech-man.com
5) Independent studies indicate that heat detectors should only be
PRODUCT INFORMATION used when property protection alone is involved. Under no
circumstances should heat detectors be relied on as the sole
means of fire protection.
Description: The Intelligent Rate-of-Rise and Fixed-Temperature
Heat Detector (HRS) is a component of the Signature Series. This 6) Maintenance (Regular or Selected) should be planned in
intelligent analog device contains rate-of-rise and fixed-temperature accordance with the requirements of the authority having
heat sensors to detect fire. The heat sensors monitor the temperature jurisdiction to ensure proper operation. Refer to NFPA 72 and
of the surrounding air and the detector analyzes the data from both ULC Standard CAN 536. See the Technical Bulletin for additional
sensors to determine whether an alarm should be initiated. The rate- information and for cleaning instructions.
of-rise heat sensor can quickly detect a fast, flaming fire. The fixed- 7) The bright orange-colored dust cover (supplied) MUST remain on
temperature heat sensor detects fire when the air temperature near the detector during installation, and then be removed prior to
the detector exceeds the alarm point. A heat detector by itself, operation. The dust cover is NOT a substitute for removing the
however, does NOT provide life safety protection. For life safety detector during new construction or heavy remodeling.
situations, a heat detector should be used in conjunction with 8) To ensure proper operation, store the detector within the
ionization or photoelectric smoke detectors or a combination thereof. recommended ranges. Allow the detector to stabilize to room
LEDs: The HRS provides two LEDs that show detector status. temperature before applying power.
Normal: Green LED flashes
Alarm: Red LED flashes
Standalone alarm: Green and red LEDs glow continuously
Electronic addressing: The loop controller automatically assigns
SPECIFICATIONS
addresses to the detector. Custom addresses can be assigned to the
detectors via laptop computer. No addressing switches are used. Operating voltage range: 15.2 - 19.95 Vdc
Stand-alone operation: If isolated from the loop controller, the Normal operating current: 45 mA
detector alarms when heat levels exceed preset values. See the Alarm current: 45 mA
applicable control panel manual to verify standalone capabilities. Standalone alarm current: 18 mA
Self-diagnostics: The HRS contains a microprocessor capable of ULI fixed-temp alarm rating: 135 °F (57 °C)
performing comprehensive self-diagnostic tests and storing results. ULC fixed-temp alarm rating: 140 °F (60 °C)
Details such as hours of operation, last maintenance date, sensitivity Actual alarm point: 130 to 140 °F (54 to 60 °C)
values, and number of alarms and troubles are stored in nonvolatile Rate-of-rise: 15 °F (8 °C)/min.
memory. These statistics may be retrieved and reviewed as desired. Operating temperature range: 32 to 100 °F (0 to 38 °C)
Operating humidity range: 0 to 93 % RH, non-condensing
Storage temperature range: -4 to 140 °F (-20 to 60 °C)
Maximum spacing: 70 ft (21.3 m) centers
Construction and finish: High impact engineering polymer, white
INSTALLATION INSTRUCTIONS Compatible bases
Standard: SB, SB4
1) Push a small screwdriver into the tamper-resist access slot and Relay: RB, RB4
rotate the detector counterclockwise to remove it. Note: You can Isolator: IB, IB4
permanently disable the tamper-resist mechanism by breaking Audible: AB4
and removing the plastic lever arm from the base. Shipping weight: 7.7 oz. (218 g)
2) See the Technical Bulletin for installation guidelines.
3) Install and wire the base as described in the Installation Sheet
supplied with the base. PRODUCT DIAGRAM
4) Peel off the removable serial number label from the detector and
apply it to the appropriate location in the serial number log book.
5) Connect the detector to the base by rotating the detector
clockwise until it snaps into the locked position.
Tamper-Resist Lever Arm
6) NFPA code requires that a calibrated sensitivity test be performed - Break off to disable -
upon completion of the original installation and following any (Located on Base)
modifications or additions to the system. The Signature Series
can perform this test and generate a system sensitivity report.
7) In Canada your installation must meet the requirements of
CAN/ULC-S524-M91: Standard for the Installation of Fire Alarm Access Slot for
Systems, and the local Authority Having Jurisdiction. Tamper-Resist Mechanism
8) Before initial testing, remove the dust cover from the detector and
notify the proper authorities that the fire alarm system is
undergoing maintenance and will be temporarily out of service.
SIGA-HRS
1) This detector will NOT operate without electrical power. As fires Intelligent Fixed Temperature
frequently cause power interruption, we suggest you discuss
further safeguards with your local fire protection specialist. Rate-of-Rise Heat Detector
2) This detector will NOT sense fires that start in areas where heat
cannot reach the detector. Heat from fires in walls, roofs, or on INSTALLATION SHEET P/N: 387018P FILE NAME: 387018P.CDR
the opposite side of closed doors may not reach the detector.
REVISION LEVEL: 7.0 APPROVED BY: R. Right
3) This detector is intended for use with ionization and/or
photoelectric smoke detectors. The heat detector by itself does DATE: 11DEC98 CREATED BY: D. Chinell
NOT provide life safety protection. RELATED DOCUMENTS
4) This detector will NOT detect oxygen levels, smoke, toxic gases, Technical Bulletin (P/N 270145)
or flames. This device should only be used as part of a broad
based life safety program which includes a variety of information EDWARDS SYSTEMS TECHNOLOGY
sources pertaining to heat and smoke levels, extinguishment
systems, visual and audible devices, and other safety measures. 6411 Parkland Drive 625 6th Street East
TM
Sarasota, FL 34243 Owen Sound, Ontario
USA Canada N4K 5P8
Technical Manuals Online! - http://www.tech-man.com
Technical Manuals Online! - http://www.tech-man.com
PRODUCT INFORMATION circumstances should heat detectors be relied on as the sole means
of fire protection.
6) Maintenance (regular or selected) should be planned in
Description: The Intelligent Heat Detector (HRSI) is a component of accordance with the requirements of the Authority Having
the Signature Series. This intelligent analog device contains a Grade Jurisdiction to ensure proper operation.
1 heat sensor that detects heat from fire. The heat sensor monitors 7) The bright orange-colored dust cover (supplied) MUST remain on
the surrounding air temperature and the detector analyzes this data to the detector during installation, and then be removed prior to
determine whether an alarm should be initiated. operation. The dust cover is NOT a substitute for removing the
The heat sensor can quickly detect a fast, flaming fire when the air detector during new construction or heavy remodeling.
temperature near the detector exceeds the alarm point. A heat 8) To ensure proper operation, store the detector within the
detector by itself, however, does NOT provide life safety protection. recommended ranges. Allow the detector to stabilize to room
For life safety situations, a heat detector should be used in temperature before applying power.
conjunction with ionization or photoelectric smoke detectors or both.
LEDs: The HRSI provides two LEDs that indicate the status of the
detector.
Normal: Green LED flashes
Alarm: Red LED flashes
Standalone alarm: Green and red LEDs glow continuously
SPECIFICATIONS
Electronic addressing: The loop controller automatically assigns
addresses to the detector. Custom addresses can be assigned to the Operating voltage range: 15.2 - 19.95 Vdc
detectors via laptop computer. No addressing switches are used. Normal operating current: 45 mA
Standalone operation: In the event of communications failure with Alarm current: 45 mA
the loop controller, the detector will alarm when heat levels exceed its Standalone alarm current: 18 mA
preset value. Refer to the applicable fire alarm control panel manual Classification: Grade 1
for verification of standalone capabilities. Operating temperature range: 32 to 100 °F (0 to 38 °C)
Self-diagnostics: The HRSI contains a microprocessor capable of Operating humidity range: 0 to 93 % RH, noncondensing
performing comprehensive self-diagnostics and storing the results. Storage temperature range: -4 to 140 °F (-20 to 60 °C)
Details such as hours of operation, last maintenance date, sensitivity Maximum spacing: 70 ft (21.3 m) centers
values, and number of alarms and troubles are stored in nonvolatile Construction and finish: High impact engineering polymer, white
memory. With some systems, these statistics may be retrieved and Compatible bases
reviewed as desired. Standard: SB, SB4
Relay: RB, RB4
Isolator: IB, IB4, IBS
Audible: AB4
Shipping weight: 7.7 oz (218 g)
INSTALLATION INSTRUCTIONS
1) Push a small screwdriver into the access slot for the tamper-resist
mechanism while rotating the detector counterclockwise to PRODUCT DIAGRAM
remove the detector. Note: The tamper-resist mechanism may be
permanently disabled by breaking and removing the plastic lever
arm from the base.
2) Refer to the technical bulletin for installation guidelines.
3) Install and wire the base as described in the installation sheet Tamper-Resist Lever Arm
supplied with the base. - Break off to disable -
4) Peel off the removable serial number label from the detector and (Located on Base)
apply it to the appropriate location in the serial number log book.
5) Connect the detector to the base by rotating the detector
clockwise until it snaps into the locked position. Access Slot for
6) Before initial testing, remove the dust cover from the detector and Tamper-Resist Mechanism
notify the proper authorities that the fire alarm system is
undergoing maintenance and will be temporarily out of service.
WARNINGS
INSTALLATION SHEET
7
4
1
North American 1-Gang Box
2 3-1/2 in by 1-1/2 in (38 mm) Deep Octagon Box
DATA IN (-) DATA OUT (-) 4 in by 1-1/2 in (38 mm) Deep Octagon Box
European 1-Gang (75 mm) Box w/60.3 mm Fixing Centers
BESA Box
NOTES:
DATA IN (+) DATA OUT (+)
From Signature Controller to Next Device 1) These bases will accept 12, 14, 16, 18 AWG (2.05 sq mm, 1.5 sq mm,
or Back to Loop 1.0 sq mm, and 0.75 sq mm) wire. Sizes 16 and 18 are preferred.
or Previous Device
Controller 2) Write the address assigned to the detector on the label provided and
apply the label to the inside rim of the base.
3) Break wire run at each terminal. Do not loop signaling circuit field
wires around terminals.
Term Description
1 Not Used
2 DATA IN/OUT (+)
3 DATA IN (-)
4 Not Used
5 Not Used
6 DATA OUT (-) SIGA-IB
7 Not Used
INSTALLATION SHEET
SIGA-IB
Detector Base
DATE: 01/18/99
6 6 6
5 5 5
7
7
4
4
7
4
_
3
3
1
1
3
+
1
S 2 2 2
2 2 3
_ Insulate Shield/Drain
with tape Shield/Drain
+
S
Control Panel
1. Shielded wire is required ONLY in environments with very high electrical noise.
3 For Class B wiring, there is no shield connection to ground at the last device.
MOUNTING DIAGRAMS
1.5 in
1.1 in (38 mm)
(27 mm)
0.8 in 0.8 in
(20 mm) (20 mm)
2.0 in 2.0 in
(51 mm) (51 mm)
3-1/2 in or 4 in by 1-1/2 in (38 mm) Deep Octagon Box European 1-Gang (75 mm) Box 60.3 mm Fixing Centers
1.5 in
(38 mm) 1.75 in
(45 mm)
0.8 in
(20 mm) 0.8 in
(20 mm)
2.0 in
(51 mm) 2.0 in
(51 mm)
7
4
(1.0 mm ), and #18 (0.75 mm ) wire. Sizes #16 and #18 are
2 2
SIGA-IB4
INSTALLATION SHEET
SIGA-IB4
Detector Base
DATE: 01/18/99
Refer to Standard Detector Base Relay Detector Base Isolator Detector Base
compatible panel
Installation Sheet
for terminal
assignments.
6 6 6
5 5 5
7
7
4
4
7
4
_
3
3
1
1
3
+
1
S 2 2 2
2 2 3
_ Insulate Shield/Drain
with tape Shield/Drain
+
S
Control Panel
1. Shielded wire is required ONLY in environments with very high electrical noise.
3 For Class B wiring, there is no shield connection to ground at the last device.
MOUNTING DIAGRAMS
4 in by 1-1/2 in (38 mm) Deep Square Box (Surface Mount) 4 in Box Trim Skirt/Ring
1.5 in
(38 mm)
0.8 in
(20 mm)
2.0 in
(51 mm)
4 in by 1-1/2 in (38 mm) Deep Square Box (Flush Mount) Flush Mount Electrical Box
NOTES:
1) A 4 in Box Trim Skirt/Ring (SIGA-TS) must be installed to give a
"finished" appearance to the 4 in base.
1.5 in
2) Refer to Installation Sheet P/N 387056P for additional
(38 mm)
information.
0.8 in
(20 mm)
2.0 in
(51 mm)
ELECTRONIC ADDRESSING
The loop controller automatically assigns the address to the SIGA-IM or a
custom address can be assigned to the isolator modules via laptop
computer, no addressing switches are used. One (1) detector address is
required for each SIGA-IM. Refer to the appropriate manufacturer's
documentation for automatic and custom addressing.
MOUNTING
The SIGA-IM can be mounted in a North American 2-1/2" (64 mm) deep 2-
gang box, standard 4" square 1-1/2" (38 mm) deep box, or European 100
mm square box. The terminal blocks will accept #14, 16 or 18 AWG wire
(1.5 mm 2, 1.0 mm 2, 0.75 mm2 ). Sizes #16 and #18 are preferred.
SPECIFICATIONS
Operating Voltage Range 15.2 - 19.95 Vdc
Standby Current 45mA
Activated Current 45mA
Maximum Circuit Resistance
Between Isolators 6W
SIGA-IM
Operating Temperature Range 32 to 120°F (0 to 49°C)
Operating Humidity Range 0 to 93% RH
Storage Temperature Range -4 to 140°F (-20 to 60°C)
Construction High Impact Polymer
Shipping Weight 7.7 oz (218 g)
Compatible Electrical Boxes
North American 2-1/2" (64 mm) Deep 2-Gang Box
Standard 4" Square Box 1-1/2" (38 mm) Deep Box
European 100 mm Square Box
WARNINGS
1) This module will NOT operate without electrical power. As fires INSTALLATION SHEET:
frequently cause power interruption, we suggest you discuss further
safeguards with your local fire protection specialist. SIGA-IM
Isolator Module
INSTALLATION SHEET P/N: P-047550-1788
FILE NAME: P-047550-1788.CDR
REVISION LEVEL: 2.0 APPROVED BY: JB
DATE: 08/18/97 CREATED BY: MR
Strip 1/4" (6.4 mm) from the ends of ALL wires that connect to the
terminal block of the module.
CAUTION:
Exposing more than 1/4" (6.4 mm) of wire may cause a ground fault.
Exposing less than 1/4" (6.4 mm) of wire may result in a faulty
connection.
Isolator
Control Relay Module, Module,(Personality
SIGA-CR SIGA-IM Code 8)
1) For maximum wire resistance, refer to the appropriate
manufacturer's documentation.
2) Max. #14 AWG (1.5 mm 2) wire.
3 Refer to Signature Loop Controller Installation Sheet for wiring
specifications.
4 This module should be used only with Class A wiring.
5 Maximum circuit resistance between isolators is 6W.
6) All wiring is power-limited and supervised.
WARNINGS
INSTALLATION SHEET
1) This detector will NOT operate without electrical power. As fires
frequently cause power interruption, discuss further safeguards SIGA-IPHS(B)
with your local fire protection specialist. Intelligent 4D Multisensor
2) This detector will NOT sense fires in areas where smoke cannot
reach it. Smoke from fires in walls, roofs, or on the opposite side
Smoke Detector
of closed doors may not reach the detector.
3) Ionization detectors are best suited for detecting fast, flaming INSTALLATION SHEET P/N: 387016P FILE NAME: 387016P.CDR
fires. Photoelectric detectors are best suited for detecting slow, REVISION LEVEL: 7.0 APPROVED BY: B. Right
smoldering fires. The heat sensor in this device provides a source
of supplemental information to that provided by the other sensors. DATE: 08JUN99 CREATED BY: D. Chinell
The heat sensor by itself does NOT provide life safety protection. RELATED DOCUMENTS
4) Maintenance (regular or selected) should be planned in Technical Bulletin (P/N 270145)
accordance with the requirements of the Authority Having
Jurisdiction to ensure proper operation. Refer to NFPA 72 and EDWARDS SYSTEMS TECHNOLOGY
ULC Standard CAN 536.
5) The bright orange-colored dust cover (supplied) MUST remain on 6411 Parkland Drive 625 6th Street East
TM
Sarasota, FL 34243 Owen Sound, Ontario
USA Canada N4K 5P8
Technical Manuals Online! - http://www.tech-man.com
Technical Manuals Online! - http://www.tech-man.com
6) The bright orange-colored dust cover (supplied) MUST remain on
PRODUCT INFORMATION the detector during installation, and then be removed prior to
operation. The dust cover is NOT a substitute for removing the
detector during new construction or heavy remodeling.
Description: The Intelligent Ionization Smoke Detector (IS) is a
component of the Signature Series. This intelligent analog device 7) To ensure proper operation, store the detector within the
senses changes in air samples, analyzes the information, then recommended ranges. Allow the detector to stabilize to room
determines whether an alarm should be initiated. temperature before applying power.
The detector continuously monitors changes in sensitivity due to the 8) Under normal conditions, this unit does not require calibration.
environment (e.g. dirt, smoke, temperature, humidity) and notifies the However, if calibration is required, return to:
loop controller of its condition. The IS issues a dirty-sensor warning GS Building Systems Corporation
when it reaches its preset limit. This notifies the operator of the need 5 North Main Street
for service while the detector is still operating within UL/ULC limits. Pittsfield, ME 04967-1500
LEDs: The IS detector has two LEDs that show its status. Refer to the Technical Bulletin for additional information and
Normal: Green LED flashes cleaning instructions.
Alarm/active: Red LED flashes 9) Test the detector with Smoke Detector Tester and Model 1490
Standalone alarm: Green and red LEDs glow continuously Adapter/Tube Accessory, manufactured by Home Safeguard, Inc.
Electronic addressing: The loop controller automatically assigns
addresses to the detectors. Custom addresses can be assigned to
the detectors via laptop computer. No addressing switches are used.
Standalone operation: If unable to communicate with the loop SPECIFICATIONS
controller, the detector alarms when smoke levels exceed its preset
value. Refer to the applicable fire alarm control panel manual for Operating voltage range: 15.2 - 19.95 Vdc
verification of standalone capabilities. Normal operating current: 45 mA
Self-diagnostics: The IS contains a microprocessor capable of Alarm current: 45 mA
performing comprehensive self-diagnostics and storing the results. Standalone alarm current: 18 mA
Details such as hours of operation, last maintenance date, sensitivity Ionization source: Americium 241, 1 mCi
values, and number of alarms and troubles are stored in non-volatile ULI/ULC smoke sensitivity: 0.61 to 1.91 % obsc./ft (305 mm)
memory. These can be retrieved and reviewed as desired. Operating temperature range: 32 to 120 °F (0 to 49 °C)
Operating humidity range: 0 to 93% RH, Non-condensing
Storage temperature range: -4 to 140 °F (-20 to 60 °C)
Environmental compensation: Automatic
INSTALLATION INSTRUCTIONS Construction and finish: High impact engineering polymer, white
Compatible bases
Standard: SB, SB4
1) Push a small screwdriver into the tamper-resist access slot while Relay: RB, RB4
rotating the detector counterclockwise to remove the detector. Isolator: IB, IB4
Note: You can permanently disable the tamper-resist mechanism Audible: AB4
by breaking and removing the plastic lever arm from the base. Shipping weight: 7.7 oz. (218 g)
2) See the Technical Bulletin for installation guidelines. Maximum distance from ceiling (wall-mounted): 12 in (305 mm)
3) Install and wire the base as described in the installation sheet Maximum installation altitude: 6,000 ft (1,828 m)
supplied with the base.
4) Peel off the removable serial number label from the detector and
apply it to the appropriate location in the serial number log book. PRODUCT DIAGRAM
5) Connect the detector to the base by rotating the detector
clockwise until it snaps into the locked position.
6) NFPA code requires that a calibrated sensitivity test be performed
upon completion of the original installation and following any
modifications or additions to the system. The Signature Series
can perform this test and generate a system sensitivity report.
7) In Canada your installation must meet the requirements of
CAN/ULC-S524-M91: Standard for the Installation of Fire Alarm
Systems, and the local Authority Having Jurisdiction.
8) Before initial testing, remove the dust cover from the detector and
notify the proper authorities that the fire alarm system is
undergoing maintenance and will be temporarily out of service.
WARNINGS
INSTALLATION SHEET
4) Maintenance (regular or selected) should be planned in DATE: 09DEC98 CREATED BY: D. Chinell
accordance with the requirements of the Authority Having RELATED DOCUMENTS
Jurisdiction to ensure proper operation. Refer to NFPA 72 and Technical Bulletin (P/N 270145)
ULC Standard CAN 536.
5) Install the detector away from air supplies and air diffusers. The EDWARDS SYSTEMS TECHNOLOGY
average air velocity should NOT exceed 75 ft/min (22.8 m/min).
6411 Parkland Drive 625 6th Street East
Brief gusts up to 300 ft./min (91.4 m/min.) are allowed. Sarasota, FL 34243 Owen Sound, Ontario
TM
USA Canada N4K 5P8
Technical Manuals Online! - http://www.tech-man.com
Technical Manuals Online! - http://www.tech-man.com
Product Information Specifications
DESCRIPTION LED Type Clear Lens,
The Remote LED Alarm Indicator, Model SIGA-LED, is a Red Light Emitting Diode
component of the Signature Series System. This polarized Luminous Intensity 65 mcd
device provides visual indication when a detector initiates an Operation Pulses on Alarm Condition
alarm. A clear lens, light emitting diode pulses on and off in the Resistance per Wire 10W Max.
event of an alarm condition. Operating Temperature Range 32 - 120°F (0 - 49°C)
Operating Humidity Range 0 - 93% RH
The SIGA-LED can ONLY be used with the Standard Detector
Base, Model SIGA-SB or SIGA-SB4. It is NOT compatible with Storage Temperature Range -4 - 140°F (-20 - 60°C)
any other bases. Compatible Detectors SIGA Series Detectors
Compatible Bases Standard Bases: SIGA-SB, -SB4
NOTE: -Not for use with 24V DC circuits.
Duct Applications
WARNINGS Duct Detector Mounting Plate, SIGA-DH
Compatible Electrical Boxes
1) This remote annunciator is NOT intended to be used as an North American 1-Gang Box
evacuation signal for Life Safety situations. Standard 4" Square Box 1-1/2" (38 mm) Deep w/ 1-Gang Cover
2) This remote annunciator will NOT operate if the device that Wire Size Max. Wire Distance
2
it is connected to it is not powered. #18 AWG (0.75 mm )* 1,567 ft. (478 m)
2
#16 AWG (1.0 mm )* 2,490 ft. (759 m)
3) The LED used in this device has a 180° range of visibility,
2
but the best visibility is achieved in direct viewing #14 AWG (1.5 mm )* 3,960 ft. (1,207 m)
applications. This device should NOT be installed in areas
* Preferred wire size.
of direct sunlight, or where its intensity may be reduced.
Construction & Finish High Impact
Engineering Polymer, White
Installation Instructions Shipping Weight 3.2 oz (90 g)
SIGA-LED
REMOTE LED ALARM INDICATOR
SPECIFICATIONS
Operating Voltage Range 15.2 to 19.95 VDC
Current Ratings
Class B IDC
Personality Code(s) 1, 2, 3, or 4
Standby Current 250 mA
Activated Current 400 mA
EOL Resistor 47 KW
Class A IDC
Personality Code(s) 9, 10, 11, or 12
Standby Current 223 mA
Activated Current 365 mA SIGA-MAB
EOL Resistor N/A
Class A or B NAC
Personality Code(s) 15 or 16
Standby Current 223 mA CHNO
LOGY
365 mA
S TE
Activated Current
STEM
S SY
47 KW for Class B
RD
ED
EOL Resistor
EDWA
JP2
IMIT
JP1
No EOL for Class A
RL
B
7356
E
-MA
Output Ratings
38 7 P O W
98 1 56 P
SIGAO.
24 VDC 2A
S
4733
3
0
N
UIT
25 V Audio 50 W
CAT
IRC
70 V Audio 35 W
LC
AL
SIGA-MAB
Class A/B Input/Output Module
INSTALLATION SHEET P/N: 387356P FILE NAME: 387356P.CDR
REVISION LEVEL: 1.0 APPROVED BY: R. Right
DATE: 08/17/98 CREATED BY: B. Graham
MOUNTING INSTRUCTIONS
! Caution! 4 Secure the module to the motherboard with both of its captive
screws.
Observe static-sensitive material handling practices. 5 Wire the terminal blocks according to the wiring instructions of this
installation sheet (following pages).
6 Write the module's address on the label provided and apply the label
to the module.
7 Peel off the removable bar-coded serial number label from the
module and apply it to the appropriate location in the Serial Number
Logbook.
387356P.CDR Page 2 of 4
Technical Manuals Online! - http://www.tech-man.com
Dry Contact Input Wiring (Personality Codes 1, 2, 3, 4, 9, 10, 11, or 12)
UL/ULC
Personality Codes: 1, 2, 3, or 4
Notes Listed
47KW
EOL
Maximum 25W resistance per
1 wire. Maximum circuit
1 2 4
capacitance of 0.1 mF.
SIGA-MAB
473387356
TB7
8 All wiring is supervised and codes 1, 2, 3, 4, 9, 10, 11, or
12.
CAT NO.
power-limited. Data Out
4
3 3
2
1
No connections required for SIGA-MAB using TB15
6 personality codes 1, 2, 3, 4, 9, 10, 11, or 12. Remove motherboard jumpers.
1 23 4
387356P.CDR Page 3 of 4
Technical Manuals Online! - http://www.tech-man.com
Single Input Wiring (Personality Code 15 or 16)
Personality Typical Speaker Circuit
! Transient Protection Caution Code 15
The SIGA-MAB requires transient protection for
installations that connect electromechanical bells or
horns to output circuits. The module's circuitry
requires a bi-polar transient protector (P/N
235196P) for protection against transient spikes
caused by the inductive load of bells or horns.
UL/ULC
Connect the bi-polar transient protector assembly Listed
across the terminals of the bell or horn electrically
closest to the module. The bi-polar transient Personality Typical Notification Appliance Circuit 47KW
EOL
protector is not polarity-sensitive. Code 16
+ + + + + +
Locate bells and horns at least 6ft. (1.83 m) from
the module.
_ _ _ _ _ _
Data In 4
3 Riser 1 Out
2
EDWARDS SYSTEMS TECHNOLOGY
4 1 Riser 1 In
Signature
3
Data TB14
2 JP2
Circuit 1
JP1
4 7 8 9
SIGA-MAB
TB7
473387356
Data Out
CAT NO.
Notes
1 For maximum resistance, see the appropriate technical reference manual. Maximum circuit capacitance is 0.1 mF.
Supervised and power limited when connected to a power limited source. If the source is non-power limited, power limited marking shall
7
be eliminated.
9 Use UL/ULC Regulated Power Supply listed for Fire Protective Signaling.
387356P.CDR Page 4 of 4
Technical Manuals Online! - http://www.tech-man.com
Product Information Specifications
DESCRIPTION Compatible Modules SIGA Series Modules (Table A)
The Transponder Mounting Bracket, Model SIGA-MB4, is a Compatible Electrical Boxes
component of the Signature Series System. This bracket allows North American 2-1/2" (64 mm) Deep 2-Gang Box
for mounting two 1-gang compatible modules in a European 100 Standard 4" Square Box 1-1/2" (38 mm) Deep Box
mm Square Box or Standard North American 4" Square Box. European 100 mm Square Box
WARNINGS
Ensure that the self-adhesive bar code label on the module is not
lost or damaged when removing the 1-gang module from the 1-
gang mounting bracket and installing it in the 2-gang mounting
bracket. Without the bar code label, you will be unable to
address the module.
Installation Instructions
The following items must be retained from the 1-gang
module(s) that are to be mounted in the SIGA-MB4:
• Self-adhesive address labels
• End-of-line resistors, if supplied
• Bilingual faceplate labels
• Peel-off bar code labels
Warning!
?
PROGRAMMING Disconnect power to the cabinets before removing or installing
components. Failure to do so may result in serious injury or loss of life.
Personality Code 5: Riser Selector (Single Input)
Personality code 5 configures the SIGA-MCC1 as a signal power (24 Vdc)
or audio evacuation (25 or 70 Vac) riser selector, and disables the ring-tone
generator. The output is monitored for open or shorted wiring. If a short ! Caution!
exists, the control panel inhibits the activation of the audible/visual signal
circuit, so the riser is not connected to the wiring fault.
Observe static-sensitive material handling practices.
Personality Code 6: Riser Selector (Single Input), Ring-tone
Personality code 6 configures the SIGA-MCC1 as a telephone riser
selector. When a telephone handset is plugged into its jack or lifted from its
hook, the SIGA-MCC1 will generate its own ring-tone signal. A separate SIGA-MCC1
ring-tone riser is not needed. The module sends a signal to the control
panel to indicate that an off-hook condition is present, and waits for the
system operator to respond to the call. When the system operator LOGY
ED
EDWA
IMIT
9 81 35 2P E R L
2
8735
-MC
38 7 P O W
SIGAO.
S
4733
0
N
UIT
INSTALLATION INSTRUCTIONS
CAT
IRC
LC
AL
5 Wire the terminal blocks according to the wiring instructions of this SIGA-MCC1
installation sheet (next page).
Single Input Signal Module
6 Write the address assigned to the module on the label provided and
apply the label to the module. INSTALLATION SHEET P/N: 387352P FILE NAME: 387352P.CDR
7 Peel off the removable bar coded serial number label from the module REVISION LEVEL: 1.0 APPROVED BY: R. Right
and apply it to the appropriate location in the Serial Number Logbook. DATE: 08/17/98 CREATED BY: B. Graham
Note: All wiring should conform to NFPA 70-1996, National Electrical Code GS BUILDING SYSTEMS CORPORATION
A UNIT OF GENERAL SIGNAL
Article 760, Section 760-54(a)(1), Exception No. 2 and 3. Refer to 6411 Parkland Drive 625 6th Street East
UIO series motherboard installation sheets for wire routing GS BUILDING SYSTEMS Sarasota, FL 34243 Owen Sound, Ontario
CORPORATION
information. USA Canada N4K 5P8
Technical Manuals Online! - http://www.tech-man.com
WIRING
Personality Typical Speaker Circuit
! Transient Protection Caution
Code 5
UL/ULC Listed
The SIGA-MCC1 requires transient protection
47KW EOL
for installations that connect electromechanical
bells or horns to output circuits. The module's
circuitry requires a bi-polar transient protector
(P/N 235196P) for protection against transient
spikes caused by the inductive load of bells or Personality Typical Telephone Circuit
horns. Code 6
Connect the bi-polar transient protector
assembly across the terminals of the bell or UL/ULC Listed
horn electrically closest to the module. The bi- 47KW EOL
polar transient protector is not polarity-sensitive.
Locate bells and horns at least 6ft. (1.83 m)
from the module. Personality Typical Notification Appliance Circuit
Code 5
+ + + + + +
UL/ULC Listed
Bi-polar Transient Protector (P/N 235196P) _ _ _ _ _ _ 47KW EOL
Data In 6 3 4
3
Riser 1 In
2
EDWARDS SYSTEMS TECHNOLOGY
1 Riser 1 Out
Signature 4
Data 3 TB14
Circuit 2 4 7 8 9
1
SIGA-MCC1
473387352
TB7
CAT NO.
Data Out
4 No connections required for
3
2 SIGA-MCC1. Other modules
1 may require connections.
Green LED (Normal) TB15
Red LED (Active)
SIGA-UIOR series motherboard
1 23 4 individual Riser 1 connection. Install
5 7 9 the jumpers between adjacent
modules that use the same riser.
Riser 1 In Riser 1 Out
Notes Warnings
For maximum resistance, see the appropriate technical reference manual.
1 1 The SIGA-MCC1 will not operate without electrical
Maximum circuit capacitance is 0.1mF.
power. As fires frequently cause power interruption,
2 we suggest you discuss further safeguards with your
Maximum #12 AWG (2.5 mm ) wire; Minimum #18 AWG (0.75 mm ).
2 2
9 Use UL/ULC Regulated Power Supply listed for Fire Protective Signaling.
387352P.CDR Page 2 of 2
Technical Manuals Online! - http://www.tech-man.com
PRODUCT INFORMATION SPECIFICATIONS
DESCRIPTION Operating Voltage Range 15.2 to 19.95 Vdc
The SIGA-MCC2 Dual Input Signal Module is an addressable Signature Standby Current 223 mA
Series component, which connects supervised output circuits to signal
risers 1 and 2. The SIGA-MCC2 does not supervise the riser; the fire Activated Current 100 mA
alarm panel must provide this function. Upon command from the Output Ratings
Signature controller, the SIGA-MCC2 connects the output circuit to the 24 Vdc 2A
riser input, which may be 24 Vdc, to operate polarized audible and visual 25 V Audio 50 W
appliances, or 25/70 Vac, to operate audio evacuation circuits. 70 V Audio 35 W
During system configuration, the Signature controller downloads the EOL Resistor Value 47 KW
personality code, which determines the function performed by the SIGA- Operating Temperature 32 to 120 °F (0 to 49 °C)
MCC2, and automatically assigns the two addresses it requires. A
custom address can be assigned to the module via the SIGA-PRO. No Operating Humidity 0 to 93% RH
addressing switches are used. Storage Temperature -4 to 140 °F (-20 to 60 °C)
Note: See the programming information, below, for the definitions of the Construction High impact engineering polymer
personality codes.
Shipping Weight 0.10 lb (0.05 kg)
Diagnostic LEDs provide visible indication of module status. A flashing
green LED indicates normal status. A flashing red LED indicates the Mounting SIGA-UIO(R) series motherboard
alarm/active state.
The SIGA-MCC2 plugs into any available module space on a SIGA-
UIO(R) series motherboard, and captive screws secure it to the board.
All wiring connections are made to terminals on the motherboard.
Warning!
?
PROGRAMMING Disconnect power to the cabinets before removing or installing
components. Failure to do so may result in serious injury or loss of life.
ED
EDWA
9 81 35 3P E R L
C
3
8735
-MC
38 7 P O W
SIGAO.
0
N
UIT
installation sheet.
CAT
IRC
LC
AL
1 23 4 SIGA-MCC2
7 8 9
6 3
4
Data In 3 Riser 1 Out
2
EDWARDS SYSTEMS TECHNOLOGY
1 Riser 1 In
Signature 4
3 TB14
Data 2
Circuit 1
SIGA-MCC2
473387353
TB7
CAT NO.
Data Out 7 8 9
4
3 Riser 2 Out
2
1 Riser 2 In
Green LED (Normal) TB15
Red LED (Active)
SIGA-UIOR series motherboard
7 9 individual Riser 1 connection. Install
the jumpers between adjacent
1 23 4 modules that use the same riser.
Riser 1 In Riser 1 Out
Notes
For maximum resistance, see the appropriate technical reference
1
manual. Maximum circuit capacitance is 0.1 mF.
3 See the Signature controller installation sheet for wiring specifications. Warnings
4 The SIGA-UIO6R and the SIGA-UIO2R do not come with TB14.
1 The SIGA-MCC2 will not operate without electrical
5 The SIGA-UIO6 does not come with TB8 through TB13. power. As fires frequently cause power interruption, we
suggest you discuss further safeguards with your local
6 Supervised and power limited. fire protection specialist.
2 The personality code for the SIGA-MCC2 is factory set
7 Supervised and power limited when connected to a power limited to 7.
source. If the source is non-power limited, power-limited marking shall
be eliminated. 3 The SIGA-MCC2 does not support conventional smoke
detectors.
8 The input for this riser is common to all modules.
387353P.CDR Page 2 of 2
Technical Manuals Online! - http://www.tech-man.com
PRODUCT INFORMATION SPECIFICATIONS
Description
Operating Voltage Range 15.2 to 19.95 Vdc
The SIGA-MCR Control Relay Module is an addressable Signature
Series component. A Form C dry contact relay in the SIGA-MCR may Standby Current 100mA
control equipment shutdown or external appliances like door closers, Activated Current 100mA
fans, and dampers. The system firmware ensures that the relay is in
the proper ON/OFF state. The SIGA-MCR relay energizes upon Contact Rating (Pilot Duty)
command from the Signature controller. 30 Vdc 2A
120 Vac 0.5 A
The SIGA-MCR requires one device address, which the Signature
controller automatically assigns. A custom address can be assigned to Relay Type Form C
the module via the SIGA-PRO. No addressing switches are used. Operating Temperature 32 to 120 °F (0 to 49 °C)
Note: See Programming, below, for the application and definition of Operating Humidity 0 to 93% RH
personality code 8.
Storage Temperature -4 to 140 °F (-20 to 60 °C)
Diagnostic LEDs provide visible indication of module status. A flashing
green LED indicates normal status. A flashing red LED indicates the Construction High impact engineering polymer
alarm/active state. Shipping Weight 0.10 lb (0.05 kg)
The SIGA-MCR plugs into any available module space on a SIGA- Mounting SIGA-UIO(R) series motherboard
UIO(R) series motherboard, and captive screws secure it to the board.
All wiring connections are made to terminals on the motherboard.
?
PROGRAMMING Warning!
Personality Code 8: Dry Contact Output
The SIGA-MCR is factory assigned personality code 8, which Disconnect power to the cabinets before removing or installing
configures the SIGA-MCR as an output dry contact relay. components. Failure to do so may result in serious injury or loss of life.
3 Plug the SIGA-MCR into any available position on the motherboard. LOGY
CHNO
S TE
STEM
D
EDWA
ITE
screws.
LIM
R
ER
8
8735
#0.0
387 P O W
ATIB 9810 58P
SIGAO.
3
N
UIT
ILIT
CAT
IRC
6 Write the module's address on the label provided and apply the
LC
MP
AL
7 Peel off the removable bar-coded serial number label from the
module and apply it to the appropriate location in the Serial Number
Logbook.
INSTALLATION SHEET:
SIGA-MCR
Control Relay (Dry)
2 6
1 23 4 SIGA-MCR
5 1 SIGA-UIO(R) series motherboard
Data In
3
4 4
3 3
2
SIGA-MCR
473387358
may require connections.
CAT NO.
4
3
2
Green LED (Normal) 1
Red LED (Active) TB15
1 23 4
4
No connections required for
SIGA-MCR. Other modules
may require connections.
Warnings
Notes
7 Maximum #12 AWG (2.5 mm2 ) wire; Minimum #18 AWG (0.75 mm2 ).
387358P.CDR Page 2 of 2
Technical Manuals Online! - http://www.tech-man.com
PRODUCT INFORMATION SPECIFICATIONS
Description Operating Voltage Range 15.2 to 19.95 Vdc
The SIGA-MCRR Control Reversing Relay Module is an addressable Standby Current 100mA
Signature Series component used to power and activate the audible
sounder in SIGA-AB4 audible bases. Upon command from the Activated Current 100mA
Signature controller, the SIGA-MCRR relay energizes, reversing the Contact Rating (Pilot Duty)
polarity of its 24 Vdc output. 24 Vdc 2A
The SIGA-MCRR requires one device address, which the Signature 120 Vac 0.5 A
controller assigns to it automatically. A custom address can be assigned Relay Type Form C
to the module via the SIGA-PRO. No addressing switches are used.
Operating Temperature 32 to 120 °F (0 to 49 °C)
Note: See the programming information, below, for the application and
definition of Personality Code 8. Operating Humidity 0 to 93% RH
Diagnostic LEDs provide visible indication of module status. A flashing Storage Temperature -4 to 140 °F (-20 to 60 °C)
green LED indicates normal status. A flashing red LED indicates the Construction High impact engineering polymer
alarm/active state.
Shipping Weight 0.10 lb (0.05 kg)
The SIGA-MCRR plugs into any available module space on a SIGA-
UIO(R) series motherboard, and captive screws secure it to the board. Mounting SIGA-UIO(R) series motherboard
All wiring connections are made to terminals on the motherboard.
?
PROGRAMMING Warning!
Personality Code 8: Contact Output
The SIGA-MCRR is factory assigned personality code 8, which Disconnect power to the cabinets before removing or installing
configures the SIGA-MCRR as an output dry contact relay. components. Failure to do so may result in serious injury or loss of life.
! Caution!
INSTALLATION INSTRUCTIONS
Observe static-sensitive material handling practices.
The SIGA-MCRR is shipped from the factory as an assembled unit; it
contains no user-servicable parts and should not be disassembled.
D
EDWA
ITE
motherboard.
LIM
R R
ER
7359
-MC
#0.0
3 87 P OW
Y ID
S
screws.
4733
3
N
UIT
ILIT
CAT
IRC
LC
6 Write the address assigned to the module on the label provided and
apply the label to the module.
7 Peel off the removable bar coded serial number label from the
module and apply it to the appropriate location in the Serial Number
Logbook.
IN/OUT
JW1
JW1 JW2
JW2 6254A-003
Polarity reverses EOL Relay
10 11
1
(+)IN/OUT
OUT
when activated. required for
2
DATA (-)(-)OUT
DATA (-)(-)ININ
supevision
9
DATA(+)
SIG ++
DATA
DATA
8
SIG- -
DATA
SIG
SIG
7
6
5
4 8 7
Signature
Data Data Out
Circuit
For normal operation SIGA-CT1
For General Fire
5
Alarm Operation
UL/ULC Listed 4 3 2 1
24 Vdc power
supply or
1 23 4 1 23 4
SIGA-MCRR
4 1 SIGA-UIO(R) series motherboard
Data Out 4
3
2
EDWARDS SYSTEMS TECHNOLOGY
SIGA-MCRR
473387360
473387359
TB7
CAT NO.
CAT NO.
Data In
4 Green LED (Normal)
3 Red LED (Active)
2
1 No connections required for
TB15 SIGA-MCRR. Other modules
Green LED (Normal) may require connections.
Red LED (Active) 1 23 4 1 23 4
3 3
Optional SIGA-MCRR
or SIGA-MCR for No connections required
disabling/disconnecting for SIGA-MCRR. Other
an audible base. modules may require
Notes
connections.
1 Refer to the Signature controller installation sheet for wiring
specifications.
Warnings 2 The SIGA-UIO6R and the SIGA-UIO2R do not come with TB14.
387359P.CDR Page 2 of 2
Technical Manuals Online! - http://www.tech-man.com
PRODUCT INFORMATION SPECIFICATIONS
DESCRIPTION
Operating Voltage Range 15.2 to 19.95 Vdc
The SIGA-MCT2 Dual Input Module is an addressable Signature Series
component used to connect up to two Class B normally-open dry contact Standby Current 396 mA
initiating device circuits (IDCs) to a Signature controller. Activated Current 680 mA
The Signature controller downloads the personality code to the SIGA- Operating Temperature 32 to 120 °F (0 to 49 °C)
MCT2 during system configuration to determine its application: alarm,
supervisory, or monitor. The SIGA-MCT2 requires two addresses, which Operating Humidity 0 to 93% RH
the Signature controller assigns to it automatically. A custom address can Storage Temperature -4 to 140 °F (-20 to 60 °C)
be assigned to the module via the SIGA-PRO. No addressing switches are
used. Construction High impact engineering polymer
Note: See the programming information, below, for the definitions of the Shipping Weight 0.10 lb (0.05 kg)
personality codes. Mounting SIGA-UIO(R) series motherboard
Diagnostic LEDs provide visible indication of module status. A flashing Initiating Device Circuit
green LED indicates normal status. A flashing red LED indicates the EOL Resistor Value 47 KW, UL Listed
alarm/active state.
Max. Circuit Resistance 50 W (25 W per wire)
The SIGA-MCT2 plugs in any available module space on a SIGA-UIO(R) Max. Circuit Capacitance 0.1 mF
series motherboard, and captive screws secure it to the motherboard. All
wiring connections are made to terminals on the motherboard. Wire Size Max Distance to EOL Resistor
#18 AWG (0.75 mm ) 2
3,930 Ft (1,198 M)
? #16 AWG (1.0 mm ) 2
6,225 Ft (1,897 M)
PROGRAMMING #14 AWG (1.5 mm ) 2
9,900 Ft (3,018 M)
Personality Code 1: N/O Alarm Latching (Class B)
Personality code 1 configures the SIGA-MCT2 for Class B normally-open
dry contact initiating devices (for example: pull-stations and heat Warning!
detectors). When the N/O input contact of an initiating device closes, an
alarm signal is sent to the Signature controller and the alarm condition is
Disconnect power to the cabinets before removing or installing
latched at the module. This is the default personality code assigned by the
components. Failure to do so may result in serious injury or loss of life.
factory.
Personality Code 2: N/O Alarm Delayed Latching (Class B)
Personality code 2 operates like personality code 1, but the contact must
remain closed for approximately 16 seconds before an alarm status is ! Caution!
generated. Personality code 2 is only used with non-retarded waterflow
alarm switches. Observe static-sensitive material handling practices.
Personality Code 3: N/O Active Non-latching (Class B)
Personality code 3 typically monitors equipment like fans, dampers, and
doors. A contact closure causes an active status, which does not latch at the
module, instead of an alarm status.
SIGA-MCT2
Personality Code 4: N/O Active Latching (Class B)
Personality code 4 typically monitors supervisory and tamper switches. A
GY
NOLO
ED
EDWA
IMIT
1
8735
-MC
38 7 P O W
SIGAO.
ITS
4733
0
N
INSTALLATION INSTRUCTIONS
CU
CAT
IR
LC
AL
7 Peel off the removable bar coded serial number label from the module REVISION LEVEL: 1.0 APPROVED BY: R. Right
and apply it to the appropriate location in the Serial Number Logbook. DATE: 08/17/98 CREATED BY: B. Graham
Note: All wiring should conform to NFPA 70-1996, National Electrical GS BUILDING SYSTEMS CORPORATION
Code Article 760, Section 760-54(a)(1), Exception No. 2 and 3.
A UNIT OF GENERAL SIGNAL
6411 Parkland Drive 625 6th Street East
Refer to UIO motherboard installation sheets for wire routing GS BUILDING SYSTEMS Sarasota, FL 34243 Owen Sound, Ontario
information. CORPORATION
USA Canada N4K 5P8
Technical Manuals Online! - http://www.tech-man.com
WIRING
1 2 4
SIGA-MCT2
1 23 4
SIGA-UIO(R) series motherboard
3
Data In 4
3
5
EDWARDS SYSTEMS TECHNOLOGY
2
4 1
Signature 3 TB14 No connections required for
Data 2
1
SIGA-MCT2
Circuit
SIGA-MCT2
473387351
Data Out
4
3
2
1
Green LED (Normal)
TB15
Red LED (Active)
1 2 3 4
Notes Warnings
1 Maximum 25 W resistance per wire. 1 The SIGA-MCT2 will not operate without electrical
power. As fires frequently cause power interruption, we
2 Maximum #12 AWG (2.5 mm ) wire; Minimum #18 AWG (0.75 mm ).
2 2
suggest you discuss further safeguards with your local
fire protection specialist.
3 Refer to Signature controller installation sheet for wiring specifications.
2 The personality code for the SIGA-MCT2 is factory set
to 1.
4 Maximum 10 Vdc @ 350 mA
3 The SIGA-MCT2 does not support conventional smoke
5 The SIGA-UIO6R and the SIGA-UIO2R do not come with TB14. detectors.
387351P.CDR Page 2 of 2
Technical Manuals Online! - http://www.tech-man.com
PRODUCT INFORMATION SPECIFICATIONS
DESCRIPTION
The Monitor Module, Model SIGA-MM1, is a component of the Signature Operating Voltage Range 15.2 - 19.95 Vdc
Series System. The SIGA-MM1 is an analog addressable device used to Standby Current 250mA
connect a Class B normally-open monitor type dry contact Initiating Device Activated Current 400mA
Circuit (IDC) to a Signature Loop Controller. One (1) device address is
Operating Temperature Range 32 to 120°F (0 to 49°C)
required.
Operating Humidity Range 0 to 93% RH
The loop controller assigns an address to the SIGA-MM1 automatically or a Storage Temperature Range -4 to 140°F (-20 to 60°C)
custom address can be assigned to the module via laptop computer; no Construction High Impact Engineering
addressing switches are used. Polymer
Shipping Weight 5.1 oz (145 g)
Diagnostic LEDs provide visible indication of the status of the module when Compatible Electrical Boxes
the cover plate is removed. North American 2-1/2" (64 mm) Deep 1-Gang Box
Standard 4" Square Box 1-1/2" (38 mm) Deep Box w/1-Gang Cover
Initiating Device Circuit (IDC):
EOL Resistor Value (EOLR) 47KW, UL Listed
Status LED Indicator Max. Circuit Resistance 50W (25W per wire)
Max. Circuit Capacitiance 0.1mF
Normal Green LED flashes.
Alarm/Active Red LED flashes.
Wire Size Max. Distance to EOLR
#18 AWG (0.75 mm 2 ) 3,930' (1,198m)
The SIGA-MM1 can be mounted in a North American 2-1/2" (64 mm) deep 1- #16 AWG (1.0 mm 2 ) 6,225' (1,897m)
gang box, or standard 4" square box 1-1/2" (38 mm) deep with 1-gang cover.
The terminal blocks will accept #14, 16, or 18 AWG wire (1.5 mm 2, 1.0 mm 2 , #14 AWG (1.5 mm 2) 9,900' (3,018m)
0.75 mm2 ). Sizes #16 and #18 are preferred.
IMPORTANT NOTE:
TRANSIENT PROTECTION
INSTALLATION SHEET:
SIGA-MM1
Monitor Module
Strip 1/4" (6.4 mm) from the ends of ALL wires that connect to the
terminal block of the module.
CAUTION:
Exposing more than 1/4" (6.4 mm) of wire may cause a ground fault.
Exposing less than 1/4" (6.4 mm) of wire may result in a faulty
connection.
The SIGA-MP1 is a mounting plate which allows for Size 9.25" x 6.25" (L x W)
installation of four (4) SIGA-CC1's, SIGA-CC2's., or SIGA-UM's Material 1/8" Aluminum
( larger modules) or eight (8) CT-1's, CT-2's, SIGA-CR's, SIGA- Weight .6 lb. (.27kg)
MM1's, or SIGA-WTM's (smaller modules). Any combination Mounting 1 Standard Module
of the SIGA modules can be mounted on the SIGA-MP1. Footprint
The SIGA-MP1 is a flat aluminum plate which mounts in Module Space Available 4
EST's standard equipment enclosures. (Refer to the Network (Large)
Hardware Technical Reference Manual Vol. 1 for Module Space Available 8
information on equipment enclosures.) The plate can be (Small)
mounted in any standard full footprint OPTION module
position in the enclosure. The SIGA-MP1 removes the need Figure 1
for gang boxes and provides the ease of mounting
needed equipment in a common enclosure.
Warnings
Installation Instructions
ECN95 - 0742
Mounting the SIGA-MP1:
SHT 5 OF 13
1. Mount the SIGA-MP1 in a standard enclosure. The
SIGA-MP1 requires one standard full footprint and
mounts in any OPTION module position using #6
screws. (Refer to Figure 3.)
SIGA M
ODULE
SIGA-MP
1
ENCLOSURE BACKPLATE
Standoffs
TB3 TB3
10 9 10 9
8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1
TB1 TB1
SIGA-MP1
WITH MODULES
TB3
#6 Screws TB3
10 9
10 9
8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1
TB1 TB1
The SIGA-MP2 is a mounting plate which allows for Size 8.25" x 2.75" (L x W)
installation of two (2) SIGA-CC1's, SIGA-CC2's., or SIGA-UM's Material 1/8" Aluminum
(larger modules) or four (4) CT-1's, CT-2's, SIGA-CR's, SIGA- Weight .45 lb (.2kg)
MM1's, or SIGA-WTM's (smaller modules). Any combination Mounting 1/2 Standard Module
of the SIGA modules can be mounted on the SIGA-MP2. Footprint
The SIGA-MP2 is a flat aluminum plate which mounts in Module Space Available 2
EST's standard equipment enclosures. (Refer to the Network (Large)
Hardware Technical Reference Manual Vol. 1 for Module Space Available 4
information on equipment enclosures.) The plate can be (Small)
mounted in any standard 1/2 footprint OPTION module
position on the inside, left/right side of the enclosure. The
SIGA-MP2 removes the need for gang boxes and provides
Figure 1
the ease of mounting needed equipment in a common
enclosure.
Warnings
2. Snap the SIGA-MP2 onto the two (2) stand-offs INSTALLATION SHEET:
located on the inside left or right side of the SIGA-MP2
enclosure. Either side is adequate depending on MOUNTING PLATE
the enclosure setup. (Refer to Figure 3.)
INSTALLATION SHEET PART NO.: 387161 FILE NAME: 387161.CDR
3. Wire modules per the appropriate installation REVISION LEVEL: 1.0 APPROVED BY: Project Engineer
sheets. (Refer to the Signature Series Technical DATE: 7/24/95 CREATED BY: DRM
Reference Manual or the EST2 Technical Reference
Manual for module installation sheets.) EDWARDS SYSTEMS TECHNOLOGY
SARASOTA, FL. 813-755-4811 Fax: 941-751-6384
FARMINGTON, CT. 203-678-0410 Fax: 203-677-1621
OWEN SOUND, CANADA 519-376-2430 Fax: 519-376-7258
INTERNATIONAL: CANADA 905-678-6767 Fax: 905-678-2872
SIGA-MP2
SIGA M
ODULE
TYPICAL ENCLOSURE
SIGA-MP2
Mounting Plate
Standoffs
Standard Standard
1/2 Footprint SIGA Modules 1/2 Footprint
Module Space Module Space
Standoffs
The SIGA-MP2L is a mounting plate which allows for Size 11.8" x 2.75" (L x W)
installation of three (3) SIGA-CC1's, SIGA-CC2's., or SIGA- Material 1/8" Aluminum
UM's (larger modules) or six (6) CT-1's, CT-2's, SIGA-CR's, SIGA- Weight .3lb (.14kg)
MM1's, or SIGA-WTM's (smaller modules). Any combination Mounting 1/2 Standard Module
of the SIGA modules can be mounted on the SIGA-MP2L. Footprint
The SIGA-MP2L is a flat aluminum plate which mounts in Module Space Available 3
EST's standard equipment enclosures. (Refer to the Network (Large)
Hardware Technical Reference Manual Vol. 1 for Module Space Available 6
information on equipment enclosures.) The plate can be (Small)
mounted in any standard 1/2 footprint OPTION module
position on the inside, left/right side of the enclosure. The
SIGA-MP2L removes the need for gang boxes and provides
Figure 1
the ease of mounting needed equipment in a common
enclosure.
Warnings
2. Snap the SIGA-MP2L onto the two (2) stand-offs INSTALLATION SHEET:
located on the inside left or right side of the SIGA-MP2L
enclosure. Either side is adequate depending on MOUNTING PLATE
the enclosure setup. (Refer to Figure 3.)
INSTALLATION SHEET PART NO.: 387162 FILE NAME: 387162.CDR
3. Wire modules per the appropriate installation REVISION LEVEL: 1.0 APPROVED BY: Project Engineer
sheets. (Refer to the Signature Series Technical DATE: 7/24/95 CREATED BY: DRM
Reference Manual or the EST2 Technical Reference
EDWARDS SYSTEMS TECHNOLOGY
Manual for module installation sheets.) SARASOTA, FL. 813-755-4811 Fax: 941-751-6384
FARMINGTON, CT. 203-678-0410 Fax: 203-677-1621
OWEN SOUND, CANADA 519-376-2430 Fax: 519-376-7258
INTERNATIONAL: CANADA 905-678-6767 Fax: 905-678-2872
SIGA-MP2L
SIGA M
ODULE
TYPICAL ENCLOSURE
SIGA-MP2L
Mounting Plate
Standoffs
Standard Standard
1/2 Footprint 1/2 Footprint
Module Space Module Space
SIGA Modules
Standoffs
WARNINGS
1) This detector will NOT operate without electrical power. As fires INSTALLATION SHEET
frequently cause power interruption, discuss further safeguards
with your local fire protection specialist. SIGA-PHS
2) This detector will NOT sense fires in areas where smoke cannot Intelligent 3D Multisensor
reach the detector. Smoke from fires in walls, roofs, or on the
opposite side of closed doors may not reach the detector.
Smoke Detector
3) Photoelectric detectors have a wide range of sensing capabilities,
and are best suited for detecting slow, smoldering fires. The heat INSTALLATION SHEET P/N: 387015P FILE NAME: 387015P.CDR
sensor in this device provides a source of supplemental REVISION LEVEL: 7.0 APPROVED BY: R. Right
information to that provided by the photoelectric smoke sensor.
The heat sensor by itself does NOT provide life safety protection. DATE: 09DEC98 CREATED BY: D. Chinell
4) Maintenance (regular or selected) should be planned in RELATED DOCUMENTS
accordance with the requirements of the Authority Having Technical Bulletin (P/N 270145)
Jurisdiction to ensure proper operation. Refer to NFPA 72 and
ULC Standard CAN 536. EDWARDS SYSTEMS TECHNOLOGY
5) The bright orange-colored dust cover (supplied) MUST remain on
the detector during installation, and then be removed prior to 6411 Parkland Drive 625 6th Street East
TM
Sarasota, FL 34243 Owen Sound, Ontario
USA Canada N4K 5P8
Technical Manuals Online! - http://www.tech-man.com
Technical Manuals Online! - http://www.tech-man.com
PRODUCT INFORMATION 6) The bright orange-colored dust cover (supplied) MUST remain on
the detector during installation, and then be removed prior to
operation. The dust cover is NOT a substitute for removing the
Description: The Intelligent Photoelectric Smoke Detector (PS) is a detector during new construction or heavy remodeling.
component of the Signature Series. This intelligent analog device
7) Under normal conditions, this unit does not require calibration.
uses an optical sensing chamber to detect smoke. The detector
However, if calibration is required, return to:
analyzes the sensor data to determine when an alarm is initiated.
The detector continuously monitors changes in sensitivity due to the GS Building Systems Corporation
environment (e.g. dirt, smoke, temperature, humidity) and notifies the 5 North Main Street
loop controller of its condition. The PS issues a dirty sensor warning Pittsfield, ME 04967-1500
when it reaches its preset limit. This notifies the operator of the need Refer to the Technical Bulletin for additional information and
for service while the detector is still operating within UL/ULC limits. cleaning instructions.
LEDs: The PS provides two LEDs that show its status.
Normal: green LED flashes 8) Test the detector with Smoke Detector Tester and Model 1490
Alarm/active: red LED flashes Adapter/Tube Accessory, manufactured by Home Safeguard, Inc.
Standalone alarm: both LEDs glow continuously
Electronic addressing: The loop controller automatically assigns
addresses to the detectors. Custom addresses can be assigned to
the detectors via laptop computer. No addressing switches are used.
SPECIFICATIONS
Standalone operation: If unable to communicate with the loop
controller, the detector alarms when smoke levels exceed its preset Operating voltage range: 15.2 to 19.95 Vdc
value. Refer to the applicable fire alarm control panel manual for Normal operating current: 45 mA
verification of standalone capabilities. Alarm current: 45 mA
Self-diagnostics: PS contains a microprocessor capable of Standalone alarm current: 18 mA
performing comprehensive self-diagnostics and storing the results. Air velocity range: 0 to 5000 ft/min (0 to 25.39 m/s)
Details such as hours of operation, last maintenance date, sensitivity ULI/ULC smoke sensitivity range: 0.67 to 3.77 % obsc/ft (305 mm)
values, and number of alarms and troubles are stored in non-volatile Operating temperature range: 32 to 120 °F (0 to 49 °C)
memory. These can be retrieved and reviewed as desired. Operating humidity range: 0 to 93 % RH, non-condensing
Storage temperature range: -4 to 140 °F (-20 to 60 °C)
Environmental compensation: Automatic
Construction and finish: High impact engineering polymer, white
Compatible bases
INSTALLATION INSTRUCTIONS Standard: SB, SB4
Relay: RB, RB4
1) Push a small screwdriver into the tamper-resist access slot while Isolator: IB, IB4
rotating the detector counterclockwise to remove the detector. Audible: AB4
Note: You can permanently disable the tamper-resist mechanism Shipping weight: 7.7 oz (218 g)
by breaking and removing the plastic lever arm from the base. Maximum distance from ceiling wall-mounted: 12 in. (305 mm)
2) See the Technical Bulletin for installation guidelines.
3) Install and wire the base as described in the installation sheet
supplied with the base. PRODUCT DIAGRAM
4) Peel off the removable serial number label from the detector and
apply it to the appropriate location in the serial number log book.
5) Connect the detector to the base by rotating the detector
clockwise until it snaps into the locked position.
6) NFPA code requires that a calibrated sensitivity test be performed Tamper-Resist Lever Arm
- Break off to disable -
upon completion of the original installation and following any (Located on Base)
modifications or additions to the system. The Signature Series
can perform this test and generate a system sensitivity report.
7) In Canada your installation must meet the requirements of
CAN/ULC-S524-M91: Standard for the Installation of Fire Alarm Access Slot for
Systems, and the local Authority Having Jurisdiction. Tamper-Resist Mechanism
8) Before initial testing, remove the dust cover from the detector and
notify the proper authorities that the fire alarm system is
undergoing maintenance and will be temporarily out of service.
WARNINGS
INSTALLATION SHEET
1) This detector will NOT operate without electrical power. As fires SIGA-PS
frequently cause power interruption, discuss further safeguards
with your local fire protection specialist.
Intelligent Photoelectric
2) This detector will NOT sense fires in areas where smoke cannot Smoke Detector
reach the detector. Smoke from fires in walls, roofs, or on the
opposite side of closed doors may not reach the detector.
INSTALLATION SHEET P/N: 387014P FILE NAME: 387014P.CDR
3) Photoelectric detectors have a wide range of sensing capabilities,
but are best suited for detecting slow, smoldering fires. REVISION LEVEL: 7.0 APPROVED BY: R. Right
4) Maintenance (regular or selected) should be planned in DATE: 09DEC98 CREATED BY: D. Chinell
accordance with the requirements of the Authority Having RELATED DOCUMENTS
Jurisdiction to ensure proper operation. Refer to NFPA 72 and Technical Bulletin (P/N 270145)
ULC Standard CAN 536.
5) To ensure proper operation, store the detector within the EDWARDS SYSTEMS TECHNOLOGY
recommended ranges. Allow the detector to stabilize to room 6411 Parkland Drive 625 6th Street East
temperature before applying power. Sarasota, FL 34243 Owen Sound, Ontario
TM
USA Canada N4K 5P8
Technical Manuals Online! - http://www.tech-man.com
Technical Manuals Online! - http://www.tech-man.com
WIRING DIAGRAMS SPECIFICATIONS
Operating Temperature Range 32 to 120 °F (0 to 49 °C)
Relay Detector Base, SIGA-RB Operating Humidity Range 0 to 93% RH
Shipping Weight
SIGA-RB 3.2 oz (91 g)
CONTACT RATING
1.0 Amp @ 30 VDC
(Pilot Duty)
INSTALLATION SHEET
SIGA-RB
Detector Base
DATE: 01/18/99
7
7
4
4
7
4
_
3
3
1
1
3
+
1
S 2 2 2
2 2 3
_ Insulate Shield/Drain
with tape Shield/Drain
+
S
Control Panel
1. Shielded wire is required ONLY in environments with very high electrical noise.
3 For Class B wiring, there is no shield connection to ground at the last device.
MOUNTING DIAGRAMS
1.5 in
1.1 in (38 mm)
(27 mm)
0.8 in 0.8 in
(20 mm) (20 mm)
2.0 in 2.0 in
(51 mm) (51 mm)
3-1/2 in or 4 in by 1-1/2 in (38 mm) Deep Octagon Box European 1-Gang (75 mm) Box 60.3 mm Fixing Centers
1.5 in
(38 mm) 1.75 in
(45 mm)
0.8 in
(20 mm) 0.8 in
(20 mm)
2.0 in
(51 mm) 2.0 in
(51 mm)
INSTALLATION SHEET
SIGA-RB4
Detector Base
DATE: 01/18/99
Refer to Standard Detector Base Relay Detector Base Isolator Detector Base
compatible panel
Installation Sheet
for terminal
assignments.
6 6 6
5 5 5
7
7
4
4
7
4
_
3
3
1
1
3
+
1
S 2 2 2
2 2 3
_ Insulate Shield/Drain
with tape Shield/Drain
+
S
Control Panel
1. Shielded wire is required ONLY in environments with very high electrical noise.
3 For Class B wiring, there is no shield connection to ground at the last device.
MOUNTING DIAGRAMS
4 in by 1-1/2 in (38 mm) Deep Square Box (Surface Mount) 4 in Box Trim Skirt/Ring
1.5 in
(38 mm)
0.8 in
(20 mm)
2.0 in
(51 mm)
4 in by 1-1/2 in (38 mm) Deep Square Box (Flush Mount) Flush Mount Electrical Box
NOTES:
1) A 4 in Box Trim Skirt/Ring (SIGA-TS) must be installed to give a
"finished" appearance to the 4 in base.
1.5 in
2) Refer to Installation Sheet P/N 387056P for additional information.
(38 mm)
0.8 in
(20 mm)
2.0 in
(51 mm)
6
Compatible Electrical Boxes
5 North American 1-Gang Box
3-1/2 in by 1-1/2 in (38 mm) Deep Octagon Box
4 in by 1-1/2 in (38 mm) Deep Octagon Box
7
4
NOTES:
2
DATA OUT (-) 1) The SIGA-SB provides wiring terminals for connection to Remote
DATA IN (-)
LED, Model SIGA-LED.
2) These bases will accept 12, 14, 16, and 18 AWG (2.05 sq mm, 1.5 sq
mm, 1.0 sq mm, and 0.75 sq mm) wire. Sizes 16 and 18 are
DATA IN (+) DATA OUT (+) preferred.
From Signature Controller To Next Device 3) Write the address assigned to the detector on the label provided and
or Previous Device apply the label to the inside rim of the base.
4) Break wire run at each terminal. Do not loop signaling circuit field
wires around terminals.
Term Description
1 Not Used
2 DATA IN/OUT (+)
3
4
Not Used
DATA IN (-)
SIGA-SB
4 Remote LED
5 Remote LED
6 Not Used
7 DATA OUT (-)
INSTALLATION SHEET
SIGA-SB
Detector Base
DATE: 01/18/99
6 6 6
5 5 5
7
7
4
4
7
4
_
3
3
1
1
3
+
1
S 2 2 2
2 2 3
_ Insulate Shield/Drain
with tape Shield/Drain
+
S
Control Panel
1. Shielded wire is required ONLY in environments with very high electrical noise.
3 For Class B wiring, there is no shield connection to ground at the last device.
MOUNTING DIAGRAMS
3-1/2" or 4" by 1-1/2" (38 mm) Deep Octagon Box European 1-Gang (75 mm) Box 60.3 mm Fixing Centers
INSTALLATION SHEET
SIGA-SB4
Detector Base
DATE: 01/18/99
6 6 6
5 5 5
7
7
4
4
7
4
_
3
3
1
1
3
+
1
S 2 2 2
2 2 3
_ Insulate Shield/Drain
with tape Shield/Drain
+
S
Control Panel
1. Shielded wire is required ONLY in environments with very high electrical noise.
3 For Class B wiring, there is no shield connection to ground at the last device.
MOUNTING DIAGRAMS
4" by 1-1/2" (38 mm) Deep Square Box (Surface Mount) 4" Box Trim Skirt/Ring
4" by 1-1/2" (38 mm) Deep Square Box (Flush Mount) Flush Mount Electrical Box
NOTES:
1) A 4" Box Trim Skirt/Ring (SIGA-TS) must be installed to give a
"finished" appearance to the 4" base.
1.5" (38 mm) 2) Refer to Installation Sheet P/N 387056P for additional information.
INSTALLATION INSTRUCTIONS
1) Refer to the Installation Sheet provided with the base. Mount the base
to the electrical box.
2) Align the tabs on the trim skirt/ring with the notches on the base.
3) Push the trim skirt/ring onto the base until it snaps into position.
4) Refer to the Installation Sheet provided with the detector. Install the
detector in its base.
SIGA-TS
INSTALLATION SHEET
SIGA-TS
4" Box Trim Skirt/Ring
DATE: 01/18/99
! Caution!
P1 P2
Interior surface of enclosure SIGA-UIO2R
#6-32 TB15
Mounting space
Self-tapping
Screws
TB8 TB9
Mounting holes
0.125 in 3.175 mm diameter 1
INSTALLATION SHEET:
3
Module Input/Output Wiring SIGA-UIO2R
1 2 3 4 1 2 3 4
TB1 TB2
Data In
TB7
Signature 4 TB15
3
Data 2 4
Common input/output
Circuit 1 3
2 bus for Signature M series
1
Data Out modules
5
TB8 TB9
1 2 3 4 1 2 3 4
Jumpers connect common
inputs/outputs between 1
Module Input/Output Wiring modules
5 3
Notes
1
Jumpers may be used to make the inputs/outputs
between modules common.
Refer to individual Signature M series installation sheets Observe static-sensitive material handling practices.
3
for jumper settings and wiring information.
In cabinets that house only one motherboard:
4 Do not mix incompatible signals. Group all modules with nonpower-limited sources to
the right of the motherboard and route their wiring to
5 Maximum current is 8 Amps. the right.
Group all modules with power-limited sources to the
left of the motherboard and route their wiring to the
left.
6 Maintain 1/4 in (6.4 mm) separation between power-
limited and nonpower-limited wiring. Maintain a 1/4 inch (6.4 mm) spacing between power-
limited and nonpower-limited wiring or use FPL, FPLP,
FPLR, or an equirvalent in accordance with the NEC.
Wire Stripping Guide
Installations with multiple motherboards or enclosures,
Strip 1/4 inch from the ends of ALL wires that connect to the terminal which include other wiring, require FPL, FPLR, FPLP, or
blocks of the motherboard.
equivalent NEC-approved wiring for all power-limited
wiring.
1/4 in (6.4 mm)
Observe the details of supervision and power-limited vs.
CAUTION: nonpower-limited circuits, as found in the Signature M series
Exposing more than 1/4 inch of wire may cause a ground fault.
installation sheets.
Exposing less than 1/4 inch of wire may result in a faulty connection.
2 See the installation sheets of the individual SIGA-M series A UNIT OF GENERAL SIGNAL
GS BUILDING SYSTEMS CORPORATION
modules for mounting instructions to the SIGA-UIO6(R). 6411 Parkland Drive 625 6th Street East
GS BUILDING SYSTEMS Sarasota, FL 34243 Owen Sound, Ontario
CORPORATION
USA Canada N4K 5P8
Technical Manuals Online! - http://www.tech-man.com
WIRING
Strip 1/4 inch from the ends of ALL wires that connect to the terminal blocks of the motherboard.
SIGA-UIO6
Power-limited wiring Nonpower-limited wiring
TB1 through TB6
provide module
input/output wiring. Maintain 1/4 in (6.4 mm) separation between power-limited and nonpower-limited wiring.
Refer to individual
module installation 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 SIGA-UIO6
TB1
TB2
sheet for wiring details.
TB3
TB6
TB4
TB5
TB14 Input/Output Bus 1
Data In 4 Common to all
3 SIGA-M series
2
4 1 modules (maximum
Signature 3 current is 8 Amps)
Data 2 TB15
Circuit 1 4 Input/Output Bus 2
TB7 3 Common to all
2 SIGA-M series
Data Out 1
modules (maximum
current is 8 Amps)
TB2
TB3
TB6
TB4
TB5
Data In
TB7
4
Signature 3
Data TB15
2 Input/Output Bus 2
Circuit 1 4
3 Common to all
2
1 SIGA-M series
Data Out modules (maximum
current is 8 Amps)
TB11
TB8
TB9
TB10
TB13
TB12
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
Jumpers connect
common inputs and
outputs between
modules. Module Input/Output Wiring (maximum current is 8 Amps)
Refer to individual module installation sheet for wiring details.
! Caution!
In cabinets that house only one SIGA-UIO(R) motherboard:
Group all modules with nonpower-limited sources to the right of the motherboard and route their wiring to the right.
Group all modules with power-limited sources to the left of the motherboard and route their wiring to the left.
Maintain 1/4 inch separation between power-limited and nonpower-limited wiring, or use FPL, FPLR, FPLP, or an equivalent in
accordance with the National Electric Code.
Installations with multiple SIGA-UIO(R) motherboards or enclosures, which include other wiring, require FPL, FPLR, FPLP, or equivalent NEC-
approved wiring for all power-limited wiring.
Observe the details of supervision and power-limited vs. nonpower-limited circuits, as found in the SIGA-M series installation sheets.
387473.CDR Page 2 of 2
Technical Manuals Online! - http://www.tech-man.com
PRODUCT INFORMATION
Personality Code 10: N/O Alarm Delayed Latching (Class A)
Personality code 10 operates the same as personality code 9 except that
DESCRIPTION
contact closure must be maintained for approximately 16 seconds before an
The Universal Class A/B Module, Model SIGA-UM, is a component of the
alarm status is generated. Personality code 10 is typically used with waterflow
Signature Series System. The SIGA-UM is an analog addressable device
alarm switches.
used to connect any one of the following:
a) Dual Input Class B Initiating Device Circuit (IDC) Personality Code 11: N/O Active - Non-latching (Class A)
b) Class A or B Initiating Device Circuit (IDC) Personality code 11 operates the same as personality code 9 except that
c) Class A or B Notification Appliance Circuit (NAC) contact closure causes an active instead of an alarm status, and does NOT
d) Class A or B Circuit for 2-Wire Smoke Detectors and Initiating latch at the module. Personality code 11 is typically used for monitoring fans,
Devices on one circuit dampers, doors, etc.
e) Form "C" Dry Contact Relay Personality Code 12: N/O Active - Latching (Class A)
Personality code 12 operates the same as personality code 9 except that
The actual function performed by the SIGA-UM is determined by the
contact closure causes an active instead of an alarm status, which is latched at
personality code downloaded to the module from the Signature Loop
the module. Personality code 12 is typically used for monitoring supervisory
Controller during system configuration. The loop controller assigns
and tamper switches.
addresses to the SIGA-UM automatically or custom addresses can be
assigned to the module via laptop computer; no addressing switches are Personality Code 13: 2-Wire Smoke - Non-Verified (Class B)
used. Two (2) device addresses are required. Personality code 13 configures the SIGA-UM for monitoring of 2-wire
conventional smoke detectors (that do NOT require alarm verification) and
Diagnostic LEDs provide visual indication of the status of the module when normally-open contact initiating devices (e.g., pull-stations, heat detectors,
the cover plate is removed. etc.) on the same circuit.
Personality Code 14: 2-Wire Smoke - Verified (Class B)
Personality code 14 configures the SIGA-UM for monitoring of 2-wire
Status LED Indicator
conventional smoke detectors (that require alarm verification). Normally-
Normal Green LED flashes. open contact initiating devices may NOT be mixed with 2-wire conventional
smoke detectors.
Alarm/Active Red LED flashes. Personality Code 15: Signal Output (Class A)
Personality code 15 configures the SIGA-UM for connection of a Class A
output notification appliance circuit (NAC). Personality code 15 is typically
The SIGA-UM may be mounted in a North American 2-1/2" (64 mm) deep 2- used to control bells, speakers, etc.
gang box, standard 4" square 1-1/2" (38 mm) deep box, or European 100
mm square box. The terminal blocks will accept #14, #16, or #18 AWG wire Personality Code 16: Signal Output Module (Class B)
(1.5 mm 2, 1.0 mm 2, 0.75 mm2 ). Sizes #16 and #18 are preferred. Personality code 16 configures the SIGA-UM for connection of a Class B
output notification appliance circuit (NAC). Personality code 16 is typically
JUMPER SETUP used to control bells, speakers, etc.
Jumper JP1 is factory installed on pins 1 and 2 for NORMAL operation. In Personality Code 20: 2-Wire Smoke - Non-Verified (Class A)
order to operate the SIGA-UM as a Form "C" dry relay contact to control Personality code 20 operates the same as personality code 13, except that
external appliances (door closers, fans, dampers, etc.), JP1 must be moved wiring is Class A.
to pins 2 and 3 and personality code 8 must be downloaded to the module.
Personality Code 21: 2-Wire Smoke - Verified (Class A)
SYSTEM/CONTROLLER COMPATIBILITY Personality code 21 operates the same as personality code 14, except that
The SIGA-UM is factory assigned personality code 0 to input channels 1 and wiring is Class A.
2. The SIGA-UM requires the Signature Loop Controller. The loop controller
downloads a user-selectable personality code which determines how the
module will operate. The following personality codes may be downloaded to
the SIGA-UM:
Personality Code 1: N/O Alarm Latching (Class B) Universal Class A/B Module, SIGA-UM
Personality code 1 configures input 1 and/or 2 of the SIGA-UM for Class B
normally-open dry contact initiating devices (e.g., pull-stations, heat
detectors, etc.). When the N/O input contact of an initiating device is closed,
an Alarm signal is sent to the loop controller and the alarm condition is
latched at the module.
Personality Code 2: N/O Alarm Delayed Latching (Class B)
Personality code 2 operates the same as personality code 1 except that
contact closure must be maintained for approximately 16 seconds before an
alarm status is generated. Personality code 2 is only for use with non-
retarded waterflow alarm switches.
Personality Code 3: N/O Active - Non-Latching (Class B)
A contact closure causes an active instead of an alarm status and does NOT
latch at the module. Personality code 3 is typically
IMPORTANT NOTE: used for monitoring fans,
TRANSIENT PROTECTION
dampers, doors, etc.
Personality Code 4: N/O Active Latching (Class B)
A contact closure causes an active instead of an alarm status which is
latched at the module. Personality code 4 is typically used for monitoring
INSTALLATION SHEET:
supervisory and tamper switches.
Personality Code 8: Dry Contact Output SIGA-UM
Personality code 8 configures the SIGA-UM as a Form "C" Dry Relay Universal Class A/B Module
Contact to control external appliances (door closers, fans, dampers, etc.) or
equipment shutdown. NOTE: Jumper JP1 MUST be moved to pins 2 and 3 INSTALLATION SHEET P/N: P-047550-1726 FILE NAME: P0475501726.CDR
for dry contact operation.
Personality Code 9: N/O Alarm Latching (Class A) REVISION LEVEL: 2.0 APPROVED BY: RR
Personality code 9 configures the SIGA-UM for connection of Class A DATE: 04/20/98 CREATED BY: MR
normally-open dry contact initiating devices (e.g., pull-stations, heat
detectors, etc.). When the N/O input contact of an initiating device is closed, A UNIT OF GENERAL SIGNAL
GS BUILDING SYSTEMS CORPORATION
an alarm signal is sent to the loop controller and the alarm condition is 6411 Parkland Drive 625 6th Street East
latched at the module. GS BUILDING SYSTEMS
CORPORATION Sarasota, FL 34243 Owen Sound, ON, Canada
Technical Manuals Online! - http://www.tech-man.com
SPECIFICATIONS
Operating Voltage Range 15.2 - 19.95 Vdc
Ripple Voltage 2V AC
Contact Ratings
24V DC 2A
120V DC 0.5A This module requires transient protection for installations in which
Relay Type Form "C" electromechanical bells or horns are connected to the output circuits.
Operating Temperature Range 32 to 120°F (0 to 49°C)
A Bi-Polar Transient Protector (P/N 235196P) MUST be used to protect the
Operating Humidity Range 0 to 93% RH module's electronic circuitry from the effects of electronic transients caused
Storage Temperature Range -4 to 140°F (-20 to 60°C) by the inductive load of bells or horns.
Construction High Impact Polymer
Shipping Weight 7.7 oz (218 g) The bi-polar transient protector assembly should be connected across the
Compatible Electrical Boxes terminals of the bell or horn located electrically closest to the module. The
North American 2-1/2" (64 mm) Deep 2-Gang Box bi-polar transient protector is not polarity sensitive.
Standard 4" Square Box 1-1/2" (38 mm) Deep Box Bells and horns MUST be located a minimum distance of 6 ft. (1.83 m) from
European 100mm Square Box the module.
UL Compatibility ID 0.0
Initiating Device Circuit (IDC): Compatible Smoke Detectors
Max. Circuit Resistance (per channel) 50W (25W per wire) Max.
Comp.
Max. Circuit Capacitiance (per channel) 0.1mF Manufacturer Model Description UL ID
Base Qty.
Max. Alarm Current (per channel) 17mA
System Sensor 1451 Ionization A/A B401(B) 10
Operating Voltage Range 16.0 to 24.0V DC
System Sensor 2451 Photoelectric A/A B401(B) 10
Edwards 6250B Ionization 001/001 6251B-001 20
Edwards 6270B Photoelectric 001/001 6251B-001 15
Mode of Operation Personality Code Standby Current Activated Current EOL Resistor
Class B Initiating Device Circuit 1, 2, 3, or 4 396mA 680mA 47KW
Form "C" Dry Contact Relay 8 100mA 100mA N/A
Class A Initiating Device Circuit 9, 10, 11, or 12 223mA 365mA N/A
2-Wire Smoke Detectors and Initiating Devices 13, 14, 20, or 21 2.0mA (from 3rd wire) N/A 15KW (for class B)
First SIGA-UM module to go into alarm (Class A or B) N/A N/A 12mA Smoke Detector N/A
17mA Contact Closure
Each subsequent SIGA-UM to go into alarm N/A N/A 100mA (from data line) N/A
Class A or B Notification Appliance Circuit 15 or 16 223mA 365mA 47KW (for class B)
N/A (for class A)
INSTALLATION INSTRUCTIONS
1) The SIGA-UM is shipped from the factory as an assembled
unit; it contains no user-serviceable parts and should NOT
be disassembled.
2) Refer to Technical Bulletin (P/N 270145) for installation
guidelines.
3) Verify that all field wiring is free of opens, shorts, and ground
faults.
4) Make all wiring connections as shown in the wiring diagram.
5) Write the address assigned to the module on the label provided
and apply the label to the module. Peel off the removable serial
number label from the module and apply it to the appropriate
location in the Serial Number Logbook.
6) Using the two 6-32 x 3/8" (9.5 mm) machine screws provided,
mount the module to the electrical box.
7) Using the four 4-24 x 5/16" (7.9 mm) self-tapping screws
provided, mount the wall plate to the module.
NOTE:
1) A valid personality code MUST be downloaded to the module
through system programming for the unit to operate.
2) Wire in accordance with NFPA70-1996,
National Electrical Code Article 760, Section 760-54(a)(1),
Exception No. 2 and 3.
Strip 1/4" (6.4 mm) from the ends of ALL wires that connect to the
terminal block of the module.
CAUTION:
Exposing more than 1/4" (6.4 mm) of wire may cause a ground fault.
Exposing less than 1/4" (6.4 mm) of wire may result in a faulty
connection.
10 Supervised and power limited when connected to power limited source. If non-
power limited, then all power limited wiring in box must use FPL, FPLR, or,
FPLP cable or equivalent per NEC. Power limited marking must be eliminated.
11 Power limited when connected to power limited source. If non-power limited,
then all power limited wiring in box must use FPL, FPLR, or, FPLP cable or
equivalent per NEC. Power limited marking must be eliminated.
11
9
Technical Manuals Online! - http://www.tech-man.com
Single Input Module (Personality Codes, 9, 10, 11, or 12)
t
9
Mixing 2-Wire Smoke Detectors and Initiating Devices (Personality Codes 13, 14, 20, or 21)
Ratings
10 24V DC 2A
25V Audio 50W
70V Audio 35W
3 9
Technical Manuals Online! - http://www.tech-man.com
PRODUCT INFORMATION SPECIFICATIONS
DESCRIPTION Operating voltage range: 15.2 to 19.95 Vdc
The Waterflow/Tamper Module, Model SIGA-WTM, is a component of Standby current: 396 mA
the Signature Series System. The SIGA-WTM is an analog addressable Activated current: 680 mA
device used to connect Class B normally-open waterflow alarm and Operating temperature range: 32 to 120°F (0 to 49°C)
supervisory initiating device circuits (IDCs) to a Signature loop controller. Operating humidity range: 0 to 93% RH
Two (2) device addresses are required. Storage temperature range: -4 to 140°F (-20 to 60°C)
Construction: High impact engineering polymer
Input channel 1 of the SIGA-WTM is used for waterflow alarm Shipping weight: 5.1 oz (145 g)
applications. Input channel 2 is used for supervisory applications. The Compatible electrical boxes
loop controller assigns two addresses to the SIGA-WTM automatically North American 2-1/2 in (64 mm) deep 1-gang box
or custom addresses can be assigned to the module via laptop Standard 4 in square box 1-1/2 in (38 mm) deep
computer; no addressing switches are used. box w/1-gang cover
Initiating device circuit (IDC):
Diagnostic LEDs provide visible indication of the status of the module EOL resistor value (EOLR): 47 KW, UL listed
when the cover plate is removed. Max. circuit resistance: 50 W (25 W per wire) (per channel)
Normal: Green LED flashes Max. circuit capacitance: 0.1 mF (per channnel)
Alarm / Active: Red LED flashes
Personality Code 4: N/O Active Latching (Class B) 1) This module will NOT operate without electrical power. As fires
Personality code 4 is factory assigned to input channel 2 of the frequently cause power interruption, we suggest you discuss
SIGA-WTM. This configures channel 2 for use with supervisory and further safeguards with your local fire protection specialist.
tamper switches. Contact closure generates an active status which is
latched at the module. 2) This module does NOT support conventional smoke detectors.
SIGA-WTM
SIGA-WTM
Waterflow/Tamper Module
Strip 1/4" (6.4 mm) from the ends of ALL wires that connect to the
terminal block of the module.
CAUTION:
Exposing more than 1/4" (6.4 mm) of wire may cause a ground fault.
Exposing less than 1/4" (6.4 mm) of wire may result in a faulty
connection.
W
W
2) Loosen the captive screw on the front plate of the station and remove
the front plate. Remove the glass panel from inside the station.
PRODUCT DIAGRAM
3) Verify that all field wiring is free of opens, shorts, and ground faults.
6) Using the two machine screws provided, mount the break glass
station back plate to the electrical box.
7) Reinstall the glass panel inside the station and reattach the front
plate to the station using the captive screw on the front plate.
NOTE:
Strip 1/4 in (about 6 mm) from the ends of ALL wires that connect to REVISION LEVEL: 2.0 APPROVED BY: R.Right
the terminal block of the module.
DATE: 22JUL99 CREATED BY: M. Rimes
CAUTION: Exposing more wire may cause a ground fault. Exposing
less wire may result in a faulty connection. GS BUILDING SYSTEMS CORPORATION
A UNIT OF GENERAL SIGNAL
6411 Parkland Drive 625 6th Street East
GS BUILDING SYSTEMS Sarasota, FL 34243 Owen Sound, Ontario
CORPORATION
USA Canada N4K 5P8
Red
Data In/Out (+)
Black Black Wire Red Wire
Data In/Out (-) Black/White
Data In/Out (-)
From Signature
B/W Wire
Controller
or Previous
Device
See wiring
detail above.
7
4
1.1 in 1) These bases will accept 12, 14, 16, and 18 AWG (2.05 sq mm,
(27 mm) 1.5 sq mm, 1.0 sq mm, and 0.75 sq mm) wire. Sizes 16 and 18
0.8 in are preferred.
(20 mm)
2) Write the address assigned to the detector on the label provided
2.0 in and apply the label to the inside rim of the base.
(51 mm)
1.5 in
(38 mm)
0.8 in
(20 mm)
2.0 in
(51 mm)
2.0 in
(51 mm) SIGI-IBS
Detector Base
4.4 in (112 mm)
European 1-Gang (75 mm) Box with 60.3 Fixing Centers INSTALLATION SHEET P/N: P-047550-1749 FILE NAME: P-047550-1749.CDR
DATE: 01/15/99
1.75 in
REVISION LEVEL: 3.0
(45 mm)
0.8 in APPROVED BY: B. Right
(20 mm)
CREATED BY: C. Hanrahan 7 93016 02785 6
2.0 in
(51 mm)
A UNIT OF GENERAL SIGNAL
GS BUILDING SYSTEMS CORPORATION
6411 Parkland Drive 625 6th Street East
GS BUILDING SYSTEMS Sarasota, FL 34243 Owen Sound, Ontario
4.4 in (112 mm) CORPORATION
USA Canada N4K 5P8
7
4
7
4
_
1
3
+
1
S 2 2
2 3
_ Insulate Shield/Drain
with tape Shield/Drain
+
S
Control Panel
NOTES TO
T-TAPPED
1. Shielded wire is required ONLY in environments with very high DEVICE
PROPER METHOD
2
electrical noise.
Shields must be continuous and insulated from ground.
OK FOR T-TAPS
YES NO NO