Professional Documents
Culture Documents
Customer:
Engineer:
Pump Manufacturer:
Technical Data
Submittal Document
Model JP3
Across the Line Start
Jockey Pump Controller
Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections
Technical Data
Model JP3 Jockey Pump Controller
JP3
Shortcircuit 200V to 208V 220V to 240V 380V to 416V 440V to 480V 600V
Withstand 50hz - 60Hz 60Hz 50Hz - 60Hz 60Hz 60hz
Rating
HP
Optional 42kA 7.5HP Max. 7.5HP Max. 7.5HP Max. 7.5HP Max. 7.5HP Max.
Optional 65kA 3HP- 15HP Max. 5HP - 15HP Max. 7.5HP - 40HP Max. 7.5HP - 40HP Max. N/A
Optional 100kA 2HP Max. 3HP Max. 5HP Max. 5HP Max. N/A
Seismic
TRU Compliance, LLC
Certification TWEI Project No.: 15014
A Tobalski Watkins Affiliate
Company
Mounting
Rigid wall mounting
details
Seismic
Building Test Seismic AFLX-H ARIG-H AFLX-V ARIG-V
Certification
Code Criteria Parameters
SDS z/h IP
Seismic IBC
Information ICC- 2.0 1.0 1.5 3.20 2.40 1.33 0.53
2015, ASCE 7-10
ES
CBC Chapter 13
AC156 3.2 0.0 1.5 3.20 1.28 2.13 0.85
2016
1.0
0.1
0.1 1.0 10.0
Frequency, f (Hz)
Notes:
• Components are tested in accordance with ICC-ES AC156, IBC 2015 & CBC 2016.
• OSHPD Special Seismic Certification Preapproval (OSP)
A4 Elapsed time meter (time totalizer) L01 Other language and English (bilingual)
A5 Motor run alarm contact L02 French
A6 Loss of power alarm contact L03 Spanish
A7 Overload or short circuit alarm contact L04 German
D12 CE Mark c/w externally mounted wetted parts L05 Italian
D13A Externally mounted wetted parts L06 Polish
D14 Export packing for 1 controller L07 Romanian
D18 Audible alarm L08 Hungarian
D19 Anti-condensation heater and thermostat L09 Slovak
D20 Anti-condensation heater and humidistat L10 Croatian
D21 Tropicalization L11 Czech
Phase reversal / failure pilot light and alarm L12 Portuguese
D22
contact L13 Dutch
Controller power healthy pilot light and alarm L14 Russian
D23
contact
L15 Turkish
Pump failure via current sensing relay with pilot
D24 L16 Swedish
light and dry alarm contact
L17 Bulgarian
D25 Low zone pump control function
L18 Thai
D26 Mid zone pump control function
L19 Indonesian
D27 High zone pump control function
L20 Slovenian
D28 Selector switch in auto alarm contacts
L21 Danish
D29 Selector switch in off alarm contacts
L22 Greek
D30 Motor heater circuit
L23 Arabic
Service entrance rated - 100kA short circuit
withstand rating: L24 Hebrew
• 120V/1ph (0.5hp max.) L25 Chinese
• 240V/1ph (1hp max.)
D32
• 200V-208V - 60hz (2hp max.)
• 220V-240V - 60hz (3hp max.)
• 380V-416V - 50hz - 60hz (5hp max.)
• 440V-480V - 60hz (5hp max.)
Service entrance rated - 65kA short circuit
withstand rating:
• 120V/1ph (0.5hp max.)
• 240V/1ph (1hp max.)
D33
• 200V-208V - 60hz (3hp-15hp max.)
• 220V-240V - 60hz (515hp max.)
• 380V-416V - 50hz - 60hz (7.5hp - 40hp max.)
• 440V-480V - 60hz (7.5hp-40hp max.)
Service entrance rated - 42kA short circuit
D34 withstand rating:
• 600V - 60hz (7.5hp max.)
Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.
3 2
4 7
HAND AUTO
5
8