Microcomputer Thermostat Serial
Hold ,then press or
《EW-981 Directions》 simultaneously. Choose ,
ELIWELI is an enterprise which is speciallized in pro Set represents Warm Mode, re-
EW-981
present Cold Mode.
-ducing eletronic controller.We always insist that quality
of product and best service is our goal. Hold ,then press or
Our sensor is especially precisely made and sealed; it simultaneously. Choose lowe-
Set st temperature limits:
is moisture-proof , therefore its performances are more EW-981
-45℃ To Temperature control+1℃
stable and reliable.

Technical Specifications Hold ,then press or


simultaneously. Choose high-
1、Operating voltage: AC12V ±10% 50HZ/60HZ
Set
est temperature limits:
2、Output Load : Compressor Relay10A/220V/AC EW-981 Temperature control+1℃ to 80℃
3、Power Consumption: ≤3W
4、Working environment: -10℃ ~50℃ R H≤90%
Hold ,then simultaneously
5、Input signal :one line NTC-sensor input 20K X 1.5meter press or to set delayed
6、Controlling Output: Compressor AC Contactor Set star time from 0 to 5 minutes.
EW-981
7、Control Range: —45℃~80℃
8、Resolving Power:1℃ Accuracy: ±1℃
Hold ,then press or
9、Overall Dimension:77(length)×34(wide)×62(high)mm simultaneously. Choose tem-
10、Hole Size: 71(length)×29(wide)mm Set perature correction:
EW-981
-15℃ to 15℃
Brief on Operation
Hold , then press or
Normally display
current temperature simultaneously. Choose ret-
Set urn difference:1℃ to 15℃
EW-981

Error symbol: when the sensor


Set
EW-981
is opened or shorted circuit.
Set Code “EI” will be displayed.
EW-981
Loud poer LED

Demand of install Electrical Schematic diagram

1.The voltage must accord with controller's demand. The


voltage's deviation is no more than ±10%.
Mode:EW-981H
2.The loop of sensor is possible to keep away from the Output Load :
loop of power. 10A/220V/AC 12V/AC
3.The sequence of line's must have been connected
Properly.

1 2 3 4 5 6 7 8 9 10
Brief on Controlling Procedure
1.Temperature setting:Press gently to display con Load
-trolling temperature。press or to change controll NTC
sensor
-ing temperature. Transformer
2.Data setting:Press for 6 seconds for setting. On 220V/AC
entering setting , will be displayed. Then Press or
to set .
Feature descriptions Parameters for Procedure
Factory
Cooling: When the current temperature ≥ settin tempera- Code Function Setting Range Stting Unit
ture + temperature hysteresis and delay the setting of the
"delay time" , the load relay On.
Refrigerating
H/C C —
/warming
Alarm on lowlimit
Cooling stop: When the real temperature ≤ the set temp- -45 to temperature comtrol-1 -45 ℃
Temperature
erature, the load relay is Off. Alarm on high limit
Temperature
Temperature comtrol+1 to 80 80 ℃
Heating system: When the current temperature ≤the setting
Delayed Time 0~5 1 Min
temperature - the temperature hysteresis and delay the
setting of the "delay time", the load relay Off. Temperature -15~15 00 ℃
Correction
Temperature Return
1~15 2 ℃
Heating system to stop: when the current temperature ≥ Difference

setting temperature, the load relay is disconnected.


Attention: The highest temperature limited (HS) and the lowest
Tips: cooling and heating conversion set in the parameter H / temperature limited (LS) have been locked. Please don't change.
C menu selection, H is the heating system, C is cooling.

Trouble shooting

Failure Causes Precautions


No display when power Check if the power is broken or the Check power supply and change fuse.
is on. thermostat failture. Check if the input voltage is right or change
the thermostat with our distributor.
The setting temperature is higher than the
Displaying and machine present temperature. Reset the necessary controlling temperature.
doesn't work The heat protector is open circuit because the Check the reasons for overload and overheating.
pressure is over loads. After the trouble is solved, restart to work.
Displayed temperature is The sensor is interfered; or poor wiring;
unstable or there exists Separate sensor wiring with power cables or change
or Together with other power cord
misplay. shielded lines or check if the contact is tight or not.

All sensors should be corrected at their locations.


Measurement error betw- The installation position of the sensor is
een current temperature not correct; or the sensor's wiring is too Enlarge the cross section of the expanded wires.
and displayed. long and its resistance is over; or the Make sure the wires sealed is good. or Change the
wiring connected poor; or the sensor is
sensor.
Machine does not stop The sensor is not correctly installed and cannot Check if the sensor has accurately measured the
when the temperature measure the correct temperature. Compressor
reaches. contactor fails. temperature or not. Change compressor contactor.
Return difference value is too small or the Reset and enlarge return difference value. Adjust
Relay work with overload setting for pressure protection is not correct. setting for pressure protection.

The sensor is opened or shorted circuit. Check to see if the sensor wiring has good contact
“EI” is displayed with coupling end or not.

Warnings

1. Please read this product instruction carefully and connect If you have any doubt or problem concerning the
input/output plugs of power & sensor to the corresponding sockets electronic temperature or humidity controller made by
strictly by following connection diagram, otherwise the usage & us, please contact our distributors and we will provide
operations will be affected. Check again to make sure there is no you high-quality after-sale services. Thanks!
mistake. Tighten all the screw of connection plugs again, and then
connect it to the power for running.

2. Keep away this product from moist or corrosiIve air and high
magnetic field. Otherwise the normal operaton of this product will
be affected. Guangzhou Eliweli Autocontrol Tech. Co., Ltd.
.
http://www.eliweli.com
3. All our products have passed strict quality inspections before
leaving factory. We provide one-year quality guarantee (which is
limited to product itself) period for this product.