Index Index
Pg. Pg.
PARAMETER DESCRIPTION PARAMETER DESCRIPTION
No. No.
Features 4 QFD To set quick freeze duration. 15
Items Included. 5 CND6 To set condenser on delay time. 15
Key Introduction 6
CND7 To set condenser status at hot gas 15
Fault Messages. 7 defrost.
LED Indication. 8 L1 To set Evaporator Fan stop temperature. 16
Parameter List. 9
L2 To set Evaporator Restart Delay. 16
SET POINT To set the cut-out point of the controller. 9
L3 To set Evaporator Fan status at 16
QFS To set the quick freeze set point. 9 compressor off.
EXIT End of set mode 9 L4 To set Evaporator Fan differential. 16
To set other parameter 9 L5 To set Evaporator probe calibration. 17
P2 To set allowable high temperature limit. 10 L7 To set Evaporator Fan status at Door 17
P3 To set allowable low temperature limit. 10 open condition.
P4 To set the differential for compressor 10 L8 To set Evap Fan status during defrost. 17
restart.
BUZ To enable / disable buzzer. 17
P5 To set probe calibration. 11
AL Alarm Relay Enable / Disable. 18
P6 To set time delay between relay restart 11
time. ADT HT Power ON alarm delay. 18
P7 To set duration of defrost. 12 ADD Alarm/Buzzer output delay at Door open 18
P8 To set defrost frequency. 12 THD Temperature Hold Duration at Door open 18-19
P9 To set power on defrost delay. 12 C-UL Under load limit for compressor current. 19
P10 To set type of defrost. 13 C-OL Over load limit for compressor current. 19
P11 To set drip time for defrost. 13
C2 Current sensing delay. 20
P12 To set type of computation for defrost time. 13 D0 To enable or Disable HP sensing. 20
P13 To set defrost stop temperature. 14 D1 To enable or disable LP sensing. 20
DI-D To select AUX or compressor thermal D2 Fault sensing logic. 21
trip digital I/P 14
D3 To set LP sensing delay. 21
OPS To Enable / Disable Oil Pressure Switch
14 D4 To set reset mode for HP fault. 21
(OPS) I/P.
E1 To set Compressor Relay status on
Probe Failure. 22
01 02
Index Features:
03 04
Items included Key Introduction
Used to enter in manual defrost and to stop defrost if defrosting
NO. ITEMS QTY is ON.
Used to enter into the Set mode. Also used as enter key if controller
is in Set mode/program mode. Also used to save changed value.
PRG
Used to enter in display Amp. mode where compressor current can
be viewed.
Amp
05 06
Fault Messages : LED Indication
High temperature alarm for Room temperature means, room Messages Mode Discription
Ht
temperature is equal or above the set value of P2 parameter.
ON Comp. Relay ON.
Low temperature alarm for Room temperature means, room OFF Comp. Relay OFF.
Lt
temperature is equal or below the set value of P3 parameter. Flashing Comp. Relay Time delay.
Room temperature fail means, Room sensor not connected or
PP ON Cond. Relay ON.
out of range. C OFF Cond. Relay OFF.
E-PP Evaporator temperature fail means, Evaporator sensor not ON Evap. Relay ON.
connected or out of range. OFF Evap. Relay OFF.
E
DO Door Input Fault. Flashing Evap. Relay Time delay.
ON Defrost Relay ON.
SPPR SPPR Fault. OFF Defrost Relay OFF.
Flashing Defrost Relay Time delay.
C-OL Compressor over load fault.
ON LSV Relay ON.
OFF LSV Relay OFF.
C-UL Compressor under load fault. ON Alarm Relay ON.
OFF Alarm Relay OFF.
HP HP fault. Flashing Controller is in drip time.
07 08
Min: MINIMUM Max : MAXIMUM Description of parameters and functions.
Fact. Set : FACTORY SETTING(DEFAULT)
Sr. Parameter Parameter setting method
Description of parameters and functions. No.
Sr. Parameter Parameter setting method P2 Function : To set allowable high
No. 01
Parameter temperature limit.
SET MODE To change P2 parameter, Use UP/DOWN key to set desired value.
To set other parameter Display will show ‘SP’ and scroll the press the set key. Once set at a particular value, this will not
Press & hold SET key for description of the parameter. allow the set point to go above this
2 seconds To go to other parameters, use UP / value and below P3 setting.
DOWN keys. After desired value, press Range
the SET key & you will see “----” which Min Max Fact. Set Example : Setting this parameter at
confirms that the parameter value has 50.00C will not allow the set point to go
been stored in memory. SP+0.5ºC 50.0ºC 50.0ºC above 50.00C also if the temperature
reaches 50.00C, the display will show HT
01 SP To set the cut-out point of the controller. (High Temperature). The alarm will be
(Message on Display) ON. But at power on till the ADT delay is
To change Set Point parameter, Display will change to set value.
over controller will not generate HT Alarm.
press the set key. The set point value can now be changed
Range by using the UP/DOWN key.
02 P3 Function : To set allowable low
Min Max Fact. Set QFS = Quick Freeze Set Point Parameter temperature limit.
QFS+0.5 P2-0.5ºC -20.0ºC
To change P3 parameter, Use UP/DOWN key to set desired value.
02 QFS To set the quick freeze set point. press the set key. Once set at a particular value, this will not
allow the set point to go below this value
To change QFS parameter, Use UP/DOWN keys to set desired value. Range
and above P2 setting.
press the set key. Min Max Fact. Set
If controller is in quick freeze mode then Example : Setting this parameter at
compressor will cut in/ cut out as per this -40.0ºC QFS- -40.0ºC
Range -40.00C will not allow the set point to go
set point till the quick freeze duration is 0.5ºC
Min Max Fact. Set over. below -40.00C also if the temperature
reaches -40.00C, the display will show LT
P3+0.5 SP-0.5 -25.0ºC SP : Set Point. (Low Temperature). The alarm will be ON.
(Message on Display)
03 EXIT End of set mode
03 P4 Function : To set the differential for
PROGRAM MODE Parameter compressor restart.
Display will show '0000'. Set correct To change P4 parameter, Use UP/DOWN keys to set desired value.
To set other parameter press the set key.
password to enter into program mode. The
display will show 'P2' and scroll the Example(Cooling Mode) : If the set point
Press & hold PRG key for Range
2 seconds description of the parameter. is set at 10.00C and differential is set at
To go to other parameters, use UP / DOWN Min Max Fact. Set 2.00C, then when the system reaches
keys. After desired value, press the SET 10.00C, the comp. relay will cutout. Since
PRG 0.5ºC 20.0ºC 2.0ºC
key & you will see “----” which confirms that the differential is 2.00C, the comp. Relay
the parameter value has been stored in will cutin at 12.00C
memory. (10.00C + 2.00C).
09
10
Description of parameters and functions. Description of parameters and functions.
Sr. Parameter Parameter setting method Sr. Parameter Parameter setting method
No. No.
P5 Function : To set room probe calibration. P7 Function : To set duration of defrost.
04 06
Parameter Parameter
To change P5 parameter, Use UP/DOWN keys to set desired value. To change the P7 parameter, Use UP/DOWN keys to set desired value.
press the set key. In time it may be possible that the display press the set key.
may be offset by a degree or so. This is maximum amount of time allowed
Range To compensate this error, you may need Range for defrost. If set to 0, there will be no
defrost cycle.
Min Max Fact. Set to add or minus the degrees required to Min Max Fact. Set
achieve the correct temperature.
-10.0ºC 10.0ºC 0.0ºC Example : If P7 is set to 15 Mins and P8
0 Min 99 Min 30 Min
Example : The temperature on the parameter is set to 1 Hr. then after every 1
display is 28.0OC, whereas the actual Hr defrosting will take place for 15 mins.
temperature is 30.0OC. You may need to
set this parameter to 2.0OC, which means
that once out of the programming 07 P8 Function : To set defrost frequency.
parameter, the display will show the Parameter
temperature 30.0OC (28.0OC + 2.0OC). To change the P8 parameter, Use UP/DOWN keys to set desired value.
press the set key. This is the amount of time between two
Range defrost cycles.
05 P6 Function : To set time delay between
Parameter compressor relay restart time. Min Max Fact. Set Example : same as P7 parameter.
To change P6 parameter, Use UP/DOWN keys to set desired value. 1 Hr 31 Hrs 6 Hr
press the set key. This parameter is used to protect the fan
from restarting in a short period of time
Range and can be set between 0 to 20 minutes. P9 Function : To set power on defrost delay.
08
Min Max Fact. Set Parameter
Example : If this parameter is set at 3 To change the P9 parameter, Use UP/DOWN keys to set desired value.
1 Min 20 Min 3 Min minutes, once compressor will cut off at press the set key. This is the amount of time at power on
the set temperature, it will not restart for a
minimum of 3 minutes, even if the Range after which defrosting will take place
differential is achieved earlier. This once.
Min Max Fact. Set
parameter is good to protect the life of the
compressor when there are power 0 Min 99 Min 0 Min If this parameter is set to 0, there will be no
fluctuations and the compressor is power ON defrost.
switched off and on within a few seconds.
Example : If P9 parameter is 30 mins
then at power after 30 mins defrosting will
take place once.
11 12
Description of parameters and functions. Description of parameters and functions.
Sr. Parameter Parameter setting method Sr. Parameter Parameter setting method
No. No.
09 P10 Function : To set type of defrost. P13 Function : To set defrost stop
12
Parameter Parameter temperature
To change the P10 Parameter, Use UP/DOWN keys to set desired value. To change the P13 Parameter, Use UP/DOWN keys to set desired value.
press the set key. press the set key.
HTR : Heater defrost where compressor If coil/Evap temperature is reached upto
Range is OFF. this temperature defrost will stop.
Range
Min Max Fact. Set HTG : Hot Gas defrost where compressor
is ON. Min Max Fact. Set Example : If this parameter is set to
HTR HTG HTR 4.0ºC, then if defrosting is in progress
-40.0ºC 50.0ºC 4.0ºC then when temperature reaches 4.0ºC,
P11 Function : To set drip time for defrost. the defrost process will stop.
10
Parameter
To change the P11 Parameter, Use UP/DOWN keys to set desired value. 13 DI-D Function : To select AUX or
press the set key. Parameter compressor thermal trip digital I/P
During this period Compressor,
Range Evaporator Fan, LSV relay and Heater To change the DI-D Parameter , Use UP/DOWN keys to set desired
will stay OFF so that the defrost water can press the set key. value.
Min Max Fact. Set drain out.
Range If Selected as “AUX” then at fault it will
0 Min 30 Min 1 Min
Min Max Fact. Set display "AUX” on display.
P12 Function : To set type of computation
11 AUX CTH CTH If Selected as “CTH” then at fault it will
Parameter for defrost time..
display “CTH”.
To change the P12 Parameter, Use UP/DOWN keys to set desired value.
press the set key. REAL = Total of real time.
Range Example : This means that the time OPS Function : To Enable / Disable OPS I/P.
14
calculation for defrost frequency will be Parameter
Min Max Fact. Set for the total hours the unit has been
To change the OPS Parameter, Use UP/DOWN keys to set desired
running.
REAL CRH REAL press the set key. value.
CRH - Sum of total compressor
operating times. This means that for Range ENB : OPS I/P is enabled.
time calculation, the unit will add the total
time the compressor has been in an ON Min Max Fact. Set DIS : OPS I/P is disabled.
mode. DIS ENB ENB
It keeps a record of the hours worked +/-½
Hour incase of a power failure.
13 14
Description of parameters and functions. Description of parameters and functions.
Sr. Parameter Parameter setting method Sr. Parameter Parameter setting method
No. No.
QFD Function : To set quick freeze duration. L1 Function : To set Evaporator Fan stop
15 18
Parameter Parameter temperature.
To change the QFD Parameter, Use UP/DOWN keys to set desired value. To change the L1 parameter, Use UP/DOWN keys to set desired value.
press the set key. press the set key. This setting is used to limit the Max.
This is the maximum amount of time Range temperature beyond which the Evap.Fan
Range allowed for Quick Freeze. If set to “0”, will cut off.
Min Max Fact. Set
Min Max Fact. Set there will be no quick freeze. Example : If this parameter is set to 2.0ºC,
-40.0ºC 50.0ºC 2.0ºC then Evap. Fan will cut OFF at 2.0ºC.
0 Hr 12 Hrs 2 Hr Example : If QFS is set to -20.0ºC, and
quick freeze duration is set to 1 hr ,then 19 L2 Function : To set Evaporator Restart
when it is in quick freeze mode, then the Parameter Delay.
Comp. will work on -20.0ºC set point for To change the L2 parameter, Use UP/DOWN keys to set desired value.
1hr. press the set key.
Once the fan get OFF at L1 condition, it
CND6 Function : To set condenser ON delay will not get restart until L2 duration is over.
16
Parameter timings. Range Example : If this is set at 1 minutes, Evap.
To change the CND6 Use UP/DOWN keys to set desired value. Min Max Fact. Set Fan relay will cut off at the set by Evap.
parameter, press the set key. Fan Stop TC. Parameter but the Fan will
When Compressor delay over Condenser 0 Min 20 Min 1 Min not come on for a minimum of 1 minutes
Range
Fan will come ON first, after cond. On even if it’s differential is achieved earlier.
Min Max Fact. Set delay over Comp will come ON.
20 L3 Function : To set Evaporator Fan status
0 Sec 30 Sec 15 Sec Parameter at compressor off.
To change the L3 parameter, Use UP/DOWN keys to set desired value.
17 CND7 Function : To set condenser status at press the set key. OFF : Evaporator Fan will be OFF at
Parameter hot gas defrost. Range compressor OFF.
To change the CND7 Use UP/DOWN keys to set desired value. Min Max Fact. Set ON : Evaporator Fan will be ON at
parameter, press the set key. OFF ON ON compressor OFF.
This function is used to decide the
Range 21 L4 Function : To set Evaporator Fan
condenser status when hot gas defrost is
Parameter differential.
Min Max Fact. Set ON. This parameter is not applicable for
Heater defrost. To change the L4 parameter, Use UP/DOWN keys to set desired value.
OFF ON OFF At hot gas defrost, press the set key. Example : If L1parameter is set to 2.0ºC,
OFF : Condenser will be OFF and if Evaporator Fan differential
ON : Condenser will be ON Range
parameter is set to 2.0ºC,then Evap. Fan
Min Max Fact. Set will cut off at 2.0ºC and restart only at
0.0ºC.
0.5ºC 20.0ºC 2.0ºC (2.0ºC-2.0ºC = 0.0ºC) (L1 - L4)
15 16
Description of parameters and functions. Description of parameters and functions.
Sr. Parameter Parameter setting method Sr. Parameter Parameter setting method
No. No.
L5 Function : To set Evaporator probe AL Function : This parameter is used to
22 26
Parameter calibration. Parameter Enable / Disable alarm relay.
To change the L5 parameter, Use UP/DOWN keys to set desired value. To change the AL Parameter, Use UP/DOWN keys to set desired value.
press the set key. press the set key. DIS : To deactivate Alarm Relay in fault
In time it may be possible that the display Range condition.
Range may be offset by a degree or so. To
Min Max Fact. Set
Min Max Fact. Set compensate for this error, you may need ENB : To activate Alarm Relay in fault
to add or minus the degrees required to DIS ENB ENB condition.
-10.0ºC 10.0ºC 0.0ºC achieve the correct temperature. Setting
value is from -10.0ºC to + 10.0ºC. 27 ADT Function : This parameter is used to set
Parameter HT power on delay for alarm.
23 L7 Function : To set Compressor- To change the ADT parameter, Use UP/DOWN keys to set desired value.
Parameter Evaporator Fan status at Door open press the set key.
condition. Example : If you set this parameter to 20,
Range once the power is switched on, the HT
To change the L7 parameter, Use UP/DOWN keys to set desired value. alarm will not activate for 20 minutes after
press the set key. Min Max Fact. Set the power is switched on. This is most
At Door Open,
Range NORM : Normal. 0 Min 99 Min 30 Min useful to avoid the nuisance alarms when
the ambients are high when the machine
Min Max Fact. Set FAN : Evaporator Fan OFF. is switched on after a long time.
COMP : Compressor OFF.
NORM F-C NORM F-C : Compressor and Evaporator Fan ADD Function : This parameter is used for
28 Parameter time delay to activate Alarm/Buzzer relay
OFF.
at Door Open.
24 L8 Function : To set Evaporator Fan
Parameter status during defrost. To change the ADD parameter, Use UP/DOWN keys to set desired value.
press the set key. Example : This Parameter is set to 60 Sec
To change the L8 parameter, Use UP/DOWN keys to set desired value.
press the set key. Range & Door is open then Alarm/Buzzer will be
OFF : Evaporator Fan OFF during ON
Range defrost. Min Max Fact. Set after 60sec, if AL & BUZ parameters are
Min Max Fact. Set ON : Evaporator Fan ON during 0 sec 600 sec 60 sec enabled.
defrost.
OFF ON OFF THD Function : This parameter is used to set
29 Parameter duration for temperature hold at door
25 BUZ Function : To enable / disable buzzer. open.
Parameter To change the THD parameter, Use UP/DOWN keys to set desired value.
To change the BUZ parameter, Use UP/DOWN keys to set desired value. press the set key.
press the set key. Example: Example : This Parameter is set to 60sec,
Range ENB : Buzzer enabled. Range Room Temperature is -18.0OC & Door open
condition occurs then Room Temp value
Min Max Fact. Set DIS : Buzzer disabled. Min Max Fact. Set -18.0OC at Door open condition will be hold
DIS ENB ENB 0 sec 180 sec 0 sec for the 60sec, if Room Temperature is
Cont.
17 18
Description of parameters and functions. Description of parameters and functions.
Sr. Parameter Parameter setting method Sr. Parameter Parameter setting method
No. No.
increasing. C2 Function : Current sensing time delay.
32
After over the Temperature hold duration Parameter
display temperature will be increased by
To change the C2 parameter, Use UP/DOWN keys to set desired value.
0.1OC at every sec until it reaches current press the set key.
Room Temperature. Example : If C2 = 5 sec then, any current
Range
C-UL Function : Under load limit for fault will be valid only when it exists for
30 Parameter compressor current. Min Max Fact. Set more than 5 sec.
5 Sec 120 Sec 5 Sec
To change the C-UL parameter, Use UP/DOWN keys to set desired value.
press the set key. D0 Function : To enable or Disable HP
Example : If C-UL= 1.0A and compressor 33
Range Parameter sensing.
current is less than 1.0A then and exists till
Min Max Fact. Set C2 current sensing delay then it is To change the D0 parameter, Use UP/DOWN keys to set desired value.
registered as UL fault. Compressor will press the set key.
0.0A (C-OL 1.0A get OFF on this fault. If after 3 retries Example :
Range
-1.0)A within 1 Hour current drawn is still less If this parameter is set to
than 1.0Amp the controller will trip the Min Max Fact. Set ENB : HP sensing is enabled.
DIS : HP sensing is disabled.
compressor on fault and activate DIS ENB ENB
respective alarm relay. Also display will Setting this parameter to disable will
flash ‘C-UL’. Controller will go in manual ignore HP fault for compressor. If this
parameter is set to Enable then controller will
reset mode.
detect HP trip.
Function : Over load limit for compressor
31 C-OL current. D1 Function : To enable or disable LP
Parameter 34
Parameter sensing.
To change the C-OL parameter, Use UP/DOWN keys to set desired value.
To change D1parameter, Use UP/DOWN keys to set desired value.
press the set key.
press the set key.
Example : If C-OL= 15.0 A and Example:
compressor current is greater than 15.0 A Range
Controller with 20A CT If this parameter is set to
then and exist till C2 current sensing delay Min Max Fact. Set ENB : LP sensing is enabled.
Range then C-OL fault exists and flash on DIS : LP sensing is disabled.
Min Max Fact. Set display. Compressor will be tripped on this DIS ENB ENB
fault. Setting this parameter to disable will
(C-UL 20.0A 15.0A ignore LP fault for compressor. If this
+1.0) A parameter is set to Enable then controller will
NOTE: 20/50A CT option available detect LP trip.
Controller with 50A CT
while ordering controller.
Range
Min Max Fact. Set
(C-UL 50.0A 25.0A
+1.0) A
19 20
Description of parameters and functions. Description of parameters and functions.
Sr. Parameter Parameter setting method Sr. Parameter Parameter setting method
No. No.
21 22
Description of parameters and functions. Description of parameters and functions.
Sr. Parameter Parameter setting method Sr. Parameter Parameter setting method
No. No.
E8 Function : Defrost duration during Coil DIS : Pump down disable.
42
Parameter probe failure.
To change E8 parameter, Use UP/DOWN keys to set desired value. ETMP : Pump down enable at Set point
press the SET key. when compressor tripped on Set Point.
Example: If this is set to 10 min, then
Range EDEF : Pump down enable at Set point
manual defrost for 10 min will take place
when heater defrost condition occurs.
Min Max Fact. Set during Coil probe fail.
Fact. Set
1 Min 15 Min 5 Min Example :
LD Function : To set time delay to switch ETMP : If this parameter is set to ETMP
43 then SV relay will be ON/FF & pump down
Parameter off the light .
at Set point.
To change LD parameter, Use UP/DOWN keys to set desired value.
press the SET key. This parameter is used set the time delay EDEF : If this parameter is set to EDEF
Range to automatically switch OFF the light. If LD then SV relay will be ON/OFF on SP &
is set to 0 then this parameter is disabled. pump down only at heater defrost
Min Max Fact.
Fact. Set
Set Example : If this parameter is set to 7 mins condition.
0 Min 30 Min 7 Min then, when light is switched ON, after 7 PW Function : To change password.
46
mins it will be switch OFF automatically. Parameter
44 LSD Function : This parameter is used to To change the PW parameter, Use UP/DOWN key to change the
Parameter enable / disable light relay ON at door press the set key. password.
open.
Range User can enter into program mode
To change LSD parameter, Use UP/DOWN keys to set desired value.
Min Max Fact. Set only if correct password is entered. If the
press the SET key. If this parameter is set to Enable then Fact. Set password is wrong it will show ‘INVALID
Range whenever Door get open, the Light Relay 0 9999 0 PASSWORD’.
will be ON.
Min Max Fact. CRH Function : To view Compressor run
Fact. Set
Set 47
If this parameter is set to Disable then Parameter Hours.
DIS ENB ENB
Light Relay will be ON/OFF functioning It will display compressor run hours. It's a
manually and as per LD parameter. read only parameter.
PDN Function : To activate Solenoid Valve CCRH Function : Clear Compressor Run
45 48
Parameter relay. Hours.
To change PDN parameter, Use UP/DOWN keys to set desired value.
Range If this parameter is set to ‘YES’
press the set key.
compressor run hours (CRH) are cleared.
Min Max Fact.
Fact. Set
Set
Range
NO YES NO
Min Max Fact.
Fact. Set
Set
DIS EDEF DIS Cont.
23 24
Description of parameters and functions. Description of parameters and functions.
Sr. Parameter Parameter setting method Sr. Parameter Parameter setting method
No. No.
49 ID Function : To set Device ID. 23 PDIS Function : To set display at power OFF
52
Parameter Parameter mode.
To change Device ID This parameter is used to set the Device To change PDIS parameter, Use UP/DOWN keys to set desired value.
parameter, press the SET key. ID for the controller. press the SET key.
Range At power OFF mode power OFF LED
Range will glow & display will be as below,
Min Max Fact. Min Max Fact.
Fact. Set
Fact. Set
Set Set
LED : Display Will be Blank.
1 240 - LED TEMP LED
OFF : Display will show OFF.
TEMP : Display will show Temperature.
50 LP Function : To activate Keypad Lock.
Parameter
23 FS Function : To restore default settings of
To change Keypad Lock This parameter can lock the keypad so 53
Parameter the controller.
parameter, press the set key. that tempering is not possible by by-
standers. To change FS parameter, Use UP/DOWN keys to set desired value.
Range press the SET key.
NO : deactivates keypad lock. When set to YES all parameters are
Min Max Fact.
Fact. Set
Set YES : activates keypad lock. Range programmed to factory values.
NO YES NO Min Max Fact. Useful to debug setting related problems.
Fact. Set
Set
On activation, all the parameters can only
be viewed, but not modified. NO YES NO
If the keypad is locked “LOCK” message
will be displayed.. 54 EP Function: To exit from program mode.
Parameter
23 PO Function : To enable/disable Power To exit programming Once the set key is pressed, the controller
51
Parameter Switch. parameter, press the SET key. goes into the normal mode and displays
To change PO parameter, Use UP/DOWN keys to get desired the Room Temperature and all settings
press the SET key. value & press SET key to confirm. are recorded.
25 26
Technical Data
Housing : Plastic / Sheet Metal (as per customer
requirement)
Dimensions : Plastic : (H)400 x (W) 300 x (D)135 mm
Sheet Metal : (H)450 x (W) 400 x (D)200 mm
Mounting : Wall mounting.
Controller : CRC-2052
Connection : Spring clamp terminal block.
4 sq. mm wire.
Display : 4 Digit, 1” Dot matrix Display and 13 LEDs for
indication.
Data Storage : Non-Volatile EEPROM Memory.
Power Input (Options) : 415Vac +/-10%, 50-60Hz.
3Phase Supply with Neutral
Operating Temp : 50C to 500C(non-condensing).
Storage temp : -200C to 700C(non-condensing).
Output :
Compressor Relay : 5A/230vac
Defrost Relay : 5A/230vac
Evap. Relay : 5A/230vac
Condenser Relay : 10A/230vac
Light Relay : 5A/230vac
Alarm Relay : 5A/230vac
LSV Relay : 10A/230vac
Sensors :
1) Temperature sensor:
Sensor Type : NTC Thermistor.
Resolution : 0.10C.
Accuracy : +/-10C.
Probe Tolerance at 250C : +/-0.30C.
Room & Evap Temperature :
Range : -50.00C to 50.00C
Analog I/p:
Compressor current (R,Y,B)
Resolution : 0.1Amp.
Accuracy : +/-1 Amp.
Digital Inputs:
HP, LP, Auxiliary / CTH(Compressor Thermal) , Oil Pressure Switch(OPS),
Door, SPPR, R-Ph, Y-Ph, B- Ph.
Buzzer : Internal
RS485 Connectivity : Modbus RTU Protocol
Baud Rate : 9600
Device ID : 1 (By Default)
27
Instruction Manual Introduction
LVM (Line Voltage Monitor) Three Phase VMRC-10/3 VMRC-10/3 is three phase Line voltage monitor (LVM) used to protect device
from Single Phasing, voltage unbalance, phase reversal and under/over
voltage. It shows real time voltages between phase and neutral.
Index
There is an Output of alarm relay is given to the controller as SPPR input.
Pg. Features are easily understood by examples in the instruction below.
PARAMETER DESCRIPTION
No.
Introduction 29
Get to know your Controller. 29
To set program mode. 30 Get to Know Your Controller
To set Reference Voltage. 30
To set Over voltage Limits. 30
To set Undervoltage Limits. 31
To set Un Balance Value. 31
To set Time Delay. 31
To set fault recover delay. 32 R Y B N
15 17 19 18 21
To set Calibration of Voltage. 32
To set Calibration of Voltage. 32
To set Calibration of Voltage. 33
To set Display mode. 33
To Restore factory defaults. 33
End programming. 34 VMRC-10/3
Technical Data. 35
Front View & Connection Diagram. 35
RELAY
NO C NC
7 8 9
28 29
Description of parameters and functions. Description of parameters and functions.
Sr. Parameter Parameter setting method Sr. Parameter Parameter setting method
No. No.
To set other parameter 03 Function : To set Undervoltage Limits.
Press & hold PRG key for Display will show ‘rEF’ and scroll the To change the uV parameter, Use UP/DOWN keys to set desired value.
4 seconds description of the parameter. press the set key. If the a/c voltages goes below this
limit will trip respective a/c on
To go to other parameters, Range undervoltage(”Uv”) fault.
use up / down keys.
Min Max Fact. Set
Function : To set Reference voltage. Example : Under voltage is calculated
01 5V 75V 35V depending on Reference voltage - Uv
value. i.e Uv Set Point = Ref - Uv , When
To change the rEF Parameter, Use UP/DOWN keys to set desired value. controller trip on Uv Fault it will recover
press the set key. Base reference voltage to calculate under when input voltage above (Ref – (Uv /2).
voltage and over voltage values.
Range
04 Function : To set Un Balance value.
Min Max Fact. Set
Min and Max value will change
381V 415V 415V according to display type for settings. To change the unb parameter, Use UP/DOWN keys to set desired
press the set key. value.
Example : If dsP is L-L then Min= 381V,
Max= 415V. Range Unbalance fault raised when voltage
Function : To set Overvoltage Limits. Min Max Fact. Set difference between any of two phases
02 goes above Unb value and recovers when
10V 120V 60V the difference is less than (UNB/2).
To change the oV parameter, Use UP/DOWN keys to set desired
press the set key. value. Function : To set time delay.
If the a/c voltages goes above this 05
Range limit will trip respective a/c on
To change the ttd parameter, Use UP/DOWN keys to set desired
Min Max Fact. Set Overvoltage(”Ov”) fault. press the set key. value.
5V 75V 35V Example : Over voltage is calculated
Range Time delay provided to avoid false
depending on Reference voltage + Ov
value. i.e, Ov Set Point = Ref + Ov , When Min Max Fact. Set triggering, when any fault last more than
controller trip on Ov Fault it will recover TTD value then only fault is raised and this
when input voltage fall below (Ref - (Ov 0Sec 60Sec 10Sec fault is applicable to Under voltage, Over
/2). voltage and Unbalance fault.(i.e., In case
of Phase Loss or Phase sequence fault
alarm will come immediately).
30 31
Description of parameters and functions. Description of parameters and functions.
Sr. Parameter Parameter setting method Sr. Parameter Parameter setting method
No. No.
06 Function : To set fault recover delay. 09 Function : To set calibration of voltage
for r-b or b-n phase.
To change the tdr parameter, Use UP/DOWN keys to set desired To change the Crb parameter, Use UP/DOWN keys to set desired
press the set key. value. press the set key. value.
Range Time delay provided to add delay in fault Range This parameter provided to calibration
Min Max Fact. Set recover time, to avoid sudden fault Min Max Fact. Set voltage reading.
triggering and reset.
0Sec 240Sec 10Sec -15V 15V 0V When dsP is L-L then it sets calibration for
r-b.
Function : To set calibration of voltage When dsP is L-n then it sets calibration for
07 b-n.
for r-y or r-n phase.
To change the CrY Parameter, Use UP/DOWN keys to set desired
press the set key. value. 10 Function : To set view display mode.
Range This parameter provided to calibration To change the dsP parameter, Use UP/DOWN keys to set desired
Min Max Fact. Set voltage reading. press the set key. value.
-15V 15V 0V When dsP is L-L then it sets calibration for Range There are two type of display output, Line
r-y. Min Max Fact. Set to Line Voltage (L-L) and Line to Neutral
When dsP is L-n then it sets calibration for (L-n), Depending on this parameter REF
r-n. L-L L-n L-L parameter also changes.
32 33
Description of parameters and functions. Technical Data
Sr. Parameter Parameter setting method
No. Main Functions : Voltage Monitoring.
Phase Sequence Monitoring.
12 Function :To end programming. Phase Loss and Phase Unbalance detection.
Uv and Ov Detection.
To change the end parameter, Once the set key is pressed, the controller Settable Uv and Ov Parameter.
press the set key. goes into the normal mode and displays Dimensions : Front : 70mm X 45mm,
the voltage readings. Depth : 72.3 mm
Input : R, Y, B Phases and Neutral Input.
Output : Alarm Relay : 5A Resistive.
General Specification :
Input Voltage Range from 100VAC to 265VAC.
Mounting : Din rail mounting.
Connections : Screw terminals : < 2.5sqmm one wire/terminal only.
VMRC-10/3
R Y B N
15 17 19 18 21
1 2 3 7 8 9
NO C NC
RELAY
34 35
36
Controller Notice
Controller should be installed in a place protected by vibration, water and The information in this document is subject to change in order to improve
corrosive gasses and where ambient temperature does not exceed the values reliability, design or function without prior notice and does not represent a
specified in the technical data. commitment on the part of the company. In no event will the company be liable
for direct, indirect, special, incidental or consequential damage arising out of
Probe the use or inability to use the product or documentation, even if advised of the
To give a correct reading, the probe must be installed in a place protected from possibility of such damages. No part of this manual may be reproduced or
thermal influences, which may affect the temperature to be controlled. transmitted in any form or by any means without the prior written permission of
the company.
Caution
WIRING : The probe and its corresponding wires should never be installed Disclaimer
in a conduit next to control or power supply lines. The electrical wiring This manual & its contents remain the sole property of PVR Controls, India and
should be done as shown in the diagram. The power supply circuit should
be connected to a protection switch. shall not be reproduced or distributed without authorization. Although great
care has been taken in the preparations of this document, the company or its
WARNING : Improper wiring may cause irreparable damage and personal vendors in no event will be liable for direct, indirect, special, incidental or
injury. Kindly ensure that wiring is done by qualified personnel only. consequential damage arising out of the use or inability to use the product or
documentation, even if advised of the possibility of such damages. No part of
Maintenance : Cleaning : Clean the surface of the controller with a soft
moist cloth. Do not use abrasive detergents, petrol, alcohol or solvents. this manual may be reproduced or transmitted in any form or by any means
without the prior written permission of the company. PVR Controls, reserves
the right to make and changes or improvements without prior notice.
Warranty
This product is warranted against defects in materials and workmanship for a
period of one year from the date of purchase. During the warranty period,
product determined by us to be defective in form or function will be repaired or,
at our option, replaced at no charge. This warranty does not apply if the product
has been damaged by accident, abuse, and misuse or as a result of service or
modification other than by the company. This warranty is in lieu of any other
warranty expressed or implied. In no event shall the company be held liable for
incidental or consequential damages, such as lost revenue or lost business
opportunity arising from the purchase of this product.
37 38