PARTICULAR REQUIREMENT FOR MCC

System : Power Gen Room System : 380V, 3phase 4W Item : Tunnel MCC -1 to9 : 9Nos.
Fault Level : 25KA Busbar : 100A Cu. Ambient Temp : 45Deg.C
Insulation : 2.5KV Deg. of Protection: IP 52 Paint : Epoxy Powder Coated

S.N Connected Load Type of Type of Rating Contact O/L Ind Push Button Metering Qty
o. Equipment in KW Starter Protecti of or Relay Lamps
on MPCB / Rating Phasing
MCCB (Amps) Protectio R G W Forward Reverse Start Stop
Amps n

1. Incomer - - MCCB 100A - -   - - - - - Digital Ammeter, -


Voltmeter
2. Discharger 22 DOL MPCB 50A 63A 32 -50    - -   Analog Meter with 1
Suppressed Scale
3. Actuator 7.5 RDOL MPCB 16A 32A 10-16A      -  Analog Meter with 1
Suppressed Scale
4. Sump 5 DOL MPCB 16A 16A 8 - 12.5A    - -   Analog Meter with 1
Pump Suppressed Scale
5. Exhaust 2 DOL MPCB 5A 12A 3.2 - 5A    - -   Analog Meter with 1
Fan Suppressed Scale
6. Belt Scale 1.1 Feeder MCCB 16A - -   - - - - - Digital Ammeter 1
7. Spare 22 DOL MPCB 50A 63A 32 -50    - -   Analog Meter with 1
Suppressed Scale

Note : 1. Contactor and O/L Relay shall be provided with 2NO+2NC spare potential free contacts, wired upto terminal blocks

2. MPCB Rating and O/L Relay Range based on "Siemens Selection Chart for Type -2 co-ordination

S.M. Engineers & Consultants - 15 -


PARTICULAR REQUIREMENT FOR MCC

Location : Power Gen Room System : 380V, 3phase 4W Item : Tripper MCC 1 & 2 : 2Nos.
Fault Level : 25KA Busbar : 32A Cu. Ambient Temp : 45Deg.C
Insulation : 2.5KV Deg. of Protection: IP 52 Paint : Epoxy Powder Coated

S.N Connected Load Type of Type of Rating Contact O/L Ind Push Button Metering Qty
o. Equipment in HP Starter Protecti of or Relay
Lamps
on MPCB / Rating Phasing
MCCB (Amps) Protectio R G W Forward Reverse Start Stop
Amps n

1. Incomer - - MCCB 32 - -   - - - - - Digital Ammeter 1


and Voltmeter
2. Tripper Car 1.5 RDOL MPCB 4 9A 2.5 -4      -  Analog Ammeter 1
with Suppressed
Scale
3. Cable 2.2 RDOL MPCB 5 9 3.2-5      -  Analog Ammeter 1
Reeling with Suppressed
Drum Scale
4. Flap Gate 3 RDOL MPCB 8 12A 5-8      -  - 1
5. Spare - Feeder MCCB 16A - -   - - - - - - 2

Note : 1. Contactor and O/L Relay shall be provided with 2NO+2NC spare potential free contacts, wired upto terminal blocks
2. MPCB Rating and O/L Relay Range based on "Siemens Selection Chart for Type -2 co-ordination

S.M. Engineers & Consultants - 16 -


PARTICULAR REQUIREMENT FOR MCC

Location : Power Gen Room System : 380V, 3phase 4W Item : DS Panel - 1,2 : 2Nos.
Fault Level : 25KA Busbar : 32A Cu. Ambient Temp : 45Deg.C
Insulation : 2.5KV Deg. of Protection: IP 52 Paint : Epoxy Powder Coated

S.N Connected Load Type Type of Rating Contact O/L Relay Ind Push Button Metering Qty
Equipment in HP of Protection of or Phasing
Lamps
Starter MPCB Rating Protection
/ (Amps) R G W Forward Reverse Start Stop
MCCB
Amps
1. Incomer - - MCCB 16 - -  - - - - - Digital Ammeter 1
and Voltmeter
2. Fan 0.75 DOL MPCB 2 9 1.25 -2   - -   Analog Ammeter 1
with Suppressed
Scale
3. Drain 3.1 DOL MPCB 8 12 5-8   - -   Analog Ammeter 1
Pump with Suppressed
Scale
4. Spare - Feede MCCB 16 - -  - - - - - - 1
r

Note : 1. Contactor and O/L Relay shall be provided with 2NO+2NC spare potential free contacts, wired upto terminal blocks
2. MPCB Rating and O/L Relay Range based on "Siemens Selection Chart for Type -2 co-ordination