System : Power Gen Room System : 380V, 3phase 4W Item : Tunnel MCC -1 to9 : 9Nos.
Fault Level : 25KA Busbar : 100A Cu. Ambient Temp : 45Deg.C
Insulation : 2.5KV Deg. of Protection: IP 52 Paint : Epoxy Powder Coated
S.N Connected Load Type of Type of Rating Contact O/L Ind Push Button Metering Qty
o. Equipment in KW Starter Protecti of or Relay Lamps
on MPCB / Rating Phasing
MCCB (Amps) Protectio R G W Forward Reverse Start Stop
Amps n
Note : 1. Contactor and O/L Relay shall be provided with 2NO+2NC spare potential free contacts, wired upto terminal blocks
2. MPCB Rating and O/L Relay Range based on "Siemens Selection Chart for Type -2 co-ordination
Location : Power Gen Room System : 380V, 3phase 4W Item : Tripper MCC 1 & 2 : 2Nos.
Fault Level : 25KA Busbar : 32A Cu. Ambient Temp : 45Deg.C
Insulation : 2.5KV Deg. of Protection: IP 52 Paint : Epoxy Powder Coated
S.N Connected Load Type of Type of Rating Contact O/L Ind Push Button Metering Qty
o. Equipment in HP Starter Protecti of or Relay
Lamps
on MPCB / Rating Phasing
MCCB (Amps) Protectio R G W Forward Reverse Start Stop
Amps n
Note : 1. Contactor and O/L Relay shall be provided with 2NO+2NC spare potential free contacts, wired upto terminal blocks
2. MPCB Rating and O/L Relay Range based on "Siemens Selection Chart for Type -2 co-ordination
Location : Power Gen Room System : 380V, 3phase 4W Item : DS Panel - 1,2 : 2Nos.
Fault Level : 25KA Busbar : 32A Cu. Ambient Temp : 45Deg.C
Insulation : 2.5KV Deg. of Protection: IP 52 Paint : Epoxy Powder Coated
S.N Connected Load Type Type of Rating Contact O/L Relay Ind Push Button Metering Qty
Equipment in HP of Protection of or Phasing
Lamps
Starter MPCB Rating Protection
/ (Amps) R G W Forward Reverse Start Stop
MCCB
Amps
1. Incomer - - MCCB 16 - - - - - - - Digital Ammeter 1
and Voltmeter
2. Fan 0.75 DOL MPCB 2 9 1.25 -2 - - Analog Ammeter 1
with Suppressed
Scale
3. Drain 3.1 DOL MPCB 8 12 5-8 - - Analog Ammeter 1
Pump with Suppressed
Scale
4. Spare - Feede MCCB 16 - - - - - - - - 1
r
Note : 1. Contactor and O/L Relay shall be provided with 2NO+2NC spare potential free contacts, wired upto terminal blocks
2. MPCB Rating and O/L Relay Range based on "Siemens Selection Chart for Type -2 co-ordination