You are on page 1of 24

Premises

27
Willem Boeke and Paul Le Brun

Contents 27.6.3 Floors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 606


27.6.4 Ceilings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 606
27.1 Processes as a Starting Point for the Design of Areas 27.6.5 Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 607
and Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 586 27.6.6 Furniture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 607
27.2 Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 586 27.7 The Implementation Phase of Building or Rebuilding 607
27.2.1 Main Layout Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 586
27.2.2 Sterile Stock Preparations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 587 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 608
27.2.3 Aseptic Stock Preparations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 588
27.2.4 Aseptic Extemporaneous Preparations . . . . . . . . . . . . . . . . . . . 588
27.2.5 Non-sterile Stock Production . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 588
27.2.6 Non-sterile Extemporaneous Preparations . . . . . . . . . . . . . . . 588 Abstract
27.2.7 Storage Rooms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 589 This chapter outlines the general aspects of premises
27.3 User Requirements Specification . . . . . . . . . . . . . . . . . . . . . . 589 designed for pharmaceutical preparation activities and
the steps to consider in order to achieve a justified design,
27.4 Functional Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 590
27.4.1 Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 590 construction and qualification of these premises. Also the
27.4.2 Classification of Premises . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 590 built-in technical facilities are discussed. Premises and its
27.4.3 Interlock Systems for Air Locks . . . . . . . . . . . . . . . . . . . . . . . . . 593 technical facilities are an essential link in achieving good
27.4.4 Communication and Interior Design . . . . . . . . . . . . . . . . . . . . . 593 preparation practice. Their design and qualities should be
27.4.5 Routing and Gowning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 593
derived from the kind of products that will be produced
27.5 Built-in Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 593 in it.
27.5.1 Installations for Heating, Ventilation and Air
European and WHO GMP define in general terms
Conditioning (HVAC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 594
27.5.2 Installations for Storage and Distribution preconditioned criteria that have to be met by premises,
of Pharmaceutical Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 597 including storage areas, weighing areas etc. However this
27.5.3 Provisions for Pressurised Air, Vacuum and Various chapter does not define exactly what is appropriate in any
Gasses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 603
27.5.4 Electrical and ICT Provisions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 603
specific facility. The emphasis is on the interrelationship
27.5.5 Building Control Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 604 between the demands, the building, the installations and
the provisions. The scope is general so that all small-scale
27.6 Detail Specification and Building . . . . . . . . . . . . . . . . . . . . . . 604
27.6.1 Inner and Outer Walls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 604 production facilities for healthcare establishments and
27.6.2 Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 605 preparation centres are covered in the discussion. Also
ready-made premises or modules can be assessed by
comparison of their qualities with the ones mentioned in
this chapter.
Based upon the chapter Ruimten en Installaties by Willem Boeke, This chapter’s arrangement follows the general
Marco Prins and Jeannine van Asperen in the 2009 edition of approach of best practices in qualification. Important
Recepteerkunde.
subjects covered are:
W. Boeke (*) • Processes that underlie the necessity to build a prepa-
Klinische Farmacie Ziekenhuisgroep Twente, Hengelo,
ration facility
The Netherlands
e-mail: boeke@wxs.nl • Products and the legislative framework
• Routing of goods and personnel and communication
P.P.H. Le Brun
Apotheek Haagse Ziekenhuizen, The Hague, The Netherlands • Specification and classification of premises
e-mail: p.lebrun@ahz.nl2 • Built-in installations for HVAC, water and gasses

Y. Bouwman-Boer et al. (eds.), Practical Pharmaceutics, 585


DOI 10.1007/978-3-319-15814-3_27, # KNMP and Springer International Publishing Switzerland 2015
586 W. Boeke and P.P.H. Le Brun

• Detail specification and building execution them having substantial knowledge in their fields. Still the
• Walls, doors, floors, ceilings, heating, fixtures and specific knowledge of the design and qualification of a
fittings pharmaceutical preparations facility and its installed equip-
ment might be insufficient among those parties, unless a
Keywords specialist company is chosen for the design and building.
Premises  Building  HVAC  Construction  Built-in Conversely consulting engineers are important for the
facilities  Water incorporation of every aspect of safe building which usually
is an unfamiliar topic for the pharmacist. This should prevent
failures in construction stability, escape routes, fire and
explosion prevention, etc.
27.1 Processes as a Starting Point
It should be decided which categories of products are to
for the Design of Areas and Installations
be prepared and on what scale. The products involve prepa-
ration processes that basically determine what is necessary
At the initial design stage for a new preparation facility
for a specific facility, taking into account legislation.
attention should be paid to a variety of subjects, such as:
Pharmacy preparation processes can arbitrarily be
• The type and product range of medicines that will be
subdivided into the following categories each with their
required from the facility
own specific premises:
• Developments within the pharmaceutical and medical
I. Extemporaneous sterile and non-sterile preparations
environments and possible future product and process
Examples of this kind of preparations are: Aseptic
demands
handling, i.e. uncomplicated operations with sterile
• The production scale and the batch volumes per product,
medicines in closed containers after which they get a
considering peak loads and annual volume
very short usage period, reconstitution of sterile and
• The scope of the facility and its requirements, e.g. to
non-sterile authorised medicines and extemporaneous
supply other pharmacies with pharmacy prepared
non-sterile preparations from raw materials.
medicines
II. Extemporaneous preparations involving specific risks,
Whatever motives there might be for a (re-)building project
such as complex aseptic handling and preparation with
it should always be kept in mind that the design is specific to
hazardous substances. Involved in this category is aseptic
the type and volume of products for which it is built. Cutting
handling with most antineoplastics, medication cartridges,
out one detail might ruin the possibilities to achieve a
radiopharmaceuticals, biological or advanced therapy
validated production process.
medicinal products (ATMP’s).
III. Sterile and non-sterile stock preparations. Involved are:
Small Detail; Big Consequences. . . • Non-sterile stock preparations
Standard doors will always have certain tolerances in • Sterile stock preparations (sterilisation in final
their rate of warping. However the entry doors to container)
premises with an air pressure hierarchy, as required • Sterile aseptic stock preparations
by the production process, must be checked for this The products to be prepared can be organised into a table as
property in advance. This is to avoid the almost in Table 27.1, related to their categories. This may help to
unsolvable problems in the qualification of the air estimate the extent of provisions and the level of required
pressure hierarchy due to leakages by not perfectly standards that are necessary per product type.
closing doors. Neither the suppliers of doors nor
contractors are usually aware of the importance of
assessing these tolerances in advance. After all, if
this air pressure hierarchy really was required but 27.2 Design
could not be qualified as such, a validated production
process will not be achieved. 27.2.1 Main Layout Considerations

Starting from the classification of preparation processes a


Therefore, at the initial design stage in the construction of rough preliminary design is drafted indicating the position of
premises for pharmaceutical preparations the responsible production areas, their interrelationship and logistics. The
pharmacist or an advisor who has proven capabilities in relations between departments and premises, flow of goods
this specific area must have a decisive input and a coordina- and persons are plotted. This start document is preferably
tive role. He will have to deal with architects, companies of formulated by the one who will be responsible in future for
consulting engineers, (sub-)contractors and installers, all of the preparation processes.
27 Premises 587

Table 27.1 Categorisation of products for designing premises


A. Stock preparations Categories A correct constructional design has to be derived from
A1 Sterile the process and will prevent any confluence or cross-
Aseptic preparations (vials, ampoules, infusion fluids III ing of routes. However, in practice crossing cannot
in bags, prefilled syringes) always be avoided. In that case procedural solutions
Autoclavable preparations (vials, ampoules, infusion III should warrant that all goods are to be labelled and
fluids in bags or bottles)
packed securely (e.g. in closed boxes) before being
Eye drops III or II
exposed to crossing lines. Routing questions at the
Sterile ointments and creams III
design of a layout of premises will frequently be with
A2 Non-sterile
regard to processes such as weighing raw materials,
Packaging e.g. in Unit Dose III
Tabletting III
sampling, input and output to and from any temporar-
Fluids (solutions and suspensions) III
ily deposit store for intermediates or quarantine,
Ointments and creams III cleaning of reusable utensils and label printing.
Suppositories III For example, it is important to consider if the weighing
B. Extemporaneous preparations process will or will not be carried out in a centralised
B1 Sterile weighing room thus requiring subsequent transport of
Aseptic handling (complex, see Sect. 31.3.2) II the labelled portions to the preparation room. In a
Total parenteral nutrition, medication cassettes centralised weighing room, thorough precautions
Aseptic handling (hazardous, see Sect. 31.3.5) should be taken to prevent cross contamination of the
Antineoplastics, radiopharmaceuticals raw materials. The same goes when two workers use
Simple aseptic handling; short shelf-life I the same set of weighing apparatus in a pharmacy.
B2 Non-sterile
Capsules, suppositories, fluids, ointments and creams I
Reconstitution of licensed pharmaceutical preparations I • The location of the preparation department in relation to
logistic functions, etc. For example radiopharmaceuticals
(see Sect. 15.6.1) should be prepared nearby or at the
nuclear medicine department.
The preliminary design should be drawn up based on the • The required apparatus and utensils, the preparation pro-
following considerations: cesses they are used for and the required provisions such
• The extent of the preparation department: Available as air conditioning, clean water, electricity, compressed
premises usually are confined. However, sufficient room

PRODUCTION
air and gasses. For extremely hazardous preparations
must be available for apparatus and materials. Apparatus (antineoplastics, radiopharmaceuticals, see Sect. 26.3.5)
should be stored in a way that minimises contamination. and for sterile preparations separate premises may be
Therefore, a separate accommodation near the prepara- required to protect products and operators adequately, as
tion premises is preferred over the placement in the is also laid down in GMP. Scaling up of the processes
preparation room itself. may lead to partitioning of the rooms into areas for
Sufficient room should be available for the operators to dedicated functions.
work efficiently and safely. After classifying the preparation processes and the corres-
• Avoiding crossing routes for personnel and goods: In a ponding premises and its outlines the preliminary design will
pharmacy several products are usually being prepared on be drafted. Some examples are given below for a few prepa-
the same day. This brings about a higher risk of cross ration processes.
contamination when compared to a large pharmaceutical
industry producing only one product on a dedicated pro-
duction line. Inadvertent mixing up of a sterile and a not 27.2.2 Sterile Stock Preparations
yet sterilised product or of products of different batches
constitutes a similar threat. Separate rooms are necessary for the preparation and for
• Entrance: The entrance to premises for preparation filling into e.g. infusion bags or ampoules prior to final
should be provided by means of, preferably heat sterilisation. In addition, one or more sterilisers with
sex-separated, gowning rooms for staff and a separate corresponding technical rooms (including the access) are
air locked entrance exclusively for goods. If necessary needed.
the separation of the sexes might be achieved by The premises for the most critical preparation steps
separating in time. However it should be realised that (e.g. filling) must be built as a clean room (see Sect. 27.3)
this may jeopardise the efficiency of the production. and require a controllable air conditioning installation.
588 W. Boeke and P.P.H. Le Brun

Those premises must comply with GMP class C (see hazardous products, may require dedicated rooms and con-
Sect. 27.4.2 and Table 27.2) [1]. tainment conditions (see Sect. 26.7).
Sterile stock preparations usually require such high For aseptic handling in closed systems a cabinet with
volumes of water that separate technical installation unidirectional airflow (LAF or safety cabinet) or an isolator
premises are required to accommodate the installation for can be used (see Sect. 28.3). The requirements for the back-
the production of water for injections. ground room depend on national guidelines and on the types
Finally, premises for examining and for packaging and of containment in the cabinets. Adjustments are allowed but
labelling are necessary. must be based on a risk assessment.
Appropriate rooms (laboratories) for pharmaceutical
microbiological control and for chemical quality control
Strictly, air quality class A cannot be claimed if the
should not be left out. However the possibility of
background qualification is less than class B. However
microbiological contamination from this laboratory requires
this class A safeguard is strictly only required for
a completely separated air handling.
aseptic stock preparation and any aseptic handling
Alternatively the microbiological control could be out-
that is executed with non-closed systems. Under spe-
sourced implying yet other, more procedural complications
cific conditions a class C condition as background
such as the need for Service Level Agreements and meeting
might be acceptable. On the basis of a thorough risk
the requirements of GMP Chap. 7 (Outsourced activities).
assessment and a monitoring and validation program
even a class D background for well-defined aseptic
handling may be justified, see Sect. 31.3.4.
27.2.3 Aseptic Stock Preparations

In premises for aseptic preparation from sterile raw materials


the preparation room usually is combined with the filling
27.2.5 Non-sterile Stock Production
room because carrying the bulk product into another room
will introduce an additional contamination risk. In this situ-
This department can be divided into separate premises for
ation a separate room for preliminary operations, e.g. disin-
solid (dusty), semisolid and fluid preparations. Preparation
fection of utensils and surfaces of containers, is required.
processes with inflammable substances may require specific
At the most critical places, especially at the filling point
provisions such as a fume cupboard or more intensive venti-
of the aseptic fluids, the premises must meet GMP class A
lation. Premises for tableting and similar dust-producing
conditions [1]. A class A condition usually needs a back-
preparation processes should be equipped with a suitable
ground condition of class B to be able to maintain the class A
installation for air conditioning and dust exhaustion. Apply-
condition during operation. However exceptions to this rule
ing a negative pressure will prevent dust from active
can be warranted, e.g. using an isolator.
substances escaping from the preparation room. Even for
Classified premises are expensive both in procurement
repackaging activities (e.g. into unit dose package) a sepa-
and maintenance. Therefore, it is justified to analyse each
rate room is to be preferred. Specific GMP classification
preparation process for all critical steps and to limit their
A-D is not required for non-sterile preparations. However
number as far as possible.
the GMP principles such as cleanability are applicable.
Premises for examining and for packaging and labelling
Therefore, in practice, facilities for non-sterile preparation
can be combined with those for sterile stock preparations.
are often classified as grade D.

27.2.4 Aseptic Extemporaneous Preparations 27.2.6 Non-sterile Extemporaneous


Preparations
Also in this situation a separate room is required for prelim-
inary operations, e.g. disinfection of utensils and surfaces of The underlying principles for premises for non-sterile stock
materials. In the preparation room medicines are preparations should be used for extemporaneous prepara-
reconstituted, e.g. filling of syringes, infusion bags, medica- tions as well. Preparation activities in a community phar-
tion cartridges, disposable infusion pumps and irrigations. In macy usually are confined to reconstitution, aseptic
addition, parenteral nutrition fluids, antineoplastics, handling, manipulation of licensed medical products and
radiopharmaceuticals and eye preparations may be prepared non-sterile preparation from raw materials. The avoidance
in these premises. Radiopharmaceuticals and other very of crossing process lines in small-scale situations is a
27 Premises 589

challenge but it is almost impossible to prevent crossing with dust or even insects. So either only complete units have
lines just by the layout of the premises. Routing has to be to be used or the remaining materials should be rewrapped or
specified by procedures and organisational measures have to repacked.
be taken, e.g. working with trays or closed boxes per Storage rooms should be kept clean at a normal house-
activity. hold level and vermin-free. No specific additional demands
The requirements for the premises may turn out to be are made because the package of the products should protect
quite moderate, provided that they are based on a well- them sufficiently against any contamination.
documented risk assessment. It will at least imply that
premises shall be exclusively dedicated for preparation
activities, e.g. shall not give direct access to toilets and
27.3 User Requirements Specification
will have to be physically separated from any public area.
The layout should not compromise a logical sequence of
As soon as the draft design, the program of requirements and
activities. Specific gowning and cleaning procedures must
a thorough (risk) analysis of the anticipated production
apply.
activities is gathered, this information should be ’translated’,
Attention should be paid to the ventilation of any premise
usually by professional advisors, into a keynote document or
and its upkeep. In newly built premises, the ventilation
user requirements specification (URS). This document
capacity might have been minimised due to energy saving
should describe and specify in detail the required situation
policy, especially in northern countries. Therefore the risk
after the (re-)building. It should clearly underpin the listed
has to be assessed that the ventilation might fail to meet
demands and points of departure, which for their part should
minimal requirements. Any so-called ’natural ventilation’
be traceable to relevant legislation. In addition the URS
might clear the way for insects to enter, unless specific
should, after realisation of the building, offer direct control
measures are taken (e.g. insect screens). Air quality can be
points to all critical aspects of the intended processes. The
improved by using a recirculating dust exhaust cabinet
conformity of the final situation to the original plan must be
which should be available in every community pharmacy,
proven which only can be done by checking systematically
e.g. for the reconstitution of antibiotic oral liquids.
all critical control points of the completed premises to the
original plan as previously specified in the URS.
The delivery of this evidence is called the performance
27.2.7 Storage Rooms qualification (PQ), see further Sect. 34.15. It is important to
pay attention to the future PQ as, in contrast to other

PRODUCTION
Apparatus to achieve specific, usually low temperature, stor- qualifications, the PQ cannot be outsourced. A well-
age conditions are described in Sect. 28.9. The design of formulated URS takes account of the implementation of
storage rooms should take into account that the temperature the future PQ tests and therefore its tenor extends far beyond
should not exceed 25  C for prolonged periods (see Sect. a more trivial ’Plan of Demands’.
36.9.4). This may involve the necessity of air conditioning. The URS should account for regulatory demands of
Additional provisions should be provided to avoid long GMP, Occupational Safety and Health and Environmental
lasting humidity levels over 60 % RV or below 20 % RV Care. Additionally preparation demands, required apparatus,
or penetration of direct sunlight. HVAC (installations for Heating, Ventilation and Air Con-
Specific conditions, like lockable safety cupboards, may ditioning) controls, routing of personal and goods as well as
be required for the storage of any specific class of hazardous gowning and cleaning instructions should be specified. It
(e.g. inflammable or poisonous) products. should be stated explicitly which regulations (e.g. GMP,
A properly considered location of storage rooms, ISO standards, Occupational Safety and Health legislation)
separated quarantine storage and laboratory may ease rout- do apply, thus delimiting the legislative framework. By
ing very much. adding the prefix ’c-’ (current) to the name of any law
There should be ample space for input and output of goods (e.g. c-GMP) it is stated that the regulation may be develop-
without the need of rearranging the goods at each occasion ing during the life of the premises and that always the most
(first-in first-out principle). Especially the manoeuvring of recent version has to be consulted.
pallets should be accounted for. Clean rooms are usually involved in the design of a
Empty packing material is usually wrapped in airtight pharmaceutical production facility. The term ’cleanroom’
wrappings or transport casings. However after opening the is specified in detail in the ISO standards 14644 (parts 1, 2,
wrap, packing materials are open to the rather unconditioned 4, 5 and 7) and 14698 (parts 1 and 2) [2–5]. Particularly ISO
environment of the storage room and thus open for pollution 14644 part 4 deals with the design, the construction and the
590 W. Boeke and P.P.H. Le Brun

initial start-up of a clean room and includes a useful be proved at any moment and place, measures are prescribed
checklist [4]. that should guarantee this absence with substantial safety
margins:
• The inlet air should be filtered, through HEPA (Highly
Efficient Particulate Air) filters.
27.4 Functional Specification
• A specified air replacement factor per hour (ventilation
factor; see Sect. 27.5.1 HVAC) should be achieved.
27.4.1 Contents
• The premises must be kept clean in relation to lower
classified neighbouring premises by the application of
Next step in the design process is drawing the functional
pressure differences.
requirements specification (FRS), also called the physical
Annex 1 of the GMP applies. This document specifies four
requirements specification. The FRS documents elaborated
grades for low particulate premises: A, B, C and D. See
demands for connections, heat burden, floor load, acoustic
Table 27.2.
demands, specifications of the walls, HVAC etc.
GMP Annex 1 states that a certain air quality class can
The heat burden is the amount of heat that is generated in a
only exist when the access to the room is achieved through
room per unit of time by humans and apparatus. Provisions for
an air lock in which the same class prevails. The Annex
air supply have direct impact on product quality. In the FRS
1 classification refers to the ISO classification (see
for clean rooms the limits are specified for the allowable
Table 27.3) that define intermediate air quality specifications
number of particles at rest and in operation, i.e. the clean
by decimal class designations.
room class (see Sect. 27.4.2 below), along with desired turbu-
According to ISO 14644–1 the air classification scheme is
lence limits, limits for air pressure and microbiological limits.
distinguished by a mathematically coherent approach and
It provides the final specifications for premises, fixtures and
based upon a formula:
fittings and a map with the positions of furniture and appara-
tus. The FRS contains also technical or procedural measures
Cn ¼ 10N ð0:1=DÞ2, 08 ð29:1Þ
to prevent cross contamination or crossing lines for personal
or goods [5]. Obviously all specifications in the FRS are
where
substantiated at the base of their application. As an example,
Cn ¼ maximum number concentration of particles per m3
in premises intended for complex aseptic handling or recon-
with diameter  the considered particle diameter,
stitution of hazardous sterile medicines, any choice for the
rounded to a maximum of 3 digits;
classification of the background conditions should be justified.
N ¼ ISO classification number;
D ¼ considered particle diameter;
0.1 ¼ the reference diameter, a constant with the
27.4.2 Classification of Premises
dimension mm.
The idea behind GMP is to preclude any factor with an As the ISO classification is defined by a continuous
unpredictable or undetermined impact on the production pro- formula with the particle size as a variable and the GMP
cess as this impairs the process validity. Particles, micro- grades are defined in discrete counts for specific particle
organisms and (gaseous) chemical contaminants arising sizes, the comparison between GMP grades and ISO
from the air from outside might constitute such a factor, classifications is formally not possible. Additionally ISO
especially relevant for the process of producing sterile and classifications can be formulated in decimals where the
aseptic preparations. Therefore, GMP requires that premises GMP grades cannot. However as a practical approach the
for this kind of preparations must be classified. Since the comparison is possible as e.g. grade B at rest will match ISO
absence of invisible micro-organisms and dust is hard to 5 for most practical purposes.

Table 27.2 Grades of air conditioning according to GMP


Maximum permitted number of particles per m3 equal to or greater than the tabulated size
At rest In operation
Grade 0.5 μm 5.0 μm 0.5 μm 5.0 μm
A 3,520 20 3,520 20
B 3,520 29 352,000 2,900
C 352,000 2,900 3,520,000 29,000
D 3,520,000 29,000 Not defined Not defined
27 Premises 591

Table 27.3 ISO 14644–1 classification of air cleanliness


Maximum permitted number of particles per m3 equal to or greater than the tabulated size
(in operation)
Class 0.1 μm 0.2 μm 0.3 μm 0.5 μm 1 μm 5 μm
1 10 2
2 100 24 10 4
3 1,000 237 102 35 8
4a 10,000 2,370 1,020 352 83
5(GMP B at rest) 100,000 23,700 10,200 3,520 832 29
6 1,000,000 237,000 102,000 35,200 8,320 293
7 (GMP grade B in operation, Grade C at rest) 352,000 83,200 2,930
8 (GMP grade C in operation, Grade D at rest) 3,520,000 832,000 29,300
9 35,200,000 8,320,000 293,000
a
EU GMP Grade A meets ISO 4.8

How Is the Classification of the Premises Actually cabinet is at least class B. The background room for
to be Derived from the URS? aseptic reconstitution or handling in a LAF, or safety
A basic principle is that raw materials, intermediate cabinet may have a lower classification than B,
products and final products that are not yet in their provided that it is based on risk assessment. Confor-
final, primary package should never be exposed to any mation to the latest views of inspectorates and profes-
unconditioned air. The primary package is the airtight sional associations e.g. PIC/S [1] is advised.
enclosing package of the final product that is in direct
contact with the product. Should therefore also
non-sterile extemporaneous preparations (Category I;
community pharmacy or small hospital pharmacy) be For premises designed for non-sterile preparations over-
prepared in a classified premise? The principal objec- pressure is preferable to prevent any penetration of uncon-
tive is that during preparation of non-sterile products no trolled air. For premises designed for sterile or aseptic
contamination from whatever source can occur. To that preparations this is required by GMP.
end adequate procedures should be organised such as a Generally working with hazardous substances – as almost

PRODUCTION
warranted adequate maintenance (cleaning, prevention all active substances are – requires containment. In the
of impairment) and also warranted procedures should specific case of radiopharmaceuticals, Nuclear Energy legis-
apply to prevent disturbances such as any opening of lation requires the application of negative pressure (see Sect.
doors or windows during preparation activities. Under 15.6.3). In the situation of aseptic handling, which requires
such conditions, a specific classification of premises has positive pressure, with radiopharmaceuticals, this results
limited meaning and usually can be left out. After all essentially in contradictory pressure demands. A solution
Class D only specifies a maximum number of particles may be achieved by putting the whole complex of prepara-
at rest which is usually easy achievable except when a tion rooms with air locks at negative pressure relative to its
current badly functioning ventilation system is in action environment. The system of walls, floors and ceilings should
or during specific (weather) conditions, incurring a high be completely airtight in that case. Pipe entries, electrical
concentration of fine particles or pollen. sockets as well as porous stone in the wall parts above the
Also if products are sterilised in their primary pack- ceiling are frequent sources of (substantial) leakage of
age a low microbial starting contamination is essential. contaminated air. Thus all chinks and gaps have to be filled
Therefore products to be sterilised must be filled under and porous stone has to be coated.
class C conditions but the preparation of the bulk By now putting the air locks at some additional negative
solution may take place under class D conditions. pressure a relative overpressure in the preparation premises
Aseptic handling and preparation must be executed is created relative to the admission air locks. The deeper
under class A conditions, usually a LAF (Laminar Air negative pressure in the air lock will however lead to a
Flow) cabinet, a LDF (Laminar Down Flow) cabinet, a vigorous influx of contaminated air as soon as the outer
safety cabinet or an isolator see Sect. 28.3. The back- door is opened, contaminating the lock and compromising
ground room for stock preparations in a LAF, or LDF its function. To prevent this an additional ’front air lock’
should be considered. The front air lock should have a slight
(continued)
592 W. Boeke and P.P.H. Le Brun

negative pressure relative to the environment and will be Weighing of solid substances will release dust. A dust
supplied with clean HEPA filtered air. Alternatively, a clean extract cabinet, equipped with a High Efficiency Particulate
air lock or corridor giving access to other (positive pressure) Air (HEPA) or Ultra Low Particulate Air (ULPA) filter (see
premises can serve as a front air lock to a negative pressure Table 27.4) in the rear wall or in the exhaust, or both, will
premise. See Fig. 27.1. limit the exposure of operators to active substances. Addi-
tional options are the wearing of respirators (see Sect.
26.4.1) and a closed weighing vessel.
In many respects the hazards of many antineoplastics
The air turbulence from a dust extract cabinet may disturb
and radiopharmaceuticals for staff are similar. Also the
the functioning of electronic balances. A dedicated construc-
required skills for aseptic handling are similar. This
tion in each of the preparation premises to manage this is
may lead to the consideration of designing a standard
layout for all premises for handling with extremely
hazardous substances. However, for antineoplastics Table 27.4 Survey of HEPA and ULPA filters
no formal requirement for pressure applies (see Sect. Filter class according
26.8). Therefore, the viewpoint that overpressure to EN 1822:2009 Efficiency % Penetration %
warrants a better microbiological air quality usually E10 85 15
will prevail. In addition the validity of negative pres- E11 95 5
sure premises may be impaired as a result of almost E12 99.5 0.5
unavoidable air leakages. H13 99.95 0.05
The objective can also be achieved with the use of H14 99.995 0.005
negative pressure cabinets sited in positive pressure U15 99.9995 0.0005
rooms. U16 99.99995 0.00005
U17 99.999995 0.000005

Fig. 27.1 Model plan for


pressure hierarchy around
negative pressure premises.
Adapted from Recepteerkunde
2009, #KNMP

clean air corridor


+15 Pa

sliding
door LDF
underpressure
cabinet
gowning lock -30 cleanroom -15 Pa

Materials
lock

surrounding area; 0 Pa
27 Premises 593

expensive and therefore cannot always be achieved. If for


this reason a separate weighing chamber is designed all intercom apparatus. A ‘voice actuated system’ - the
measured portions should be transported in well-closed and voice of the speaker actuates the communication line -
identified vessels. might be a better solution. Background noise
(e.g. from LAF cabinets) however may impart the
correct functioning of such a system. A wireless head-
27.4.3 Interlock Systems for Air Locks set or a mobile telephone that stays within the premise
and is cleaned / disinfected daily may be an
For the maintenance of an air pressure regime and an air alternative.
quality class of a preparation premise an air lock is required.
It controls access from any lower qualified premise. Person-
nel locks should be discriminated from materials locks. In
personnel locks the required gowning regime has to be
determined in advance. In most cases this results in the 27.4.5 Routing and Gowning
requirement of sex-separated gowning locks.
For materials locks the prevailing transport direction and The FRS design document should consider the usual tracks
the usual volume of materials is important. If possible the of personnel. Routing of personnel and thus required
transport direction should be assured for instance by means gowning rooms are principally independent of the routing
of a catch that transmits a standardised vehicle (e.g. a crate) of materials. Therefore, materials locks or transmission
in only one direction. cabinets are indispensable in a good design. A correct
All air locks must be equipped with a so-called interlock gowning procedure for personnel can hardly be maintained
system. This system ensures that both doors of the air lock when employees have to use the changing lock for material
will never be opened at the same time. transport.
For a gowning lock the following requirements can be put
Different interlock principles exist: forward:
• Both doors are permanently closed by magnets, • A clear division between the ’dirty’ and the ’clean’ part,
necessitating a separate hand operated switch to preferably by means of a step-over bench
open one of them. • A correct location of a washbasin and a dispenser for
• Both doors are permanently unlocked, in which hand disinfectant
• Drains (from washbasins) should not be sited on the

PRODUCTION
case the opposite door is locked by opening the
other door. ’clean’ side of the lock
Considerations for the choice are: the hand operated • A cabinet for clean, unused clothing, and a bin for used
switch is a potential source of cross contamination, clothing is provided
magnets consume electricity and emergency escape • A locker to stow away personal belongings
routes depend on easy access. Toilets should not be accessible directly from a preparation
premise from the clean part of a gowning lock [2].
For the design of the routing and communication it might
be useful to have well in advance the future staff ‘virtually’
preparing the products, based on concept drawings and let
27.4.4 Communication and Interior Design them document all of their detailed activities. Together they
should properly review all process steps in detail to find out
Employees who are working in separate rooms within the which provisions have to be taken.
premises should be able to communicate with each other. If
no well-designed communication resources were in place the
personnel would be forced to communicate to each other
27.5 Built-in Installations
through windows, locks, opened doors, etc. Routing of per-
sonnel and goods will then be seriously jeopardised.
Built-in installations that will be dealt with in this chapter
are:
Mobile telephones in preparation premises are notori- • Air conditioning installations
ous sources of cross contamination and thereby not • Installations for storage and distribution of pharmaceuti-
appreciated. The same goes for a hand operated cal water
• Provisions for pressurised air, vacuum and gasses
(continued)
594 W. Boeke and P.P.H. Le Brun

• Electrical installations (power supply, emergency power its own separate air inlet and outlet. In practise overflow
supply, signalling and ICT provisions. grids are used frequently to transport air from one room with
In a community pharmacy (category I preparations; see relative high air pressure to an adjacent room or air lock with
Table 27.1) usually limited provisions will be sufficient, a lower air pressure. However, in that case no independent
e.g. if water of suitable pharmaceutical quality is purchased control of the air pressure or the ventilation factor is possi-
in bottles. See also subsection 27.2.5. ble. So during the design it is necessary to consider any
possible contamination of overflow air from an adjacent
room and the limitations to control it.
27.5.1 Installations for Heating, Ventilation In principle a HVAC installation consists of three
and Air Conditioning (HVAC) components, i.e. the preliminary treatment installation
(make-up casing), the recirculation- and control installation
A HVAC installation is quite space consuming as air ducts (recirculation casing) and the distribution network with fine
usually must be voluminous to warrant the distribution of the tuning per room. See the example in Fig. 27.2.
required air volumes within acceptable noise nuisance
limits. In existing constructional premises the layout of the 27.5.1.1 Preliminary Treatment Installation
air ducts often is not possible without any compromise. The make-up casing draws in fresh air through a bird grid
Ideally, but expensive, each room is to be equipped with and a rough dust filter. Subsequently the air is, according

11

P
6 7 9 10

2
3 4 5
1 8
12
P
13

19 17 16 15

14
20 20 20 18
21 21 21

22 22 22

Legenda Figure 27.2


1. Bird grid (air inlet) 12. Recirculation ventilator
2. Coarse dust filter 13. Restriction with pressure difference measurement (Dp)
3. Inlet ventilator 14. Regulating valve
4. Restriction with pressure difference measurement (Dp) 15. Steam injector (moistening)
5. Regulating valve 16. Heat exchanger for heating
6. Steam injector (moistening) 17. Heat exchanger for cooling and drying
7. Heat exchanger for cooling and drying 18. Drain for condensate
8. Drain for condensate 19. Dust filter
9. Heat exchanger for heating 20. Heat exchanger for temperature adjustment in the premise
10. Dust filter 21. HEPA filter and inlet grid
11. Pretreatment installation 22. Premise

Fig. 27.2 Schematic representation of a HVAC installation for clean rooms


27 Premises 595

to weather conditions, heated, cooled, moistened or dried.


In the (almost) airtight classified clean rooms, with or laminar airflow, having a velocity of about 0,4 m/s.
recycled air, atmospheric humidity can easily increase Higher velocities soon give raise to turbulence of the
above limits by water vapour or exhaled human air. This air; lower velocities displace any particles too slowly.
will not level with environmental air conditions as quickly The airflow rate (volume per unit of time; D) can be
as usual in normal, non-airtight buildings. Drying of derived from this air velocity s and the area A of the air
(inlet or recirculated) air is achieved by condensing inlet grid [5]: D ¼ s  A.
over a cold heat exchanger placed in the air stream. It has to be decided whether the total airflow rate to
Provisions for drying and moistening are critical installa- be distributed over the premises is controlled by a
tion parts because moist air can easily foster growth of so-called fixed volume controller or by a variable
accumulating moulds. A well-designed control plan volume controller. A fixed volume controller main-
should prevent this. tains a constant pressure fall over a fixed constriction
in the main air transportation channel. The controller
thus serves to maintain a steady air volume per unit of
27.5.1.2 Recirculation- and Control Installation
time independent of variations in input air pressure
To save energy, as well as to control air quality a substantial
(wind!), pressure fall over filters and leakage through
portion (usually 80 %) of air returning from the premises is
chinks and gaps. A variable volume controller delivers
reused by means of a recirculation ducting. The remaining
the air at a slightly variable flow rate as this controller
20 %, leaving the premises by leakage and by direct exhaust
directs the airflow at the basis of a specific air pressure
to the outside of the building has to be replenished by the
in one or more reference rooms.
make-up ducting. The recirculation ducting controls air
The consequence of a fixed volume controller is
quality by:
that small variations in the amount of air leaking
• Filtering the supply air through a central HEPA filter
through chinks and seams soon give raise to substan-
• Adjusting temperature and humidity
tial differences in the air pressure hierarchy. In this
• Adjusting airflow rates (volume of air per unit of time) to
case pressure steps between different rooms need a
the distinct rooms
level of 15 Pa to cope with any unavoidable variations
The air drying over cold heat exchangers makes independent
in leakage.
control of humidity and temperature difficult. Apart from
With a variable volume controller there is a direct
that the circulation of air through filters generates frictional
feedback from the air pressure in each separate room.
heat. The prediction of the amount of heat and moisture
Small variations in air leakages will result in adjusting

PRODUCTION
generated from the production process therefore is both
the air control valve in such a way that the air pressure
complex and important design information.
differences are maintained. Usually a smaller pressure
The HEPA filter makes the distributed air (almost) free
step between rooms, e.g. 10 Pa, will be sufficient to
from particles (see Table 27.4). Preferably the pressure fall
maintain the pressure difference and airflow. The ISO
over the filter is continuously monitored to signal leakages
standard 14644-4 mentions pressure steps of 5 – 20 Pa.
(pressure fall is too low) or blockage by pollution (pressure
However it should be borne in mind that 1 Pa
fall is too high and has usually gradually increased).
(1/100.000 bar) is a very small pressure difference,
The volume of each room and the required ventilation
which is hard to control. In the design therefore a
factor determine the airflow rate that has to be achieved in
certain margin should be observed. GMP specifies a
the room. The ventilation factor or replacement factor is the
guidance value of 10–15 Pa between rooms.
number of times that the volume of a room is completely
Although at first glance a variable volume control-
replaced with fresh air. In the ISO standard 14644-4 [4]
ler would be preferred it has a drawback that the
advisory ventilation factors are given in relation to the air
recovery time of a clean room after the introduction
quality class in a classified premise. Occupational safety and
of contaminating particles at validation will not easily
health legislation will also add requirements to the ventila-
show reproducible results.
tion factor.
An additional problem may be raised by the con-
troller. The opening of a door for instance will create a
Air Velocity, Ventilation Factor and Airflow Rate zero pressure difference. If the controller reacts too
Control fast overcompensation of the feedback loop takes
Starting from ISO class 5 no ventilation factor is given place resulting in fierce auto-reinforcing fluctuations
as this class can only be achieved by a unidirectional of air pressure [5].

(continued) (continued)
596 W. Boeke and P.P.H. Le Brun

Exhaust
Apart from the fixed volume controller and the
variable volume controller also hybrid controllers are
available: a variable volume controller with a limited
range of variation or a fixed volume controller with a
variable controlled exhaust volume. Which type suits a
specific clean room depends on the level of control of
the flushing pattern of the air inside the room, the air Ceiling

pressure differences and the recovery time.


One-way
valve

27.5.1.3 Distribution Net and Fine Tuning


For the design of preparation premises an air balance per
room should be drafted regarding: Exhaust
• The free volume of the room (room volume minus the ventilator
volume of fixtures and fittings)
• The required overpressure relative to linked premises LDF safety workbench
• The required ventilation factor
• Any volume of direct exhaust (e.g. through safety
cabinets)
• The heat burden (amount of heat generated by apparatus Floor

and humans)
Additionally the required air quality class (GMP, see Fig. 27.3 Draught diverter
Table 27.2 or ISO, see Table 27.3) must be documented
and it should be documented that the pattern of air flushing
through the room is effective at all functionally relevant the designed air balance within the room. The use of a
spots. The actual air sweep will have to be validated after draught diverter facilitates the possibility to switch off the
construction and must meet the specifications. cabinet itself as the extraction ventilator will then bypass
The ventilation factor and the room pressure determine it. The functioning of the extraction ventilator should be
the volume of air that has to be let in and thus the dimensions interlinked with the HVAC installation in such a way that
of the air duct, the number of inlet grids and the position of if the latter fails or is switched off, the capacity of the
the metering valve of the involved supply channel or the area extracting ventilator should be adjusted, or, in case of fire
of the involved overflow grid. The heat burden and the alarm, switched off. In addition any direct or indirect failure
admitted airflow rate furthermore determine the maximum of the extracting ventilator must lead to an alarm condition
inlet air temperature or the required capacity of any after- as this impairs directly staff safety.
heating radiator.
The air quality class determines the type of HEPA filter
(see Table 27.4) mounted in the inlet grid and the thereby Principle Draught Diverter
raised air friction. All HEPA filters should be entered into a When a so called draught diverter is implemented the
maintenance plan; at least once a year a leakage test and a exhaust channel is placed over the outlet of the equip-
filter integrity test should be performed [5]. ment like an inverted funnel. At switched-off status,
In premises equipped with direct external exhaust it has to air will be sucked out from the room, bypassing the
be determined in advance if the connection to the exhaust equipment. When switched-on the air leaves the room
duct will be fixed or achieved by means of a so called mainly through the equipment. Accounting for the
draught diverter (Fig 27.3). volume of air that passes through the equipment is
Examples of equipment with an external exhaust are necessary in the calculation of the air balance. For
e.g. fume cupboards and flue gas exhausts, fitted to an the air pressure or ventilation factor in the room it
ampoule filling machine or to an atom absorption spectro- doesn’t matter whether the equipment is switched on
photometer. Also a safety cabinet or a non-recirculating dust or off.
suction cabinet (e.g. Wibojekt®) and negative pressure In any case it should be warranted, whether the
isolators have external exhausts. When the equipment has a equipment is fitted with a draught diverter or with a
fixed connection the exhaust ventilator must be switched on
continuously and thus the equipment has a direct impact on (continued)
27 Premises 597

knowledge of the specifications of pharmaceutical quality


fixed outlet connection, that never, e.g. in the case of water. The most important characteristics and the
breakdown of the external exhaust ventilator, outside categorisation of pharmaceutical water, according to the
air can enter the preparation premise. The opposite European Pharmacopoeia, is discussed in Sect. 23.3.1.
should be prevented as well: if a safety cabinet shuts The leading principle in storage and distribution of phar-
down the exhaust should close at the same time, maceutical water in bulk is continuous circulation in a loop
because otherwise environmental air could exchange that includes at least the following:
with the air from within the premises, thus • Apparatus for the measurement of temperature, conduc-
contaminating the HEPA filter. A well-designed tivity and TOC (Total Organic Carbon; i.e. the total
draught inverter with a one-way valve provides all carbon load of organic, carbon containing substances)
those functions. • A storage vessel
• Filter(s) in the production part of the installation and for
pressure levelling out with air from the outside of the
system
27.5.2 Installations for Storage and Distribution
• Apparatus for heating
of Pharmaceutical Water
• Apparatus for cooling
• Taps
In this subsection only built-in installations required for
• Apparatus for disinfection (only for cold water systems).
storage and distribution of pharmaceutical water are
See Fig 27.4
discussed. Apparatus for the production of pharmaceutical
Distinct requirements that apply for different qualities of
water are discussed in Sect. 28.4.
pharmaceutical water will be discussed below.
Water of pharmaceutical quality is used as a raw material,
excipient, solvent, and as cleansing agent. In addition the
pharmaceutical production facility needs water for (thermal)
disinfection or sterilisation and for the preparation of phar- 27.5.2.1 Purified Water in Bulk
maceutical quality reagents [6]. The most commonly used systems for the production of
Engineering of installations for the storage and distribu- purified water deliver water with temperatures around
tion of pharmaceutical water can only be understood with room temperature. Therefore adequate measures have to be

PRODUCTION
tank vent with
air filter UV-lamp (only cold
water systems)

temperature conductivity temperature

conductivity

taps

spray ball

Ozon generator (only


apparatus for water purification level measurement cold water systems) restriction

cold
water
tap

tap
cooler

pre-filter
storage vessel
Softener or RO
drinking water supply apparatus or EDI distiller flowmeter
via non-return valve apparatus or any
and break tank combination of those drain pump

Fig. 27.4 Schematic diagram of water storage and distribution systems. Source Recepteerkunde 2009, #KNMP
598 W. Boeke and P.P.H. Le Brun

taken to manage and control total viable aerobic counts 27.5.2.3 Design Criteria for the Quality of Water
during preparation and storage (see Sect. 23.3.1). For the chemical specifications of pharmaceutical water see
The design capacity should be balanced with the Sect. 23.3.1. A sufficient low conductivity, specified in the
predicted need per instance, e.g. for the most water consum- Ph. Eur., warrants that any metals, ions and inorganic
ing activity and the predicted need over time. Involved are contaminants will be practically absent. During the produc-
considerations of production time per batch, investment tion, storage and distribution Water for Injections in bulk is
costs and the time to re-fill the storage vessel. It should be tested continuously at conductivity, temperature and at TOC
taken into account that drawing off or flushing out the water content. TOC can be measured either in-line, involving a
will curtail the ongoing growth of micro-organisms. metering sensor that is permanently mounted into the loop,
During transport through the loop the water passes sev- or off-line, implying periodical measurement in tapped
eral valves in which biofilm formation may occur (see Sect. water samples [7]. Water samples should be tested off-line
19.3.5). This biofilm can easily extend beyond the valve as periodically on nitrates, aluminium (especially in water
the system for purified water usually is not heated. Therefore intended for dialysis applications), heavy metals and bacte-
the most critical place in the loop is the point beyond valves, rial endotoxins. Purified water in bulk should be monitored
i.e. where the water runs back into the storage vessel. That is at the same parameters. The (expensive) TOC assay might
the right spot for placing critical measurement apparatus in be partly replaced by periodical testing on oxidisable
the loop, such as for temperature and conductivity. substances. Bacterial endotoxins in purified water should
be monitored, especially when the water is used in
27.5.2.2 Water for Injections in Bulk haemodialysis. In purified water additional monitoring
The Ph. Eur. specifies that ’water for injections in bulk is might be indicated, e.g. of ozone (during and after disinfec-
obtained from water that complies with the regulations for tion), the hardness of the feeding water and the luminosity of
water intended for human consumption or from purified the UV source (decaying ozone).
water by distillation in an apparatus of which the parts in
contact with the water are of neutral glass, quartz or a
Suppliers of equipment usually use American termi-
suitable metal and which is fitted with an effective device
nology in their documentations, including the term
to prevent the entrainment of droplets.’ So the quality of this
“sanitisation” referring to disinfection methods that
water is essentially defined by the very specific way it is
are known to be effective to sterilisation processes,
produced. The reason for this is that there is no reference
however in which (formally defined) sterility as a final
water quality to compare.
result will not be proven.
During production and storage adequate measures should
be taken to monitor and control the total viable count (see
Sect. 19.6.3). This can be measured in freshly tapped water
for injections in bulk (maximum 10 CFU/100 ml). Ph. Eur.
27.5.2.4 Measuring Conductivity
actually gives this value as an action limit, but to control
Measurement of conductivity during production, storage and
microbial contamination it is better used as a maximum
distribution of (highly) purified water and water for
value. During production by means of distillation, water
injections is indispensable. One conductivity sensor usually
for injections reaches a temperature between 94 and 99  C.
will be mounted into the pipe that carries the hot, freshly
By maintaining high temperatures in the storage vessel and
distilled water from the distiller into the storage vessel.
the loop any growth of micro-organisms is prevented. In this
Usually this sensor is combined with a temperature sensor.
way the content of endotoxins (see Sects. 19.3.4 and 32.8)
Additionally a conductivity and temperature sensor must be
can be kept low (standard: less than 0,25 IU/ml), as well as
mounted into the return flow of the loop. This is necessary to
the total viable count.
prove that the water that runs back into the vessel still has
The water for injections limit for conductivity is lower
adequate quality.
than that for purified water. At 80  C water for injections
may have a conductivity of maximal 2,7 microSiemens/cm.
Usually only the storage vessel and not the loop is heated. Ph. Eur. extensively describes the procedure for the
So during the passage of the loop the water will cool down measurement of conductivity, the calibration of the
gradually. Additionally any inadvertent leakage of a valve conductivity sensor and the calibration of the system.
(e.g. the one that provides a washing machine with water for The measurement is complicated as there is no refer-
injections) may impair the quality of the water in the system. ence for low-level conductivity measurements. When
These facts underline the choice of the most critical spot for the off-line conductivity turns out to be too high a
all measurements being the place where the water runs back
into the storage vessel. (continued)
27 Premises 599

transport pipes made of stainless steel or synthetic materials,


second measurement is prescribed after previously the inner side of storage vessels, taps and membranes in
stirring atmospheric carbon dioxide into the water. valves.
When this second measurement still reads too high a
third step is prescribed adding a potassium chloride
27.5.2.7 Systems for the Storage
solution and measuring pH. Only then a conclusion
of Pharmaceutical Water
can be drawn about the quality of the conductivity
At the design of the pharmaceutical water installation the
measurement.
capacity of the storage vessel should be determined based on
the maximum daily consumption, the average consumption
and the maximum peak consumption per product batch. The
water consumption by sterilisers and washing / disinfection
27.5.2.5 Total Organic Carbon (TOC)
machines should also be taken into account.
TOC is an indicator for any existent (decayed) organic
The higher the peak water consumption, the larger the
material in the water, often originating from living or dead
storage vessel. If the demand for water has a more steady
micro-organisms. A low TOC (less than 0.5 mg/ml) may be
character then the vessel can be smaller. In case of a large
interpreted as a useful indicator that the water has a proper
vessel the available floor area and its load capacity must be
microbiological quality [7, 8]. This assay can be performed
accounted for. Continuous production implies that one or
easily and immediately before use.
more tanks are being filled and drained continuously. Qual-
ity control should take place in a continuous way, completed
27.5.2.6 Microbiological Quality of Water with intermittent additional tests. After maintenance and
Operations, storage and transport methods all can influence also periodically the system should be disinfected. The fre-
the growth of micro-organisms. quency of the disinfection depends on the results of the
In practice microbiological quality of water is monitored process validation [9, 10]. Further specifications of the sys-
by action and alert levels. Thus the user will be early notified tem follow the required water quality. The required storage
about any deviation of critical parameters. For instance temperature also plays a role:
an alert level might be put at a factor 10 below an action • Cold storage implies storage conditions between 4  C and
level. To determine these levels a good set of total viable 10  C at which micro-organisms grow very slowly. Cold
aerobic counts, endotoxin assay results and TOC assay storage renders the system effective and reliable. Disin-
results should be available. For the collection of these fection occurs only occasionally and can be performed

PRODUCTION
results, particularly in the start-up phase very frequent with hot water. Drawbacks are the expense of a cooling
measurements must be executed. installation and its considerable energy consumption.
The development of a biofilm (see Sect. 19.3.5) in the Stainless steel, PVDF, polypropylene and polyethylene
water production system has to be prevented. The rougher cross-linked (PEX) all are suitable as a material for the
the surface the easier a biofilm will develop. Nevertheless storage of purified water at low temperatures. The design
even onto polished metal, synthetic materials, glass and in of the vessel should be aimed at the lowest possible total
streaming water it may develop, therefore the micro- viable aerobic count. This implies that all surfaces, pipe
biological quality of the water has to be controlled fre- holes, valves, etc. should be accessible and made of very
quently. In demineralised water the growth proceeds faster smooth material.
than in distilled water as a consequence of more available • Storage and distribution at ambient temperatures (15  C -
nutrients. As soon as a biofilm causes contamination the 30  C) is reasonably effective and reliable and the invest-
term biofouling is used. The best way to eliminate a once ment and operation is comparatively cheap. However the
formed biofilm is mechanical cleaning, which is becoming risk of building up a biofilm is substantial. Therefore,
more and more common in industry. However, when the non-cooled storage systems should be disinfected fre-
surface is not accessible for mechanical cleaning, other quently by flushing with hot water or by adding ozone.
cleaning methods must be applied, such as flushing with Materials for loop and storage vessel are similar as for
hot alkaline followed by hot acetic acid or flushing with cold storage [9, 10] however the method of disinfecting
concentrated sodium chloride solution followed by hot acid can limit the choice. More aggressive methods such as
solution or hot alkaline. The microbiological safety of the treatment with steam are preferable, but require expen-
installation thus not only depends on the application of heat sive materials such as stainless steel.
but on the (im-)possibilities to dispose of any formed biofilm • Hot storage and distribution means storage and distribu-
as well. Risky surfaces are demineralisation resin, tubes, tion at a temperature continuously kept over 70  C [1]. In
600 W. Boeke and P.P.H. Le Brun

practice an ample safety margin is implemented and


usually the actual storage and distribution temperature is Only during tapping the heat exchanger is temporarily
well above 85  C. Hot storage is the most effective and flushed with cold water, locally chilling the pharma-
reliable way to prevent growth of micro-organisms. With ceutical water. Only a very limited amount of the
the aid of well mounted isolation material in the heating chilled pharmaceutical water will return to the loop
mantle a storage vessel can be kept at high temperature at by means of mounting a so-called restriction disc just
low expense. The loop piping should also, preferably, be before the junction. So chilled product water will
insulated. Taps should be placed at short distances from hardly mix with the main stream in the loop. When
the loop. Before use the tap has to be flushed with hot no chilled water is tapped sufficient water will pass the
water. Hot storage involves relative high investment costs heat exchanger, the tap valve and the restriction disc to
and moderate running costs. It introduces a specific risk maintain this part of the loop at the required
of rouging. Hot storage does not diminish the content of temperature.
endotoxins. The distribution loop can be combined with
taps equipped with sanitary coolers to deliver the phar-
maceutical water at ambient temperature.
The water level in the storage vessel has to be controlled
continuously, preferably with the aid of a building control
Rouging
system (see Sect. 27.5.5). Thus a low level signals to restart
At sustained exposure to very pure hot water or steam
the production, however a very low level should produce an
a thin red, reddish brown, orange, light blue or black
alarm signal shutting down the complete installation to pre-
deposit (tarnish) might built up. This is seen particu-
vent, among other things, the circulation pump running dry.
larly at less polished spots, e.g. burrs, scratches, sharp
A high level will stop the production and an extra high level
edges, material transition areas or bad welds and is
should give an alarm signal to alert the risk of overflow
called rouging. In fact rouging is an oxidation process.
through the vent filter.
When metal ions in micro-caves dissolve into the
The storage vessel and the loop for water for injections is
water potential differences might occur at a micro-
preferably made of stainless steel AISI 316 L and polished to
scopic scale leading to hydrolysis and oxidation. The
a roughness grade of 0.4-0.6 μm mean pore diameter [9,
coloured material consists of iron oxide, iron carbon-
10]. The water should return from the loop into the vessel
ate or iron hydroxide or any combination of these.
through a (rotating) spray ball. By this means the empty
Rouging itself doesn’t yield any immediate hazard.
upper part of the vessel will be kept hot and germ free. The
However once rouging has been built up it might
vessel or at least the lowest point in the loop should be
expand and eventually lead to development of rust in
equipped with a sanitary bottom valve ensuring that after
which case the smoothness of the texture is affected
complete draining (e.g. for maintenance purpose) no tainting
and the risk of biofilm formation increases. Therefore,
water will stay behind in the system [10].
highly polished stainless steel constitutes a barrier
both against rouging and biofilm formation. Removal
of rouging is a very expensive process involving Tank Vent
experts [10, 11]. A level control system can only be used if the system
has been designed according to GMP. Tapping of
water from the storage vessel will lower the level in
the tank. The sucked-in air entering the vessel has to
be filtered through a 0.2 μm hydrophobic membrane
filter that can be tested and which should be mounted
Tap for Cooled Water in a stainless steel casing onto the vessel. A pressure
A tap cooler mounted into a hot distribution loop safety provision is mounted to safeguard against any
requires a special design. The loop and the storage possible overpressure in the vessel. The filter has to be
vessel must be kept at high temperature while no replaced at least once yearly as a preventive measure.
long branches filled with stationary (colder) water During the hot storage of pharmaceutical water the
can be accepted. Therefore the loop splits near the filter also has to be kept at a high temperature to
cold tap into two parallel pipes both continuously prevent the occurrence of condensate. This condensate
being flushed with the hot pharmaceutical water. In would provide an ideal substrate for micro-organisms
one of the two branches a heat exchanger is mounted. which might grow through the filter.

(continued)
27 Premises 601

27.5.2.8 Maintenance and Disinfecting Water usually consists of continuously monitoring the intensity of
Storage and Distribution Systems the UV light. An alarm signal should indicate when the lamp
Biofilm will emerge especially fast on ion exchange resins, has to be replaced [9, 10].
Reversed Osmosis (RO) -membranes and piping made of
stainless steel or plastics. Therefore, systems for pharmaceu- 27.5.2.11 UV-light for Germ Reduction
tical water should not contain stationary water and should be UV-light with a wavelength of 200–300 nm not only
disinfected at start-up and after each maintenance process. degrades ozone but also reduces the total viable aerobic
Even systems for the preliminary treatment of feed water count in pharmaceutical water, especially in systems with
have to be constructed as a recirculating system [10]. cold storage and distribution. UV-light disrupts the DNA of
Cold water systems usually cannot be steamed. Instead micro-organisms and thus obstructs their growth. Irradiation
chemical disinfection or disinfection using ozone is custom- with UV-light is not intended to replace any disinfection
ary. An important benefit of ozone treatment compared to method. The effectiveness of the irradiation process depends
other chemical methods is that it can be executed on water quality, light intensity, flow rate of the water,
automatically. duration of the irradiation and the identity of the micro-
Frequent hot water disinfection is a good alternative as a organisms in the water and thus is difficult to validate
preventive measure, provided that all materials are sufficient [9, 11].
heat-resistant. It is carried out at a temperature of 90–95  C
during at least 2 h of exposure. This process must be 27.5.2.12 Clean Steam
validated [10]. The problems to remove a once formed Only the USP includes a monograph for pure steam [12],
biofilm is discussed above in Sect. 27.5.2.6. also called clean steam. Clean steam is obtained from
RO membranes may not be exposed to ozone. The pro- purified water heated over 100  C and brought into the
ducer of the membrane should indicate how to treat and vaporised phase in such a way that no drops of feeding
disinfect it in a correct way. water are carried over. In any situation where steam or
steam condensate might stay in immediate contact with
27.5.2.9 Chemical Disinfection critical, product affecting surfaces, clean steam must be
If the equipment is provided with adequate connection utilised. An example is the interior surface of a filling appa-
systems a chemical disinfection is possible. Commonly a ratus. Technical steam is steam generated at some central
solution of hydrogen peroxide and per-acetic acid is diluted location in the building. The quality is defined with pressure
to 8-10 % and then flushed through the equipment. The and temperature. Clean steam may be utilised during prepa-
system must be thoroughly rinsed afterwards.. The method ration, in steam sterilisation and during controlled steaming

PRODUCTION
is quite effective, however it involves the additional efforts of installation as a sterilisation method after cleaning [13].
of purchasing, storage and handling of the disinfecting Quality control of clean steam is carried out on its con-
agent. densate. Additional requirements are in force when the
steam is utilised for sterilisation (see Sect. 30.5.1).
27.5.2.10 Ozonisation
Ozonisation is a specific means of chemical disinfection as 27.5.2.13 Transport Systems for Pharmaceutical
the active agent (ozone) is generated in the equipment itself. Water
Ozone is used for the periodical disinfection of pharmaceu- A system for transport or distribution of pharmaceutical
tical water installations when disinfection by steaming or water should meet at least four requirements:
with hot water is not possible. Ozone is a strong oxidising • It should deliver water that meets all quality requirements
agent and kills micro-organisms in water. To obtain suffi- (see Sect. 23.3.1).
cient disinfecting power ozone should be present in the • The water should always flow at the required flow rate,
water for a sufficient time and in an adequate concentration, especially at the instance of drawing off.
according to the guidance of the producer of the ozonisation • The water should be delivered at the temperature required
apparatus. Concentrations with a maximum of 10-50 ppm for the process at hand.
(sometimes even less) are most common. The ozone genera- • The system should function at acceptable investment and
tor that is mounted in the loop produces the ozone gas. running costs.
However after ozonisation the utilised pharmaceutical
water must be freed of ozone again. Therefore, UV lamps 27.5.2.14 Piping
are included in the loop at a spot that is transparent to UV By means of a sanitary pump and a flow rate meter showing
light. UV light of 254 nm degrades ozone turning it into the flow rate, the water circulates in a loop through a sanitary
oxygen. Thus quality control of the lamp is necessary; it (hygienic, well-disinfectable) piping system. Unused water
602 W. Boeke and P.P.H. Le Brun

runs back into the storage vessel. Micro-organisms, corro-


sion, (hidden) construction flaws and aging can all affect the oxygen-rich water, diluted nitric acid or oxalic acid.
loop system. The loop should not contain any branches in When all residues of acid are flushed away with water
which water is stationary. For this purpose specific calcula- for injections the installation can be steamed and put
tion schemes exist. Generally the length of any branch in the into operation.
loop never should exceed 6D (diameter of the loop pipe) The welds in a stainless steel loop never should
but in practice 3D or even 2D is to be preferred. Also corrode, leak or become a source of rouging or biofilm.
purified water as feeding water for a distiller installation Welding work therefore should be inspected closely
should recirculate when nothing is drawn off. and be thoroughly documented. Specialised instruments
The support and mounting of the piping should be are being used for this purpose. The welder must be
constructed in such a way that no sagging occurs, a risk qualified. All handmade welds should be fully con-
that is more prominent with synthetic materials at higher trolled; in orbital welded pipework usually 20–30 %
temperatures than with stainless steel. Preferably the piping of the welds are tested.
is mounted at a slight slope with the bottom valve at its Other, also demountable, fittings between pipes and
lowest point. The usual angle of the slope of horizontal installations are of the type clamp, flange or screw
piping at short distances is advised at 2 % and at 0,5-1 % fitting.
for greater lengths. For transport of water for haemodialysis and
Joints must never be mounted at a residual strain because purified water, plastics may be used for the tubing.
that could cause leakages, which can lead to considerable However for these materials it is also required that
damage. The support system for the piping must not cause connections are meticulously welded, inspected,
any galvanic corrosion. The distribution system must be documented and cleaned. The use of glues (e.g. the
immune to ozone or the heat of steam. It has to resist a glue to join classical grey plastic, PVC, tubes for
specified water pressure and turbulence as well. The interior non-pharmaceutical use) introduces an unacceptable
of the piping should have a surface as smooth as possible to uncertainty because residues of the glue and solvents
prevent corrosion and formation of a biofilm. Stainless steel may contaminate the water. Analysis of this kind of
piping must be polished at the inside for this reason. Piping contaminants preceding the formal acceptance of the
of synthetic materials used for the distribution of pharma- system is not a realistic option [9, 10].
ceutical water are smooth plastics like PVDF, polypropylene For pharmaceutical water guidelines of, among
or PEX. The piping may not release any substances or others, FDA and DIN 11864 apply for these kind of
(metal) ions and should be corrosion resistant [9, 10]. fittings. Anyhow, the number of fittings should be kept
as low as possible.
Welding, Mordanting and Passivation
Stainless steel contains chrome that generates a tarnish
of chrome dioxide, which protects against rust. How-
ever over time some form of corrosion will develop; 27.5.2.15 Pump
totally non-rusting steel does not exist. A circulation pump should have a highly polished finish and
The installer should weld the piping work orbitally. should be well cleanable. It must resist any disinfecting
Orbital welding is the partly automated method of process, preferably steaming. Also the pump must allow
welding highly alloyed steel pipes together using a complete drainage. The latter implies that no water residue
tungsten electrode under inertial gas, also indicated must stay behind when the complete loop is drained during
as TIG-welding (tungsten inert gas). By this method maintenance.
a very smooth weld develops. Subsequently the instal- The pump should be able to generate a flow rate of
lation must be cleaned, mordanted, passivised and 1–2,5 m per second in the loop, still achieving an acceptable
finally be flushed and steamed. Cleaning after welding water pressure. The pressure depends also on the loop resis-
is done by flushing with caustic detergents and water. tance. Usually a restriction disk mounted in the loop serves
Mordanting implies that the corrosion resistant tarnish to prevent a major pressure drop when water is withdrawn by
is removed temporarily using strong acids (chromic opening a tap. The flow rate causes the flow to be turbulent
acid or strong nitric acid). Immediately thereafter the and thus prevents the risk at (almost) stationary water
reactive metal alloy is passivised by oxidising in the e.g. near valves and other small bulges in the loop. After
air. Passivation is also executed by flushing with all, any stationary water would substantially increase the risk
of building up biofilm [9, 10].
(continued)
27 Premises 603

27.5.2.16 Tapping Points Requirements depend on the use and therefore may differ
Membrane valves must be completely drainable and from those to medical gasses. Gasses that are in direct
disinfectable, preferably by steam. The membrane made of contact with the (end-) product should meet the requirements
plastic should be replaced 1–2 x per year. Sometimes globe derived from the product itself.
valves are used to shut off steam pipes, because they are
more wear-resistant.
The requirements for medical gasses may differ from
A sufficient number of sample tapping points should be
those for pharmaceutical gasses. As an example,
available. The tapping of water during any dysfunction
requirements to safeguard continuous availability
(e.g. deviation of temperature, deviation of conductivity or
carry more weight with the clinical process of artificial
low level) of the water installation must be prevented. This
respiration than with a pharmaceutical application.
can be done by automatically blocking all tapping points at
But the chemical purity of e.g. nitrogen used for filling
the basis of any alarm signal originating from the installation
ampoules will be more important in pharmaceutical
[9, 10].
than in medical applications. Purity has to be backed
by traceability of the origin. Certain suppliers there-
27.5.2.17 Responsibility for the Validation
fore provide cylinders with designations such as ‘trace
and Qualification of Water Systems
pharma’.
The validation of this equipment has to account for its built-
in status. Therefore the validation plan already has to be part
of the design and realisation phase of the installation. The requirements for gasses can be:
The person responsible for the water quality to be used in • Technical (capacity, pressure, availability)
pharmaceutical preparations usually is the pharmacist who is • Chemical (content assay, contaminants, moist content)
also responsible for the preparation processes. This person is • Physical (absence of particles and oil)
accountable for all procurement, validations, qualifications, • Microbiological
maintenance, deviations and changes of the installation(s). A low moisture content (dew point) in a gas under pressure is
He should always be fully informed about all those aspects. most important because at expansion moist could lead to
This also applies when the water preparation installation is condensation, which would enable micro-organisms to grow
installed outside of the premises of the pharmacy e.g. in the [9, 13].
premises of the technical services or any laboratory [11].
27.5.3.2 Vacuum

PRODUCTION
A vacuum installation may have impact at the final product,
27.5.3 Provisions for Pressurised Air, Vacuum
e.g. when vacuum is used to prevent air being beaten into a
and Various Gasses
viscous mass or to remove air from it. A choice has to be
made between a central installation and a local one such as a
27.5.3.1 Gasses and Pressurised Air
water jet pump or an electrical vacuum pump. At a centrally
Medical gasses (including medical air) are gasses that as
placed installation a provision has to prevent the pressure
such are used in the treatment of patients. Medical gasses
inside the tubes rising above a predefined value. Otherwise
administered to patients are medicines [13], see also Sect.
contaminated air could enter a negative pressure room if the
23.13.
pump were to break down.
Gasses used in production processes are called pharma-
ceutical gasses. They are applied as:
• Gasses that are immediately immersed into the interme-
diate medicinal product, e.g. nitrogen as a means to dispel 27.5.4 Electrical and ICT Provisions
oxygen from aqueous solutions or pressurised air to carry
over fluids. At the design of preparation premises the availability of
• Gasses that are necessary at the preparation or filling electrical and ICT provisions should be well considered in
process, but are not directly in contact with the product, advance. Sufficient data and electrical sockets should be
e.g. natural gas and oxygen for opening and sealing of provided in walls and at worktops.
ampoules. Keyboards and mouses should easily be cleaned and
• Gasses used for pharmaceutical analyses, such as acety- disinfected and therefore must be chemically resistant. The
lene for atomic absorption spectrophotometry and helium casings of the computers should be installed in such a way
for gas chromatography. that accumulation of dust is diminished, for the protection of
• Gasses (usually pressurised air) for technical purposes the computer as well as the pharmaceutical product. The air
such as pneumatic operation of installations. in classified rooms will hardly carry any dust, but
604 W. Boeke and P.P.H. Le Brun

nevertheless the casing should be opened at least once a year of independent alarms. Also rules have to be implemented
to remove any dust. The casing should also being placed as regarding the procedure for the resetting of any alarm and for
far from the critical places as possible, if possible outside of the documentation of its actual follow-up.
the room. Wireless tablets may circumvent all difficulties
with cables and fans. Cleaning and disinfecting of worktops
is much easier when cables are tucked in cable ducts or 27.6 Detail Specification and Building
under the worktop.
For each apparatus or installation it should be considered The documenting of the functional specification (FRS) of a
whether it has to be provided with emergency power supply preparation facility is followed by the detail specification
or preferential power supply. Therefore, the risks of any (DS) or tendering specifications. A subtle difference between
short or longer lasting power cut should be analysed in DS and tendering specifications is that the latter will be
advance. Especially the consequences of any disturbance drafted for the purpose of contracting-out. However the DS
of air pressures and the breakdown of exhaust installations is primarily aimed at verifiability during the IQ phase. Usu-
must be considered. ally just one document will serve both functions. In this
document choices are made (usually a professional advisor
does the job) for floor and wall covering, ceiling materials,
27.5.5 Building Control Systems etc. The HVAC installation will now be specified in full
detail, communication means are specified and detailed
Apart from the pharmaceutical installations, already men- building and arrangement maps are drafted and updated.
tioned in this chapter, buildings are generally equipped with The choices must comply with the FRS, which in turn
heating and cooling equipment, fire prevention equipment, must comply with the URS. Therefore each choice should be
burglar security systems, personal access control, sun blinds, well documented and justified at this basis.
elevators, sewage pumps, etc. What should be attended to in the assessment of the DS?
So altogether the building incorporates a vast multitude In premises intended for sterile and aseptic preparations
of technical systems, several of them influencing each other. (clean rooms) the most severe requirements apply to the
This might raise a need for an overall monitoring and control walls, doors, floors, ceilings, heating and furniture, see fur-
system. ther subsections. Premises which are only intended for
Usually control and monitoring are integrated in one non-sterile preparations can do with less far-reaching
system providing a central point from which the functioning demands. Nevertheless in practice it might be wise to
of all systems can be monitored, registered and adjusted. apply the requirements for sterile premises also for
Furthermore, failure alarm signals are channelled through non-sterile premises if both are at stake. In the first place in
the building monitoring system. a new building the itemisation of methods and materials
When pharmaceutically critical systems (refrigerators, between premises meant for sterile preparation and for
HVAC systems, purified water systems, etc.) are to be mon- non-sterile preparation usually doesn’t yield much cost
itored by a building monitor system it has to be independent reduction. Additionally many of the starting points for the
from more general systems in the building and its validity requirements for sterile preparations more or less apply to
has to be assessed in advance. Additionally systems for the ’non-sterile’.
registration of measurements must be independent of
systems that operate the installations and all installations
(i.e. their sensors, adjustment tuners and alarm signals) 27.6.1 Inner and Outer Walls
must be fit to be connected to the building control system.
All possible alarm signals have to be listed and Where premises for preparation are adjacent to any outer
documented regarding alert- and action levels, hysteresis wall a specific problem emerges. Constructional walls, also
(to prevent them from switching on and off continuously at outer walls, never will be completely airtight. In case of
a non-stable parameter) and timeliness (providing short- wind pressure always air from outside will influx, bringing
termed deviations without unnecessary alarms or providing pollen (in spring), mould spores (in autumn) and fine partic-
a reaction time before exciting the alarm). A scheme of ulate dust (in winter). This can only be prevented by building
procedures has to be defined to be followed after any alarm a double wall system, i.e. by complete separation of the
is triggered. The follow-up instruction after any alarm preparation premises from all outer walls (so-called box-in-
should include an indication about its urgency, e.g. if imme- box principle) which is usually accomplished by building a
diate action is obligatory when the alarm occurs in the night gallery corridor. If this is no option, then at least a separate
or in the weekend. No alarm signal should be overruled, secondary glazing is necessary in the windows of outer walls
covered up or left invisible in case of concurrent triggering to level out any wind pressure. Such a secondary glazing
27 Premises 605

At places where damage could occur the wall should usually as a metal corner bracket or metal u-moulding,
be made of impact-proof and scratch-proof material, which must be protected against rust. This again
e.g. melamine resin sheet material like Trespa®. At requires early planning of the right layout of any
other places, e.g. above breast height, cheaper gypsum suspended cupboards, worktops, etc.
board walls can be used, provided that they are treated
with a specific water-resistant coating that can also
resist the chemicals used for cleaning and disinfecting.
Seams, e.g. at places where fixed cupboards are
concrete floor
placed against the wall, should be closed with a well-
chosen acid-resistant joint sealant. Any seam should
have a width between 2 and 4 mm to safeguard that the
sealant will stick firmly into the joint. Wall connectors profile
for electricity and ICT provisions must not give entry for
compression
contaminated air or vermin. Therefore the interior sup- ribbon
ply pipes should be made airtight with sealant. In prac- coating
tice usually a hollow wall modular construction is used gypsum
for clean room building (‘Metal Stud’, see Figure 27.5) double board
with all pipework and tubes sealed within the wall. version
All pipework and tubes (electricity, water, gasses,
air ducts, etc.) should be documented by photographs
25 12,5
before the wall is finally closed during construction.
Those pictures can demonstrate later that the finished 45
construction indeed does correspond with the as-built
drawings. As-built drawings are the drawings that 82,5
exactly represent the finally built constructive reality.
At places where the wall should be loaded with objects
to be mounted, the constructor should apply back Fig 27.5 Metal Stud wall. Source: Recepteerkunde 2009,
styles. These are fortifications introduced in the wall, #KNMP

PRODUCTION
(continued)

introduces a wasted space between the inner glazing and the Light switches, as being touched by many persons, can be
outer one, in which at some time vermin will emerge. best placed outside of the room e.g. at the entrance to
Cleaning might be facilitated by having the outer glazing personnel gowning locks. In that way an important source
accessible from the outside. of cross contamination is ruled out.
If carrying in or out large apparatus must be possible, a
demountable, resealable, partition in the wall should be
27.6.1.1 Inner Walls
considered.
A requirement for premises for sterile preparations (clean
rooms) is that walls are free from any ledges and seams to
enable effective cleaning and disinfection. The provision of
ample glazing for supervision and well-being of personnel 27.6.2 Doors
should be considered. The ledge free and seamless mounting
of windows and doors into walls is known as ’flush fitting’. Doors in clean rooms must be flush mounted, smooth, clean-
In order to adequately flush the room with clean air the able, if necessary disinfectable and as far as possible seam-
exhaust should not be positioned near the inlet grids in the less. This especially goes for doors in GMP classified
ceiling. Special inlet grids (diffusers) should generate turbu- premises as indicated in Sect. 27.4.2. Points of special inter-
lent airflow. In air class B exhaust at floor level is mostly est are:
preferred. A hollow wall construction offers the possibility • Air leakage through chinks between doorframe or thresh-
of incorporating air ducts (exhaust channels) within the wall. old and a shut door will render the air pressure within the
These may make, however, other provisions on that particu- room out of control and it may raise an annoying wheezing
lar part of the wall impossible. noise. Therefore, doors should close firmly and not warp.
606 W. Boeke and P.P.H. Le Brun

Fig. 27.6 Dropseal. Source


Recepteerkunde 2009, #KNMP Floor Covering Materials
The choice for floor covering materials depends on the
kind of activities. As an example, in a preparation
room where iodine or organic solvents will be
processed, the floor should be chemically resistant in
the first place. When processing inflammable products
the generation of sparks due to static electricity has to
be prevented. For aseptic handling chemical resistance
of course is much less important. The primary empha-
sis for a floor in a premise for handling radiopharma-
ceuticals or other very hazardous substances, is on
suitability for thorough and effective decontamination
and disinfection.
A synthetic floor covering, e.g. like marmoleum or
a good quality of vinyl, laid in strips or tiles and sealed
• Air leakage by the bottom of the shut door may be with synthetic laces is a quite frequently used material.
prevented by implementing dropseals mounted within As an alternative a floor made of epoxy resin (a
the bottom part of the door (see Fig. 27.6). A pawl at so-called cast floor) can be considered, with its
the hinge side actuates a lever mechanism at shutting the advantages of high load bearing capacity, smooth sur-
door. This mechanism pushes a rubber strip against the face and absence of seams. A drawback is its slipperi-
floor. At the opening of the door a spring mechanism ness, especially if wet there is a risk of skidding.
pulls the strip back up again into its casing. Additionally it is very critical to have the cast floor
• Doors should never shut against the air pressure, as the applied completely free of dust or dirt.
higher air pressure behind the door may raise leakages. If The floor covering material preferably should butt
the preferred turning direction is not feasible, e.g. in case to the walls by means of a hollow skirting. Fitted
of an emergency route from a positive pressure room, the furniture that is not mounted hovering over the floor
door should seal on all sides, including top and bottom, should be placed upon pre-mounted dado’s, after
into a soft rubber groove. In some cases the preferred which the floor covering can be installed with a hollow
turning direction of a door based on function is opposite skirting against the dado.
to the preferred turning direction based on air pressure
hierarchy. A sliding door may solve that problem,
provided that it is equipped with an effective push mech-
anism when shut and is well cleanable.
27.6.4 Ceilings

27.6.3 Floors Ceilings are preferably completely closed, i.e. manufactured


from fixed mounted, smooth and cleanable sheets.
Floors must be easily cleaned and disinfected. Drains should Pipework should be tucked away behind the ceiling,
be avoided, as these are important sources of contamination. because otherwise dust builds up. If possible pipes or
If a drain is unavoidable because the equipment demands it, tubes transporting water should be avoided at the top of
it should be equipped with a sanitary valve, preferably a type any preparation premise because leakage would have disas-
that closes automatically when the connected equipment is trous consequences. This is in regard not only to pipes
shut down. Such a drain requires a well-documented disin- transporting pharmaceutical water but also to the sewer
fection procedure. system, rainwater drains, condensate drains and steam
Floors should be practically seamless because seams can pipes. The possibility of the occurrence of condensate on
easily become filthy. However each type of floor covering cold water pipes during warm weather should also be con-
will come with seams and dilatation joints are necessary to sidered. If the pipes cannot be avoided, any leaking water
allow for any shrinkage or dilatation, also in clean rooms. At should drain off by a gutter. Regular maintenance of the
least any seams and dilatation joints must be avoided near pipework and timely replacement of gaskets will be neces-
the most critical places. sary as well.
27 Premises 607

substances. The flow pattern in a safety cabinet can easily


System Ceilings or Closed Ceilings be disturbed by an incorrectly placed or ill-chosen air inlet
A lowered, so-called system ceiling can be used, how- grid in the ceiling [5].
ever it has several snags: the joining to the walls
usually results in a right angled corner that is difficult
to clean. Additionally the system sheets, lying rather
27.6.6 Furniture
loosely within the frame, can easily snap open, espe-
cially when air pressure jolts occur at the opening or
The upper side of cupboards should join to the ceiling, or
closure of doors. If that occurs unpredictable amounts
alternatively a slant finishing should connect the upper side
of dust and dirt will enter the room. Even special clips
to the ceiling. Personnel should not be able to place objects
to fix the ceiling tiles cannot prevent this completely,
on top of a cupboard. As far as cupboards are made from
as after maintenance work those clips are frequently
wood, plywood or chipboard these parts should be laminated
not replaced. Sealed ceilings are free of those
on all sides, e.g. also at the backside of shelves. Holes to
drawbacks and they force the designer of the building
adjust shelves in height should be filled up. ‘Open’ wood or
to create an alternative entry to the space above the
chipboard may release spores. Workbenches should prefera-
ceiling. This entry will not come from the preparation
bly hover or be attached to the wall. Floors under worktops
room, but by means of an admission hatch e.g. from a
must be well accessible for cleaning. Fixed furniture prefer-
neighbouring gallery corridor or by means of a trap-
ably should be placed upon pre-mounted dado’s.
door from an upper storey. The benefit of this is that
Refrigerators and freezers within the preparation premise
maintenance or repair work, e.g. at pipework or the
are unwanted for several reasons such as that the expansion
replacement of lamps, situated behind the ceiling, can
radiator at their backside cannot be cleaned. If a refrigerator
be executed without entering the premise itself. If
or freezer in the preparation premise is indispensable it
completely sealed ceilings are not feasible in all
should be airtight separated from the room, e.g. by means
rooms entrance to the space above the ceiling from
of a flat shaft of sheets up to the ceiling or a throughput
gowning rooms or connection corridors are preferred;
through the wall.
the ceiling should never be entered from the prepara-
Chairs should not possess seats made of wood or covered
tion room itself.
with textile. The undercarriage should be easily cleanable.

Light fittings do easily attract dust as a consequence of

PRODUCTION
their static electricity. Therefore they should be incorporated 27.7 The Implementation Phase of Building
in the ceiling and be shut off by means of a glazed or or Rebuilding
transparent synthetic sheet. In classified premises no sub-
stantial air leakage must occur past the fitting. During the execution phase of newly built or rebuilt phar-
maceutical premises (including clean rooms) the building
control department should take a few particularities into
27.6.5 Heating account. The ISO 14644-4 standard [4] specifies those
particularities for clean rooms.
The cleaning of heating radiators is very laborious and not • Verification of matters that cannot be demonstrated after
very feasible in practice. Therefore, they are unsuitable for implementation. Design drawings should be continuously
pharmaceutical preparation premises. If they nevertheless updated such as to be finally correct ’as-built’ drawings.
cannot be avoided, sheet radiators mounted at sufficient Pictures of the inner part of hollow walls can support the
distance from the wall to allow effective cleaning, are to verification process. The sealing of any pipe holes or
be preferred. However, in GMP classified premises as meant cutaways must be checked systematically.
in Sect. 27.4.2 even sheet radiators are absolutely undesir- • Special attention should be paid to prevent the fouling of
able. Heating and cooling in that case should be achieved by air channels during their mounting. Air channel
means of the ventilation system (see Sect. 27.5.1). components must be supplied clean and closed on both
In using air for heating, attention should be paid to the ends. Partly mounted air ducts again must be shut at the
type of inlet grid. In a well-designed preparation premise a open end to keep them clean inside. The building area
high ventilation factor will prevail. If not a specific whirl should be swept clean daily.
grid is mounted draught will occur. This is not only annoying • Eating, drinking and smoking in the building area has to
for those working within the premise, it also may lead to be forbidden and this ban should be enforced strictly to
inadvertent displacement of weighed portions of active prevent that any organic material (like bread or tobacco
608 W. Boeke and P.P.H. Le Brun

crumbs) are left in hollow walls, under or behind rooms after disturbance is checked, viable and non-viable
cupboards or in air channels. particles are counted, temperature- and humidity are
As a consequence of its high costs the execution phase of measured, etc.
a building usually is very tight. Especially in the end phase The IQ and OQ are usually executed by the contractor in
this can result in working against the clock. A common cooperation with the customer. When this phase is
completion process assumes the premises to be put into completed, the work is delivered up to the customer and
operation immediately after completion, accepting the doc- accepted. Then the performance qualification (PQ) is
umentation of a few residual points that will be settled later, executed by the customer. In this phase it will be proven
in practice already during operation. For clean rooms this is that the premises will work as they were meant to be work-
not possible. The starting-up procedure involves many steps ing as defined in the URS. Installations will function and
that must be planned well in advance and are described in a classifications of the rooms are met (see Sect. 34.15).
Validation Plan. This plan encompasses general examina- The validation requires time and manpower. For a small
tion, qualification and validation. During examination the scale preparation facility a time frame of 3 to 6 month is not
as-built premises are checked against the detail specification uncommon. It is quite obvious that the start-up process to
(DS). In addition some of the specifications will be checked operational status of preparation premises will never allow
that are described in the FRS and even the URS e.g. the time for any delayed activity for a constructive residual point
smoothness of the walls. The control of all these such as the mounting of another light fitting afterwards.
specifications is also called as-built verification. If all Planning in advance is paramount.
specifications are met the premises and built-in equipment
is qualified. Next all systems such as HVAC are put in use
and checked for their proper operation and safety. The air References
balance is adjusted. Calibration of e.g. pressure difference
meters is performed. This phase is also called commission- 1. PIC/S Guide to Good Practice for the Preparation of Medicinal
Products in Health Care Establishments. PE 010–3, 2008
ing and is usually executed by the contractor.
2. NEN-EN-ISO 14644 Cleanrooms and associate controlled
All deficiencies found during commissioning have to be environments; parts 1, 2, 4, 5 and 7
solved. The premises and installations are cleaned and sub- 3. NEN-EN-ISO 14698 Cleanrooms and associated controlled
sequently the validation can start based on procedures environments - Biocontamination control; parts 1 and 2
4. NEN-EN-ISO 14644-4:2001(E) Cleanrooms and associate con-
approved by the owner, usually the pharmacist. Validation trolled environments part 4: Design, construction and start-up
has several standard structures with the main subjects: IQ, 5. NEN-EN-ISO 14644-5:2004(E): Cleanrooms and associate con-
OQ and PQ (Sect. 34.10). Validation is a formal GMP trolled environments; part 5: Operations
requirement. 6. Note for Guidance on quality of water for Pharmaceutical use.
EMEA 2002
In case of a (new) building with installations the IQ and
7. Bader K, Hyde J, Watler P, Lane A (2009) Online Total Organic
OQ phase comprises a verification of the checks done during Carbon (TOC) as a process analytical technology for cleaning
the as-built verification and the commissioning including the validation risk management. Pharm Eng 29(1):8–21
check of all GMP critical aspects. It is not necessary to 8. Collentro WV (2007) Pharmaceutical water, system design, opera-
tion and validation. Informa Healthcare, Richmond
repeat all tests of the commissioning. Some additional tests
9. ISPE Water and Steam Systems; Baseline guide. ISPE, 2001
are done such as challenging critical limits of documented 10. Mathiesen T, Rau J, Frantsen JE, Terävä J, Björnstedt P-A, Henkel
functional specifications in practice and adjusting them if B (2002) Using exposure tests to examine rouging of stainless steel.
necessary, provided that they still comply with the FRS. Pharm Eng 22(4):90–97
11. ISPE Good Practice Guide: Commissioning and Qualification of
Also the documentation is completed such as manuals, Pharmaceutical Water and Steam Systems. ISPE, 2007
cleaning, disinfecting and maintenance procedures, 12. Pure Steam (2014) USP Unites States Pharmacopoeia 27:5176
instructions, a monitoring program. Microbiological (con- 13. NEN-EN-ISO 7396-1:2007(E) Medical gas pipeline systems – part
tact) samples (see Sect. 31.6) are taken, recovery time of the 1: Pipeline systems for compressed medical gases and vacuum

You might also like