You are on page 1of 2

Edition October 2013

ProductNews
HIMax® X-CPU 31

Functionality
■■ CPU and system bus function
are united in one module
■■ Safe run of all core
functionalities, including
safe communication via
safeethernet

Benefits
■■ HIMax is more scalable
■■ Lower investment costs
■■ Ideal for distributed
structures, thus less wiring
■■ Tailored performance range

Features
■■ Higher channel density
through up to 4 additional
slots for I/O and/or COM
modules in the first rack
■■ 64 I/O and 4 COM modules
on up to 16 racks
■■ Redundant system
configuration possible
■■ Up to 1,024 redundant I/Os
■■ HIMax can process or
change up to 32 user X-CPU 31 Connector Board
programs simultaneously
and independently and
interference-free from one
another (multitasking) Now for small and mid-size safety applications
■■ Recording up to 5,000
events The nonstop safety system HIMax was first choice for high performance and large safety
■■ Stores diagnostic entries applications. With the newly developed processor module X-CPU 31, HIMax is now also
created by the processor advisable for small and medium-sized applications with fewer I/Os. On the X-CPU 31 the
module CPU and system bus functions are united in one module. Thus, up to 4 slots in the first
■■ Stores diagnostic entries rack will be free for additional I/O and/or COM modules. The processor module X-CPU 31
created by I/O modules can accommodate up to 64 I/O modules and 4 COM modules on up to 16 racks.
■■ Interface to the SILworX®
programming tool (PADT)
■■ 4 different new base plates
with pre-mounted dual
redundant connector boards
Edition October 2013

ProductNews
ProductNews | HIMax® X-CPU 31

CPU and system bus functionality in one module Applications


HIMax with processor module X-CPU 01
HIMax systems with the
Slots 1 + 2: System bus module X-SB 01
processor module X-CPU 31
Slots 3 – 6: Up to 4 processor modules X-CPU 01
are suitable, e.g., for the
following applications:
■■ Emergency Shutdown
HIMax with the new processor module X-CPU 31
Slots 1 + 2: Up to 2 processor modules X-CPU 31 incl. systems (ESD)
■■ Fire & Gas systems (F&G)
integrated system bus functionality
■■ Burner safety and boiler

protection (BCS)
■■ Turbomachine and
Application Examples Mono System
Compressor operation
The module may be used in slots 1 and The processor module is inserted in slot 1 of
(TMC): Separate overspeed
2 of rack 0. The required I/O modules rack 0. A spare module is inserted in slot 2.
protection
may be inserted in slot 3 and following Only system bus A is therefore available. ■■ Pipeline Management &
slots. The connection to the PADT is The mono system can also be configured
Control (PMC): Detection of
implemented at the Ethernet interface with one processor module in slot 2 and a
pipeline breaks
Eth1 or Eth2 of the processor module spare module in 1. In this case, only system
inserted in rack 0. bus B is available.

Standards /
X-CPU 31
X-CPU 31

X-CPU 31
X-BLK

Certificates

1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
TÜV certified up to SIL 3
Eth1

Eth2
■■ IEC 61508 Parts 1-7:2010
Rack 0 Rack 0 ■■ EN 61511 Parts 1-3:2004
■■ EN ISO 13849-1:2008 +
AC:2009
Redundant System Redundant System ■■ EN 62061:2005
X-SB 01
X-SB 01

If the system is configured redundantly, with Extension Rack ■■ EN 50156-1:2004


the processor modules are inserted in The following figure shows ■■ EN 12067-2:2004
slots 1 and 2. the wiring of multiple 1 2 3 4 5 6 7 8 9 10 ■■ EN 298:2003
racks. The processor ■■ EN 61131-2:2007
modules must be located IEC 61326-3-1:2008
X-CPU 31
X-CPU 31

Rack 1 ■■

in the base plate (rack 0). ■■ EN 54-2:1997 + AC:1999 +


The connection to the
96 9000557 1013 V01 © by HIMA Paul Hildebrandt GmbH + Co KG

A1:2006
® = registered trademark HIMA Paul Hildebrandt GmbH + Co KG

X-CPU 31
X-CPU 31

extension rack (rack 1, ■■ NFPA 72:2010


1 2 3 4 5 6 7 8 9 10
rack 2, …) is performed ■■ NFPA 85:2011
via the X-SB 01 system bus 1 2 3 4 5 6 7 8 9 10 ■■ NFPA 86:2011
Specifications subject to change without notice.

Rack 0 modules.
Rack 0
X-SB 01
X-SB 01

1 2 3 4 5 6 7 8 9 10

Rack 2

www.hima.com I info@hima.com