Check
1. _____Generator must be bolted to the concrete pad which has been engineered to meet code.
2._____Exhaust System
Indoor units must have the exhaust completely installed. The flexible connector must
not be used as an offset of 90 degree. An engineered thimble MUST be used were the
exhaust penetrates the roof or wall. At the termination there must a rain cap on vertical
discharge and on horizontal discharge there must be either a rain cap or the pipe cut off
at a 45 degree with bird screen installed.
Outdoor units require the exhaust to be completely installed including the rain cap which
must be able to open and close freely. Rain caps may be secured for shipping.
Start-up dates are reserved on a first come first serve basis and require at least 1-2 week notice.
Starts up are to be performed during normal business hours and generally can be completed in 1-2
business days. If after hours testing is required there will be additional charges.
If there is anything on this list that is marked as being ready and it is not, requiring a second trip, the
contractor will be held responsible for the additional trip charges.