Professional Documents
Culture Documents
Grids
Tamal Paul1, Harsha Ravindra2, Michael Steurer2, and Jonathan W. Kimball1
1 2
Department of Electrical and Computer Engineering Center for Advanced Power Systems
Missouri University of Science and Technology Florida State University
Rolla, Missouri USA Tallahassee, Florida USA
tpzmb@mst.edu, kimballjw@mst.edu hr09g@my.fsu.edu, steurer@caps.fsu.edu
Abstract— Voltage stability analysis is essential in any power growing increase in power demand, voltage stability
system. This paper addresses the voltage stability in a typical problems are also on the rise and pose a serious threat to
smart grid type system with multiple independent entities. A system operators. The problem of voltage stability can be
typical smart grid operation involves various loading excursions attributed to the inability of the system to cater to the reactive
(changes in power, both generated and consumed) undertaken
power needs of its elements. It can this be described as a
by all these independent entities. For a smooth functioning of
any generic smart grid type system, correct behavior of all these reactive power problem [5].
independent entities must be preserved when one or more of Studies undertaken to analyze voltage stability require
these entities are subjected to various loading levels. Correct careful investigation of a large number of system states and
behavior of all the entities (sub-systems) will ensure correct contingency situations. This makes a steady state approach
behavior of the overall system (smart grid). Invariants, if forced seem more feasible. Literature studies reveal special
to be true, ensure correct behavior on a subsystem level and algorithms that target the voltage stability problem using
thus preserve the overall system correctness. An invariant is a static methods [6]. However, such studies are labor intensive
logical predicate on a system state that should not change its and fail to provide sensitivity information. Certain operators
truth value if satisfied by system execution [1]. This paper
derives an invariant that preserves voltage stability. This
make use of the Q-V curve at some of the independent
invariant is based on an online indicator which is derived from entities to determine the proximity of voltage instability [7].
fundamental Kirchhoff’s laws and will predict the proximity of The major drawback of such an approach is that the excessive
voltage collapse at one or more entities in a smart grid. The focus on a small number of local components fails to provide
efficiency of the invariant in predicting voltage collapse has information about the overall system-level voltage stability
been verified with simulations performed on a typical seven
node smart grid system. Thus an online monitoring of the B. Voltage Instability
system parameters gives an indication of the system voltage
stability. The voltage stability invariant works for both static
and dynamic states. This method is also a fast and powerful tool
Voltage instability leads to a progressive (or periodic) fall (or
to predict the voltage stability margin of a generic smart grid rise) in voltage of the system. As mentioned earlier, this loss
system by a simple monitoring of the system parameters. of voltage stability stems from the inability of the system to
supply the reactive power needed by one or more independent
entities. A voltage decay/fall in the system is usually caused
I. INTRODUCTION by an increasing in loading or change in system conditions at
Voltage stability is of utmost importance to power system one or more entities thereby causing an excessive increase in
operation. Drop in voltage levels poses serious concerns in reactive power demand which the system is unable to meet.
electric utilities and appliances. According to ANSI Thus the loading pattern of the individual components affects
standards, system voltages should not drop below 5% of their the system-level voltage stability. This emphasizes the
nominal value for a satisfactory operation of the power importance of enforcing voltage stability constraints at the
system [2-4]. Any study on voltage stability of a power sub-system level in order to ensure a proper functioning of
system should investigate how close the system voltage is to the overall system and eliminate the possibility of voltage
collapsing, at what precise moment does the collapse occur, collapse in the system.
what are the vulnerable areas in the system and what are the
factors contributing to this collapse.
II. VOLTAGE COLLAPSE
A. Voltage Stability Studies One of the key indicators of a healthy system is steady
The concept of voltage stability is critical for the proper voltage levels at all of its sub-systems. The system is planned
functioning of a smart grid type system. With the ever to operate in such a way that whenever there is an increased
2
voltage stability and be forewarned should the invariant A. Case I: Increase the loading at one bus (j) and observe
indicate an impending voltage collapse. the voltage collapse of that bus. Monitor the stability
indicator for that bus ( L j ) and another bus ( Li )
V. MODEL DESCRIPTION
The system conditions are given as:
The model was simulated using RSCAD as shown in Fig. 1.
The power system model used for the study is the seven 1) The generation at each bus is kept at 0; thus assuming
section FREEDM feeder system. The system derives its name no local generation.
from seven primary line sections. The feeder has 7 lumped 2) The loading at buses 2-7 are kept at 205 kW.
loads connected through 7 load SSTs. The feeder is rated at 3) Loading at bus 1 is increased throughout the simulation
12.47 kV. The maximum load on the feeder is 2 MVA. The from 205 kW to 1605 kW.
feeder has some peculiar features pertaining to studies in 4) The total load on the system is the summation of the
FREEDM. The system is a looped system. It is also an load at each bus.
islanded feeder. The loads are served primarily by two diesel 5) Generator 1 tries to supply the excess load in the
generators. system
Although the feeder is looped, it could be operated in
radial mode. The two diesel generators are rated at 1.4 MVA The loading at bus 1 is increased; keeping the load at all the
each. One of them operates in droop mode (G2) while the other buses fixed at 205 kW. The indicator for bus 1 (L1) is
other operates in isochronous mode (G1). As mentioned observed in Fig. 2(a). The indicator for bus 3 (L3) is observed
before, the feeder primary is made up of seven line sections. in Fig. 2(b). Thus j=1 and i=3.
The impedance of each line section is identical. Each load Results are indicated in Fig. 2. The solid blue line
SST is rated at 285 kVA. On the secondary of each load SST, indicates bus 1 per unit voltage and solid red line indicates L1
there is a lumped load, lumped distributed generation (DG) in Fig 2(a). The solid blue line indicates per unit voltage of
and storage connected. The model parameters are given as: bus 1 and the solid green line indicates L3 in Fig. 2(b).
• Generators: Rated at 1.4 MVA, 380 V line-to
neutral.
• Transformer: Rated at 1.5 MVA, 0.38kV:12.47kV
• Lines: 0.77039 ȍ (Positive Sequence resistance),
1.967 mH (Positive Sequence inductance),
2.310927 ȍ (Zero Sequence resistance), 5.9 mH
(Zero Sequence inductance)
The droop generator is set to run at 400 kW with 5% droop.
(a)
(b)
Fig. 2. Change in voltages and indicators as loading as bus 1
Fig. 1: Single line diagram of the 7-bus system increases, (a) V1 and L1 and (b) V1 and L3.
3
Bus 1 collapses at around 34 seconds when the loading at
bus 1 is 1.404 MW. The per-unit voltage of bus 1 at that
instant is less than 0.95 p.u (does not meet ANSI mandated
5% voltage deviation standards). L1 however intersects the
per unit voltage at around the 24 second instant when the
loading is 1.005 MW. This is the “online monitored voltage
collapse indication point” where L1 approaches unity. If
loading is continued beyond this point, the voltage collapses
shortly and eventually the system totally crashes.
Although the indicator for bus 1 indicates voltage
instability when the loading at bus 1 reaches the voltage
collapse point, the other bus indicator (L3) gives a false sense
of voltage stability by not indicating a violation of the
condition for voltage stability. This confirms the importance
of choosing the maximum value of L for determining the
(a)
voltage collapse point of the overall system.
Thus the online monitored indicator can signal when the
system is on the brink of voltage collapse and can thus act as
a guard/invariant to prevent the system into entering such an
undesirable state.
B. Case 2: Increase the loading at one bus (i) and observe
the voltage collapse of another bus (j). Monitor the
stability indicator for the other bus ( L j ) and the bus
which is being loaded ( Li )
The system conditions are identical to that of Case 1. The
loading at bus 1 is increased; keeping the load at all the other
buses fixed at 205 kW. The indicator for bus 1 (L1) is
observed in Fig. 3(a). The indicator for bus 4 (L3) is observed
in Fig. 3(b). Thus j=4 and i=1. (b)
The solid blue line indicates bus 4 per unit voltage and Fig. 3. Change in voltages and indicators as loading as bus 1
solid red line indicates L4 in Fig. 3(a). The solid blue line increases, (a) V4 and L4 and (b) V4 and L1.
indicates per unit voltage of bus 4 and the solid green line
indicates L1 in Fig. 3(b).
It is seen that bus 4 collapses at 34.67 seconds when the
loading at bus 1 is 1.428 MW. The per unit voltage of bus 4 at
that instant is less than 0.95 p.u. L4 never intersects the per
unit voltage curve; L1 however does.
Although the indicator for bus 4 does not indicate voltage
collapse when its own bus reaches the voltage collapse point
due to loading at bus 1, the other bus indicator (L1) indicates
an invariant violation. This re-iterates the importance of
choosing the maximum value of L for all the buses to
determine the voltage collapse point of the overall system.
For both cases 1 and 2, the voltage starts to collapse
because of insufficient reactive power in the system. This is
shown by Fig. 4 which depicts the generator 1 and 2 reactive
power. It can be seen while generator 1 absorbs reactive
power for these two cases, generator 2 supplies reactive
power; thereby keeping the overall reactive power generation
positive. However as the loading is further continues to
increase, generator 2 is unable to provide the reactive power
to compensate for the increased consumption of reactive
power of the system. Hence the voltage starts to collapse at
this point at one or more buses when the supplied reactive
Fig. 4. Plot of generator 1 and 2 reactive power against time
with increased loading at bus 1
4
power is greater than the reactive power needed to maintain
one or more bus voltages.
When the system is stressed, the droop generator supplies
reactive power to maintain the bus voltages. Case 3 is a study
of the system when the droop generator has been removed. In
the absence of a droop generator, the system becomes more
vulnerable than before and cannot be subjected to its previous
loading levels. If the loading is increased at one of the buses
(the loading levels being much smaller than the previous two
cases given that the system is already vulnerable in the
absence of an extra reactive power supplying generator),
generator 1 tries to supply the reactive power need of the
system as long as it can; but ultimately fails thereby resulting
in a total system crash as shown in Case 3.
C. Case 3: Increase the loading at one bus (j) in the system Fig. 6. Plot of generator 1 reactive power against time with
without any droop and observe the voltage collapse of increased loading at bus 1.
that bus. Monitor the stability indicator for that bus
the crash as it intersects the voltage curve prior to the system
( L j ) and the point where the voltage collapses. crash.
The system conditions are given as: The invariant signals the nearing of the system to voltage
collapse well ahead of time. Thus in a transaction based [10]
1) The generation at each bus is kept at 0; thus assuming power system, each and every customer’s (sub-system’s)
no local generation. obligation can be determined using this online system state
2) The loading at buses 2-7 are kept at 0 kW. monitoring indicator.
3) Loading at bus 1 is increased throughout the simulation VII. CONCLUSIONS AND FUTURE WORK
from 205 kW to 1500 kW.
4) The total load on the system is the summation of the An invariant which predicts the proximity of voltage collapse
load at each bus. in a smart grid type setting has been presented. This invariant
5) Generator 1 tries to supply the excess load in the is based on a real time online monitoring of system
system. parameters. The invariant can be suitably modified to provide
insight about the system voltage stability in the absence of
In the absence of the droop, the system collapses as can be current/live system values. The efficacy of the invariant in
seen for a much lesser load as demonstrated in Fig. 5. This predicting voltage collapse has been verified with
crash is because the second generator no longer supplies the experimental simulations. Should loading be continued any
deficit reactive power for the system. The only generator in further, the system does go on to collapse. The invariant thus
the model supplying reactive power quickly runs short of is useful in locating the vulnerable locations in the system.
reactive power causing a total system crash as shown in Fig. The voltage collapses because of a deficit of reactive
6. The indicator for bus 1 signals the imminent occurrence of power supply in the system as the reactive power needed to
maintain the sub-system voltages within acceptable levels
increases with increased loading at the buses. Generator 2
provides a “stabilizing” factor to the model by being a
provider of reactive power. In the absence of the droop
generator, the vulnerability of the system increases, its
tolerance towards loading decreases and it crashes at a much
lower load than it would have had the droop generator been
available. Thus the droop generator is important in widening
the satisfactory range of operation of the system and catering
to higher loads.
The invariant currently relies on online measurements of
the system states to give an effective assessment of the
proximity of the system to its collapse. Future work (in
progress) will explore what assumptions/ modifications can
be imposed on the existing indicator for it to function when
one or more system state measurements might not be
Fig. 5. Plot of V1 and L1 against time with increased loading at
available for a variety of reasons. Unavailability of system
bus 1 for the system with no droop generator.
states may be due to absence of current/updated values or
5
deliberate corrupt/bogus values. In the absence of reliable [5] J. A. Diaz de Leon II, C. W. Taylor, “Understanding and
data, the indicator must be modified accordingly so that it can Solving Short-Term Voltage Stability Problems,” IEEE Power
still predict voltage collapse just like it does now when real Engineering Society Summer Meeting, 2002, pp. 745-752.
time correct system state data is available. [6] I Aumuller, C.A.; Saha, T.K., "Investigating the impact of
Powerformer on voltage stability by dynamic simulation,"
ACKNOWLEDGMENTS Power Systems, IEEE Transactions on, vol.18, no.3,
pp.1142,1148, Aug. 2003.
This work was supported by the National Science
[7] Huang, G.M.; Kun Men, "Contribution allocation for voltage
Foundation under award EEC-0812121, the Future
stability in deregulated power systems," Power Engineering
Renewable Electric Energy Delivery and Management Society Summer Meeting, 2002 IEEE , vol.3, no.,
Systems Center (FREEDM). pp.1290,1295 vol.3, 25-25 July 2002.
REFERENCES [8] Wood and B.F Wollenberg, “Power Generation, Operation and
Control”, John Wiley, New York, 1996.
[1] Paul, T.; Kimball, J.W.; Zawodniok, M.; Roth, T.P.; McMillin,
[9] I. Kumaraswamy, W.V Jahnavi, T. Devaraju, P.Ramesh, “An
B., Chellappan, S., "Unified Invariants for Cyber-Physical
Optimal Power Flow (OPF) Method with Improved Voltage
Switched System Stability," Smart Grid, IEEE Transactions on,
Stability Analysis”, Proceedings of the World Congress on
vol.5, no.1, pp.112,120, Jan. 2014.
Engineering, London, UK, July 4-6, 2012.
[2] ANSI C84.1-2011.
[3] Kusko, A. and Thompson, M. (2007). Power Quality in [10] Kazari, H.; Abbaspour-Tehrani Fard, A.; Dobakhshari, A.S.;
Electrical Systems. New York: McGraw-Hill. Ranjbar, A.M., "Voltage stability improvement through
[4] Pacific Gas and Electric Company. (1999). Voltage Tolerance centralized reactive power management on the Smart Grid,"
Boundary. Innovative Smart Grid Technologies (ISGT), 2012 IEEE PES,
pp.1,7, 16-20 Jan. 2012.