You are on page 1of 5

CLIENT : DUBAI ELECTRIC & WATER AUTHORIY

BUREAU VERITAS PROJECT : RFX-2121900085 INTEGRITY INSPECTION


FOR FUEL SYSTEMS AT ‘H’ STATION PHASE II
PO BOX: 9110, Dubai, UAE CONTRACT NO.: DBA.4.19.970
REPORT NO. : BV/DEWA/AWEER/UTG-001 DATE:-19.10.2020
PAGE NO: 1 OF 5
ULTRASONIC THICKNESS GAUGING REPORT
SITE : AL AWEER POWER STATION ,DUBAI DRAWING NO. : SI-61667
SPECIFICATION : NA EQUIPMENT : CYGNUS1 SR NO: 7535
PROCEDURE NO: BV/DEWA/UTG-001 REV-0 CALIBRATION: DUE DATE DEC-20
MATERIAL: SS400 CALIBRATON BLOCK :15 mm Block
THICKNESS: VARIOUS COUPLANT : Cellulose Paste
SURFACE CONDITION : AS SMOOTH CONDITION EQUIPMENT TAG /LINE NO : Mention Below
ITP Observed Thickness( mm) Remarks
Line No/Tag No Sch./WT
NO. Location A B C D
(mm)
0⁰ 90⁰ 180⁰ 270⁰
CROWN FACE 7.3 7.5 7.4 7.5

KNUCKLE FACE 8.2 8.0 8.1 7.9

STRAIGHT FACE 7.1 7.4 7.3 7.2


41EGD 20
AT003 SHELL Location 1 6.2 6.2 6.3 6.2
A
SHELL Location 2 6.4 6.3 6.2 6.2
STRAIGHT FACE 8.3 8.3 8.4 8.3
KNUCKLE FACE 7.8 7.7 7.9 7.8
CROWN FACE 7.7 7.5 7.6 7.5
CROWN FACE 8.5 8.6 8.4 8.0

KNUCKLE FACE 7.7 7.8 8.0 7.7


41EGD 20 STRAIGHT FACE 7.8 7.6 7.5 7.6
AT003
SHELL Location 1 6.3 6.4 6.5 6.3
B
SHELL Location 2 6.2 6.4 6.4 6.3
STRAIGHT FACE 8.5 8.4 8.5 8.3
KNUCKLE FACE 8.0 8.0 7.9 7.8
CROWN FACE 7.5 7.6 7.5 7.6
CROWN FACE 8.0 8.2 8.1 8.3
41EGD 20 KNUCKLE FACE 7.9 7.8 7.6 7.8
AT004 STRAIGHT FACE 7.2 7.3 7.2 7.3
A SHELL Location 1 6.3 6.2 6.3 6.4
SHELL Location 2 6.2 6.3 6.3 6.3
NDT INSPECTOR CLIENT TPI
Name : MANOJ PANDIT Company : Company :
Signature : Name : Name :
Qualification : NDT Level II Signature : Signature :

Date : 19.10.2020 Date: Date :

CLIENT : DUBAI ELECTRIC & WATER AUTHORIY

Documents No: BV /UTG-001 Rev-0


PROJECT : RFX-2121900085 INTEGRITY INSPECTION
BUREAU VERITAS FOR FUEL SYSTEMS AT ‘H’ STATION PHASE II
CONTRACT NO.: DBA.4.19.970
PO BOX: 9110, Dubai, UAE REPORT NO. : BV/DEWA/AWEER/UTG-001 DATE:-19.10.2020
PAGE NO: 2 OF 5

ULTRASONIC THICKNESS GAUGING REPORT CONTINUE SHEET


ITP Sch./ Observed Thickness( mm) Remarks
Line No/Tag No
NO. Location WT A B C D
(mm) 0⁰ 90⁰ 180⁰ 270⁰

41EGD 20 STRAIGHT FACE 8.0 7.9 7.6 7.9


AT004 KNUCKLE FACE 8.1 8.1 8.2 8.1
A
CROWN FACE 7.9 7.6 7.5 7.4
CROWN FACE 8.0 8.2 7.9 8.0
KNUCKLE FACE 8.1 8.0 8.0 8.0

STRAIGHT FACE 7.2 7.5 7.4 7.3


41EGD 20
SHELL Location 1 6.2 6.3 6.3 6.2
AT004
B SHELL Location 2 6.2 6.3 6.2 6.2

STRAIGHT FACE 8.3 8.4 8.5 8.3

KNUCKLE FACE 7.5 7.7 7.6 7.5

CROWN FACE 7.5 7.4 7.4 7.3

CROWN FACE 7.9 7.9 8.0 8.0

KNUCKLE FACE 8.2 8.1 8.3 8.0


42EGD 20 STRAIGHT FACE 7.2 7.2 7.1 7.0
AT003 SHELL Location 1 6.2 6.2 6.3 6.2
A
SHELL Location 2 6.4 6.3 6.2 6.3
STRAIGHT FACE 8.5 8.3 8.4 8.3
KNUCKLE FACE 7.7 7.8 7.9 7.8
CROWN FACE 7.7 7.6 7.4 7.5
CROWN FACE 7.8 7.6 7.9 7.9
KNUCKLE FACE 8.2 8.0 8.1 8.0
42EGD 20
STRAIGHT FACE 7.3 7.2 7.0 7.1
AT003
B SHELL Location 1 6.2 6.3 6.3 6.3
SHELL Location 2 6.3 6.2 6.4 6.3
STRAIGHT FACE 8.4 8.5 8.4 8.6
NDT INSPECTOR CLIENT TPI
Name : MANOJ PANDIT Company : Company :

Signature : Name : Name :


Qualification : NDT Level II Signature : Signature :

Date : 19.10.2020 Date: Date :

CLIENT : DUBAI ELECTRIC & WATER AUTHORIY


BUREAU VERITAS PROJECT : RFX-2121900085 INTEGRITY INSPECTION
FOR FUEL SYSTEMS AT ‘H’ STATION PHASE II
CONTRACT NO.: DBA.4.19.970
Documents No: BV /UTG-001 Rev-0
PO BOX: 9110, Dubai, UAE REPORT NO. : BV/DEWA/AWEER/UTG-001 DATE:-19.10.2020
PAGE NO: 3 OF 5

ULTRASONIC THICKNESS GAUGING REPORT CONTINUE SHEET


ITP Observed Thickness( mm) Remarks
Line No/Tag No Sch./WT
NO. Location A B C D
(mm)
0⁰ 90⁰ 180⁰ 270⁰
42EGD 20 AT003 KNUCKLE FACE 7.9 7.8 8.1 8.0
B
CROWN FACE 7.7 7.5 7.6 7.5

CROWN FACE 7.9 7.6 7.8 7.6


KNUCKLE FACE 8.0 8.2 8.3 8.1
STRAIGHT FACE 7.2 7.3 7.4 7.3

42EGD 20 AT004 SHELL Location 1 6.3 6.4 6.2 6.3


A
SHELL Location 2 6.3 6.3 6.3 6.2

STRAIGHT FACE 8.4 8.3 8.4 8.2

KNUCKLE FACE 8.0 8.0 8.1 7.9

CROWN FACE 7.7 7.4 7.6 7.4

CROWN FACE 7.8 7.3 7.6 7.4

KNUCKLE FACE 8.2 8.0 8.0 7.9

STRAIGHT FACE 7.1 7.2 7.3 7.2


42EGD 20 AT004
B SHELL Location 1 6.2 6.2 6.2 6.3
SHELL Location 2 6.3 6.4 6.2 6.2
STRAIGHT FACE 8.4 8.5 8.6 8.4
KNUCKLE FACE 8.1 7.9 7.9 7.8
CROWN FACE 7.7 7.5 7.6 7.5
CROWN FACE 7.9 7.9 7.9 8.2
KNUCKLE FACE 8.1 8.3 8.1 8.0
43EGD 20 AT003 STRAIGHT FACE 7.2 7.2 7.0 7.2
A SHELL Location 1 6.3 6.3 6.3 6.3
SHELL Location 2 6.2 6.4 6.4 6.3
STRAIGHT FACE 8.4 8.4 8.4 8.3
NDT INSPECTOR CLIENT TPI
Name : MANOJ PANDIT Company : Company :

Signature : Name : Name :


Qualification : NDT Level II Signature : Signature :

Date : 19.10.2020 Date: Date :

CLIENT : DUBAI ELECTRIC & WATER AUTHORIY


BUREAU VERITAS PROJECT : RFX-2121900085 INTEGRITY INSPECTION
FOR FUEL SYSTEMS AT ‘H’ STATION PHASE II
CONTRACT NO.: DBA.4.19.970

Documents No: BV /UTG-001 Rev-0


PO BOX: 9110, Dubai, UAE REPORT NO. : BV/DEWA/AWEER/UTG-001 DATE:-19.10.2020
PAGE NO: 4 OF 5

ULTRASONIC THICKNESS GAUGING REPORT CONTINUE SHEET


Observed Thickness( mm) Remarks
Line No/Tag No ITP NO. Sch./WT
Location A B C D
(mm)
0⁰ 90⁰ 180⁰ 270⁰
43EGD 20 AT003 KNUCKLE FACE 7.7 7.2 7.6 7.7
A
CROWN FACE 7.5 7.4 7.4 7.3

CROWN FACE 7.9 8.0 8.0 8.1


KNUCKLE FACE 8.3 8.2 8.3 8.2
STRAIGHT FACE 7.1 7.3 7.2 7.0

43EGD 20 AT003 SHELL Location 1 6.3 6.2 6.3 6.2


B
SHELL Location 2 6.4 6.3 6.3 6.4

STRAIGHT FACE 8.5 8.3 8.4 8.4

KNUCKLE FACE 7.8 7.9 7.8 7.5

CROWN FACE 7.6 7.4 7.5 7.3

CROWN FACE 8.0 8.0 8.2 7.9

KNUCKLE FACE 8.1 8.2 8.3 8.2

STRAIGHT FACE 7.1 7.2 7.1 7.1


43EGD 20 AT004
A SHELL Location 1 6.3 6.4 6.3 6.4
SHELL Location 2 6.3 6.3 6.2 6.3
STRAIGHT FACE 8.5 8.3 8.5 8.5
KNUCKLE FACE 7.7 7.9 7.8 7.7
CROWN FACE 7.6 7.6 7.5 7.4
CROWN FACE 7.9 8.1 8.0 7.0
KNUCKLE FACE 8.2 8.3 8.2 8.4
STRAIGHT FACE 7.1 7.3 7.4 7.1
43EGD 20 AT004 SHELL Location 1 6.3 6.2 6.2 6.3
B SHELL Location 2 6.3 6.2 6.4 6.3
STRAIGHT FACE 8.3 8.4 8.5 8.3
KNUCKLE FACE 7.9 7.8 7.7 7.6
CROWN FACE 7.6 7.5 7.4 7.7
NDT INSPECTOR CLIENT TPI
Name : MANOJ PANDIT Company : Company :

Signature : Name : Name :


Qualification : NDT Level II Signature : Signature :

Date : 19.10.2020 Date: Date :

Documents No: BV /UTG-001 Rev-0


SKETCH

Documents No: BV /UTG-001 Rev-0