BUREAU VERITAS PROJECT : RFX-2121900085 INTEGRITY INSPECTION
FOR FUEL SYSTEMS AT ‘H’ STATION PHASE II PO BOX: 9110, Dubai, UAE CONTRACT NO.: DBA.4.19.970 REPORT NO. : BV/DEWA/AWEER/UTG-001 DATE:-19.10.2020 PAGE NO: 1 OF 5 ULTRASONIC THICKNESS GAUGING REPORT SITE : AL AWEER POWER STATION ,DUBAI DRAWING NO. : SI-61667 SPECIFICATION : NA EQUIPMENT : CYGNUS1 SR NO: 7535 PROCEDURE NO: BV/DEWA/UTG-001 REV-0 CALIBRATION: DUE DATE DEC-20 MATERIAL: SS400 CALIBRATON BLOCK :15 mm Block THICKNESS: VARIOUS COUPLANT : Cellulose Paste SURFACE CONDITION : AS SMOOTH CONDITION EQUIPMENT TAG /LINE NO : Mention Below ITP Observed Thickness( mm) Remarks Line No/Tag No Sch./WT NO. Location A B C D (mm) 0⁰ 90⁰ 180⁰ 270⁰ CROWN FACE 7.3 7.5 7.4 7.5
KNUCKLE FACE 8.2 8.0 8.1 7.9
STRAIGHT FACE 7.1 7.4 7.3 7.2
41EGD 20 AT003 SHELL Location 1 6.2 6.2 6.3 6.2 A SHELL Location 2 6.4 6.3 6.2 6.2 STRAIGHT FACE 8.3 8.3 8.4 8.3 KNUCKLE FACE 7.8 7.7 7.9 7.8 CROWN FACE 7.7 7.5 7.6 7.5 CROWN FACE 8.5 8.6 8.4 8.0
KNUCKLE FACE 7.7 7.8 8.0 7.7
41EGD 20 STRAIGHT FACE 7.8 7.6 7.5 7.6 AT003 SHELL Location 1 6.3 6.4 6.5 6.3 B SHELL Location 2 6.2 6.4 6.4 6.3 STRAIGHT FACE 8.5 8.4 8.5 8.3 KNUCKLE FACE 8.0 8.0 7.9 7.8 CROWN FACE 7.5 7.6 7.5 7.6 CROWN FACE 8.0 8.2 8.1 8.3 41EGD 20 KNUCKLE FACE 7.9 7.8 7.6 7.8 AT004 STRAIGHT FACE 7.2 7.3 7.2 7.3 A SHELL Location 1 6.3 6.2 6.3 6.4 SHELL Location 2 6.2 6.3 6.3 6.3 NDT INSPECTOR CLIENT TPI Name : MANOJ PANDIT Company : Company : Signature : Name : Name : Qualification : NDT Level II Signature : Signature :
Date : 19.10.2020 Date: Date :
CLIENT : DUBAI ELECTRIC & WATER AUTHORIY
Documents No: BV /UTG-001 Rev-0
PROJECT : RFX-2121900085 INTEGRITY INSPECTION BUREAU VERITAS FOR FUEL SYSTEMS AT ‘H’ STATION PHASE II CONTRACT NO.: DBA.4.19.970 PO BOX: 9110, Dubai, UAE REPORT NO. : BV/DEWA/AWEER/UTG-001 DATE:-19.10.2020 PAGE NO: 2 OF 5
42EGD 20 STRAIGHT FACE 7.2 7.2 7.1 7.0 AT003 SHELL Location 1 6.2 6.2 6.3 6.2 A SHELL Location 2 6.4 6.3 6.2 6.3 STRAIGHT FACE 8.5 8.3 8.4 8.3 KNUCKLE FACE 7.7 7.8 7.9 7.8 CROWN FACE 7.7 7.6 7.4 7.5 CROWN FACE 7.8 7.6 7.9 7.9 KNUCKLE FACE 8.2 8.0 8.1 8.0 42EGD 20 STRAIGHT FACE 7.3 7.2 7.0 7.1 AT003 B SHELL Location 1 6.2 6.3 6.3 6.3 SHELL Location 2 6.3 6.2 6.4 6.3 STRAIGHT FACE 8.4 8.5 8.4 8.6 NDT INSPECTOR CLIENT TPI Name : MANOJ PANDIT Company : Company :
Signature : Name : Name :
Qualification : NDT Level II Signature : Signature :
Date : 19.10.2020 Date: Date :
CLIENT : DUBAI ELECTRIC & WATER AUTHORIY
BUREAU VERITAS PROJECT : RFX-2121900085 INTEGRITY INSPECTION FOR FUEL SYSTEMS AT ‘H’ STATION PHASE II CONTRACT NO.: DBA.4.19.970 Documents No: BV /UTG-001 Rev-0 PO BOX: 9110, Dubai, UAE REPORT NO. : BV/DEWA/AWEER/UTG-001 DATE:-19.10.2020 PAGE NO: 3 OF 5
ITP Observed Thickness( mm) Remarks Line No/Tag No Sch./WT NO. Location A B C D (mm) 0⁰ 90⁰ 180⁰ 270⁰ 42EGD 20 AT003 KNUCKLE FACE 7.9 7.8 8.1 8.0 B CROWN FACE 7.7 7.5 7.6 7.5
CROWN FACE 7.9 7.6 7.8 7.6
KNUCKLE FACE 8.0 8.2 8.3 8.1 STRAIGHT FACE 7.2 7.3 7.4 7.3
42EGD 20 AT004 SHELL Location 1 6.3 6.4 6.2 6.3
A SHELL Location 2 6.3 6.3 6.3 6.2
STRAIGHT FACE 8.4 8.3 8.4 8.2
KNUCKLE FACE 8.0 8.0 8.1 7.9
CROWN FACE 7.7 7.4 7.6 7.4
CROWN FACE 7.8 7.3 7.6 7.4
KNUCKLE FACE 8.2 8.0 8.0 7.9
STRAIGHT FACE 7.1 7.2 7.3 7.2
42EGD 20 AT004 B SHELL Location 1 6.2 6.2 6.2 6.3 SHELL Location 2 6.3 6.4 6.2 6.2 STRAIGHT FACE 8.4 8.5 8.6 8.4 KNUCKLE FACE 8.1 7.9 7.9 7.8 CROWN FACE 7.7 7.5 7.6 7.5 CROWN FACE 7.9 7.9 7.9 8.2 KNUCKLE FACE 8.1 8.3 8.1 8.0 43EGD 20 AT003 STRAIGHT FACE 7.2 7.2 7.0 7.2 A SHELL Location 1 6.3 6.3 6.3 6.3 SHELL Location 2 6.2 6.4 6.4 6.3 STRAIGHT FACE 8.4 8.4 8.4 8.3 NDT INSPECTOR CLIENT TPI Name : MANOJ PANDIT Company : Company :
Signature : Name : Name :
Qualification : NDT Level II Signature : Signature :
Date : 19.10.2020 Date: Date :
CLIENT : DUBAI ELECTRIC & WATER AUTHORIY
BUREAU VERITAS PROJECT : RFX-2121900085 INTEGRITY INSPECTION FOR FUEL SYSTEMS AT ‘H’ STATION PHASE II CONTRACT NO.: DBA.4.19.970
Documents No: BV /UTG-001 Rev-0
PO BOX: 9110, Dubai, UAE REPORT NO. : BV/DEWA/AWEER/UTG-001 DATE:-19.10.2020 PAGE NO: 4 OF 5
Observed Thickness( mm) Remarks Line No/Tag No ITP NO. Sch./WT Location A B C D (mm) 0⁰ 90⁰ 180⁰ 270⁰ 43EGD 20 AT003 KNUCKLE FACE 7.7 7.2 7.6 7.7 A CROWN FACE 7.5 7.4 7.4 7.3
CROWN FACE 7.9 8.0 8.0 8.1
KNUCKLE FACE 8.3 8.2 8.3 8.2 STRAIGHT FACE 7.1 7.3 7.2 7.0
43EGD 20 AT003 SHELL Location 1 6.3 6.2 6.3 6.2
B SHELL Location 2 6.4 6.3 6.3 6.4
STRAIGHT FACE 8.5 8.3 8.4 8.4
KNUCKLE FACE 7.8 7.9 7.8 7.5
CROWN FACE 7.6 7.4 7.5 7.3
CROWN FACE 8.0 8.0 8.2 7.9
KNUCKLE FACE 8.1 8.2 8.3 8.2
STRAIGHT FACE 7.1 7.2 7.1 7.1
43EGD 20 AT004 A SHELL Location 1 6.3 6.4 6.3 6.4 SHELL Location 2 6.3 6.3 6.2 6.3 STRAIGHT FACE 8.5 8.3 8.5 8.5 KNUCKLE FACE 7.7 7.9 7.8 7.7 CROWN FACE 7.6 7.6 7.5 7.4 CROWN FACE 7.9 8.1 8.0 7.0 KNUCKLE FACE 8.2 8.3 8.2 8.4 STRAIGHT FACE 7.1 7.3 7.4 7.1 43EGD 20 AT004 SHELL Location 1 6.3 6.2 6.2 6.3 B SHELL Location 2 6.3 6.2 6.4 6.3 STRAIGHT FACE 8.3 8.4 8.5 8.3 KNUCKLE FACE 7.9 7.8 7.7 7.6 CROWN FACE 7.6 7.5 7.4 7.7 NDT INSPECTOR CLIENT TPI Name : MANOJ PANDIT Company : Company :
Signature : Name : Name :
Qualification : NDT Level II Signature : Signature :