You are on page 1of 5

Voltage Sags/Swells Subsequent to Islanding

Transition of PV-Battery Microgrids


Pan Zhongmei, Hou Tonghui, Wang Yuqing
Electrical Engineering Department
Xi’an University of Technology
panpan@xaut.edu.cn

Abstract—This paper investigates the transient voltage frequency within the stand-alone microgrid. And single master
sags/swells subsequent to islanding of a PV-Battery microgrid. operation or multi master operation is applied according to one
For an unplanned islanding and micro-grid formation, during or more DERs are operated to maintain the voltage and
islanding detection time, the microgrid is disconnected from frequency.
main grid while the control mode of the BESS stays the same as
before. Consequently the microgrid will undergo transient The microgrid islanding process may be an intentional
voltage sag or swell caused by the mismatch of the source output disconnection from the main grid for maintenance purpose[3]
and the load power and the switch transients. The microgrid or be an unscheduled disconnection due to either a fault and its
studied includes a diesel synchronous generator, an inverter- subsequent switching incidents or some other unexpected
based PV system and an inverter-based battery storage system. switching process[4].
The PV system is operated in MPPT mode. And the battery
system is operated by a PQ controller in grid-connected mode The transition of microgrid from grid-connected mode to
and by a V/f controller in islanded mode. Matlab/Simulink is islanded mode has been discussed in [4]-[9]. The improvement
adopted to model the microgrid under study. The voltage or modification of power management and control strategy for
transients in several scenarios of the microgrid are simulated. smooth transition is discussed in[5]-[6]. In [7]-[8], small signal
dynamic model of a micro-grid with inverter based DG and
Keywords—microgrid; unplanned islanding; voltage sag/dip; synchronous generator has been developed. In [4] the dynamic
voltage swell; PQ control; V/f control performance of preplanned islanding and fault-triggered
islanding of a microgrid which includes a conventional rotating
I. INTRODUCTION synchronous machine and a inverter-based DG is investigated.
With the development of distributed generation In [9], impacts of different control schemes of the inverter-
technologies, microgrids are introduced. A microgrid is based DG and microgrid load types on the microgrid stability
technically a small scale power system capable of autonomous subsequent to fault-forced islanding are investigated. Voltage
operation when islanded from main grid. Islanding is sags/swells can be observed moreorless from the voltage
performed to disconnect the microgrid from a faulty waveform of above literatures but few investigations are
distribution network to safeguard the components of microgrid carried out.
from upstream disturbances and allow an uninterrupted supply
This paper emphasizes the transient voltage sags/swells
of loads. It is also performed to protect voltage sensitive loads
during preplanned and unplanned islanding conditions of
from significant voltage drops when a quick solution to main
microgrid. The microgrid includes three DGs: a diesel
grid voltage problems is not available[1].
synchronous generator, an inverter-based PV system and a
A microgrid can operate under two different conditions[2]: inverter-based battery storage system. Master-slave control
scheme is adopted with the storage system and diesel generator
Ь Grid-connected Mode – the microgrid is connected to a operated to maintain the voltage and frequency. The PV system
main grid being either partially supplied from it or injecting is operated in MPPT mode. And the battery system is operated
some amount of power into it; by a PQ controller in grid-connected mode and by a V/f
Ь Islanded Mode – the microgrid operates autonomously controller in islanded mode. Matlab/Simulink is adopted to
when the disconnection from the upstream MV network occurs. model the microgrid under study. The voltage transients in
several scenarios of the microgrid are investigated.
In grid-connected mode, the main grid serves as an infinite
bus with unlimited power supply or demand, enables The paper is organized as follows. In Section II, the
mitigating power mismatches in the microgrid by power configure and control scheme of the studied microgrid system
transfer from or to the main grid. When the microgrid is is introduced. In Section III, the cause of voltage sags/swells
connected to the distribution system, the controllable during microgrid islanding is analyzed. Section IV describes
distributed energy resources (DER) are usually controlled by a the specifics of the Matlab/Simulink model of the study system.
constant power (PQ) controller. Once the microgrid is In Section V the transient analysis of the mode transition is
disconnected from the main gird, at least one DER must serve conducted and results of the study are reported. Conclusions
to keep the voltage and frequency right. The droop controller are stated in Section VI.
or the V/f controller is employed to maintain the voltage and
Supported by Shaanxi Special Foundation of Provincial Key Discipline

978-1-4673-8644-9/16/$31.00 2016
c IEEE 2317
II. MICROGRID CONFIGURATION AND CONTROL STRATEGY kiP
idref = (k pP + )( Pref − P)
s
A. Micro-grid configuration
kiQ
The micro-grid considered in this paper as shown in Fig.1 iqref = (k pQ + )(Qref − Q )
is a simple system with a battery energy storage system, a s (2)
diesel synchronous generator and a PV system. The load is The inverter output currents id and iq are compared with the
represented by a three-phase constant load with unity power references idref and iqref and regulated by a PI controller. To
factor. The PV system works in MPPT mode and the energy eliminate the interference of the coupling voltageɘ௣௟௟ ‫ܮ‬௦ ݅௤ and
storage serves to control voltage and frequency subsequent to
the output voltage vd, vq, the outputs of the current regulators
islanding. The synchronous generator is connected to the
vsd and vsq are obtained :
system after the micro-grid is islanded to maintain the voltage
and frequency. The micro-grid is connected to the utility grid at k ii
point of common coupling (PCC) bus. v sd = (k pi + )(idref − id ) − ω pll Ls iq + v d
s
k
v sq = (k pi + ii )(iqref − iq ) − ω pll Ls id + v q
s (3)
The control principle of V/f controller also consists of two
control loops. The current control loop is similar to the one of
PQ controller. The inner loop of the V/f controller is shown in
Fig. 4. In accordance with the setting reference of voltage and
frequency, the inverter terminal voltages are obtained by the
controller. idref and iqref are obtained from the V/f PI controller.

Fig. 1. Microgrid with multiple DERs.

B. Inverter Control Scheme of Battery Storage


The circuit diagram of the inverter-based battery energy
storage system is shown in Fig.2. There are three legs and L
filters in the ac side. The inverter of storage system needs to
switch its control strategies in response to the mode transition
of the micro-grid from PQ control strategy to V/f control
strategy.
(a) The PQ control loop

Fig. 2. Inverter topology


(b) The current control loop
The control principle of PQ controller is shown in Fig. 3. It
Fig. 3. Inverter PQ controller.
has a PQ regulate loop as shown in Fig.3(a) and an current
regulate loop as shown in Fig.3(b). The measured inverter
output voltage va, vb, vc and currents ia, ib, ic are transformed to
dq frame noted vd and vq, id and iq, respectively. The inverter
output active P and reactive power Q are calculated by:
P = v d id + v q i q
Q = v d id − v q i q
(1)
Fig. 4. The voltage control loop of V/f controller.
After compared with their references Pref and Qref, the
inverter dq reference currents idref and iqref are obtained through III. VOLTAGE SAGS/SWELLS
a PI controller: Voltage sags and swells are the most common types of
power-quality disturbances. Voltage sag is defined as a

2318 2016 IEEE 11th Conference on Industrial Electronics and Applications (ICIEA)
decrease in the root-mean-square (rms) value of an ac voltage TABLE I. PV MODULE PARAMETERS
between 0.1 and 0.9 p.u. of the nominal voltage ae at the power
frequency for durations of 0.5 cycles to 1 min [10]. The IEC Parameters(Unit) Value
defines this phenomenon as voltage dip [11]. Voltage sags and
swells are characterized by their duration, magnitude and phase Open-circuit voltage Uoc(V) 880
angle shift. Each type of equipment in the customer’s facility Short-circuit current Isc(A) 68.9
has different sensitivity to voltage sag. Once the severity of
voltage sag exceeds its sensitivity threshold, the equipment Maximum Power Point voltage Um(V) 700
may malfunction, which may result in substantial financial
losses [12]. Maximum Power Point current Im(A) 63.7

Short circuits, starting large motors, sudden changes of


load, and energization of transformers are the main causes of TABLE II. INVERTER CONTROLLER AND FILTER PARAMETERS
voltage sags [13]. In this paper voltage sags during and
subsequent to the islanding of microgrid with PV and energy Parameters Value
storage are investigated.
L filter 8 mH
The equivalent circuit of the studied microgrid is shown in
Fig.(5). In grid-connected mode, the inverter-based micro- Kip 100
sources controlled by PQ controllers can be modeled as a PQ controller of battery
controlled current source. In islanded mode it can be modeled Kii 0.001
as a controlled voltage source. storage system and VdcQ
KPp,KQp 2
controller of PV system
KPi,KQi 1000

Kip 10

V/f controller of energy Kii 2000

storage Kup 2

Kui 1000
Fig. 5. Equivalent circuit of the studied microgrid.

In the grid-connected mode, the PCC switch S1 is close and V. STUDY CASES
the option switch S2 is closed to 1. In the process of islanding Considering the diversity of microgrid operation
S1 is open at the time of disconnection from main grid noted as conditions, to be simplified, in the proposed microgrid system,
t1 and S2 is switched to 2 at the time of control scheme sufficient capacity should always be available, i.e. the load
transition from PQ to V/f noted as t2. In the case of unplanned requirement are assumed to be met by energy storage system in
islanding, during the period of t1 to t2, the unbalance of the a short term run and by diesel in a long term run. Besides, the
source power and the load requirement will cause voltage rise over/under voltage protection and over/under frequency
or drop. And after t2, the switch of S2 which lead to the protection of DGs are not discussed nor considered in this
parallel of two sources will introduce impulse in most cases. paper.
That is to say, there will be voltage sags/swells at t1 and t2.
Several case studies are conducted to examine the system
IV. STUDY SYSTEM MODEL voltage transients during the transition from grid-connected
mode to islanded mode. For every case, both preplanned and
To investigate the transition transients of micro-grid, the unplanned islanding are simulated. For preplanned islanding,
electromagnetic transients of the system are simulated in the the microgrid system shown in Fig. 1 is isolated from the main
environment of Matlab/Simulink. grid without any fault or grid disturbances, at 0.24s by simply
The component models used for the simulation are as opening CB1, with the control mode switched simultaneously.
follows. The main grid is represented by a 380V three-phase Then, the behavior of the microgrid during unplanned islanding
voltage source with the short-circuit capacity of 1000 MVA is discussed. CB1 open at 0.16s and the control scheme
and X/R ratio of 10. Load are modeled as constant power loads changes at 0.24s. And the synchronous generator is started at
with unity power factor. For the micro-grid under study, the 0.4s. In this paper, the unplanned islanding is supposed to be
synchronous DG is simulated by the standard synchronous caused by protection subsequent to a short circuit fault of the
machine model listed in the Matlab/SimPower library. main grid near PCC or by other operations without short circuit
Machine parameters, the diesel engine governor model and the fault. Several scenarios with various sunshine intensity and
excitation system are the same as that in [9].The model of PV load power are investigated. The load varies from 13kW,
module for simulation is built using the method given in [14]. 23kW, 33kW to 43kW; the sunshine intensity S varies from
The parameters of PV panels are listed in Table 1. The 100W/m2, 500W/m2 to 1000W/m2. The voltage waveform of
parameters of inverter topology and controller are listed in PCC bus of preplanned islanding, unplanned islanding without
Table 2. ground fault are simulated and the results are presented. The

2016 IEEE 11th Conference on Industrial Electronics and Applications (ICIEA) 2319
voltage waveform of PCC bus of preplanned and unplanned
1.5
islanding are shown respectively in Fig.6-Fig.9. S=100W /m2
S=500W /m2
S=1000W /m2
1.5
S=100W /m2
S=500W /m2
S=1000W /m2 1

U (p.u.)
1
U (p.u.)

0.5

0.5

0
0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
t(s)

0
0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 (b) Unplanned islanding without ground fault.
t(s)
Fig.6. Voltage amplitude when load power is 23kW..
(a) Preplanned islanding.
1.5
S=100W /m2
1.5
S=500W /m2
S=100W /m2
S=1000W /m2
S=500W /m2
S=1000W /m2

1
U (p.u.)
U (p.u.)

0.5

0.5

0
0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
0 t(s)
0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
t(s)
(a) Preplanned islanding.
(b) Unplanned islanding without ground fault.
1.5
Fig.6. Voltage amplitude when load power is 13kW.
S=100W /m2
S=500W /m2
1.5 S=1000W /m2
S=100W /m2
S=500W /m2
S=1000W /m2 1
U (p.u.)

1
U (p.u.)

0.5

0.5

0
0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
t(s)

0
0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 (b) Unplanned islanding without ground fault.
t(s)
Fig.7. Voltage amplitude when load power is 33kW..
(a) Preplanned islanding.

2320 2016 IEEE 11th Conference on Industrial Electronics and Applications (ICIEA)
VI. CONCLUSIONS
1.5
S=100W /m2 The transient voltage sags/swells subsequent to unplanned
S=500W /m2 islanding of a PV-BESS microgrid are investigated based on
S=1000W /m2
the electromagnetic transient simulations of matlab/Simulink.
The cases under study illustrated that the severity of voltage
1 sags/swells is affected by the output of sources, the load
demand, the cause of islanding and the islanding detection time.
U (p.u.)

REFERENCES
[1] R. H. Lasseter and P. Piagi. “MicroGrid: a conceptual solution,” Power
0.5 Electronics Specialists Conference, IEEE 35th Annual, Germany, p.
4285-4290, 2004.
[2] J. Stevens, H. Vollkommer, and D. Klapp. “CERTS MicroGrid system
tests,” IEEE Power Engineering Society General Meeting, USA,
p.4275559, 2007.
0 [3] C. K. Sao, and P. W. Lehn. “Intentional islanded operation of converter
0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
t(s) fed microgrids,” IEEE Power Engineering Society General Meeting,
Canada, p.1, 2006.
(a) Preplanned islanding. [4] F. Katiraei, M. R. Iravani, and P. W. Lehn. “Micro-Grid autonomous
operation during and subsequent to islanding process,” IEEE Trans. On
Power Delivery, vol. 20, pp. 248-257, January 2005.
1.5
S=100W /m2 [5] Meegahapola, L.G.; Robinson, D.; Agalgaonkar, A.P.; Perera, S.; Ciufo,
S=500W /m2 P., "Microgrids of Commercial Buildings: Strategies to Manage Mode
S=1000W /m2 Transfer From Grid Connected to Islanded Mode," IEEE Trans. on
Sustainable Energy, vol.5, no.4, pp.1337-1347, Oct. 2014
[6] Shahabi, M.; Haghifam, M.-R.; Mohamadian, M.; Nabavi-Niaki, S.A.,
1 "Microgrid Dynamic Performance Improvement Using a Doubly Fed
Induction Wind Generator," IEEE Trans. on Energy Conversion, vol.24,
U (p.u.)

no.1, pp.137-145, March 2009.


[7] Katiraei, F.; Iravani, M.R.; Lehn, P.W.;, "Small-signal dynamic model
of a micro-grid including conventional and electronically interfaced
0.5 distributed resources," Generation, Transmission & Distribution, IET,
vol.1, no.3, pp.369-378, May 2007
[8] Dong-Jing Lee; Li Wang;, "Small-Signal Stability Analysis of an
Autonomous Hybrid Renewable Energy Power Generation/Energy
Storage System Part I: Time-Domain Simulations," Energy Conversion,
IEEE Transactions on, vol.23, no.1, pp.311-320, March 2008
0
0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 [9] Kasem Alaboudy, A.H.; Zeineldin, H.H.; Kirtley, J.L., "Microgrid
t(s) Stability Characterization Subsequent to Fault-Triggered Islanding
Incidents," IEEE Trans. on Power Delivery, vol.27, no.2, pp.658-669,
(b) Unplanned islanding without ground fault. April 2012.
Fig.8. Voltage amplitude when load power is 43kW.. [10] IEEE Recommended Practice for Evaluating Electric Power System
Compatibility With Electronic Process Equipment, IEEE Standard 1346-
From the results above, for preplanned islanding of all the 1998, 1998.
scenarios, the microgrid can switch smoothly with slight [11] Electromagnetic Compatibility (EMC): Testing and Measurement
fluctuation. Techniques-Voltage Dips, Short Interruptions and Voltage Variations
Immunity Tests, IEC Standard 61000-4-11, Mar. 2004.
For the unplanned islanding caused by switch process [12] M. McGranaghan, D. Mueller, and M. Samotyj, “Voltage sags in
without fault near PCC bus, the microgrid will suffer voltage industrial systems,” IEEE Trans. Ind. Appl., vol. 29, no. 2, pp. 397–403,
sags or voltage swells at two moments: i) after the Mar./Apr. 1993.
disconnection from the main grid because of the power [13] Heine, Pirjo; Lehtonen, M., "Voltage sag distributions caused by power
system faults," IEEE Transactions on Power Systems, vol.18, no.4,
mismatch of the sources and loads; ii) after the control mode is pp.1367-1373, Nov. 2003
switched from PQ control to V/f control. Concerning the
[14] Sun Ziyong, Yu Hang, Yan Gangui, Li Junhui, Chen Wei, " PSCAD
former, voltage sags occur because the power of sources simulation models for photovoltaic array and MPPT controller," Power
cannot meet the demand of the loads while voltage swell System Protection and Control, vol.37, no.19, pp.61-64, Oct. 2009
occurs because the power of sources exceeds the demand of the
loads. And the latter is caused by parallel connection of two
voltage resources.

2016 IEEE 11th Conference on Industrial Electronics and Applications (ICIEA) 2321

You might also like