Professional Documents
Culture Documents
01/24/2023 11:11:42
PAGE 1
Nameplate Data
MANUFACTURER: SEL MODEL: 387E TEST STATUS: Pass
Asset ID: SERIAL NUMBER: 1213267167 DATASHEET: 0387E014X5H4X45
SUBSTATION PT RATIO: kV : V Counter Clockwise Rotation +/-180
LZOP: CT RATIO: :5 A Earthing L->N JOB #:
PROTECTION: PPTR1 RELAY FIRMWARE:
138 kV 13,8 kV
50 MVA
600 :5 A 2.500 :5 A
209,185 A 2.091,85 A
I0 elimination
DYn1 (disabled)
1,74 A 4,18 A
Single Phase Single Phase
Pickup Factor Interposing CTs 1,73 Pickup Factor
1,00
W1 W2 W1 W2
Irestraint Ioperate
I (A) ϕ (°) I (A) ϕ (°) I (A) ϕ (°) I (A) ϕ (°)
1,743 0 4,184 150
A-N 208,90 0 2.093,8 150 2 0
209,18 0 2.091,8 150
1,743 -120 4,184 30
B-N 209,00 -120,2 2.096,7 30,1 2 0
209,18 -120 2.091,8 30
1,743 120 4,184 -90
C-N 208,80 119,9 2.090,4 89,8 2 0
209,18 120 2.091,8 -90
Winding 1 Winding 2
Phase
Pickup Pickup
Pickup Pickup Error P/F Pickup Pickup Error P/F
Setting Setting
(Pu) (A) (%) (Pu) (A) (%)
(pu) (pu)
Winding 1 Winding 2
Pickup = 0,261A , Tolerance = 10% Pickup = 0,628A , Tolerance = 10%
Phase
Winding 1 Winding 2
Fundamental Current = 0,000A Fundamental Current = 0,000A
Phase
Overcurrent Settings
Fases
Manufacturer: SEL Model: All
Curve: Pickup: 2,00 A Inst: 13,25 A 2nd Inst: 0,00 A Reset: 1,00 (s)
C2 - IEC Very Inverse Mult: 0,340 Delay: 0,01 (s) 2nd Delay: 0,00 (s)
Neutro
Manufacturer: SEL Model: All
Curve: Pickup: 0,50 A Inst: 4,00 A 2nd Inst: 0,00 A Reset: 1,00 (s)
C1 - IEC Standard Inverse Mult: 0,050 Delay: 0,01 (s) 2nd Delay: 0,00 (s)
50GS
Manufacturer: IEC Model: All
Curve: I>: 0,80 A I>>: 0,00 A I>>>: 0,00 A Reset: 1,00 (s)
Definite Time Mult: 3,000 (s) tI>>: 0,00 (s) tI>>>: 0,00 (s)
A B C
Multiple
N
Multiple
3,020
2 3,00 2,400 2,850 3,000 3,150 0,66% P
3,012
3 5,00 4,000 2,850 3,000 3,150 0,41% P