Effectivity Date

Operations & Maintenance Management Department


21 October 2022
Metering Assets and Services Management Division
Page _1_ of _2_
CURRENT TRANSFORMER TEST DATA
Test Data No. CT-VISA-D2-23-02011 Reference No.
Metering Installation Specialty Pulp Manufacturing Inc. Reason For Tests:
SEIL ORMSPMI01 Preventive Maintenace
Date of Test May 29, 2023 Corrective Maintenance
Weather Cloudy Technical Assistance
Amb. Temp 28 °C Others (Pls. specify)

SPECIFICATIONS:
Manufacturer: Crompton Greaves Crompton Greaves Crompton Greaves
Model: CT 72.5/140/350 kV CT 72.5/140/350 kV CT 72.5/140/350 kV
Serial no. 30551 30552 30550
Class: 0.3 0.3 0.3
Rated Burden: No data No data No data
CTR: 50 : 5 A 50 : 5 A 50 : 5 A
No of Core: 2 cores 2 cores 2 cores
Rating Factor : No data No data No data
Frequency 60 Hz 60 Hz 60 Hz
BIL: 72.5/140/350 kV 72.5/140/350 kV 72.5/140/350 kV
Insulating Medium: Porcelain Porcelain Porcelain
Standard: ANSI C57.13 2003 ANSI C57.13 2003 ANSI C57.13 2003
Year Manufactured: 2003 2003 2003
NGCP PO No.: N/A N/A N/A

I. INSULATION POWER FACTOR TEST


TEST CURRENT % POWER FACTOR CAPACITANCE RATING
PHASE SERIAL NO. PARTS MEASURED WATTS
kV mA Measured Corrected pF (S, P, C)

A 30551 N/A N/A N/A N/A N/A N/A N/A N/A


B 30552 N/A N/A N/A N/A N/A N/A N/A N/A
C 30550 N/A N/A N/A N/A N/A N/A N/A N/A

Remarks: Not yet due for 15-year maintenance test.

II. INSULATION RESISTANCE TEST


TEST MEASURED RESISTANCE RATING
PHASE SERIAL NO. PARTS MEASURED M Ω/kV
kV MΩ (S,P,C)

Primary - Ground 10 kV 214,000 3,101 S


Primary - Secondary(X) 10 kV 227,000 3,290 S
Primary - Secondary(Y) 10 kV 145,000 2,101 S
Primary - Secondary(X,Y) 10 kV 257,000 3,725 S
A 30551
Secondary(X) - Ground 0.5 68 68 S
Secondary(Y) - Ground 0.5 79 79 S
Secondary(X) - Secondary(Y) 0.5 124 124 S
Secondary(X,Y) - Ground 0.5 39 39 S
Primary - Ground 10 kV 183,100 2,654 S
Primary - Secondary(X) 10 kV 135,000 1,957 S
Primary - Secondary(Y) 10 kV 254,000 3,681 S
Primary - Secondary(X,Y) 10 kV 185,000 2,681 S
B 30552
Secondary(X) - Ground 0.5 58 58 S
Secondary(Y) - Ground 0.5 92 92 S
Secondary(X) - Secondary(Y) 0.5 141 141 S
Secondary(X,Y) - Ground 0.5 35 35 S
Primary - Ground 10 kV 75,900 1,100 S
Primary - Secondary(X) 10 kV 1,343,000 19,464 S
Primary - Secondary(Y) 10 kV 260,000 3,768 S
Primary - Secondary(X,Y) 10 kV 1,528,000 22,145 S
C 30550
Secondary(X) - Ground 0.5 55 55 S
Secondary(Y) - Ground 0.5 77 77 S
Secondary(X) - Secondary(Y) 0.5 124 124 S
Secondary(X,Y) - Ground 0.5 32 32 S
Limiting Criteria: MegaOhms/kV New(10MΩ/kV min.) In-Service (2 MΩ/kV min.)

Remarks: Satisfactory results & recommended for continuous operation.

III- a. CURRENT TRANSFORMATION RATIO TEST


PRIMARY/
% Rated COMPUTED PHASE RATING
PHASE SERIAL NO. TAP/CONNECTIONS SECONDARY MEASURED % ERROR
Current RATIO ANGLE (S, P, C)
CURRENT
1% N/A N/A N/A N/A N/A N/A

5% N/A N/A N/A 0.05 N/A N/A

20% N/A N/A N/A N/A N/A N/A N/A

100% N/A N/A N/A N/A N/A N/A

A 30551 RF*100% N/A N/A N/A N/A N/A N/A


1% N/A N/A N/A N/A N/A N/A
5% N/A N/A N/A 0.05 N/A N/A
20% N/A N/A N/A N/A N/A N/A N/A
100% N/A N/A N/A N/A N/A N/A
RF*100% N/A N/A N/A N/A N/A N/A
Note: For IEC 1%, 5%, 20%, 100%, RF*100%; For ANSI/IEEE, 5%, 10%, 100%, RF*100%
Effectivity Date
Operations & Maintenance Management Department
21 October 2022
Metering Assets and Services Management Division
Page _2_ of _2_
CURRENT TRANSFORMER TEST DATA
Note: For IEC 1%, 5%, 20%, 100%, RF*100%; For ANSI/IEEE, 5%, 10%, 100%, RF*100%
III- b. CURRENT TRANSFORMATION RATIO TEST
PRIMARY/
% Rated COMPUTED PHASE RATING
PHASE SERIAL NO. TAP/CONNECTIONS SECONDARY MEASURED % ERROR
Current RATIO ANGLE (S, P, C)
CURRENT
1% N/A N/A N/A N/A N/A N/A
5% N/A N/A N/A 0.05 N/A N/A
20% N/A N/A N/A N/A N/A N/A N/A
100% N/A N/A N/A N/A N/A N/A
RF*100% N/A N/A N/A N/A N/A N/A
B 30552
1% N/A N/A N/A N/A N/A N/A
5% N/A N/A N/A 0.05 N/A N/A
20% N/A N/A N/A N/A N/A N/A N/A
100% N/A N/A N/A N/A N/A N/A
RF*100% N/A N/A N/A N/A N/A N/A
Note: For IEC 1%, 5%, 20%, 100%, RF*100%; For ANSI/IEEE, 5%, 10%, 100%, RF*100%
Note: For IEC 1%, 5%, 20%, 100%, RF*100%; For ANSI/IEEE, 5%, 10%, 100%, RF*100%
III- c. CURRENT TRANSFORMATION RATIO TEST
PRIMARY/
% Rated COMPUTED PHASE RATING
PHASE SERIAL NO. TAP/CONNECTIONS SECONDARY MEASURED % ERROR
Current RATIO ANGLE (S, P, C)
CURRENT
1% N/A N/A N/A N/A N/A N/A
5% N/A N/A N/A 0.05 N/A N/A
20% N/A N/A N/A N/A N/A N/A N/A
100% N/A N/A N/A N/A N/A N/A
RF*100% N/A N/A N/A N/A N/A N/A
C 30550
1% N/A N/A N/A N/A N/A N/A
5% N/A N/A N/A 0.05 N/A N/A
20% N/A N/A N/A N/A N/A N/A N/A
100% N/A N/A N/A N/A N/A N/A
RF*100% N/A N/A N/A N/A N/A N/A
Note: For IEC 1%, 5%, 20%, 100%, RF*100%; For ANSI/IEEE, 5%, 10%, 100%, RF*100%
Remarks: Not yet due for 15-year maintenance test.

IV. CURRENT CIRCUIT BURDEN MEASUREMENT


MEASURED BURDEN (VA)
Core
Phase A Phase B Phase C
X1-X2-X3 N/A N/A N/A
Y1-Y2-Y3 N/A N/A N/A

V. CURRENT TRANSFORMER SECONDARY BOX SEALS


Phase A Phase B Phase C Others
AS FOUND: 000454 000455 000456 N/A
AS LEFT: MFM-23-6186 MFM-23-6187 MFM-23-6188 N/A
Overall Remarks:
Satisfactory test results & recommended for continuous operation.

Tested by : Concurred by:

EJBaac / JLInot / JEVergara Rey Florito


Engineer/Technician Customer Representative

Checked by :

ERWIN C. NOBLE
MFM Supervisor

TEST INSTRUMENTS: Legend:

Megger/S1-1068 10 kV S - Satisfactory
(Eqpt.ID/Make/Model/SN/
Date of last calibration) 101670135 P - Poor
August 10, 2022 C - Critical

Form No.: FM-OM-OMMD-04


Form Revision No.: 00
Effectivity Date: 21 October 2022
Effectivity Date
Operations & Maintenance Management Department
21 October 2022
Metering Assets and Services Management Division
Page _1_ of _2_
VOLTAGE TRANSFORMER TEST DATA
Test Data No. PT-VISA-D2-23-02011 Reference No.
Metering Installation Specialty Pulp Manufacturing Inc. Reason For Tests:
SEIL ORMSPMI01 Preventive Maintenace
Date of Test May 29, 2023 Corrective Maintenance
Weather Cloudy Technical Assistance
Amb. Temp 28 °C Others (Pls. specify)

SPECIFICATIONS:
Manufacturer: Crompton Greaves Crompton Greaves Crompton Greaves
Model: PT 72.5/140/350 kV PT 72.5/140/350 kV PT 72.5/140/350 kV
Serial no. 30549 30547 30548
Class: 0.3 0.3 0.3
Rated Burden: No data No data No data
VTR: 69000/1.732 : 115/1.732 V 69000/1.732 : 115/1.732 V 69000/1.732 : 115/1.732 V
No of Core: 2 cores 2 cores 2 cores
Rating Factor : No data No data No data
Frequency 60 Hz 60 Hz 60 Hz
BIL: 72.5/140/350 kV 72.5/140/350 kV 72.5/140/350 kV
Insulating Medium: Porcelain Porcelain Porcelain
Standard: IEC 60044.2 IEC 60044.2 IEC 60044.2
Year Manufactured: 2003 2003 2003
NGCP PO No.: N/A N/A N/A

I. INSULATION POWER FACTOR TEST


TEST CURRENT % POWER FACTOR CAPACITANCE RATING
PHASE SERIAL NO. PARTS MEASURED WATTS
kV mA Measured Corrected pF (S, P, C)

A 30549 N/A N/A N/A N/A N/A N/A N/A N/A


B 30547 N/A N/A N/A N/A N/A N/A N/A N/A
C 30548 N/A N/A N/A N/A N/A N/A N/A N/A

Remarks: Not yet due for 15-year maintenance test.

II. INSULATION RESISTANCE TEST


TEST MEASURED RESISTANCE RATING
PHASE SERIAL NO. PARTS MEASURED MΩ/kV
kV MΩ (S,P,C)

Primary - Ground 10 kV 5,530 80.1 S


Primary - Secondary(1a) 10 kV 71,300 1,033 S
Primary - Secondary(2a) 10 kV 166,000 2,406 S
Primary - Secondary(1a,2a) 10 kV 113,500 1,645 S
A 30549
Secondary(1a) - Ground 0.5 458 458 S
Secondary(2a) - Ground 0.5 505 505 S
Secondary(1a) - Secondary(2a) 0.5 2,780 2,780 S
Secondary(1a,2a) - Ground 0.5 262 262 S
Primary - Ground 10 kV 1,717 24.9 S
Primary - Secondary(1a) 10 kV 270,000 3,913 S
Primary - Secondary(2a) 10 kV 237,000 3,435 S
Primary - Secondary(1a,2a) 10 kV 221,000 3,203 S
B 30547
Secondary(1a) - Ground 0.5 226 226 S
Secondary(2a) - Ground 0.5 191 191 S
Secondary(1a) - Secondary(2a) 0.5 738 738 S
Secondary(1a,2a) - Ground 0.5 116 116 S
Primary - Ground 10 kV 3,200 46.4 S
Primary - Secondary(1a) 10 kV 464,000 6,725 S
Primary - Secondary(2a) 10 kV 794,000 11,507 S
Primary - Secondary(1a,2a) 10 kV 170,000 2,464 S
C 30548
Secondary(1a) - Ground 0.5 143 143 S
Secondary(2a) - Ground 0.5 266 266 S
Secondary(1a) - Secondary(2a) 0.5 1,921 1,921 S
Secondary(1a,2a) - Ground 0.5 95 95 S
Limiting Criteria: MegaOhms/kV New(10MΩ/kV min.) In-Service (2 MΩ/kV min.)

Remarks: Satisfactory results & recommended for continuous operation.


Effectivity Date
Operations & Maintenance Management Department
21 October 2022
Metering Assets and Services Management Division
Page _2_ of _2_
VOLTAGE TRANSFORMER TEST DATA
III. POTENTIAL TRANSFORMATION RATIO TEST
TAP / PRIMARY/ COMPUTED PHASE RATING
PHASE SERIAL NO. MEASURED % ERROR
CONNECTIONS SECONDARY RATIO ANGLE (S, P, C)
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
A 30549
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
B 30547
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
C 30548
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A

Remarks: Not yet due for 15-year maintenance test.

IV. VOLTAGE CIRCUIT BURDEN MEASUREMENT


MEASURED BURDEN (VA)
Core
Phase A Phase B Phase C
X1-X2 N/A N/A N/A

V. VOLTAGE TRANSFORMER SECONDARY BOX SEALS


Phase A Phase B Phase C Others
AS FOUND: 000457 000458 000459 N/A
AS LEFT: MFM-23-6338 & 6349 MFM-23-6380 & 6383 MFM-23-6387 & 6394 N/A
Overall Remarks:
Satisfactory test results & recommended for continuous operation.

Tested by : Concurred by:

EJBaac / JLInot / JEVergara Rey Florito


Engineer/Technician Customer Representative

Checked by :

ERWIN C. NOBLE
MFM Supervisor Legend:
S - Satisfactory
TEST INSTRUMENTS: P - Poor
(Eqpt.ID/Make/Model/SN/
Megger/S1-1068 10 kV C - Critical
Date of last calibration)
101670135
August 10, 2022
Form No.: FM-OM-OMMD-03
Form Revision No.: 00
Effectivity Date: 21 October 2022
Effectivity Date:
Operations & Maintenance Management Department January 01, 2021
Metering Assets and Services Management Division
Page 1 of 1

LIGHTNING ARRESTER TEST DATA


Test Data No. LA-VISA-D1-23-02011 Reference No. MO no
Metering Installation Specialty Pulp Manufacturing Inc. Reason For Tests:
SEIL ORMSPMI01 Preventive Maintenace
Date of Test May 29, 2023 Corrective Maintenance
Weather Cloudy Technical Assistance
Amb. Temp 28 °C Others (Pls. specify)

SPECIFICATIONS:
Manufacturer: Crompton Greaves Crompton Greaves Crompton Greaves
Model: ZLAx50 ZLAx50 ZLAx50
Serial no. 25809 25810 25811
Discharge Current: 10 kA 10 kA 10 kA
Discharge Class: Class 2 Class 2 Class 2
MCOV Rating: 51 MCOV 51 MCOV 51 MCOV
Rated Voltage: 60 kV 60 kV 60 kV
Frequency: 60 Hz 60 Hz 60 Hz
Insulating Material: Porcelain Porcelain Porcelain
Year Manufactured: 2003 2003 2003
Customer's P.O. N/A N/A N/A

I. INSULATION RESISTANCE TESTS

TEST MEASURED RATING


PHASE SERIAL NO. PARTS MEASURED RESISTANCE MΩ/kV
kV (S, P, C)

A 25809 Primary - Ground 10 18,400 267 S
B 25810 Primary - Ground 10 24,000 348 S
C 25811 Primary - Ground 10 110 2 S

Remarks: Satisfactory test results.

II. INSULATION POWER FACTOR TESTS


PARTS TEST CURRENT % POWER FACTOR CAPACITANCE RATING
PHASE SERIAL NO. WATTS
MEASURED kV mA Measured Corrected pF (S, P, C)

A N/A N/A N/A N/A N/A N/A N/A N/A N/A


B N/A N/A N/A N/A N/A N/A N/A N/A N/A
C N/A N/A N/A N/A N/A N/A N/A N/A N/A

Remarks:

Overall Remarks: Satisfactory test results & recommended for continuous operation.

Tested by : Concurred by:

EJBaac / JLInot / JEVergara Rey Florito


Engineer/Technician Customer

Checked by :

ERWIN C. NOBLE
MFM Supervisor

Test Instruments: Legend:


(Eqpt.ID/Make/Model/SN/ Megger S1-1068, 10 kV / 101670135 S - Satisfactory
Date of last calibration) August 10, 2022 C - Critical
P - Poor

FM-OM-03A8 Rev.1