Date Issued:

20 Jan 2021

WIR/MIR Ref. No.:

Ref. ITP : Drawing No: Date of Inspection:

Checklist Ref. No.: ELECT-TIC-2.6

MV Power Cable Continuity and Insulation Resistance Test


Work Location:

Contractor Consultant
Description Inspector Inspector Remarks
Yes No N/A Yes No N/A

MV Power Cable Continuity and Insulation Resistance


A
Test
Testing is to be carried out ONLY on de-energized cables. MV
1 Cables shall be tested for their de-energized state before starting
test on them

Inspect MV cable for crimping and proper connection in


2
accordance with schematic diagram.

Perform continuity test of each core of cable drum to ensure no


3
conductor is broken with certified and calibrated Ohm-meter.

All MV Cables should be left grounded when not on test, during the
4
testing of other Cable, until completely discharged.

If MV cable ends are exposed for testing, they shall be re-sealed


5 (water and dust-proof seals) and firmly secured when not
terminated

Test shall be performed using an Insulation Resistance Test Set


6
(Megohmeter) 5000 V dc minimum.
WIR/MIR Ref No:

Ref. ITP : Drawing No: Date of Inspection:

Check List Ref No: ELECT-TIC-2.6

MV Power Cable Continuity and Insulation Resistance Test

Work Location: Contractor Consultant


Remarks

Description Inspector Inspector

Yes No N/A Yes No N/A REMARKS

Minimum insulation-resistance values should not be less than 50


7 megohms.
NETA ATS - 2009, 7.3.2.3.2.2

Investigate deviations between adjacent phases.


8
NETA ATS - 2009, 7.3.2.3.2.4

Consult cable manufacturer's published data for acceptable test results.


If published data is not available, investigate any values which deviate
9
from previous test results under similar conditions by more than 50% of
the lowest value. (NETA ATS 2009, Sec. 7.3.3.3.2)

Test Equipment Manufacturer: Serial Number:

Scale Range and accuracy: Calibration date:

Calibration Company and Technician: Calibration Expiration Date:

C TEST RESULTS

Cable Reel/PC Number Cable type Cable length Shield Resistance (Ω) Fail Re-Test Date

Test Voltage level__________ Humidity____________ Temperature_______________ Time/Date of Test____________

Temp.
MEASURED INSULATION RESISTANCE (MΩ)
Adjusted
Cable
Insulation Pass Fail Re-Test date
Reel #
Resistance R-Y Y-B B-R R-N Y-N B-N R-G Y-G B-G N-G
(MΩ)

REMARKS:

CONTRACTOR MEP QC INSPECTOR CONSULTANT

Name Name Name Name

Title Title Title Title

Signature Signature Signature Signature

Date Date Date Date

Page 2 of 3
Attachement-01(IR & Continuity Form)

A.Field Test Data

Cable Megger
Cable
Cable Size Cable Type Voltage CONNECTION Results in
Identity
Rating Megohms

A-B, to C & GRD


B-A, to C & GRD
C-A, to B & GRD
A-B, to C & GRD
B-A, to C & GRD
C-A, to B & GRD
A-B, to C & GRD
B-A, to C & GRD
C-A, to B & GRD
A-B, to C & GRD
B-A, to C & GRD
C-A, to B & GRD
A-B, to C & GRD
B-A, to C & GRD
C-A, to B & GRD
A-B, to C & GRD
B-A, to C & GRD
C-A, to B & GRD
A-B, to C & GRD
B-A, to C & GRD
C-A, to B & GRD
A-B, to C & GRD
B-A, to C & GRD
C-A, to B & GRD
A-B, to C & GRD
B-A, to C & GRD
C-A, to B & GRD
A-Neutral
B-Neutral
C-Neutral
Neutral-Ground

B CONTINUITY/PHASING CHECK

PHASE MEGGER(1KV) PHASING CHECK


CONDUCTOR TO GROUND SEQUENCE VOLTAGE REMARKS
A
B
C
A-N
B-N
C-N
N-G

Applied Voltage for Phasing Check:


Instrument:
Make :
Model/S.No
Calibration