TEST DATA
Make Siemens
A. MECHANICAL RUNDOWN
OPERATING TIME (milli - sec) MISMAT
MODE OF OPERATION RATING (S, P, C)
CH TIME
MISMAT
MODE OF OPERATION RATING (S, P, C)
PHASE A PHASE B PHASE C CH TIME
TRIP 1 27.3ms 27.4ms 27.4ms 0.1ms S
TRIP 2 27.5ms 27.7ms 27.6ms 0.2ms S
CLOSE 63.3ms 63.0ms 62.9ms 0.4ms S
Remarks: MV CB Timing Test shall have an Opening Time equal to 1- 2 cycles ( 20-40ms) and closing time equal to 2-5 cycles( 40-100ms
The exact operation time of circuit breaker is provided by the manufacturer. It can be mentioned on the nameplate of the circuit b
The results were found satisfactorily and passed the ANSI / NETA - ats - 2017 standards. The contractor
Overall Remarks:
recommends conduction annual preventive maintenance of the equipment to maintain its good working condition.
TEST INSTRUMENT:
(Eqpt.ID/Make/Model/SN/ Circuit Breaker Analyzer Legend:
Date of last calibration) Quadrant QCBT-1 S - Satisfactory
67092018a P - Poor
Calibration Date: February 9, 2021 C - Critical
Witnessed By:
TEST DATA
Make Siemens
A.MODE
MECHANICAL RUNDOWN
OF OPERATING TIME (milli - sec) MISMAT
RATING (S, P, C)
OPERATIPHASE A PHASE B PHASE C CH TIME
ON
TRIP 1 26.7ms 26.2ms 26.5ms 0.4ms S
TRIP 2 29.1ms 28.6ms 28.9ms 0.5ms S
CLOSE 63.4ms 63.8ms 63.4ms 0.4ms S
RemarkMV CB Timing Test shall have an Opening Time equal to 1- 2 cycles ( 20-40ms) and
The exact operation time of circuit breaker is provided by the manufacturer. It can b
The results were found satisfactorily and passed the ANSI / NETA - ats - 2017
Overall Re standards. The contractor recommends conduction annual preventive
maintenance of the equipment to maintain its good working condition.
TEST INSTRUM
Make/
Circuit Breaker Analyzer Legend:
Model/
SN/Date
of last Quadrant QCBT-1 S - Satisfactory
calibration
67092018a P - Poor
Calibration Date: February 9, 2021 C - Critical
TEST DATA
Make Siemens
Remarks: MV CB Timing Test shall have an Opening Time equal to 1- 2 cycles ( 20-40ms) and closing time equal to 2-5 cycles( 40-1
The exact operation time of circuit breaker is provided by the manufacturer. It can be mentioned on the nameplate of the circ
The results were found satisfactorily and passed the ANSI / NETA - ats - 2017 standards. The contractor recommends
Overall Remarks:
conduction annual preventive maintenance of the equipment to maintain its good working condition.
TEST INSTRUMENT:
Circuit Breaker Analyzer Legend:
(Eqpt.ID/Make/
Model/SN/Date of
last calibration) Quadrant QCBT-1 S - Satisfactory
67092018a P - Poor
Calibration Date: February 9, 2021 C - Critical
Witnessed by: