GAS CIRCUIT BREAKER TEST DATA


1 of 2

TEST DATA

Test Data No Module type:

Station 40MW Magapit BESS Facility "I" (live-tank)

Equipment ID Gas Circuit Breaker "Y" (live-tank)

Date of Test August 22,2021 "V" (dead-tank)

Make Siemens

Serial No 35154890A Operating Mechanism:

Type 3AP1FG Spring

Rated kV 72.5KV Pneumatic

Interrupting Capacity, kA 40KA Hydraulic

Year Manufactured 2020a

I. INSULATION RESISTANCE TESTS


TEST MEASURED RATING
BREAKER POSITION PHASE PARTS MEASURED RESISTANCE Mჲ/kV
kV Mჲ (S, P, C)

A POLE 1 - POLE 3 5KV 2577000a 515400a S

B POLE 3 - POLE 4 5KV 2855000a 571000a S

C POLE 5 - POLE 6 5KV 2578000a 515600a S

A POLE 1/2 - GND 5KV 1310000a 262000a S

CLOSED B POLE 3/4 - GND 5KV 1881000a 376200a S

C POLE 5/6 - GND 5KV 1825000a 365000a S

Remarks: Test Equipment Used


Insulation Resistance Tester
Brand: Chauvin Arnoux / C.A.6555
Serial Number: 111065QBH
Calibration Date: January 08, 2021

II. CLOSED CONTACT RESISTANCE TEST


RESISTANCE RATING
PARTS WATT-
PHASE
MEASURES LOSS
TEST TRIAL Average (S, P, C)

P1 - P2 A 40.4 µჲ 5.48%a 0.001W S

P3 - P4 B 38.3 µჲ 0.00%a 0.002W S

P5 - P6 C 39.2 µჲ 2.35%a 0.002W S

Remarks: Test Equipment Used


Contact Resistance Tester
Brand: Chauvin Arnoux / C.A.6292
Serial Number: 0000013210
Calibration Date: January 20, 2021

III. CB TIMING TEST

A. MECHANICAL RUNDOWN
OPERATING TIME (milli - sec) MISMAT
MODE OF OPERATION RATING (S, P, C)
CH TIME
MISMAT
MODE OF OPERATION RATING (S, P, C)
PHASE A PHASE B PHASE C CH TIME
TRIP 1 27.3ms 27.4ms 27.4ms 0.1ms S
TRIP 2 27.5ms 27.7ms 27.6ms 0.2ms S
CLOSE 63.3ms 63.0ms 62.9ms 0.4ms S

Remarks: MV CB Timing Test shall have an Opening Time equal to 1- 2 cycles ( 20-40ms) and closing time equal to 2-5 cycles( 40-100ms
The exact operation time of circuit breaker is provided by the manufacturer. It can be mentioned on the nameplate of the circuit b

The results were found satisfactorily and passed the ANSI / NETA - ats - 2017 standards. The contractor
Overall Remarks:
recommends conduction annual preventive maintenance of the equipment to maintain its good working condition.

Tested by: Concurred by:

Engr. Lyndon De Vera Engr. Christian Paul Liquigan


Contractor - Test Engineer Owner's Representative

TEST INSTRUMENT:
(Eqpt.ID/Make/Model/SN/ Circuit Breaker Analyzer Legend:
Date of last calibration) Quadrant QCBT-1 S - Satisfactory
67092018a P - Poor
Calibration Date: February 9, 2021 C - Critical

Witnessed By:

Francis Ortiguez Engr. Edward Baroed / Engr. Jimmy Tenoria


Siemens Energy, Inc. Fluence Energy, Inc.
Page
GAS CIRCUIT BREAKER TEST DATA
1 of 2

TEST DATA

Test Data No Module type:

Station 40MW Magapit BESS Facility "I" (live-tank)

Equipment ID Gas Circuit Breaker "Y" (live-tank)

Date of Test August 22,2021 "V" (dead-tank)

Make Siemens

Serial No 351553169A Operating Mechanism:

Type 3AP1FG Spring

Rated kV 72.5KV Pneumatic


Interrupting Capa 40KA Hydraulic

Year Manufactur 2020a

I. INSULATION RESISTANCE TESTS


BREAKE MEASURED
TEST RATING
R RESISTANC
PHASE PARTS MEASURED Mჲ/kV
POSITIO E
kV (S, P, C)
N Mჲ
A POLE 1 - POLE 3 5KV 1300000a 260000a S

B POLE 3 - POLE 4 5KV 2236000A 447200a S

C POLE 5 - POLE 6 5KV 1542000a 308400a S

A POLE 1/2 - GND 5KV 157700a 31540a S

CLOSED B POLE 3/4 - GND 5KV 166800a 33360a S

C POLE 5/6 - GND 5KV 123400a 24680a S

Remarks: Test Equipment Used


Insulation Resistance Tester
Brand: Chauvin Arnoux / C.A.6555
Serial Number: 111065QBH
Calibration Date: January 08, 2021
II. CLOSED CONTACT RESISTANCE TEST
PART RESISTANCE RATING
S WATT-
PHASE
MEAS LOSS
TEST TRIAL Average (S, P, C)
URES
P1 - P2 A 47.3 µჲ 0.00%a 0.001W S

P3 - P4 B 48.6 µჲ 2.75%a 0.001W S

P5 - P6 C 64.3 µჲ 35.94%a 0.001W S

Remarks: Test Equipment Used


Contact Resistance Tester
Brand: Chauvin Arnoux / C.A.6292
Serial Number: 0000013210
Calibration Date: January 20, 2021

III. CB TIMING TEST

A.MODE
MECHANICAL RUNDOWN
OF OPERATING TIME (milli - sec) MISMAT
RATING (S, P, C)
OPERATIPHASE A PHASE B PHASE C CH TIME
ON
TRIP 1 26.7ms 26.2ms 26.5ms 0.4ms S
TRIP 2 29.1ms 28.6ms 28.9ms 0.5ms S
CLOSE 63.4ms 63.8ms 63.4ms 0.4ms S

RemarkMV CB Timing Test shall have an Opening Time equal to 1- 2 cycles ( 20-40ms) and
The exact operation time of circuit breaker is provided by the manufacturer. It can b

The results were found satisfactorily and passed the ANSI / NETA - ats - 2017
Overall Re standards. The contractor recommends conduction annual preventive
maintenance of the equipment to maintain its good working condition.

Tested by: Concurred by:

Engr. Lyndon De Vera Engr. Christian Paul Liquigan


Contractor - Test Engineer Owner's Representative

TEST INSTRUM
Make/
Circuit Breaker Analyzer Legend:
Model/
SN/Date
of last Quadrant QCBT-1 S - Satisfactory
calibration
67092018a P - Poor
Calibration Date: February 9, 2021 C - Critical

Tested by: Concurred by:


Francis Ortiguez Engr. Edward Baroed / Engr. Jimmy Tenoria
Siemens Energy, Inc. Fluence Energy, Inc.
Page
GAS CIRCUIT BREAKER TEST DATA
1 of 2

TEST DATA

Test Data No Module type:

Station 40MW Magapit BESS Facility "I" (live-tank)

Equipment ID Gas Circuit Breaker "Y" (live-tank)

Date of Test August 22,2021 "V" (dead-tank)

Make Siemens

Serial No 20/351553189A Operating Mechanism:

Type 3AP1FG Spring

Rated kV 72.5KV Pneumatic

Interrupting Capacity, kA 40KA Hydraulic


Year Manufactured 2020a

I. INSULATION RESISTANCE TESTS


TEST MEASURED
BREAKER RATING
PHASE PARTS MEASURED RESISTANCE Mჲ/kV
POSITION (S, P, C)
kV Mჲ

A POLE 1 - POLE 3 5KV 1749000a 349800a S

B POLE 3 - POLE 4 5KV 1838000a 367600a S

C POLE 5 - POLE 6 5KV 1259000a 251800a S

A POLE 1/2 - GND 5KV 158200a 31640a S

CLOSED B POLE 3/4 - GND 5KV 201000a 40200a S

C POLE 5/6 - GND 5KV 158500a 31700a S

Remarks: Test Equipment Used


Insulation Resistance Tester
Brand: Chauvin Arnoux / C.A.6555
Serial Number: 111065QBH
Calibration Date: January 08, 2021

II. CLOSED CONTACT RESISTANCE TEST


RESISTANCE
PARTS RATING
PHASE WATT-LOSS
MEASURES (S, P, C)
TEST TRIAL Average

P1 - P2 A 38.7 µჲ 0.00%a 0.001W S

P3 - P4 B 45.6 µჲ 17.83%a 0.001W S

P5 - P6 C 43.2 µჲ 11.63%a 0.001W S

Remarks: Test Equipment Used


Contact Resistance Tester
Brand: Chauvin Arnoux / C.A.6292
Serial Number: 0000013210
Calibration Date: January 20, 2021

III. CB TIMING TEST


A. MECHANICAL RUNDOWN
MODE OF OPERATING TIME (milli - sec) MISMATCH
RATING (S, P, C)
OPERATION PHASE A PHASE B PHASE C TIME
TRIP 1 28.9ms 29.3ms 29.3ms 0.4ms S
TRIP 2 27.2ms 27.6ms 27.6ms 0.4ms S
CLOSE 63.1ms 62.5ms 62.4ms 0.7ms S

Remarks: MV CB Timing Test shall have an Opening Time equal to 1- 2 cycles ( 20-40ms) and closing time equal to 2-5 cycles( 40-1
The exact operation time of circuit breaker is provided by the manufacturer. It can be mentioned on the nameplate of the circ

The results were found satisfactorily and passed the ANSI / NETA - ats - 2017 standards. The contractor recommends
Overall Remarks:
conduction annual preventive maintenance of the equipment to maintain its good working condition.

Tested by: Concurred by:

Engr. Lyndon De Vera Engr. Christian Paul Liquigan


Contractor - Test Engineer Owner's Representative

TEST INSTRUMENT:
Circuit Breaker Analyzer Legend:
(Eqpt.ID/Make/
Model/SN/Date of
last calibration) Quadrant QCBT-1 S - Satisfactory

67092018a P - Poor
Calibration Date: February 9, 2021 C - Critical

Witnessed by:

Francis Ortiguez Engr. Edward Baroed / Engr. Jimmy Tenoria


Siemens Energy, Inc. Fluence Energy, Inc.