CURRENT TRANSFORMER 1 of 2

TEST DATA

Test Data No. SPECIFICATIONS:


Station 40MW Magapit BESS Facility Make: TRENCH
Equipment ID Current Transformer Type: IOSK 72,5
Date of Test August 14,2021 Class: 5P-0.2S/30-15
Weather Fine BIL: 72.5-140-350KV
Year 2020
Manufactured:
[ ] Revenue Metering
[ ] Protection

I. INSULATION RESISTANCE TEST


RATING
TEST MEASURED RESISTANCE
PHASE SERIAL NO. PARTS MEASURED MΩ/kV
kV MΩ @ 33 deg. Celsius
(S,P,C)
A 30156029 Primary Winding 5 37140 7428 S
B 30156030 Primary Winding 5 39060 7812 S
C 30156031 Primary Winding 5 223900 44780 S

A 30156029 1s1 - Gnd 0.5 11220 22440 S


2s1 - Gnd 0.5 6590 13180 S
3s1 - Gnd 0.5 6860 13720 S
4s1 - Gnd 0.5 7010 14020 S

B 30156030 1s1 - Gnd 0.5 3965 7930 S


2s1 - Gnd 0.5 3186 6372 S
3s1 - Gnd 0.5 2915 5830 S
4s1 - Gnd 0.5 3132 6264 S

C 30156031 1s1 - Gnd 0.5 11350 22700 S


2s1 - Gnd 0.5 9110 18220 S
3s1 - Gnd 0.5 10480 20960 S
4s1 - Gnd 0.5 12400 24800 S

A 30156029 Pri - 1s1 5 28930 5786 S


Pri - 2s1 5 38260 7652 S
Pri - 3s1 5 40790 8158 S
Pri - 4s1 5 34270 6854 S

B 30156030 Pri - 1s1 5 42820 8564 S


Pri - 2s1 5 28990 5798 S
Pri - 3s1 5 44520 8904 S
Pri - 4s1 5 35430 7086 S

C 30156031 Pri - 1s1 5 216000 43200 S


Pri - 2s1 5 193800 38760 S
Pri - 3s1 5 202300 40460 S
Pri - 4s1 5 151300 30260 S

II. EXCITATION/SATURATION TEST (For Protection)


A B C
TAP VKN IKN VKN IKN VKN IKN
V A V A V A
Core 1 94.3 0.028 85.6 0.05 86.3 0.027
Core 2 82.5 0.059 94.5 0.026 80.4 0.053
Core 3 68.9 0.067 68.3 0.071 61.2 0.063
Core 4 42.8 0.217 50.3 0.006 40.6 0.195

Remarks:
CURRENT TRANSFORMER TEST DATA Page 2 of 2

III. CURRENT TRANSFORMATION RATIO TEST

PRIMARY/
MEASURED PHASE ANGLE
PHASE SERIAL NO. CONNECTIONS SECONDARY COMPUTED RATIO % Error RATING
RATIO DEVIATION
CURRENT
300/1 300 299.05/1 9.18 0.32% S
600/1 600 600.38/1 11.52 0.06% S
Core 1
800/1 800 803.41/1 11.35 0.43% S
1000/1 1000 1004.11/1 10.12 0.41% S
300/1 300 299.25/1 9.64 0.25% S
600/1 600 602.83/1 11.76 0.47% S
Core 2
800/1 800 803.19/1 11.69 0.40% S
1000/1 1000 1002.57/1 10.45 0.26% S
A 30156029
300/1 300 299.37/1 9.85 0.21% S
600/1 600 601.33/1 11.73 0.22% S
Core 3
800/1 800 803.50/1 11.51 0.44% S
1000/1 1000 1002.88/1 10.52 0.29% S
300/1 300 300.89/1 1.46 0.13% S
600/1 600 602.14/1 1.65 0.36% S
Core 4
800/1 800 802.63/1 1.76 0.33% S
1000/1 1000 1003.62/1 1.81 0.36% S
300/1 300 301.21/1 10.03 0.40% S
600/1 600 601.73/1 11.97 0.29% S
Core 1
800/1 800 800.20/1 11.83 0.03% S
1000/1 1000 998.91/1 10.86 0.11% S
300/1 300 301.11/1 10.15 0.37% S
600/1 600 601.25/1 12.05 0.21% S
Core 2
800/1 800 800.31/1 11.96 0.04% S
1000/1 1000 999.60/1 10.94 0.04% S
B 30156030
300/1 300 301/1 10.21 0.33% S
600/1 600 601.32/1 12.16 0.22% S
Core 3
800/1 800 800.57/1 12.06 0.07% S
1000/1 1000 999.54/1 11.06 0.05% S
300/1 300 299.19/1 1.91 0.27% S
600/1 600 601.58/1 2.02 0.26% S
Core 4
800/1 800 801.51/1 2.15 0.19% S
1000/1 1000 1000.5/1 2.19 0.05% S
300/1 300 301.18/1 10.35 0.39% S
600/1 600 601.80/1 12.39 0.30% S
Core 1
800/1 800 801.11/1 12.20 0.14% S
1000/1 1000 1001.4/1 11.19 0.14% S
300/1 300 300.68/1 10.38 0.23% S
600/1 600 601.16/1 12.41 0.19% S
Core 2
800/1 800 800.84/1 12.25 0.10% S
1000/1 1000 1000.5/1 11.21 0.05% S
C 30156031
300/1 300 301.13/1 10.42 0.38% S
600/1 600 601.78/1 12.46 0.30% S
Core 3
800/1 800 800/49/1 12.30 0.06% S
1000/1 1000 1000.2/1 11.26 0.02% S
300/1 300 299.80/1 2.23 0.07% S
600/1 600 602.85/1 2.26 0.47% S
Core 4
800/1 800 802.12/1 2.29 0.27% S
1000/1 1000 1000.2/1 2.30 0.02% S

Remarks:

Overall Remarks:

Tested by : Concurred by :

Engr. Lyndon De Vera Engr. Christian Paul Liquigan


Contractor - Test Engineer Owner's Representative

TEST INSTRUMENTS: Legend:


(Eqpt.ID/Make/Model/SN/ Date S - Satisfactory
of last calibration)

CT / PT Analyzer P - Poor

Goldsol GLDL - 405 C - Critical


16648
Calibration Date February 8, 2021

Witnessed By:

Francis Ortiguez Engr. Edward Baraoed / Engr. Jimmy Tenoria

Siemens Energy, Inc. Fluence Energy, Inc.


Page
CURRENT TRANSFORMER 1 of 2

TEST DATA

Test Data No. SPECIFICATIONS:


Station 40MW Magapit BESS Facility Make: TRENCH
Equipment ID Current Transformer Type: IOSK 72,5
Date of Test August 16,2021 Class: 5P-0.2S/30-15
Weather Fine BIL: 72.5-140-350KV
Year 2020
Manufactured:
[ ] Revenue Metering
[ ] Protection

I. INSULATION RESISTANCE TEST


RATING
TEST MEASURED RESISTANCE
PHASE SERIAL NO. PARTS MEASURED MΩ/kV
kV MΩ @ 33 deg. Celsius
(S,P,C)
A 30156026 Primary Winding 5 290400 58080 S
B 30156027 Primary Winding 5 33770 6754 S
C 30156028 Primary Winding 5 15450 3090 S

A 30156026 1s1 - Gnd 0.5 12440 24880 S


2s1 - Gnd 0.5 10710 21420 S
3s1 - Gnd 0.5 12760 25520 S
4s1 - Gnd 0.5 16090 32180 S

B 30156027 1s1 - Gnd 0.5 11140 22280 S


2s1 - Gnd 0.5 11310 22620 S
3s1 - Gnd 0.5 10080 20160 S
4s1 - Gnd 0.5 11860 23720 S

C 30156028 1s1 - Gnd 0.5 64000 128000 S


2s1 - Gnd 0.5 4860 9720 S
3s1 - Gnd 0.5 6310 12620 S
4s1 - Gnd 0.5 6020 12040 S

A 30156026 Pri - 1s1 5 33400 6680 S


Pri - 2s1 5 321200 64240 S
Pri - 3s1 5 312700 62540 S
Pri - 4s1 5 192700 38540 S

B 30156027 Pri - 1s1 5 28060 5612 S


Pri - 2s1 5 29030 5806 S
Pri - 3s1 5 31220 6244 S
Pri - 4s1 5 29270 5854 S

C 30156028 Pri - 1s1 5 50550 10110 S


Pri - 2s1 5 50440 10088 S
Pri - 3s1 5 30310 6062 S
Pri - 4s1 5 43710 8742 S

II. EXCITATION/SATURATION TEST (For Protection)


A B C
TAP VKN IKN VKN IKN VKN IKN
V A V A V A
Core 1 93.8 0.029 85.3 0.029 84.8 0.023
Core 2 81.3 0.059 81.5 0.059 80.8 0.052
Core 3 62.8 0.061 62.8 0.073 60.2 0.07
Core 4 41.4 0.215 47.1 0.242 41.1 0.193

Remarks:
CURRENT TRANSFORMER TEST DATA Page 2 of 2

III. CURRENT TRANSFORMATION RATIO TEST


PRIMARY/
MEASURED PHASE
PHASE SERIAL NO. CONNECTIONS SECONDARY COMPUTED RATIO % Error RATING
RATIO DEVIATION
CURRENT
300/1 300 301.19/1 9.07 0.40% S
600/1 600 600.10/1 11.27 0.02% S
Core 1
800/1 800 801.81/1 11.13 0.23% S
1000/1 1000 1002.0/1 10.16 0.20% S
300/1 300 301.09/1 9.12 0.36% S
600/1 600 601.27/1 11.31 0.21% S
Core 2
800/1 800 802.50/1 11.17 0.31% S
1000/1 1000 1002.1/1 10.19 0.21% S
A 30156026
300/1 300 301.44/1 9.16 0.48% S
600/1 600 600.19/1 11.34 0.03% S
Core 3
800/1 800 802.25/1 11.21 0.28% S
1000/1 1000 1002.0/1 10.23 0.20% S
300/1 300 299.48/1 1.34 0.17% S
600/1 600 600.43/1 1.36 0.07% S
Core 4
800/1 800 803.85/1 1.39 0.48% S
1000/1 1000 1001.7/1 1.42 0.17% S
300/1 300 300.14/1 9.19 0.05% S
600/1 600 602.45/1 11.39 0.41% S
Core 1
800/1 800 800.98/1 11.26 0.12% S
1000/1 1000 1000.7/1 10.27 0.07% S
300/1 300 299.31/1 9.23 0.23% S
600/1 600 600.85/1 11.42 0.14% S
Core 2
800/1 800 801.36/1 11.29 0.17% S
1000/1 1000 1001.0/1 10.31 0.10% S
B 30156027
300/1 300 300.09/1 9.26 0.03% S
600/1 600 600.79/1 11.47 0.13% S
Core 3
800/1 800 800.72/1 11.32 0.09% S
1000/1 1000 999.57/1 10.35 0.04% S
300/1 300 298.86/1 1.46 0.38% S
600/1 600 601.77/1 1.49 0.29% S
Core 4
800/1 800 801.20/1 1.52 0.15% S
1000/1 1000 1003.2/1 1.54 0.32% S
300/1 300 301.13/1 9.29 0.38% S
600/1 600 602.42/1 11.51 0.41% S
Core 1
800/1 800 801.28/1 11.37 0.16% S
1000/1 1000 995.62/1 10.39 0.44% S
300/1 300 300.36/1 9.31 0.12% S
600/1 600 600.76/1 11.63 0.13% S
Core 2
800/1 800 801.34/1 11.41 0.17% S
1000/1 1000 1000.5/1 10.43 0.05% S
C 30156028
300/1 300 299.16/1 9.35 0.28% S
600/1 600 601.78/1 11.69 0.30% S
Core 3
800/1 800 800.55/1 11.48 0.07% S
1000/1 1000 1000.8/1 10.49 0.08% S
300/1 300 299.22/1 1.49 0.26% S
600/1 600 602.36/1 1.52 0.39% S
Core 4
800/1 800 802.74/1 1.55 0.34% S
1000/1 1000 10003.9/1 1.58 0.39% S

Remarks:

Overall Remarks:

Tested by : Concurred by :

Engr. Lyndon De Vera Engr. Christian Paul Liquigan


Contractor - Test Engineer Owner's Representative

TEST INSTRUMENTS: Legend:


(Eqpt.ID/Make/Model/SN/ Date S - Satisfactory
of last calibration)

CT / PT Analyzer P - Poor

Goldsol GLDL - 405 C - Critical


16648
Calibration Date February 8, 2021

Witnessed By:

Francis Ortiguez Engr. Edward Baraoed / Engr. Jimmy Tenoria


Siemens Energy, Inc. Fluence Energy, Inc.
Page
CURRENT TRANSFORMER 1 of 2

TEST DATA

Test Data No. SPECIFICATIONS:


Station 40MW Magapit BESS Facility Make: TRENCH
Equipment ID Current Transformer Type: IOSK 72,5
Date of Test August 16,2021 Class: 5P-0.2S/30-15
Weather Fine BIL: 72.5-140-350KV
Year 2020
Manufactured:
[ ] Revenue Metering
[ ] Protection

I. INSULATION RESISTANCE TEST


RATING
TEST MEASURED RESISTANCE
PHASE SERIAL NO. PARTS MEASURED MΩ/kV
kV MΩ @ 33 deg. Celsius
(S,P,C)
A 30159024 Primary Winding 5 146700 29340 S
B 30159025 Primary Winding 5 134000 26800 S
C 30159026 Primary Winding 5 132700 26540 S

A 30159024 1s1 - Gnd 0.5 12080 24160 S


2s1 - Gnd 0.5 10840 21680 S
3s1 - Gnd 0.5 9950 19900 S
4s1 - Gnd 0.5 10970 21940 S

B 30159025 1s1 - Gnd 0.5 11330 22660 S


2s1 - Gnd 0.5 6680 13360 S
3s1 - Gnd 0.5 8630 17260 S
4s1 - Gnd 0.5 9590 19180 S

C 30159026 1s1 - Gnd 0.5 11540 23080 S


2s1 - Gnd 0.5 14140 28280 S
3s1 - Gnd 0.5 12220 24440 S
4s1 - Gnd 0.5 16740 33480 S

A 30159024 Pri - 1s1 5 305600 61120 S


Pri - 2s1 5 324000 64800 S
Pri - 3s1 5 247900 49580 S
Pri - 4s1 5 201700 40340 S

B 30159025 Pri - 1s1 5 68540 13708 S


Pri - 2s1 5 65620 13124 S
Pri - 3s1 5 65060 13012 S
Pri - 4s1 5 73520 14704 S

C 30159026 Pri - 1s1 5 72270 14454 S


Pri - 2s1 5 69030 13806 S
Pri - 3s1 5 95570 19114 S
Pri - 4s1 5 72840 14568 S

II. EXCITATION/SATURATION TEST (For Protection)


A B C
TAP VKN IKN VKN IKN VKN IKN
V A V A V A
Core 1 93.9 0.031 85.9 0.025 95.2 0.03
Core 2 81.9 0.054 79.8 0.051 80.9 0.051
Core 3 63.6 0.073 61.2 0.072 59.6 0.136
Core 4 42.6 0.203 43.1 0.205 41.3 0.194

Remarks:
CURRENT TRANSFORMER TEST DATA Page 2 of 2

III. CURRENT TRANSFORMATION RATIO TEST


PRIMARY/
MEASURED PHASE
PHASE SERIAL NO. CONNECTIONS SECONDARY COMPUTED RATIO % Error RATING
RATIO DEVIATION
CURRENT
300/1 300 301.05/1 9.9 0.35% S
600/1 600 601.65/1 11.28 0.27% S
Core 1
800/1 800 801.10/1 11.13 0.14% S
1000/1 1000 1000.5/1 10.16 0.05% S
300/1 300 300.32/1 9.15 0.11% S
600/1 600 601.49/1 11.31 0.25% S
Core 2
800/1 800 801.00/1 11.16 0.13% S
1000/1 1000 1000.9/1 10.19 0.09% S
A 30159024
300/1 300 301.01/1 9.19 0.34% S
600/1 600 602.28/1 11.35 0.38% S
Core 3
800/1 800 801.62/1 11.18 0.20% S
1000/1 1000 1001.0/1 10.22 0.10% S
300/1 300 298.58/1 1.35 0.47% S
600/1 600 600.79/1 1.39 0.13% S
Core 4
800/1 800 799.94/1 1.42 0.01% S
1000/1 1000 1000.6/1 1.47 0.06% S
300/1 300 300.77/1 9.25 0.26% S
600/1 600 600.29/1 11.39 0.05% S
Core 1
800/1 800 799.72/1 11.22 0.03% S
1000/1 1000 999.72/1 10.26 0.06% S
300/1 300 300.77/1 9.29 0..26% S
600/1 600 600.25/1 11.42 0.04% S
Core 2
800/1 800 799.61/1 11.29 0.05% S
1000/1 1000 999.54/1 10.27 0.05% S
B 30159025
300/1 300 300.86/1 9.32 0.29% S
600/1 600 602.73/1 11.47 0.46% S
Core 3
800/1 800 799.54/1 11.32 0.06% S
1000/1 1000 996.31/1 10.34 0.37% S
300/1 300 298.95/1 1.39 0.35% S
600/1 600 602.23/1 1.43 0.37% S
Core 4
800/1 800 801.94/1 1.47 0.24% S
1000/1 1000 995.66/1 1.51 0.43% S
300/1 300 300.38/1 9.46 0.13% S
600/1 600 599.18/1 11.49 0.14% S
Core 1
800/1 800 798.14/1 11.36 0.23% S
1000/1 1000 997.25/1 10.39 0.28% S
300/1 300 300.85/1 9.49 0.28% S
600/1 600 600.13/1 11.53 0.02% S
Core 2
800/1 800 799.48/1 11.38 0.06% S
1000/1 1000 999.47/1 10.43 0.05% S
C 30159026
300/1 300 300.75/1 9.52 0.25% S
600/1 600 600.39/1 11.57 0.07% S
Core 3
800/1 800 799.72/1 11.42 0.04% S
1000/1 1000 999.24/1 10.49 0.08% S
300/1 300 298.56/1 1.43 0.48% S
600/1 600 600.82/1 1.46 0.14% S
Core 4
800/1 800 800.83/1 1.49 0.10% S
1000/1 1000 1000.2/1 1.55 0.02% S

Remarks:

Overall Remarks:

Tested by : Concurred by :

Engr. Lyndon De Vera Engr. Christian Paul Liquigan


Contractor - Test Engineer Owner's Representative

TEST INSTRUMENTS: Legend:


(Eqpt.ID/Make/Model/SN/ Date S - Satisfactory
of last calibration)

CT / PT Analyzer P - Poor
Goldsol GLDL - 405 C - Critical
16648
Calibration Date February 8, 2021

Witnessed By:

Francis Ortiguez Engr. Edward Baraoed / Engr. Jimmy Tenoria


Siemens Energy, Inc. Fluence Energy, Inc.
Page
CURRENT TRANSFORMER 1 of 2

TEST DATA

Test Data No. SPECIFICATIONS:


Station 40MW Magapit BESS Facility Make: TRENCH
Equipment ID Current Transformer Type: IOSK 72,5
Date of Test August 16,2021 Class: 5P-0.2S/30-15
Weather Fine BIL: 72.5-140-350KV
Year 2020
Manufactured:
[ ] Revenue Metering
[ ] Protection

I. INSULATION RESISTANCE TEST


RATING
TEST MEASURED RESISTANCE
PHASE SERIAL NO. PARTS MEASURED MΩ/kV
kV MΩ @ 33 deg. Celsius
(S,P,C)
A 30159030 Primary Winding 5 128000 25600 S
B 30159031 Primary Winding 5 346200 69240 S
C 30159032 Primary Winding 5 488000 97600 S

A 30159030 1s1 - Gnd 0.5 11220 22440 S


2s1 - Gnd 0.5 6590 13180 S
3s1 - Gnd 0.5 6860 13720 S
4s1 - Gnd 0.5 7010 14020 S

B 30159031 1s1 - Gnd 0.5 3965 7930 S


2s1 - Gnd 0.5 3186 6372 S
3s1 - Gnd 0.5 2915 5830 S
4s1 - Gnd 0.5 3132 6264 S

C 30159032 1s1 - Gnd 0.5 11350 22700 S


2s1 - Gnd 0.5 9110 18220 S
3s1 - Gnd 0.5 10480 20960 S
4s1 - Gnd 0.5 12400 24800 S

A 30159030 Pri - 1s1 5 821700 164340 S


Pri - 2s1 5 848700 169740 S
Pri - 3s1 5 785800 157160 S
Pri - 4s1 5 756300 151260 S

B 30159031 Pri - 1s1 5 338760 67752 S


Pri - 2s1 5 279310 55862 S
Pri - 3s1 5 297160 59432 S
Pri - 4s1 5 390320 78064 S

C 30159032 Pri - 1s1 5 353780 70756 S


Pri - 2s1 5 289110 57822 S
Pri - 3s1 5 367740 73548 S
Pri - 4s1 5 253480 50696 S

II. EXCITATION/SATURATION TEST (For Protection)


A B C
TAP VKN IKN VKN IKN VKN IKN
V A V A V A
Core 1 83.1 0.061 93.3 0.031 87.3 0.022
Core 2 79.1 0.052 81.7 0.058 82.5 0.062
Core 3 69.3 0.061 67.4 0.073 68.6 0.075
Core 4 42.9 0.202 47.6 0.243 47.4 0.249

Remarks:
CURRENT TRANSFORMER TEST DATA Page 2 of 2

III. CURRENT TRANSFORMATION RATIO TEST


PRIMARY/
MEASURED PHASE
PHASE SERIAL NO. CONNECTIONS SECONDARY COMPUTED RATIO % Error RATING
RATIO DEVIATION
CURRENT
300/1 300 300.32/1 9.10 0.11% S
600/1 600 602.15/1 11.27 0.36% S
Core 1
800/1 800 798.80/1 11.13 0.15% S
1000/1 1000 999.09/1 10.16 0.09% S
300/1 300 300.52/1 9.15 0.17% S
600/1 600 599.36/1 11.31 0.11% S
Core 2
800/1 800 798.75/1 11.17 0.16% S
1000/1 1000 998.35/1 10.23 0.16% S
A 30159030
300/1 300 300.46/1 9.19 0.15% S
600/1 600 599.62/1 11.35 0.06% S
Core 3
800/1 800 799.62/1 11.19 0.05% S
1000/1 1000 1003.11/1 10.27 0.31% S
300/1 300 298.72/1 1.43 0.43% S
600/1 600 602.45/1 1.49 0.41% S
Core 4
800/1 800 802.22/1 1.53 0.28% S
1000/1 1000 1000.6/1 1.61 0.06% S
300/1 300 300.40/1 9.23 0.13% S
600/1 600 600.13/1 11.39 0.02% S
Core 1
800/1 800 801.70/1 11.23 0.21% S
1000/1 1000 1000.6/1 10.29 0.06% S
300/1 300 299.08/1 9.28 0.31% S
600/1 600 602.43/1 11.42 0.41% S
Core 2
800/1 800 801.26/1 11.26 0.16% S
1000/1 1000 1001.1/1 10.31 0.10% S
B 30159031
300/1 300 299.26/1 9.31 0.25% S
600/1 600 602.73/1 11.47 0.46% S
Core 3
800/1 800 801.24/1 11.29 0.15% S
1000/1 1000 999.63/1 10.35 0.04% S
300/1 300 298.70/1 1.47 43.00% S
600/1 600 600.77/1 1.53 0.13% S
Core 4
800/1 800 803.37/1 1.57 0.42% S
1000/1 1000 1004.1/1 1.68 0.41% S
300/1 300 301.31/1 9.36 0.44% S
600/1 600 602.24/1 11.51 0.37% S
Core 1
800/1 800 800.47/1 11.32 0.09% S
1000/1 1000 1000.4/1 10.39 0.04% S
300/1 300 301.01/1 9.39 0.34% S
600/1 600 601.85/1 11.56 0.31% S
Core 2
800/1 800 800.89/1 11.39 0.11% S
1000/1 1000 999.56/1 10.42 0.04% S
C 30159032
300/1 300 299.36/1 9.39 0.21% S
600/1 600 601.57/1 11.63 0.26% S
Core 3
800/1 800 801.60/1 11.45 0.20% S
1000/1 1000 999.88/1 10.49 0.01% S
300/1 300 298.85/1 1.52 0.38% S
600/1 600 600.71/1 1.59 0.12% S
Core 4
800/1 800 802.69/1 1.62 0.34% S
1000/1 1000 1000.4/1 1.73 0.04% S

Remarks:

Overall Remarks:

Tested by : Concurred by :

Engr. Lyndon De Vera Engr. Christian Paul Liquigan


Contractor - Test Engineer Owner's Representative

TEST INSTRUMENTS: Legend:


(Eqpt.ID/Make/Model/SN/ Date S - Satisfactory
of last calibration)

CT / PT Analyzer P - Poor

Goldsol GLDL - 405 C - Critical


16648
Calibration Date February 8, 2021

Witnessed By:

Francis Ortiguez Engr. Edward Baraoed / Engr. Jimmy Tenoria


Siemens Energy, Inc. Fluence Energy, Inc.
Page
CURRENT TRANSFORMER 1 of 2

TEST DATA

Test Data No. SPECIFICATIONS:


Station 40MW Magapit BESS Facility Make: TRENCH
Equipment ID Current Transformer Type: IOSK 72,5
Date of Test August 16,2021 Class: 5P-0.2S/30-15
Weather Fine BIL: 72.5-140-350KV
Year 2020
Manufactured:
[ ] Revenue Metering
[ ] Protection

I. INSULATION RESISTANCE TEST


RATING
TEST MEASURED RESISTANCE
PHASE SERIAL NO. PARTS MEASURED MΩ/kV
kV MΩ @ 33 deg. Celsius
(S,P,C)
A 30159039 Primary Winding 5 14380 2876 S
B 30159040 Primary Winding 5 16850 3370 S
C 30159041 Primary Winding 5 26170 5234 S

A 30159039 1s1 - Gnd 0.5 11620 23240 S


2s1 - Gnd 0.5 12580 25160 S
3s1 - Gnd 0.5 10990 21980 S
4s1 - Gnd 0.5 11170 22340 S

B 30159040 1s1 - Gnd 0.5 12660 25320 S


2s1 - Gnd 0.5 1289 2578 S
3s1 - Gnd 0.5 12480 24960 S
4s1 - Gnd 0.5 14100 28200 S

C 30159041 1s1 - Gnd 0.5 11320 22640 S


2s1 - Gnd 0.5 11930 23860 S
3s1 - Gnd 0.5 11570 23140 S
4s1 - Gnd 0.5 12860 25720 S

A 30159039 Pri - 1s1 5 43550 8710 S


Pri - 2s1 5 33080 6616 S
Pri - 3s1 5 35320 7064 S
Pri - 4s1 5 44520 8904 S

B 30159040 Pri - 1s1 5 37730 7546 S


Pri - 2s1 5 33090 6618 S
Pri - 3s1 5 53750 10750 S
Pri - 4s1 5 57870 11574 S

C 30159041 Pri - 1s1 5 54810 10962 S


Pri - 2s1 5 36640 7328 S
Pri - 3s1 5 36410 7282 S
Pri - 4s1 5 30300 6060 S

II. EXCITATION/SATURATION TEST (For Protection)


A B C
TAP VKN IKN VKN IKN VKN IKN
V A V A V A
Core 1 82.8 0.063 94.6 0.031 85.7 0.022
Core 2 93.9 0.031 82.7 0.061 81.8 0.042
Core 3 69.2 0.068 68.4 0.072 60.8 0.069
Core 4 42.1 0.201 42.1 0.212 42.3 0.204

Remarks:
CURRENT TRANSFORMER TEST DATA Page 2 of 2

III. CURRENT TRANSFORMATION RATIO TEST


PRIMARY/
MEASURED PHASE
PHASE SERIAL NO. CONNECTIONS SECONDARY COMPUTED RATIO % Error RATING
RATIO DEVIATION
CURRENT
300/1 300 300.80/1 0.11% S
600/1 600 600.29/1 0.36% S
Core 1
800/1 800 796.33/1 0.15% S
1000/1 1000 998.59/1 0.09% S
300/1 300 300.71/1 0.17% S
600/1 600 600.24/1 0.11% S
Core 2
800/1 800 799.23/1 0.16% S
1000/1 1000 1000.5/1 0.16% S
A 30159039
300/1 300 300.89/1 0.15% S
600/1 600 600.10/1 0.06% S
Core 3
800/1 800 799.1/1 0.05% S
1000/1 1000 998.86/1 0.31% S
300/1 300 298.65/1 0.43% S
600/1 600 600.47/1 0.41% S
Core 4
800/1 800 800.41/1 0.28% S
1000/1 1000 1001.0/1 0.06% S
300/1 300 299.22/1 0.13% S
600/1 600 602.31/1 0.02% S
Core 1
800/1 800 801.13/1 0.21% S
1000/1 1000 999.59/1 0.06% S
300/1 300 300.14/1 0.31% S
600/1 600 601.95/1 0.41% S
Core 2
800/1 800 801.35/1 0.16% S
1000/1 1000 1001.3/1 0.10% S
B 30159040
300/1 300 299.16/1 0.25% S
600/1 600 600.22/1 0.46% S
Core 3
800/1 800 802.24/1 0.15% S
1000/1 1000 1001.3/1 0.04% S
300/1 300 301.29/1 43.00% S
600/1 600 602.18/1 0.13% S
Core 4
800/1 800 803.02/1 0.42% S
1000/1 1000 1003.4/1 0.41% S
300/1 300 300.89/1 0.44% S
600/1 600 601.19/1 0.37% S
Core 1
800/1 800 800.46/1 0.09% S
1000/1 1000 999.53/1 0.04% S
300/1 300 300.75/1 0.34% S
600/1 600 600.45/1 0.31% S
Core 2
800/1 800 799.60/1 0.11% S
1000/1 1000 999.78/1 0.04% S
C 30159041
300/1 300 300.92/1 0.21% S
600/1 600 601.78/1 0.26% S
Core 3
800/1 800 800.56/1 0.20% S
1000/1 1000 999.88/1 0.01% S
300/1 300 300.20/1 0.38% S
600/1 600 601.78/1 0.12% S
Core 4
800/1 800 803.09/1 0.34% S
1000/1 1000 999.88/1 0.04% S

Remarks:

Overall Remarks:

Tested by : Concurred by :

Engr. Lyndon De Vera Engr. Christian Paul Liquigan


Contractor - Test Engineer Owner's Representative

TEST INSTRUMENTS: Legend:


(Eqpt.ID/Make/Model/SN/ Date S - Satisfactory
of last calibration)

CT / PT Analyzer P - Poor

Goldsol GLDL - 405 C - Critical


16648
Calibration Date February 8, 2021

Witnessed By:

Francis Ortiguez Engr. Edward Baraoed / Engr. Jimmy Tenoria

Siemens Energy, Inc. Fluence Energy, Inc.


Page
CURRENT TRANSFORMER 1 of 2

TEST DATA

Test Data No. SPECIFICATIONS:


Station 40MW Magapit BESS Facility Make: TRENCH
Equipment ID Current Transformer Type: IOSK 72,5
Date of Test August 16,2021 Class: 5P-0.2S/30-15
Weather Fine BIL: 72.5-140-350KV
Year 2020
Manufactured:
[ ] Revenue Metering
[ ] Protection

I. INSULATION RESISTANCE TEST


RATING
TEST MEASURED RESISTANCE
PHASE SERIAL NO. PARTS MEASURED MΩ/kV
kV MΩ @ 33 deg. Celsius
(S,P,C)
A 30159027 Primary Winding 5 20020 4004 S
B 30159028 Primary Winding 5 19110 3822 S
C 30159029 Primary Winding 5 34730 6946 S

A 30159027 1s1 - Gnd 0.5 12700 25400 S


2s1 - Gnd 0.5 12330 24660 S
3s1 - Gnd 0.5 11480 22960 S
4s1 - Gnd 0.5 13660 27320 S

B 30159028 1s1 - Gnd 0.5 11260 22520 S


2s1 - Gnd 0.5 12690 25380 S
3s1 - Gnd 0.5 11810 23620 S
4s1 - Gnd 0.5 14180 28360 S

C 30159029 1s1 - Gnd 0.5 7610 15220 S


2s1 - Gnd 0.5 12210 24420 S
3s1 - Gnd 0.5 11430 22860 S
4s1 - Gnd 0.5 12030 24060 S

A 30159027 Pri - 1s1 5 20070 4014 S


Pri - 2s1 5 26250 5250 S
Pri - 3s1 5 23350 4670 S
Pri - 4s1 5 35220 7044 S

B 30159028 Pri - 1s1 5 29560 5912 S


Pri - 2s1 5 30950 6190 S
Pri - 3s1 5 32500 6500 S
Pri - 4s1 5 33630 6726 S

C 30159029 Pri - 1s1 5 34730 6946 S


Pri - 2s1 5 26720 5344 S
Pri - 3s1 5 45670 9134 S
Pri - 4s1 5 42690 8538 S

II. EXCITATION/SATURATION TEST (For Protection)


A B C
TAP VKN IKN VKN IKN VKN IKN
V A V A V A
Core 1 84.7 0.033 85.1 0.023 82.3 0.059
Core 2 79.9 0.06 82.1 0.061 81.5 0.053
Core 3 61.9 0.073 62.4 0.069 68.6 0.073
Core 4 47.1 0.194 41.7 0.216 43.1 0.211

Remarks:
CURRENT TRANSFORMER TEST DATA Page 2 of 2

III. CURRENT TRANSFORMATION RATIO TEST


PRIMARY/
MEASURED PHASE
PHASE SERIAL NO. CONNECTIONS SECONDARY COMPUTED RATIO % Error RATING
RATIO DEVIATION
CURRENT
300/1 300 299.26/1 0.25% S
600/1 600 602.36/1 0.39% S
Core 1
800/1 800 801.25/1 0.16% S
1000/1 1000 1003.09/1 0.31% S
300/1 300 301.03/1 0.34% S
600/1 600 600.47/1 0.08% S
Core 2
800/1 800 801.02/1 0.13% S
1000/1 1000 1002.42/1 0.24% S
A 30159027
300/1 300 301.36/1 0.45% S
600/1 600 601.28/1 0.21% S
Core 3
800/1 800 803.11/1 0.39% S
1000/1 1000 1002.70/1 0.27% S
300/1 300 301.38/1 0.46% S
600/1 600 600.28/1 0.05% S
Core 4
800/1 800 802.08/1 0.26% S
1000/1 1000 1004.01/1 0.40% S
300/1 300 300.05/1 0.02% S
600/1 600 601.49/1 0.25% S
Core 1
800/1 800 802.21/1 0.28% S
1000/1 1000 1002.21/1 0.22% S
300/1 300 301.12/1 0.37% S
600/1 600 602.01/1 0.33% S
Core 2
800/1 800 803.42/1 0.43% S
1000/1 1000 1002.02/1 0.20% S
B 30159028
300/1 300 301.12/1 0.37% S
600/1 600 601.07/1 0.18% S
Core 3
800/1 800 802.04/1 0.25% S
1000/1 1000 1002.12/1 0.21% S
300/1 300 299.13/1 0.29% S
600/1 600 601.04/1 0.17% S
Core 4
800/1 800 802.70/1 0.34% S
1000/1 1000 1003.85/1 0.39% S
300/1 300 301.24/1 0.41% S
600/1 600 601.70/1 0.28% S
Core 1
800/1 800 801.17/1 0.15% S
1000/1 1000 1001.65/1 0.16% S
300/1 300 300.11/1 0.04% S
600/1 600 600.48/1 0.08% S
Core 2
800/1 800 803.38/1 0.42% S
1000/1 1000 1000.90/1 0.09% S
C 30159029
300/1 300 299.20/1 0.27% S
600/1 600 600.22/1 0.04% S
Core 3
800/1 800 802.24/1 0.28% S
1000/1 1000 1002.83/1 0.28% S
300/1 300 299.03/1 0.32% S
600/1 600 602.12/1 0.35% S
Core 4
800/1 800 801.24/1 0.16% S
1000/1 1000 1000.28/1 0.03% S

Remarks:

Overall Remarks:

Tested by : Concurred by :

Engr. Lyndon De Vera Engr. Christian Paul Liquigan


Contractor - Test Engineer Owner's Representative

TEST INSTRUMENTS: Legend:


(Eqpt.ID/Make/Model/SN/ Date S - Satisfactory
of last calibration)

CT / PT Analyzer P - Poor
Goldsol GLDL - 405 C - Critical
16648
Calibration Date February 8, 2021
Witnessed By:

Francis Ortiguez
Siemens Energy, Inc.

Engr. Edward Baraoed / Engr. Jimmy Tenoria


Fluence Energy, Inc.