CURRENT TRANSFORMER 1 of 2
TEST DATA
Remarks:
CURRENT TRANSFORMER TEST DATA Page 2 of 2
PRIMARY/
MEASURED PHASE ANGLE
PHASE SERIAL NO. CONNECTIONS SECONDARY COMPUTED RATIO % Error RATING
RATIO DEVIATION
CURRENT
300/1 300 299.05/1 9.18 0.32% S
600/1 600 600.38/1 11.52 0.06% S
Core 1
800/1 800 803.41/1 11.35 0.43% S
1000/1 1000 1004.11/1 10.12 0.41% S
300/1 300 299.25/1 9.64 0.25% S
600/1 600 602.83/1 11.76 0.47% S
Core 2
800/1 800 803.19/1 11.69 0.40% S
1000/1 1000 1002.57/1 10.45 0.26% S
A 30156029
300/1 300 299.37/1 9.85 0.21% S
600/1 600 601.33/1 11.73 0.22% S
Core 3
800/1 800 803.50/1 11.51 0.44% S
1000/1 1000 1002.88/1 10.52 0.29% S
300/1 300 300.89/1 1.46 0.13% S
600/1 600 602.14/1 1.65 0.36% S
Core 4
800/1 800 802.63/1 1.76 0.33% S
1000/1 1000 1003.62/1 1.81 0.36% S
300/1 300 301.21/1 10.03 0.40% S
600/1 600 601.73/1 11.97 0.29% S
Core 1
800/1 800 800.20/1 11.83 0.03% S
1000/1 1000 998.91/1 10.86 0.11% S
300/1 300 301.11/1 10.15 0.37% S
600/1 600 601.25/1 12.05 0.21% S
Core 2
800/1 800 800.31/1 11.96 0.04% S
1000/1 1000 999.60/1 10.94 0.04% S
B 30156030
300/1 300 301/1 10.21 0.33% S
600/1 600 601.32/1 12.16 0.22% S
Core 3
800/1 800 800.57/1 12.06 0.07% S
1000/1 1000 999.54/1 11.06 0.05% S
300/1 300 299.19/1 1.91 0.27% S
600/1 600 601.58/1 2.02 0.26% S
Core 4
800/1 800 801.51/1 2.15 0.19% S
1000/1 1000 1000.5/1 2.19 0.05% S
300/1 300 301.18/1 10.35 0.39% S
600/1 600 601.80/1 12.39 0.30% S
Core 1
800/1 800 801.11/1 12.20 0.14% S
1000/1 1000 1001.4/1 11.19 0.14% S
300/1 300 300.68/1 10.38 0.23% S
600/1 600 601.16/1 12.41 0.19% S
Core 2
800/1 800 800.84/1 12.25 0.10% S
1000/1 1000 1000.5/1 11.21 0.05% S
C 30156031
300/1 300 301.13/1 10.42 0.38% S
600/1 600 601.78/1 12.46 0.30% S
Core 3
800/1 800 800/49/1 12.30 0.06% S
1000/1 1000 1000.2/1 11.26 0.02% S
300/1 300 299.80/1 2.23 0.07% S
600/1 600 602.85/1 2.26 0.47% S
Core 4
800/1 800 802.12/1 2.29 0.27% S
1000/1 1000 1000.2/1 2.30 0.02% S
Remarks:
Overall Remarks:
Tested by : Concurred by :
CT / PT Analyzer P - Poor
Witnessed By:
TEST DATA
Remarks:
CURRENT TRANSFORMER TEST DATA Page 2 of 2
Remarks:
Overall Remarks:
Tested by : Concurred by :
CT / PT Analyzer P - Poor
Witnessed By:
TEST DATA
Remarks:
CURRENT TRANSFORMER TEST DATA Page 2 of 2
Remarks:
Overall Remarks:
Tested by : Concurred by :
CT / PT Analyzer P - Poor
Goldsol GLDL - 405 C - Critical
16648
Calibration Date February 8, 2021
Witnessed By:
TEST DATA
Remarks:
CURRENT TRANSFORMER TEST DATA Page 2 of 2
Remarks:
Overall Remarks:
Tested by : Concurred by :
CT / PT Analyzer P - Poor
Witnessed By:
TEST DATA
Remarks:
CURRENT TRANSFORMER TEST DATA Page 2 of 2
Remarks:
Overall Remarks:
Tested by : Concurred by :
CT / PT Analyzer P - Poor
Witnessed By:
TEST DATA
Remarks:
CURRENT TRANSFORMER TEST DATA Page 2 of 2
Remarks:
Overall Remarks:
Tested by : Concurred by :
CT / PT Analyzer P - Poor
Goldsol GLDL - 405 C - Critical
16648
Calibration Date February 8, 2021
Witnessed By:
Francis Ortiguez
Siemens Energy, Inc.