You are on page 1of 3

Equipment Test Report

Prepared for

10

Equipment Tested:
abb
Uitilty sun b

Job #: 3gf11082483

Test Description: Stator


Test Stage: New - Incoming (IEEE)
Test Operator: mohammed hussein ,hussein ali
Equipment Test Report
Customer: 10

Equipment Information
Motor ID Uitilty sun b Operating Volts 400
Equipment Tag Sun.18.ed.0001b RPM 2914
Location Suba norath Power 7.5 kW
Manufacturer abb AC/DC AC

Test Information
Test Date/Time: 02-Oct-22 - 11:31:14
Winding Temp: 30 °C - Humidity: 30%
Job # 3gf11082483
Test Description Stator
Test Stage New - Incoming (IEEE)
Operator mohammed hussein ,hussein ali
Test Equipment # Electrom # 784762
PP ID#

Off-line Test Data


Winding Resistance @20 °C
Lead 1-2 Ohms 0.999704
Lead 2-3 Ohms 1.000761
Lead 1-3 Ohms 0.998648
Max Delta R (%) 0.2
Volts µAmps MOhms@40°C
Meg. @.5min. 500 0.02174 11497
Meg. @1min. 500 0.01210 20657
DAR DAR = 1.80
Volts µAmps
Hipot 2450 0.05975

Pass/Fail Results
Surge PASS
MegOhm PASS
Hipot PASS
Hipot Step Test
Ohms Balance PASS
Off-line Equip. Rating PASS

iTIG Test Report Pro by Electrom Instruments 7.4.20 06-Oct-22 - 9:47:10 AM


Equipment Test Report

AC Off-line Surge - Summary

Recommended Voltage: 1144


Voltage Reached:
1143 / 1146 / 1162
Wave Difference P-P: 1
5.1% / 5% / 4.7%
Wave Difference L1-L2: 2.6% 2
Wave Difference L2-L3: 1.1%
Wave Difference L3-L1: 2.7% 3

Surge Result: PASS

0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
mSecs

iTIG Test Report Pro by Electrom Instruments 7.4.20 06-Oct-22 - 9:47:10 AM