Prepared for
10
Equipment Tested:
Seimens
jocky pump sun
Job #: Ud 1111-1392158-002-1
Equipment Information
Motor ID jocky pump sun Operating Volts 400
Equipment Tag J a sun RPM 2965
Location Suba norath fire fighing Power 32.1 kW
Manufacturer Seimens AC/DC AC
Test Information
Test Date/Time: 02-Oct-22 - 10:22:32
Winding Temp: 30 °C - Humidity: 30%
Job # Ud 1111-1392158-002-1
Test Description Stator
Test Stage Used - Incoming (IEEE)
Operator mohammed hussein ,hussein ali
Test Equipment # Electrom # 784762
PP ID#
Pass/Fail Results
Surge PASS
MegOhm PASS
Hipot PASS
Hipot Step Test
Ohms Balance PASS
Off-line Equip. Rating PASS
Megohm Trend
Dates Megohms
02-Oct-22 371