Professional Documents
Culture Documents
4.5%
4.0% Simulation
IEEE limit
3.5%
3.0%
2.5%
2.0%
1.5%
1.0%
0.5%
0.0%
5 7 11 13 17 19 23 25 29 31 35 37 41 43 47 49 53 55 59 61 65 67 71 73 77 79 83 85 89 91 95 97 10 10
1 3
harm_volt
3.5%
Simulation
3.0%
IEEE limit
2.5%
2.0%
1.5%
1.0%
0.5%
0.0%
5 7 11 13 17 19 23 25 29 31 35 37 41 43 47 49 53 55 59 61 65 67 71 73 77 79 83 85 89 91 95 97 101 103
Page 3
Graphs (PCC)
POWER : 15 MVA
Z: 8 %
DEMAND: 13000 kVA
Harmonic Calculator WEG Ie (Estimated Waveform)
V1.00 Isc: 16.4 kA
Copyright(C) 2009 WEG. All rights reserved. IL: 1137.2 Amp
6600 V Volts
VFD Rectifier
6 pulse Case Study: Company Name
12 pulse Estimated Results
% LOAD 10.66 %
18 pulse
Ie(1) 139.9 Amp
Ie RMS 146.4 Amp
Motor IL 1137.2 Amp
Motor Voltage (rms)
IEEE-519 THDi 32.49 %
3300 V Volts TDD 4.00 %
THDv 1.70 %
Motor Rated Current (rms)
Isc / IL 14.4
310.0 Amp
Motor Power
1523.8 kW
FP: 0.86
MotorPower: 1523823.66
Ni 0.953
PCCPower: 1598975.51
Fund_IL: 139.87
I_source: 1312.1597027037
freq: 60
L_pcc: 0.000616247939651819
limite_TDD: 5
limite_TDD: 0.05
ISC/IL: 14.4230769230769
pcc_power_kV 1598.97550837665
ctrl thdv 0
ctrl tdd 0
soma ctrl 0
0
amarelo 0
vermelho 0
Soma 12537.657667223
Raiz 111.971682434547
THD06p 1.70%
Queda% 6%
thdi 6P
32.49%
Harm_IL Queda Queda^2 18P Simu Harm_IL
0 0 0 0 0.0055% 0
0 0 0 0 0.0031% 0
9.38E+00 41.5266322413 1724.4611853039 0 0.0053% 0
6.12E+00 31.99506439555 1023.68414567536 0 0.0031% 0
0 0 0 17 1.4485% 2.03E+00
0 0 0 19 1.4667% 2.05E+00
1.49E+00 13.80240870704 190.506486116256 0 0.0014% 0
1.22E+00 12.24306404542 149.892617220232 0 0.0011% 0
0 0 0 0 0.0014% 0
0 0 0 0 0.0011% 0
7.22E-01 10.16484770338 103.324128832862 35 0.3847% 5.38E-01
6.73E-01 10.01507217198 100.301670610002 37 0.3820% 5.34E-01
0 0 0 0 0.0008% 0
0 0 0 0 0.0007% 0
3.84E-01 7.270407704314 52.8588281869507 0 0.0007% 0
3.29E-01 6.485530237914 42.062102466894 0 0.0006% 0
0 0 0 53 0.1765% 2.47E-01
0 0 0 55 0.1696% 2.37E-01
2.39E-01 5.669131898378 32.1390564812062 0 0.0005% 0
2.41E-01 5.923648562941 35.0896122972321 0 0.0006% 0
0 0 0 0 0.0005% 0
0 0 0 0 0.0005% 0
1.77E-01 5.049934708055 25.5018405556225 71 0.0976% 1.37E-01
1.58E-01 4.645577586007 21.5813911076071 73 0.0961% 1.34E-01
0 0 0 0 0.0005% 0
0 0 0 0 0.0005% 0
1.19E-01 3.972431642538 15.7802131546375 0 0.0004% 0
1.16E-01 3.965547812259 15.7255694513134 0 0.0004% 0
0 0 0 89 0.0619% 8.66E-02
0 0 0 91 0.0632% 8.84E-02
9.52E-02 3.639318948474 13.2446424087216 0 0.0004% 0
9.22E-02 3.598241446144 12.9473415047496 0 0.0004% 0
0 0 0 0 0.0004% 0
0 0 0 0 0.0004% 0
Soma 3559.10083137354
Raiz 59.6582000346435
THD12p 0.90%
6P 5% Fator
pol 12P ^2 pol 18P ^2
0.0248% 0.0000% 0.0055% 0.0000% 32.2400% 0.0008158
0.0036% 0.0000% 0.0031% 0.0000% 9.3030% 0.0004090
6.7073% 0.4499% 0.0053% 0.0000% 6.4880% 1.1222256
4.3728% 0.1912% 0.0031% 0.0000% 3.2980% 1.3162523
0.0049% 0.0000% 1.4485% 0.0210% 2.4750% 0.0022877
0.0062% 0.0000% 1.4667% 0.0215% 1.9100% 0.0035817
1.0662% 0.0114% 0.0014% 0.0000% 1.1190% 0.9857015
0.8701% 0.0076% 0.0011% 0.0000% 1.0990% 0.8848044
0.0012% 0.0000% 0.0014% 0.0000% 0.6788% 0.0019107
0.0010% 0.0000% 0.0011% 0.0000% 0.6289% 0.0016489
0.5160% 0.0027% 0.3847% 0.0015% 0.5246% 1.0760579
0.4809% 0.0023% 0.3820% 0.0015% 0.4207% 1.2343713
0.0005% 0.0000% 0.0008% 0.0000% 0.3982% 0.0014448
0.0019% 0.0000% 0.0007% 0.0000% 0.3397% 0.0060141
0.2748% 0.0008% 0.0007% 0.0000% 0.2824% 1.0612606
0.2352% 0.0006% 0.0006% 0.0000% 0.2727% 0.9369270
0.0005% 0.0000% 0.1765% 0.0003% 0.2105% 0.0027145
0.0010% 0.0000% 0.1696% 0.0003% 0.2058% 0.0054859
0.1707% 0.0003% 0.0005% 0.0000% 0.1790% 1.0229050
0.1725% 0.0003% 0.0006% 0.0000% 0.1590% 1.1440252
0.0004% 0.0000% 0.0005% 0.0000% 0.1545% 0.0026544
0.0011% 0.0000% 0.0005% 0.0000% 0.1362% 0.0086784
0.1264% 0.0002% 0.0976% 0.0001% 0.1258% 1.0786963
0.1131% 0.0001% 0.0961% 0.0001% 0.1199% 1.0200167
0.0003% 0.0000% 0.0005% 0.0000% 0.1019% 0.0029323
0.0008% 0.0000% 0.0005% 0.0000% 0.1008% 0.0089871
0.0850% 0.0001% 0.0004% 0.0000% 0.0896% 1.0263540
0.0829% 0.0001% 0.0004% 0.0000% 0.0832% 1.0715230
0.0001% 0.0000% 0.0619% 0.0000% 0.0811% 0.0016928
0.0008% 0.0000% 0.0632% 0.0000% 0.0731% 0.0115113
0.0681% 0.0000% 0.0004% 0.0000% 0.0707% 1.0486838
0.0659% 0.0000% 0.0004% 0.0000% 0.0668% 1.0712895
0.0659% 0.0000% 0.0004% 0.0000% 0.0668% 1.0712895
0.0659% 0.0000% 0.0004% 0.0000% 0.0668% 1.0712895
0
0 Limite I 0
0.00%
AMP% Limite IEEE THDi calculada
Harm_i_simu ao quadr
1.29% 3% 0 0.303601 0.092174
0.52% 3% 0 0.087074 0.007582
0.56% 3% 0 0.059768 0.003572
0.37% 3% 0 0.033221 0.001104
0.31% 3% 0 0.021238 0.000451
0.28% 3% 0 0.017261 0.000298
0.21% 3% 0 0.010817 0.000117
0.21% 3% 0 0.009834 9.67E-05
0.16% 3% 0 0.00641 4.109E-05
0.16% 3% 0 0.006056 3.668E-05
0.14% 3% 0 0.004795 2.299E-05
0.12% 3% 0 0.003896 1.518E-05
0.13% 3% 0 0.003676 1.352E-05
0.12% 3% 0 0.003186 1.015E-05
0.10% 3% 0 0.00259 6.707E-06
0.10% 3% 0 0.00251 6.3E-06
0.09% 3% 0 0.001991 3.963E-06
0.09% 3% 0 0.001894 3.589E-06
0.08% 3% 0 0.001669 2.785E-06
0.08% 3% 0 0.001508 2.274E-06
0.08% 3% 0 0.001397 1.953E-06
0.07% 3% 0 0.001268 1.608E-06
0.07% 3% 0 0.001172 1.372E-06
0.07% 3% 0 0.001108 1.229E-06
0.06% 3% 0 0.00095 9.03E-07
0.06% 3% 0 0.000944 8.904E-07
0.06% 3% 0 0.000829 6.864E-07
0.06% 3% 0 0.000774 5.984E-07
0.06% 3% 0 0.000749 5.615E-07
0.05% 3% 0 0.000693 4.796E-07
0.05% 3% 0 0.000649 4.212E-07
0.05% 3% 0 0.000615 3.785E-07
0.05% 3% 0 0.000615 3.785E-07
0.05% 3% 0 0.000615 3.785E-07
soma 0.105571
Limite V 0 raiz q 0.324917
IEEE-519 Recommended Practices for Applications with
Variable
Frequency Drives
Joable Andrade Alves & Paulo José Torri
WEG Automação S.A.
Introduction
The indirect frequency converters or variable frequency drives (VFDs) are usually composed of an input diode
rectifier stage. The three-phase full-wave bridge rectifier, also known as Graetz Bridge or six-pulse rectifier
(Figure 1) is one of the most used configurations for the input stage of VFDs. The currents drained by this
converter are of pulsed-type, containing low-order harmonics that may cause voltage harmonic distortion at the
electric power supply system where VFDs are connected. The voltage distortion is related to the magnitude of the
current harmonics of the electrical equipment and also to the network impedance, i.e., to the network capacity and
to the ratio between the installed drives capacity and the network capacity.
+
D1 D2 D3
D4 D5 D6
-
Other Loads
PCC
In several applications, the six-pulse variable frequency drive with an input line reactor or a DC reactor may
perfectly meet the IEEE-519 recommendations. When it is not possible, the following options are available for
reducing the harmonic currents:
1) Increase the number of pulses of the input rectifier using 12, 18 or even 24-pulse;
2) Use an active front-end rectifier (regen-drive).
The greater the number of pulses of the rectifier, the lower the current harmonic content at low frequencies. The
characteristic harmonics can be represented as follows:
h=P. n±1
n = 1, 2, 3, 4, ....¥
Where:
h : harmonic order
P : number of rectifier pulses
At the same time that the harmonic currents at low frequencies are reduced, there are other disadvantages in
increasing the number of rectifier pulses such as: the need of using phase-shifting transformers and increase on
the cost of the configuration. Particular attention needs to be given to the increase on the equipment complexity
and to the reduction on the efficiency and reliability of the whole system (due to the use of a larger number of
components).
20 of 35
Multipulse Configuration
In the industry, the term “multipulse”, when related to frequency converters, means the association, in series or in
parallel, of six-pulse three-phase rectifiers and the mandatory use of phase-shifting transformers to feed the
rectifiers. The fundamental idea of the multipulse configurations can be understood as the interconnection of six-
pulse rectifiers so that the characteristic harmonics generated by these rectifiers are cancelled by the harmonics
generated by other sets of rectifiers. This mitigation is performed by appropriate design of the phase-shifting
transformer with multiple secondaries. The harmonics of the six-pulse rectifier that are present on the secondary
of the transformer will be cancelled and will not appear at the primary of the transformer that is connected to the
utility.
h=6 . n±1
The magnitudes of these harmonics, in respect of the fundamental, are given by:
1
A h=
6 . n±1
The following figure shows the spectrum of these harmonics and their magnitude (as a percentage of the
fundamental).
100.0%
20.0%
14.3%
9.1% 7.7%
5.9% 5.3% 4.3% 4.0% 3.4% 3.2% 2.9% 2.7% 2.4% 2.3% 2.1% 2.0%
1 5 7 11 13 17 19 23 25 29 31 35 37 41 43 47 49
Figure 3 - Theoretic harmonic spectrum of the input current for a six-pulse rectifier.
The increase in the number of the rectifier pulses and the use of an appropriate phase-shifting transformer allow
the mitigation of the harmonic components at the primary of the transformer. Figure 4 shows the expected typical
waveforms of the input currents and their respective harmonic spectrum to the 6, 12 and 18-pulse configurations.
It is important to emphasize that the harmonics multiple of the 3rd are cancelled in a balanced three-phase
system (zero sequence).
In practice, however, the non-characteristic harmonics usually present a magnitude different from zero. This is
due to the pre-existing imperfections of the electrical system, such as, voltage unbalance, pre-existing harmonic
distortion, etc. Another factor that contribute to the appearance of non-characteristic harmonics is the transformer
imperfections, which blocks the mitigation of non-characteristic harmonics at the primary of the transformer.
The data presented in the following figures were obtained considering an ideal system. In the numerical
simulation the system was modeled as: power electric system, input impedance, rectifier, capacitive filter and load
(current source).
21 of 35
35.0%
30.0%
25.0%
20.0%
15.0%
10.0%
5.0%
0.0%
5 7 11 13 17 19 23 25 29 31 35 37 41 43 47 49 53 55 59 61 65 67 71 73 77 79 83 85 89 91 95 97 101 103
6-pulse
8.0%
7.0%
6.0%
5.0%
4.0%
3.0%
2.0%
1.0%
0.0%
5 7 11 13 17 19 23 25 29 31 35 37 41 43 47 49 53 55 59 61 65 67 71 73 77 79 83 85 89 91 95 97 101 103
12-pulse
1.8%
1.6%
1.4%
1.2%
1.0%
0.8%
0.6%
0.4%
0.2%
0.0%
5 7 11 13 17 19 23 25 29 31 35 37 41 43 47 49 53 55 59 61 65 67 71 73 77 79 83 85 89 91 95 97 101 103
18-pulse
Figure 4 - Typical input currents for the 6-pulse recifier or at the primary of the phase-shifting
transformer input (12 and 18-pulse) and their respective harmonic spectrum (harmonic
components expressed as a percentage of the fundamental).
22 of 35
IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power System:
IEEE-519
This recommendation (it is not a standard) prepared by IEEE describes the main factors that may cause harmonic
distortion, indicates the measurement methods and states the distortion limits.
The scope of this recommended practice is to analyze the harmonic distortion caused by all the loads (linear and
non-linear) at the Point of Common Coupling (PCC) and not the distortion caused by one individual device. The
main concern of IEEE is what the installation reflects to the other consumers connected to the same power supply
and not what occurs within the installation.
The distortion limits are different according to the voltage and short-circuit levels at the PCC. The higher the short-
circuit current (Isc) in respect of the load current, the higher the admissible current distortion, since they will cause
a lower voltage distortion at the PCC. As the voltage level increases, the acceptable limits decrease.
The TDD – Total Demand Distortion – is defined as the current harmonic distortion, in percentage of the
maximum demand load current (15 or 30 minutes demand). This means that the TDD shall be measured at the
peak consumption.
Tables 10.2 and 10.3, obtained from IEEE-519, show the recommended limits for the THDv (Total Voltage
Harmonic Distortion) and for the TDD (Total Demand Distortion).
General
Special Dedicated
Applications* System**
System
Notch Depth 10% 20% 50%
THD (Voltage) 3% 5% 10%
Notch Area [V*us] 16400 22800 36500
In section 10.2 (Development of Current Distortion Limits), of IEEE-519, it is established 3% as the individual limit
of the voltage components at PCC in respect of its fundamental component.
IEEE-519 - Table 10.3 - “Current Distortion Limits for General Distribution Systems”.
The table 10.3 is applicable to six-pulse rectifiers and general distortion situations. However, when phase shift
transformers or converters with pulse numbers higher than six are used, the limits for the characteristic harmonic
orders are increased by a factor equal to: 1.414 for 12-pulse and 1.732 for 18-pulse.
Although the IEEE-519 is not a standard, this recommendation is being used as a reference to specify the
harmonic distortion limits allowed by the utility companies and in the design of industrial power systems.
23 of 35
Case Study: Company Name date: 7-Sep-22
This case study aims to show how to obtain, in a simple way and with a good precision, the Voltage Harmonic
Distortion (THDv) and the Total Demand Distortion (TDD) values for a system composed of a main bus bar with
known power and impedance, feeding a non-linear load with an input rectifier with the specified number of pulses.
This is a simple study, since practical aspects are being disregarded such as: the network is not ideal, phase
unbalance, influence of other loads connected to the PCC, transmission line impedance, system efficiency, etc.
The values presented herein are useful for a preliminary analysis of the harmonic distortion level of the system.
For a complete analysis, taking in account all the variables listed above, it is necessary to perform a numerical
simulation.
PCC Data
Power Capacity: 15.00 MVA
Source reactance (%): 8.00 %
Voltage: 6600 Volts
Demand Current (IL): 1137 A
Short-circuit Current (Isc): 16.40 kA
Ratio Isc/IL: 14.42
VFD System
Rectifier: 6 pulse
Considering that the fundamental is the only component that provides active power to the motor, it is possible to
calculate its value at the PCC by taking in account the typical motor displacement power factor - cos(f). With the
calculated fundamental component, the theoretical harmonic components of the current at the PCC can be known
as a function of the number of pulses of the rectifier.
√∑
∞ Where:
I 2n In are the harmonic components of the PCC current
n=2
THDi =
I ( 1) I(1) is the fundamental component of the PCC current
24 of 35
The TDD is calculated as the current harmonic distortion at the PCC in respect of its demand current (IL):
√
∞
∑ I 2n
n=2
TDD=
IL
With the given power and impedance (%) it is possible to calculate the physical inductance (L) at the PCC and,
therefore, calculate the voltage drops caused by the components of the current harmonics.
V n =I n . ( 2 . π . F n ) . L Where:
√∑
∞
V 2n Fn are the characteristic harmonic frequencies
n=2
THDV = Vn are the harmonic components of the voltage at the PCC
V (1 )
V(1) is the fundamental component of the voltage at the PCC
The results of the harmonic analysis are presented in the following table. These calculations were performed up
to the 100th harmonic.
Final Results
% of load 10.66 % Ratio between the load power and the PCC capacity
Ie(1) 139.87 A RMS value of the fundamental component of the current Ie
Ie RMS 146.44 A RMS value of the Ie current
IL 1137.21 A RMS value of the demand current at PCC
THDi 32.49 % Harmonic current distortion of the current Ie
Total Demand Distortion (considering IL as the demand current)
TDD 4.00 %
Meets IEEE-519 Isc/IL = 14 the limit is: 5%
Voltage Harmonic Distortion at the PCC
THDv 1.70 %
Meets IEEE-519 including for 'Special Applications'
4.5%
Simulation
4.0%
2.5%
2.0%
1.5%
1.0%
0.5%
0.0%
5 7 11 13 17 19 23 25 29 31 35 37 41 43 47 49 53 55 59 61 65 67 71 73 77 79 83 85 89 91 95 97 101 103
Observing figure 5 it can be concluded that: Meets IEEE 519 - table 10.3
25 of 35
3.5%
3.0%
Simulation
2.5%
IEEE limit
2.0%
1.5%
1.0%
0.5%
0.0%
5 7 11 13 17 19 23 25 29 31 35 37 41 43 47 49 53 55 59 61 65 67 71 73 77 79 83 85 89 91 95 97 101 103
Figure 6 - Individual Voltage Harmonics expressed as a percentage of the fundamental voltage at the PCC.
Summary
Individual Limit for the Voltage Harmonics at the PCC: Meets the individual limit of 3%
References
[1] PAICE, DEREK A., "POWER ELETRONIC CONVERTER HARMONICS - MULTIPULSE METHODS
FOR CLEAN POWER", IEEE PRESS, USA, 1996
[2] IEEE, "IEEE RECOMMENDED PRACTICES AND REQUIREMENTES FOR HARMONIC CONTROL
IN ELECTRICAL POWER SYSTEMS - IEEE-519", IEEE PRESS, USA, 1993
[4] ALVES, JOABLE A., & HORNBURG, EDSON, "HIGH AND LOW ORDER HARMONICS FOR
FREQUENCY INVERTERS", ANAIS DO VI INDUSCON, JOINVILLE-BRASIL, 2004
(in portuguese)
[5] ROSSA, A. J. & TORRI, P. J., “EFEITOS DA DISTORÇÃO HARMÔNICA DA REDE ELÉTRICA
SOBRE MOTORES ELÉTRICOS”, REVISTA ELETRICIDADE MODERNA, ANO XXIX, Nº 324,
BRASIL, 2001 (in portuguese)
26 of 35
Atendimento a Recomendação IEEE-519 em Aplicações
com
Inversores de Freqüência
Joable Andrade Alves & Paulo José Torri
WEG Automação S.A.
Introdução
+
D1 D2 D3
D4 D5 D6
-
Outras Cargas
PCC
Fig. 2 - Distorção da tensão provocada por correntes drenadas por uma carga não-linear
Em muitas aplicações, o inversor de freqüência com retificador de 6 pulsos adicionado a uma reatância na
entrada ou um indutor no barramento CC atende perfeitamente as recomendações da IEEE-519. Quando isto
não é possível, algumas das soluções disponíveis para redução das correntes harmônicas são o aumento do
número de pulsos do retificador utilizando 12, 18 ou até 24 pulsos ou a utilização de retificadores de entrada
ativos (regenerativos).
Quanto maior o número de pulsos do retificador menor o conteúdo harmônico da corrente nas baixas
freqüências. As harmônicas características podem ser expressas por:
h=P. n±1
n = 1, 2, 3, 4, ....¥
Onde:
h : ordem da harmônica
P : número de pulsos do retificador
27 de 35
Estruturas Multi-pulsos
Na indústria, o termo multi-pulsos relacionado a inversores de freqüência tem conotação com a associação, em
série ou paralelo, de retificadores trifásicos de 6 pulsos e a obrigatória utilização de transformadores
defasadores para alimentá-los. A idéia básica das estruturas multi-pulsos pode ser entendida como a conexão
de retificadores de 6 pulsos de tal forma que as harmônicas características geradas por estes retificadores
sejam canceladas pelas harmônicas geradas por outros conjuntos de retificadores. Este cancelamento é
possível pelo adequado projeto do transformador defasador com múltiplos secundários. As harmônicas dos
retificadores de 6 pulsos estão presentes nos secundários, são canceladas no transformador e não aparecem
no primário que está conectado a rede.
h=6 . n±1
As amplitudes destas harmônicas, relativas a componente fundamental, são dadas por:
1
A h=
6 . n±1
O gráfico seguinte ilustra o espectro destas harmônicas e a sua amplitude expressa em percentual da
componente fundamental.
100.0%
20.0%
14.3%
9.1% 7.7%
5.9% 5.3% 4.3% 4.0% 3.4% 3.2% 2.9% 2.7% 2.4% 2.3% 2.1% 2.0%
1 5 7 11 13 17 19 23 25 29 31 35 37 41 43 47 49
Cabe ressaltar que as harmônicas de ordem múltiplas de 3 são canceladas em um sistema trifásico equilibrado
(seqüência zero).
Na prática, no entanto, as harmônicas não características normalmente apresentam uma amplitude diferente de
zero. Isto se dá devido às imperfeições já presentes na rede elétrica, tais como, desequilíbrio de tensões,
distorções harmônicas pré-existentes, etc. Outros fatores que contribuem para o aparecimento de harmônicas
não características são as imperfeições do transformador, as quais impedem o perfeito cancelamento destas no
primário do mesmo.
Os dados apresentados nas figuras seguintes foram obtidos considerando a perfeita idealidade do sistema. Na
simulação numérica o sistema foi modelado como: rede de alimentação, impedância de entrada, retificador, filtro
capacitivo e carga (fonte de corrente).
28 de 35
35.0%
30.0%
25.0%
20.0%
15.0%
10.0%
5.0%
0.0%
5 7 11 13 17 19 23 25 29 31 35 37 41 43 47 49 53 55 59 61 65 67 71 73 77 79 83 85 89 91 95 97 101 103
6 pulsos
8.0%
7.0%
6.0%
5.0%
4.0%
3.0%
2.0%
1.0%
0.0%
5 7 11 13 17 19 23 25 29 31 35 37 41 43 47 49 53 55 59 61 65 67 71 73 77 79 83 85 89 91 95 97 101 103
12 pulsos
1.8%
1.6%
1.4%
1.2%
1.0%
0.8%
0.6%
0.4%
0.2%
0.0%
5 7 11 13 17 19 23 25 29 31 35 37 41 43 47 49 53 55 59 61 65 67 71 73 77 79 83 85 89 91 95 97 101 103
18 pulsos
29 de 35
Recomendação IEEE para práticas e requisitos para controle de harmônicas no sistema elétrico de
potência: IEEE-519
Esta recomendação (não é uma norma) produzida pelo IEEE descreve os principais fenômenos causadores de
distorção harmônica, indica métodos de medição e limites de distorção.
Seu enfoque é a análise da distorção harmônica no Ponto de Conexão Comum (PCC) das cargas (lineares ou
não-lineares) e não em cada equipamento individual. A filosofia é que não interessa ao sistema o que ocorre
dentro de uma instalação, mas sim o que ela reflete para o exterior, ou seja, para os outros consumidores
conectados à mesma alimentação.
Os limites diferem de acordo com o nível de tensão e com o nível de curto-circuito do PCC. Quanto maior for a
corrente de curto-circuito (Isc) em relação à corrente de carga, maiores são as distorções de corrente
admissíveis, uma vez que elas distorcerão em menor intensidade a tensão no PCC. À medida que se eleva o
nível de tensão, menores são os limites aceitáveis.
A grandeza TDD - Total Demand Distortion - é definida como a distorção harmônica da corrente, em % da
máxima demanda da corrente de carga (demanda de 15 ou 30 minutos). Isto significa que a medição da TDD
deve ser feita no pico de consumo.
As tabelas 10.2 e 10.3, extraídas da IEEE-519, apresentam os limites recomendados de THDv (Total Harmonic
Distortion) da tensão e TDD (Total Demand Distortion).
General
Special Dedicated
Applications* System**
System
Notch Depth 10% 20% 50%
THD (Voltage) 3% 5% 10%
Notch Area [V*us] 16400 22800 36500
Na seção 10.2 (Development of Current Distortion Limits), desta norma, é estabelecido 3% como o limite
individual das harmônicas de tensão no PCC em relação a sua fundamental.
IEEE-519 - Table 10.3 - “Current Distortion Limits for General Distribution Systems”.
A tabela 10.3 é aplicável para retificadores com 6 pulsos. Para retificadores com 12 pulsos, deve-se multiplicar
os limites individuais por 1.414. No caso de retificadores com 18 pulsos estes limites devem ser multiplicados
por 1.732 .
Apesar de não ser uma norma, a IEEE-519, tem sido utilizada como base para a especificação dos limites de
distorções harmônicas por concessionárias do setor elétrico e em projetos de plantas industriais.
30 de 35
Estudo de Caso: Company Name Data: 7-Sep-22
Este estudo de caso tem como objetivo mostrar como obter, de maneira simples e com um bom grau de
precisão, os valores das taxas de distorção harmônica da tensão (THDv) e da TDD, em um sistema formado por
uma barra com potência instalada e impedância definidas, alimentando uma carga não-linear com um retificador
de entrada com número de pulsos especificado. Este estudo é simplificado pois não estão sendo considerados
aspectos práticos como não idealidades da rede, desbalanceamentos entre as fases de alimentação, a
influência de outras cargas conectadas ao PCC, impedâncias da linha de transmissão, rendimento do
acionamento, etc. Os valores calculados são úteis para se obter uma idéia inicial das distorções harmônicas no
sistema apresentado. Para uma análise completa, considerando todos os aspectos apresentados é necessário
conhecer todas as variáveis e realizar uma simulação numérica do sistema completo.
As tensões e correntes estão expressas em valores eficazes.
Acionamento
Retificador: 6 pulsos
Considerando que a componente fundamental é a única a fornecer potência ativa para o motor, pode-se calcular
o valor desta no PCC, considerando o cos(f) típico do motor. Com a componente fundamental calculada, as
componentes harmônicas teóricas da corrente no PCC são conhecidas em função do número de pulsos do
retificador.
√
∞ onde:
∑ In 2
In são as componentes harmônicas da corrente no PCC
n=2
THDi = I(1) é a componente fundamental da corrente no PCC
I ( 1)
31 de 35
A TDD será calculada como sendo a distorção harmônica da corrente no PCC em relação a corrente de
demanda no mesmo (IL):
√∑
∞
I 2n
n=2
TDD=
IL
Com a potência, tensão e impedância % dadas, é possível calcular a indutância física (L) no PCC e assim,
calcular as quedas de tensão provocadas pelas componentes harmônicas da corrente.
V n =I n . ( 2 . π . F n ) . L onde:
√∑
∞
2 Fn são as freqüências harmônicas características
Vn
n=2 Vn são as componentes harmônicas da tensão no PCC
THDV =
V (1 ) V(1) é a componente fundamental da tensão no PCC
Os resultados obtidos pelas expressões apresentadas estão compilados na tabela seguinte. Os cálculos foram
efetuados com até a 100ª hamônica.
Resultados Obtidos
% carga 10.66 % Relação entre a potência da carga pela potência instalada do PCC
Ie(1) 139.87 A Valor eficaz da componente fundamental da corrente Ie
Ie RMS 146.44 A Valor eficaz da corrente Ie
IL 1137.21 A Valor eficaz da corrente de demanda no PCC
THDi 32.49 % Distorção harmônica da corrente Ie
Total Demand Distortion
TDD 4.00 %
ATENDE IEEE-519 Isc/IL = 14 o limite é: 5%
Distorção harmônica da tensão no PCC
THDv 1.70 %
Atende IEEE-519 inclusive para 'Special Applications'
4.5%
Simulação
4.0%
2.5%
2.0%
1.5%
1.0%
0.5%
0.0%
5 7 11 13 17 19 23 25 29 31 35 37 41 43 47 49 53 55 59 61 65 67 71 73 77 79 83 85 89 91 95 97 101 103
32 de 35
3.5%
3.0%
Simulação
2.5%
Limite IEEE
2.0%
1.5%
1.0%
0.5%
0.0%
5 7 11 13 17 19 23 25 29 31 35 37 41 43 47 49 53 55 59 61 65 67 71 73 77 79 83 85 89 91 95 97 101 103
Resumo
Referências
[1] PAICE, DEREK A., "POWER ELETRONIC CONVERTER HARMONICS - MULTIPULSE METHODS
FOR CLEAN POWER", IEEE PRESS, USA, 1996
[2] IEEE, "IEEE RECOMMENDED PRACTICES AND REQUIREMENTES FOR HARMONIC CONTROL
IN ELECTRICAL POWER SYSTEMS - IEEE-519", IEEE PRESS, USA, 1993
[4] ALVES, JOABLE A., & HORNBURG, EDSON, "HIGH AND LOW ORDER HARMONICS FOR
FREQUENCY INVERTERS", ANAIS DO VI INDUSCON, JOINVILLE-BRASIL, 2004
[5] ROSSA, A. J. & TORRI, P. J., “EFEITOS DA DISTORÇÃO HARMÔNICA DA REDE ELÉTRICA
SOBRE MOTORES ELÉTRICOS”, REVISTA ELETRICIDADE MODERNA, ANO XXIX, Nº 324,
BRASIL, 2001
33 de 35
34 de 35
35 de 35