Professional Documents
Culture Documents
BS 1:2002
Fire
detection and Alarm systems for
Buildings-
Code of practice for system design, installation and servicing
1. GENERAL
BS 5839:Part 1:2002 like its predecessor provides guidance by
recommendations from
the initial Planning Stage, through the Design, Installation,
Commissioning and
Final Maintenance of Fire Alarm Systems in and around buildings
other than
Domestic Dwellings, these being covered by Part 6 of the
Standard.
2. CATEGORIES OF SYSTEM
BS 5839:Part 1:2002 like the 1988 Standard Categorises Fire
Alarm Systems to satisfy
one, or both, of two principle objectives…
The Protection of Life and The Protection of Property.
Life
L1:Automatic Protection Throughout the Premises.
L2:Automatic Protection as L3, but also including Defined
areas of High Risk.
L3:Automatic Protection along Escape Routes and all Rooms
opening onto these
Escape Routes.
M:Manual. (Manual Call Point)
Property
P1:Automatic Protection Throughout the Premises.
P2:Automatic Protection in Defined Areas of High Risk.
M or Manual.
These systems purely rely on possibly the most reliable and
effective
Fire Detection device for the protection of life in existence!
i.e. A Human Being.
Consequently this type of system requires the need of
Manual Call Point
“Break Glass” Units.
3. POSITIONING OF EQUIPMENT
There have been no discernable changes in the new standard
regarding the spacing and
coverage of Automatic Fire Detectors.
i.e.
0
Both the New and Old Standards recommend that there be at least
2 off individual
Alarm Sounder Circuits within the protected premises, even if only
1 sounder was on
the second circuit. This recommendation allows that in the event of
a Sounder Circuit
Failure that at least an alarm sounder would operate to draw the
attention of the building
occupants to a Fire Condition.
5. CONTROL EQUIPMENT
BS5839:Part 1:2002 recommends that the Control and Indicating
Equipment used for
Fire Alarm Systems, including their associated power supplies
should confirm to the
requirements of EN54 Parts 2 and 4.
The practical use of this type of networked system may reduce
the cabling for the entire
system as the remote panels can be located within specific areas of
the buildings,
particularly adjacent to the areas to which the connected detection
loops are protecting.
6. CABLING
Unlike the earlier standard where the use of Non-Fire Rated
Cabling would have been
acceptable for the Detection Circuits and Fire Rated Cables used
for the
Alarm Circuits. The 2002 standard recommends the use of Fire
Rated Cables for Critical
Signal Paths, this includes both the Detection and Alarm Circuits.
Even though the
Indicating and Control Equipment is provided with means of a
“Standby Supply”
(i.e. Battery Backup) the normal Electrical Mains Supply to the
equipment is now
considered as a Critical Circuit and consequently should be
adequately protected from the
effects of fire.
7. REMOTE MONITORING
BS 5839:Part 1:2002 has identified possible inherent faults with
the current methods
of providing Fire Alarm Activations to Remote Monitoring Centres
by means of
Digital Communicators and consequently provides the
recommendations to alleviate the
short comings of current equipment;
The standard as previously stated does not identify the need for a
fire alarm system. This
is the responsibility of the purchaser, be they a Developer or Final
User of a building. This
process will evolve consultation with the Fire Authorities, Building
Control Officers and Insurers.
The ultimate responsibility for the need and category of the system
solely rest with the
purchaser. However the designer can propose a category should the
situation arise. But
the final decision must be taken by the client/purchaser.
The proposed new Fire Alarm System must take into account all
the findings of the
provided Risk Assessment which has identified the category of the
new system. Vital
importance in the design is the need to identify and
resolve/eliminate any potential causes
of false alarms.
9. INSTALLATION
BS 5839:Part 1:2002 in keeping with the recommendation about
responsibilities for both
the Purchaser/Client/User as well as the system Designer has also
identified the need for
the Competency and subsequent responsibilities for both the
Installation and
Commissioning Engineers.
The standard also calls for the mains supply to the Indicator and
Control Equipment and
any other relevant supplies associated with the Fire Alarm System
should be tested for
both Earth Continuity and Earth Fault Loop Impedance.
The field wiring and most particularly Loop Wiring to be tested for
Circuit Resistance.
All these test must be recorded for the system final documentation
plus a copy of the
results must also be forwarded to the commissioning engineer.
Once the installation and test are completed the installation
engineer would sign of the
system and provide the next Certificate for the system, the
Installation Certificate.
10. COMMISSIONING
Once the Fire Alarm System has been installed the system should
be set-up and
functionally tested, the commission.
During the commission the engineer would also inspect and check
the suitability of the
Mains Supply, Standby Power (i.e. Battery Backup) functions
correctly both on and off
load and has sufficient backup capacity. There is also a
recommendation that the batteries
are labelled with the date of installation.
The engineer would also check that the correct/specified cable has
been installed
(as as far as it is reasonably practical to ascertain), as well as the
workmanship of the
installation.
The Health & Safety (Safety Signs & Signals) Regulations 1996
requires that
Fire Alarm warning system must be provided with a guaranteed
emergency supply in
event of interruption of the normal mains supply, unless the hazard
has thereby been
eliminated. Consequently systems not having a standby power
supply
(i.e. Battery Backup) are no longer legal!