You are on page 1of 4

PROJECT : PAGE :

CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Anchorage to Pedestal Design Based on ACI 318-19 & AISC 360-10/16

INPUT DATA & DESIGN SUMMARY


CONCRETE STRENGTH fc' = 4 ksi, (28 MPa)
SPECIFIED STRENGTH OF ANCHOR futa = 65 ksi, (448 MPa)
BASE PLATE YIELD STRESS fy = 36 ksi, (248 MPa)
CRITICAL BASE PLATE CANTILEVER m= 3.3 in, (84 mm)

FACTORED AXIAL LOAD AT WORK POINT Pu = 150 kips, (667.2 kN)


FACTORED SHEAR LOAD AT WORK POINT Vu = 16 kips, ( 0 if shear lug used), (71.2 kN)
FACTORED MOMENT AT WORK POINT Mu = 120 ft-kips, (163 kN-m)
ANCHOR LOCATION TO WORK POINT
EFFECTIVE EMBEDMENT DEPTH hef = 28 in, (711 mm) Anchor X (in) Y (in) ( 1 in = 25.4 mm )
ANCHOR DIAMETER d= 1 in, (25 mm) 1 -8 8 1

BASE PLATE THICKNESS t= 1.75 in, (44 mm) 2 -8 0 1

SEISMIC LOAD ? (ASCE 14.2.2.17) == > Yes 3 -8 -8 1

PEDESTAL VERTICAL REBAR SIZE # 7 4 8 8 1

PEDESTAL HORIZONTAL SECTION AREA A2 = 576 in2 5 8 0 1

( 3716.1 cm2) 6 8 -8 1

BASE PLATE SIZE - 20 in x 20 in x 1.75 in (thk.)


Corner X (in) Y (in)
1 -9.75 -9.75 Edge = 1.75 in, (44 mm)
2 -9.75 9.75 (AISC 360 Tab J3.4 & J3.5)
3 9.75 9.75 A1 = 400 in2, base plate area
4 9.75 -9.75 ( 2580.6 cm2)
-9.75 -9.75 3 3

THE BASE PLATE & GROUP ANCHORS DESIGN IS ADEQUATE.

ANALYSIS
CHECK FLEXURAL & AXIAL COMPRESSION CAPACITY OF ANCHORED CONCRETE (ACI 318-19 21 & 22)

1200

1000

f Pn (k) 800

600

400

200

0
0 50 100 150 200 250 300 350

f Mn (ft-k)
(cont'd)
f Mn = 246 ft-kips @ Pu = 150 kips
> M u, c = '
2f C  
0.85Min  A2 , 2  , E c  57 f C' , E s  29000ksi
123 ft-kips to center of base plate
o 
[Satisfactory] Ec A
 1 
f Pmax = 972 kips        
2

> Pu = 0.85Min  A2 , 2  f C'  2   c     c   , for 0   c   o


150 ft-kips [Satisfactory]  
  A1     o    o  
fC
Nua,1 = 12.50 kips   A2 
0.85Min  , 2  f C' , for  c   o
(The 2.5 times max tension, ASCE 14.2.2.17) A
  1 

fp =
 s E s , for  s   y
4.42 ksi, the max possible concrete compression stress. fS 
(ACI 318-19 22.8.3.2 & 21.2.1, or AISC Guide - 1)  f y , for  s   y

DETERMINE EACH ANCHOR FORCES WITHOUT CONCTERE COMPRESSION CAPCAITY CONSIDERED

Anchor X (in) Y (in) XCG2 YCG2 Nua, 2 Vua


1 -8 8 64 64 5.00 2.67
2 -8 0 64 0 5.00 2.67 XCG = 0 in
3 -8 -8 64 64 5.00 2.67 YCG = 0 in
4 8 8 64 64 -55.00 2.67
5 8 0 64 0 -55.00 2.67 Pu,CG = 150.0 kips
6 8 -8 64 64 -55.00 2.67 Vu,CG = 16.0 kips
Mu,CG, X = 120.0 ft-kips
Mu,CG, Y = 0.0 ft-kips

S 384 256 -150 16

CHECK GOVERNING ANCHOR TENSILE STRENGTH (ACI 318 17.4.1.2)

 N sa   A se , N  f uta  = 29.54 kips > Nua = Max( Nua,1 , Nua,2 ) = 12.50 kips [Satisfactory]

where : f = 0.75 x 1 = 0.75 , (ACI 318-19 17.2.3.4.4)


Ase,N = 0.606 in2

CHECK GOVERNING ANCHOR SHEAR STRENGTH (ACI 318 17.5.1.2 & 17.2.3.5.3)

V sa   0.6 Ase , N f ut = 15.36 k > Vua = 2.67 kips [Satisfactory]

where : f = 0.65 x 1 = 0.65


(for built-up grout pads, first factor shall be multiplied by 0.8, ACI 318 17.5.1.3)

CHECK TENSION AND SHEAR INTERACTION OF GOVERNING ANCHORS : (ACI 318 17.6)
Since Nua,2 < 0.2 f and
Nn
Vua,2 < 0.2 f Vn the full tension design strength is permitted.

The interaction equation may be used

N ua ,2 V ua ,2
  0.34 < 1.2 [Satisfactory]
Nn V n
(cont'd)
CHECK BASE PLATE THICKNESS (AISC Guide - 1, Eq. 3.3.14a)

f p <
1.73 in t= 1.75 in [Satisfactory]
t reqD  1.5m 
Fy
CHECK SPLICE LENGTH OF TENSION ANCHOR WITH REBAR
Ls = 1.3 Ld = 19 db = 19 in, (ACI 318-19 25.5)
< hef - 2" = 26 in [Satisfactory]
 
 3   d f 
L d  MAX  , 12 in  
t e s b y
14 db =
requird
14 in
  provided  K  
 40 f 'c  c b tr   (ACI 318-19 25.4.2.3)
  db  

where r required / r provided = 0.423 ( A s,reqd / A s,provd , if not apply input zero, ACI 318-19 25.4.10.1)
db = 1 in, anchor governing
fy = 65 ksi
yt = 1.0 (1.3 for horizontal bar over 12" concrete, ACI 318-19 25.4.2.4)
ye = 1.0 (1.2 for epoxy-coated, ACI 318-19 25.4.2.4)
ys = 1.0 (0.8 for # 6 or smaller, 1.0 for other)
l = 1.0 (0.75 for light weight, ACI 318-19 25.4.2.4)
cb = 2.3 , (ACI 318-19 25.4.2)
Ktr = (Atr fyt / 1500 s n) = 0 (ACI 318-19 25.4.2.3)
(cb + Ktr ) / db = 2.3 < 2.5 , (ACI 318-19 25.4.2.3)
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Concrete Column Design Based on ACI 318-05

INPUT DATA & DESIGN SUMMARY


CONCRETE STRENGTH fc' = 4.8 ksi

REBAR YIELD STRESS fy = 54.167 ksi
COLUMN DIMENSIONS cx = 20 in
cy = 20 in 
Pu 
FACTORED AXIAL LOAD = 150 k
FACTORED MAGNIFIED MOMENT Mu,x = 123.13 ft-k
Mu,y = ft-k
FACTORED SHEAR LOAD Vu,x = k

Vu,y = 16 k
COLUMN VERT. REINF. 3 # 8 at x dir.
(Total 6 # 8)
2 # 8 at y dir.
SHEAR REINF. 10 legs,# 4 @ 2 in o.c., x dir. THE COLUMN DESIGN IS ADEQUATE.
10 legs,# 4 @ 2 in o.c., y dir.

ANALYSIS 
2 0.85 f '
C  '
o  , E c  57 f C
, E s  29000ksi
1200 Ec
       2
 c  c  ,
0.85 f C  2  for 0   c   o
'
  
1000 fC    o    o  
 '
0.85 f C , for  c   o

800

f Pn (k)  s E s , for  s   y

fS
 f , for  s   y
600  y
f Pn (kips) f Mn (ft-kips)
400
AT AXIAL LOAD ONLY 972 0
AT MAXIMUM LOAD 972 105
AT 0 % TENSION 748 204
200
AT 25 % TENSION 643 235
AT 50 % TENSION 553 254
0
0 50 100 150 200 250 300 350
AT e t = 0.002 399 274
AT BALANCED CONDITION 392 275
f Mn (ft-k) AT e t = 0.005 305 327
AT FLEXURE ONLY 0 168
CHECK FLEXURAL & AXIAL CAPACITY
Mu = ( Mu,x2 + Mu,y2 )0.5 = 123.125 ft-k, (combined bending load.) q = 0.00 o
, (the direction of combined load.)
f Pmax =0.80 f [ 0.85 fc' (Ag - Ast) + fy Ast] = 972.09 kips., (at max axial load, ACI 318-05, Sec. 10.3.6.2)
where f = 0.65 (ACI 318-05, Sec.9.3.2.2) > Pu [Satisfactory]
Ag = 400 in2. Ast = 4.74 in2.
a = Cbb1 = 9 in (at balanced strain condition, ACI 10.3.2)
f = 0.48 + 83 et = 0.652 (ACI 318-05, Fig. R9.3.2)

where Cb = d ec / (ec + es) = 11 in et = 0.002069 ec = 0.003

d = 18.5 in, (ACI 7.7.1) b1 = 0.81 ( ACI 318-05, Sec. 10.2.7.3 )


f Mn = 0.9 M n = 168 ft-kips @ Pn = 0, (ACI 318-05, Sec. 9.3.2) ,& et,min = 0.004, (ACI 318-05, Sec. 10.3.5)
f Mn = 246 ft-kips @ Pu = 150 kips > Mu [Satisfactory]
r max = 0.08 (ACI 318-05, Section 10.9) rprovd = 0.012
rmin = 0.01 (ACI 318-05, Section 10.9) [Satisfactory]

CHECK SHEAR CAPACITY (ACI 318-05 Sec. 11.1.1, 11.3.1, & 11.5.6.2)
f Vn = f (Vs + Vc) (ACI 318-05 Sec. 11.1.1)
> Vu [Satisfactory]
where f = 0.75 (ACI 318-05 Sec. 9.3.2.3) fy = 54.166667 ksi

d A0 Av Vc = 2 (fc') A0
0.5
Vs = MIN (d fy Av / s , 4Vc) f Vn
x 17.50 350 2.00 48.5 194.0 182
y 17.50 350 2.00 48.5 194.0 182

smax = 16 (ACI 318-05, Section 7.10.5.2) sprovd = 2 in


smin = 1 (ACI 318-05, Section 7.10.4.3) [Satisfactory]