Standard Operation Procedure Upload

and Upgrade software delta system


ESOA300-HAF-Series
Date: March. 21, 2018
Field Application Engineer
Contents

1 Outdoor Power System Overview

2 Comparison setup configuration

3 Upgrade SW ( Firmware version Orion Controller)

4 Upload & Activated New Parameter setup

5 Create the battery parameter without 3 type purpose

5 How to setup LVBD and LVLD disconnect


System Overview
 ESOA300-HAF01(Master Cabinet) & Slave Cabinet

Delta Confidential
System Controller
128 x 64 LCD
Dots Display
 Orion system controller Internet Web Server
Function port

Handle
Alarm LED x 5

EXIT Down
Lock

Up Enter

Delta Confidential
Comparison setup configuration

 Comparison setup configuration


Description Last Version New Version Remarks

Trigger of LVLD & LVBD - LVLD Disconnect+Hysteresis - LVLD Re-connect (recover): Usys As Indosatooredoo
Re-Covery (Reconnect) - LVBD disconnect+Hysteresis > 47V & AC mains recover Require
- LVBD Re-connect (recover): Usys
> 44V & AC mains recover
Ac1, Ac2 & Ac 3 records N/A Create In Data log record Implement since
2015

Battery parameter - 10% (C10) current limit - 10% (C10) current limit Charging -As Indosatooredoo
- Equalize duration 1440 - Add the new Type brand Battery Require
LEOCH, the file setup config - Create 6setup
become 15 File. parameter file for
LEOCH Battery
MOM with
Indosatooredoo
and Hariff at sept
2018
Data log interval time 1 Second 10 second

Delta Confidential
Setup Configuration File Information
 File setup application
File Name Battery System Remarks
Application Application

ESOA300-HAF02 3 brand battery ESOA300-HAF02 15 file Setup parameter


Narada170,
Shotto180 &
NSB170
CFG_ESOA300-HAF01 Narada GFM 170FT 3M 2B-V5.xml 2bank Narada 170 3Module 15 file setup base on battery
CFG_ESOA300-HAF01 Narada GFM 170FT 4M 3B-V5.xml 3bank Narada 170 4Module type and module
CFG_ESOA300-HAF01 Narada GFM 170FT 5M 3B-V5.xml 4bank Narada 170 5 or full Module configuration
CFG_ESOA300-HAF01 Northstar NSB 170FT+ 3M 2B-V5.xml 2bank NSB 170 3Module
CFG_ESOA300-HAF01 Northstar NSB 170FT+ 4M 3B-V5.xml 3bank NSB 170 4Module
CFG_ESOA300-HAF01 Northstar NSB 170FT+ 5M 4B-V5.xml 4bank NSB 170 5 or full Module
CFG_ESOA300-HAF01 Shoto FMX 180FT 3M 2B-V5.xml 2bank Shotto 180 3Module
CFG_ESOA300-HAF01 Shoto FMX 180FT 4M 3B-V5.xml 3bank Shotto 180 4Module
CFG_ESOA300-HAF01 Shoto FMX 180FT 5M 4B-V5.xml 4bank Shotto 180 5 or full Module
CFG_ESOA300-HAF02 LEOCH LPF12-180AH 3M 2B-V5.xml 2bank leoch 180 3Module
CFG_ESOA300-HAF02 LEOCH LPF12-180AH 4M 3B-V5. xml 3bank leoch 180 4Module
CFG_ESOA300-HAF02 LEOCH LPF12-180AH 5M 4B-V5. xml 4bank leoch 180 5 or full Module
CFG_ESOA300-HAF02 LEOCH LPF12-200AH 3M 2B-V5. xml 2bank leoch 200 3Module
CFG_ESOA300-HAF02 LEOCH LPF12-200AH 4M 3B-V5. xml 3bank leoch 200 4Module
CFG_ESOA300-HAF02 LEOCH LPF12-200AH 5M 4B-V5. xml 4bank leoch 200 5 or full Module
DWDM-modbus-V1.2B01-1005.xml All battery All system Modbus protocol
communication
orion_V5.40B29.bin All battery All system Firmware version approval
by Indosatooredoo

Noted: difference type ESOA300-HAF01 vs ESOA300-HAF02 at on quantity of Temperature Probe.


HAF01 – 3 probe (TA, TB1, TE)
HAF02 – 4 probe (TA, TB1, TB2, TE)
Delta Confidential
Controller - Web GUI
Controller - Web GUI
Controller Web GUI

 Local communication is success and ready for user control / monitoring


(Home Page)

Navigation Bar Dialog Area


Upgrade Orion Controller Firmware (SW)
 Upgrade Firmware (SW) controller version.
version
- Bring spare controller to safety your activity upgrade and upload new parameter.
- Ensure The version firmware using V5.40B29
- Upgrade FW(SW) controller only can use Web Browser.
- Before activity upgrade firmware please check system running properly
- in the Upgrading process (in progress), Please don’t do anything in the browser used and
the communication LAN cable should be stabile.

Login Configuration system  file manager  click file Type  choose Orion SW
 download file firmware from your PIC click start  wait 100% Progress upload and
the controller Reboot.
Upgrade Orion Controller Firmware (SW)
version
 Configuration file management - Location
Go to Configuration > System > File manager > Choose file firmware version
orion_V5.40B29.bin
Upgrade Orion Controller Firmware (SW)
version
 Configuration file management - Location
Press Ok
Upgrade Orion Controller Firmware (SW)
version
 Configuration file management - Location
waiting load file success > Orion controller will be reboot few minutes
Upload And Activated New parameter
 How To setup File configuration base on Battery Installed
1. Check The Type of system cabinet installed
2. Check the real battery installed
3. Take data, capture original setup in system, download setup and take picture about
information system on sites.
4. Upload parameter only can do use Web browser.

Confidential
Controller - Web GUI
 Configuration file management - Location
Go to Configuration > System > Configuration Manager

Confidential
Controller - Web GUI
 Configuration file management – Upload new configuration file
1. Click “Load File from PC” button

Confidential
Controller - Web GUI
 Configuration file management – Upload new configuration file
2. Click “Choose File” button, find the file from PC (notebook)
Click “Start” button

Confidential
Controller - Web GUI
 Configuration file management – Upload new configuration file
3. Upload file successful

Confidential
Controller - Web GUI
 Configuration file management – Activate
1. Choice one configuration file which match the actual system configuration
Click “activate” button.
Example : system using 3 Bank battery and 4 Module.
Step by step Next Page.

Confidential
Controller - Web GUI
 Configuration file management – Activate
2. Click “OK”

Confidential
Controller - Web GUI
 Configuration file management – Activate
3. Finish - the Status become synchronized

Confidential
Controller - Web GUI
 Configuration file management – Synchronize
1. If status become not synchronized due to there have change some parameters, just need
to do update for synchronization
Click “update” button

Confidential
Controller - Web GUI
 Configuration file management – Synchronize
2. Finish - the status become synchronized

Confidential
Controller - Web GUI
 Configuration file management – Delete
1. Check the file which user wants to delete
2. Click “Accept Changes”
3. Save to Pic for download setup file from system

Confidential
Controller LCD - Choice Configuration File
 Choice one configuration file that match the system configuration by LCD monitor

ENTER ENTER ENTER

Enter the Password Deactivate the default


ENTER
Using Controller button configuration file
Password:

EXIT EXIT ENTER ENTER

Find the file you want to


ENTER Press ENTER button
change
EXIT ENTER
ENTER

Confidential
Controller - Web GUI
 Changing system time to local data & time
1. Go to Configuration  System  Time & Date
2. Click “Set Clock Equal to PC”
3. Click “Accept Changes”

Confidential
Controller LCD -Time & Date Setting

 Verify system controller’s time. To change, follow there steps …

ENTER ENTER ENTER

ENTER
Enter the correct time & Date
Password: ENTER

ENTER EXIT EXIT ENTER

Confidential
Create the battery parameter without 3
type purpose
 Battery setting- for other brand battery without Narada, Shotto, northsart Blue and LEOCH

Parameter Item Remarks


Floating voltage Battery spec
Battery capacity & Current limit Battery spec
Boost Charge Battery spec
Equalize Charge Battery spec
Temperature compensation Battery spec

Confidential
Floating voltage setting
 Battery setting- floating
1. Setting value floating voltage battery
2. Click “Accept Changes”

Confidential
Controller LCD - Manual Floating Voltage

ENTER ENTER ENTER

ENTER

Password:
ENTER
EXIT EXIT ENTER

Change value floating as


require battery brand

ENTER

Confidential
Controller - Web GUI
 Battery setting- Current limit battery Base on require Battery
1. Setting value Capacity battery base on real battery installed
2. Setting Max.Ibatt / current limit base on accumulation manual from battery installed
3. Click “Accept Changes”

Confidential
Capacity and Current limit battery setting
 Changing the battery capacity setting
1. Go to Configuration  Battery  String Settings
2. Enter the Max. Ibatt (A) and Capacity (Ah) value according to actual battery installed
3. Click “Accept Changes”

Confidential
Controller LCD - Battery Capacity &
Charge Current Limit
 Ex: Four battery strings (170Ah x 2 = 340Ah) change to two battery strings
(170Ah x 2 = 340Ah). And the maximum battery charge current limit is 0.1C

ENTER ENTER ENTER

ENTER

Password:
ENTER ENTER

EXIT EXIT ENTER

ENTER

ENTER ENTER
ENTER

Confidential
Boost Charge setting
 Battery setting- Manual Boost charge Base on Battery require.
1. Setting floating voltage battery
2. Click “Start” in status
3. Edit to setting trigger choose one criteria of trigger Current, Time or Energy

Confidential
Boost Charge setting
 Battery setting- Manual Boost charge Base on Battery require.
Choose Edit for setting.
1. Setting Value Current trigger of Boost charge as spec battery requirement

Confidential
Boost Charge setting
 Battery setting- Manual Boost charge Base on Battery require.
Choose Edit for setting.
1. Setting Value Time trigger of Boost charge as spec battery requirement

Confidential
Boost Charge setting
 Battery setting- Manual Boost charge Base on require Battery
1. Setting Value Current trigger of Boost charge as spec battery requirement

Confidential
Controller LCD – Activated Automatic
 Caution:
Boost Voltage
In order to make the battery speed up charging, the first time charge  activated
Automatic boost

ENTER ENTER ENTER

ENTER

Password:
ENTER
EXIT EXIT ENTER

ENTER

Confidential
Equalize Charge setting
 Battery setting- Manual Equalize charge Base on Battery require.
1. Setting Equalize voltage Press start for manual Equalize active
2. Edit to setting trigger of Equalize mode

Confidential
Controller LCD – Equalize Setting Voltage
 Caution:
In order to make the battery speed up charging, the first time charge  setting Equalize
charge

ENTER ENTER ENTER

Password:
ENTER
EXIT EXIT ENTER

ENTER

Confidential
Temperature Compensation Setting
 Battery setting- Temperature compensation Base on require Battery
1. Setting value Temperature compensation as require battery brand
2. Delta system use measurement -mV/°C
3. Battery temperature for sensor probe used of trigger active temperature compensation
4. Click “Accept Changes”

Confidential
Controller LCD - Manual Temperature
Compensation

ENTER ENTER ENTER

ENTER

Password:
ENTER ENTER

EXIT EXIT ENTER

ENTER Select Linear for active

ENTER
ENTER Delta system
accumulation coefficient
temperature -mV/°C

Confidential
How to setup LVBD and LVLD disconnect
 LVLD disconnect
1. Setting value LVLD disconnect base on User ( Indosatooredoo ) Operation need.
Configuration Signal processing engine  Event definition  Edit Usys LVLD trip 
change value Lower Threshold as Indosatooredoo needed.

Confidential
Controller LCD – LVLD Disconnect

ENTER ENTER ENTER

ENTER

Password:
ENTER

EXIT EXIT ENTER

ENTER

Confidential
How to setup LVBD and LVLD disconnect
 LVBD disconnect
1. Setting value LVBD disconnect base on User ( Indosatooredoo ) Operation need.
Configuration Signal processing engine  Event definition  Edit Usys LVBD trip 
change value Lower Threshold as Indosatooredoo needed.

Confidential
Controller LCD – LVLD Disconnect

ENTER ENTER ENTER

ENTER

Password:
ENTER

EXIT EXIT ENTER

ENTER

Confidential
updated to the actual battery capacity installed at site.

Controller - Web GUI


 Log out from controller
1. Click “Logout” to exit

Confidential
Delta contact window of aftersales support

Confidential
Smarter. Greener. Together.