System Controller
128 x 64 LCD
Dots Display
Orion system controller Internet Web Server
Function port
Handle
Alarm LED x 5
EXIT Down
Lock
Up Enter
Delta Confidential
Comparison setup configuration
Trigger of LVLD & LVBD - LVLD Disconnect+Hysteresis - LVLD Re-connect (recover): Usys As Indosatooredoo
Re-Covery (Reconnect) - LVBD disconnect+Hysteresis > 47V & AC mains recover Require
- LVBD Re-connect (recover): Usys
> 44V & AC mains recover
Ac1, Ac2 & Ac 3 records N/A Create In Data log record Implement since
2015
Battery parameter - 10% (C10) current limit - 10% (C10) current limit Charging -As Indosatooredoo
- Equalize duration 1440 - Add the new Type brand Battery Require
LEOCH, the file setup config - Create 6setup
become 15 File. parameter file for
LEOCH Battery
MOM with
Indosatooredoo
and Hariff at sept
2018
Data log interval time 1 Second 10 second
Delta Confidential
Setup Configuration File Information
File setup application
File Name Battery System Remarks
Application Application
Login Configuration system file manager click file Type choose Orion SW
download file firmware from your PIC click start wait 100% Progress upload and
the controller Reboot.
Upgrade Orion Controller Firmware (SW)
version
Configuration file management - Location
Go to Configuration > System > File manager > Choose file firmware version
orion_V5.40B29.bin
Upgrade Orion Controller Firmware (SW)
version
Configuration file management - Location
Press Ok
Upgrade Orion Controller Firmware (SW)
version
Configuration file management - Location
waiting load file success > Orion controller will be reboot few minutes
Upload And Activated New parameter
How To setup File configuration base on Battery Installed
1. Check The Type of system cabinet installed
2. Check the real battery installed
3. Take data, capture original setup in system, download setup and take picture about
information system on sites.
4. Upload parameter only can do use Web browser.
Confidential
Controller - Web GUI
Configuration file management - Location
Go to Configuration > System > Configuration Manager
Confidential
Controller - Web GUI
Configuration file management – Upload new configuration file
1. Click “Load File from PC” button
Confidential
Controller - Web GUI
Configuration file management – Upload new configuration file
2. Click “Choose File” button, find the file from PC (notebook)
Click “Start” button
Confidential
Controller - Web GUI
Configuration file management – Upload new configuration file
3. Upload file successful
Confidential
Controller - Web GUI
Configuration file management – Activate
1. Choice one configuration file which match the actual system configuration
Click “activate” button.
Example : system using 3 Bank battery and 4 Module.
Step by step Next Page.
Confidential
Controller - Web GUI
Configuration file management – Activate
2. Click “OK”
Confidential
Controller - Web GUI
Configuration file management – Activate
3. Finish - the Status become synchronized
Confidential
Controller - Web GUI
Configuration file management – Synchronize
1. If status become not synchronized due to there have change some parameters, just need
to do update for synchronization
Click “update” button
Confidential
Controller - Web GUI
Configuration file management – Synchronize
2. Finish - the status become synchronized
Confidential
Controller - Web GUI
Configuration file management – Delete
1. Check the file which user wants to delete
2. Click “Accept Changes”
3. Save to Pic for download setup file from system
Confidential
Controller LCD - Choice Configuration File
Choice one configuration file that match the system configuration by LCD monitor
Confidential
Controller - Web GUI
Changing system time to local data & time
1. Go to Configuration System Time & Date
2. Click “Set Clock Equal to PC”
3. Click “Accept Changes”
Confidential
Controller LCD -Time & Date Setting
ENTER
Enter the correct time & Date
Password: ENTER
Confidential
Create the battery parameter without 3
type purpose
Battery setting- for other brand battery without Narada, Shotto, northsart Blue and LEOCH
Confidential
Floating voltage setting
Battery setting- floating
1. Setting value floating voltage battery
2. Click “Accept Changes”
Confidential
Controller LCD - Manual Floating Voltage
ENTER
Password:
ENTER
EXIT EXIT ENTER
ENTER
Confidential
Controller - Web GUI
Battery setting- Current limit battery Base on require Battery
1. Setting value Capacity battery base on real battery installed
2. Setting Max.Ibatt / current limit base on accumulation manual from battery installed
3. Click “Accept Changes”
Confidential
Capacity and Current limit battery setting
Changing the battery capacity setting
1. Go to Configuration Battery String Settings
2. Enter the Max. Ibatt (A) and Capacity (Ah) value according to actual battery installed
3. Click “Accept Changes”
Confidential
Controller LCD - Battery Capacity &
Charge Current Limit
Ex: Four battery strings (170Ah x 2 = 340Ah) change to two battery strings
(170Ah x 2 = 340Ah). And the maximum battery charge current limit is 0.1C
ENTER
Password:
ENTER ENTER
ENTER
ENTER ENTER
ENTER
Confidential
Boost Charge setting
Battery setting- Manual Boost charge Base on Battery require.
1. Setting floating voltage battery
2. Click “Start” in status
3. Edit to setting trigger choose one criteria of trigger Current, Time or Energy
Confidential
Boost Charge setting
Battery setting- Manual Boost charge Base on Battery require.
Choose Edit for setting.
1. Setting Value Current trigger of Boost charge as spec battery requirement
Confidential
Boost Charge setting
Battery setting- Manual Boost charge Base on Battery require.
Choose Edit for setting.
1. Setting Value Time trigger of Boost charge as spec battery requirement
Confidential
Boost Charge setting
Battery setting- Manual Boost charge Base on require Battery
1. Setting Value Current trigger of Boost charge as spec battery requirement
Confidential
Controller LCD – Activated Automatic
Caution:
Boost Voltage
In order to make the battery speed up charging, the first time charge activated
Automatic boost
ENTER
Password:
ENTER
EXIT EXIT ENTER
ENTER
Confidential
Equalize Charge setting
Battery setting- Manual Equalize charge Base on Battery require.
1. Setting Equalize voltage Press start for manual Equalize active
2. Edit to setting trigger of Equalize mode
Confidential
Controller LCD – Equalize Setting Voltage
Caution:
In order to make the battery speed up charging, the first time charge setting Equalize
charge
Password:
ENTER
EXIT EXIT ENTER
ENTER
Confidential
Temperature Compensation Setting
Battery setting- Temperature compensation Base on require Battery
1. Setting value Temperature compensation as require battery brand
2. Delta system use measurement -mV/°C
3. Battery temperature for sensor probe used of trigger active temperature compensation
4. Click “Accept Changes”
Confidential
Controller LCD - Manual Temperature
Compensation
ENTER
Password:
ENTER ENTER
ENTER
ENTER Delta system
accumulation coefficient
temperature -mV/°C
Confidential
How to setup LVBD and LVLD disconnect
LVLD disconnect
1. Setting value LVLD disconnect base on User ( Indosatooredoo ) Operation need.
Configuration Signal processing engine Event definition Edit Usys LVLD trip
change value Lower Threshold as Indosatooredoo needed.
Confidential
Controller LCD – LVLD Disconnect
ENTER
Password:
ENTER
ENTER
Confidential
How to setup LVBD and LVLD disconnect
LVBD disconnect
1. Setting value LVBD disconnect base on User ( Indosatooredoo ) Operation need.
Configuration Signal processing engine Event definition Edit Usys LVBD trip
change value Lower Threshold as Indosatooredoo needed.
Confidential
Controller LCD – LVLD Disconnect
ENTER
Password:
ENTER
ENTER
Confidential
updated to the actual battery capacity installed at site.
Confidential