Notas de Vari Curso
Notas de Vari Curso
Bypass VAV
(Tracker System CB)
Introduction ............................................................. 4
Comfort Made Simple ................................................................ 4
The Changeover Bypass VAV Comfort Advantage ....................... 4
VariTrac Product Enhancements ................................................. 4
Features and Benefits ........................................... 5–12
Overview ................................................................................... 6
Central Control Panel ................................................................. 7
Optional Operator Display .......................................................... 7
Communicating Bypass Controller ............................................. 8
Tracker System Integration ......................................................... 8
VariTrac Bypass Dampers ........................................................... 9
VariTrac Zone Dampers ............................................................ 10
Unit Control Module ................................................................ 10
Zone Sensors ...................................................................... 11–12
Application Considerations ................................ 13–24
Introduction .............................................................................. 13
Zoning Considerations .............................................................. 13
Effective Changeover Bypass VAV System Design ................ 14–19
Pressure Dependent vs. Pressure Independent .......................... 20
Local Reheat Capabilities Using VariTrane VAV Units ............. 20–21
Bypass Damper Operation ........................................................ 22
Building Pressure Control ......................................................... 23
ApplicationTip Summary .......................................................... 24
Selection Procedures ......................................... 25–29
VariTrac Dampers ................................................................ 25–26
Model Number Description ...................................................... 27
Service Model Numbers........................................................... 28
Typical Bill of Materials ............................................................. 29
Control and Electrical Data and Connections ....... 30–35
Specifications ................................................... 36–39
Acoustics .......................................................... 40–41
™ ® The following are trademarks or Dimensions and Weights .................................... 42–47
registered trademarks of their respective
companies: Precedent, ReliaTel, Trace, Tracker, Glossary ........................................................... 48–49
VariTrac, VariTrane, Voyager.
VAV-PRC003-EN 3
Introduction
4 VAV-PRC003-EN
Features and
Benefits
Bypass
Damper
Communicating
Bypass
Controller
VariTrac Zone
Damper
Zone Sensor
VariTrac Central Control Panel (CCP) Bypass Damper w/ Wire and Quick Connect
The CCP is the system level controller which A round or rectangular damper ducted
coordinates and monitors VariTrac system between the HVAC supply and return ducts. It
operation, including HVAC system supply is easily connected via a “quick-connector”
pressure and airflow, heating/cooling mode, which provides quick and consistent field wiring.The bypass
supply air temperature, all zone temperatures and setpoints, damper is modulated by the CCP to maintain required system
fan mode, economizer position (when paired with CO2 static pressure.
demand controlled ventilation), time-of-day scheduling, zone
grouping logic, system override mode (after hours
operation), and much more. Communicating Bypass Controller
A single enclosure with duct temperature sensor,
static pressure sensor, and communicating
controller (UCM) which easily mounts on the
HVAC Unit supply ductwork.The UCM provides power to
VariTrac changeover bypass systems drive the bypass damper actuator.
Rooftop
operate withTrane and non-Trane products,
including split systems, packaged rooftop
units, and water-source heat pumps.These
systems are generically referred to as HVAC
(heating, ventilating, and air conditioning) Zone Sensor
Split System units. When combined with aTrane Zone sensors (sometimes referred to as
packaged rooftop with ReliaTel™ controller, thermostats) measure space temperature and
wiring, installation, and system startup report it to the zone damper controller (UCM).
efficiency is maximized by connecting with a Five models are available to satisfy varied aesthetic and
simple twisted shielded wire pair. application preferences.
WSHP
5VAV-PRC003-EN 5
Features and
Benefits
Overview How the System Works The VAV terminal unit controller
communicates zone temperature
Changeover-bypass VAV is a comfort A changeover-bypass VAV system information to a central control panel
system developed for light commercial commonly consists of an HVAC unit (CCP). The CCP also gathers
applications. A changeover-bypass VAV with a constant-volume supply fan, and information from the system, including
system responds to changing cooling direct-expansion (DX) cooling.This duct static pressure and supply-air
or heating requirements by varying the combined system has the ability to temperature.The CCP determines zone
quantity or volume of air delivered to “change” to the heating mode or heating or cooling needs using voting
each zone. Each zone has a thermostat cooling mode, depending on individual (or polling) logic, then requests heating
for individual comfort control. An zone comfort requirements. A heating or cooling from the HVAC unit.The CCP
HVAC unit delivers a constant volume coil or a gas-fired heater and an outside directs the HVAC unit to provide
of air to the system. As the volume of air damper are possible options. ventilation air to high-occupancy areas
air required by the zone changes, A temperature sensor in each zone (demand control ventilation) or free-
excess supply air is directed to the communicates information to an cooling when the outside air
return duct via a bypass duct and electronic controller on the VAV temperature falls below the
damper. (See Figure 3 for typical terminal unit.The controller then temperature setpoint (economizer
system components.) modulates the zone damper open or control).
A changeover-bypass VAV system closed, supplying heating or cooling air Auto Changeover
combines the comfort benefits of VAV to the zone.
with the cost effectiveness and The HVAC unit delivers a constant “Auto changeover” refers to the ability
simplicity of packaged, constant- volume of supply air to the system. In of the system to automatically change
volume unitary equipment. order to maintain duct static pressure, a between the heating and cooling
bypass duct and damper are required modes.
to bypass (detour) air not required in In a changeover-bypass VAV system,
the zones. the CCP determines whether the HVAC
unit should heat or cool by polling the
temperature of the individual zones. It
then compares the zone temperatures
to the space temperature setpoints. If
the supply air does not meet the criteria
for the heat or cool mode called for, the
CCP sends a signal to the HVAC unit to
change the system to the opposite
mode.
6 VAV-PRC003-EN
Features and
Benefits
Central Control Panel Figure 5. VariTrac central control panel Figure 6. VariTrac central control panel
with optional operator display
The VariTrac central control panel (CCP)
serves as the central source of
communications and decisionmaking
between the individual zones and the
HVAC unit.The CCP determines system
heating and cooling modes and
coordinates the system supply air
temperature and static pressure to
satisfy building thermal load
conditions. Inputs to the CCP include
24VAC power and communication
wiring to the zone dampers and bypass
control.
Binary inputs consist of priority
shutdown and occupied/unoccupied
modes. Heating, cooling, and the HVAC CCP Feature Summary Optional Operator Display
unit fan on split systems and non-Trane • Communicates with up to 24 VAV unit
HVAC units can be controlled through The optional operator display is a
control modules (UCMs)
binary outputs on an accessory relay backlit, liquid crystal display with touch-
board. If aTrane rooftop air conditioner • Makes optimal heating and cooling screen programming capability.
with factory-installed electronic decisions based on setpoint and
The operator can access system and
controls is used, the CCP can control temperature information received from
zone status through the display and
heating, cooling, and the fan with a two- individual zones
perform basic setup of zone VAV UCMs
wire communication link tied to an • Automatically calibrates all dampers, and CCP system operating parameters.
interface board mounted in the rooftop. significantly reducing labor-intensive The display allows an installer to
It can also display status information and costly field calibration commission a VariTrac system without
from the electronic controller in the using a PC. The operator display has a
• Windows-based PC software simplifies
rooftop. (See Figure 4.) seven-day time clock for stand-alone
setup and control
scheduling capability.
• Provides diagnostic information for all
Figure 4. A screen representation system components via the operator Operator Display Feature Summary
from the central control panel display or PC software • Backlit LCD touch-screen display for
illustrating system status • Provides status and diagnostic easy operator interface
information forTrane HVAC units • Combination of icon- and menu-based
equipped withTrane ReliaTel or UCP navigation provides intuitive operation
electronic controls
• Provides a level of control for the daily
operator, and a second level for
commissioning and service
• Three levels of security are available to
protect system settings
• Seven-day time clock for stand-alone,
time-of-day scheduling
VAV-PRC003-EN 7
Features and
Benefits
Communicating Bypass Tracker System Integration • 365-day scheduling function and the
flexibility of up to 10 schedules
Controller The VariTrac system can be fully
integrated with the new family of • Assign all systems to a single
The communicating bypass controller schedule, if desired, for simplified
is a single control enclosure with the Tracker building controls. ATracker
building management system can schedule changes
following integrated devices included:
manage multiple VariTrac systems from • Exception scheduling feature for easy
• integrated UCM board a single control point. management of vacations and holidays
• static pressure sensor Tracker System Summary • Automatically adjusts for daylight
• discharge air temperature sensor savings time and leap year
• Controls up to 10 VariTrac systems
The communicating bypass controller from a singleTracker panel for easy • Remote communications capability
directly controls the bypass damper building operation via modem for system programming
and communicates duct conditions to and control
the central control panel via a simple • LCD touch-screen operator display or
twisted shielded wire pair. Tracker PC software interface provides
single-point building management by a
Quick Connect local operator
Minimizes field wiring labor and
assures wiring consistency
Figure 8.Tracker System Architecture
Duct Temperature Sensor
The supply air temperature sensor
allows the CCP to control heating and
cooling stages to maintain the supply
air temperature. Supply air
temperature setpoints can be edited
through the operator display or
PC software.
Static Pressure Sensor
The static pressure sensor measures
duct static pressure and positions the
bypass damper(s) to maintain the static
pressure setpoint.
Static Pressure
Sensor
Quick
Connect
8 VAV-PRC003-EN
Features and
Benefits
VariTrac Bypass Dampers Round Bypass Damper Summary Rectangular Bypass Damper Summary
Bypass dampers are non- • Round bypass dampers are available • Rectangular bypass dampers are
communicating VariTrac dampers and with inlet diameters 6, 8, 10, or 12 inches available in sizes 14 x 12, 16 x 16,
include an integrated fully-modulating 20 x 20, and 30 x 20 inches
• Heavy gage galvanized steel cylinder
24 VAC electric actuator. with rolled bend for high structural • Formed heavy gage galvanized steel
Field wiring errors are reduced with a integrity and corrosive resistance frame, mechanically joined with linkage
quick-connect harness that plugs into concealed in the side channel
• Metal-to-metal blade seal provides tight
the communicating bypass controller. shutoff for low leakage • Air linkage is minimized with an
Dampers are nominally rated up to opposed blade design with stainless
• Aerodynamic blade design provides a
1800–2400 fpm at 1.75" of static steel side seals
constant torque for stable operation at
pressure, depending on size. high velocity • Damper casing is 16 inches long and
For damper performance information, constructed of heavy gage galvanized
• Factory-installed, direct-coupled, fully-
seeTable 2. sheet metal with S cleats on the inlet
modulating 24 VAC actuator
and outlet for easy installation
• Rated up to 2400 fpm at 1.75" of static
• Blades are six-inch nominal width,
pressure
heavy gage galvanized steel
• A blade rotation stop feature prevents
over-rotation of the blades in the fully
open position
• Factory-installed, direct-coupled, fully-
modulating 24 VAC actuator
• Rated up to 3000 fpm at 2" of static
pressure
VAV-PRC003-EN 9
Features and
Benefits
10 VAV-PRC003-EN
Features and
Benefits
Zone Sensors
Figure 10. DDC zone sensors Figure 11. DDC zone sensor with LCD
DDC Zone Sensor DDC Zone Sensor with LCD Digital Zone Sensor Summary
The direct digital control (DDC) zone The DDC zone sensor with LCD (liquid • Displays setpoint adjustment and space
sensor is an uncomplicated, reliable crystal display or digital) is compatible temperature in °F or °C
electro-mechanical room sensor. No with VariTrane VAV and VariTrac • Simple, two-button control of space
programming is required and most controllers. setpoint
sensors contain an internal
communications jack. • Setpoint control and room temperature
display can be optionally disabled
Models are available with combinations
of features such as override (on-cancel) • Includes button for timed override and
buttons and space-mounted setpoint. a cancel feature for after-hours system
operation
Four sensor variations are available:
• An easily accessible communications
• Sensor only (no communications jack) jack is provided forTrane portable edit
• Sensor with override buttons terminal devices
• Sensor with temperature setpoint only • Nonvolatile memory stores last
• Sensor with temperature setpoint and programmed setpoints
override buttons • For field balancing, maximum and
minimum airflow or position can be
overridden from the sensor
VAV-PRC003-EN 11
Features and
Benefits
Figure 12. Wall-mounted CO2 sensor Figure 14. Zone occupancy sensor Figure 15. Auxiliary temperature
sensor
12 VAV-PRC003-EN
Application
Considerations
VAV-PRC003-EN 13
Application
Considerations
Figure 17. Design process steps Effective Changeover cooler, casual attire, such as golf shirts,
light slacks, skirts, or shorts?
Bypass VAV System Design
Gather as much usage information as
Step 1. Define Occupant Unitary zoning systems feature low possible before designing a system.
Comfort Needs first cost and quick, easy system design This can be challenging, particularly
Involves architect, and equipment selection. The system is when finishing out tenant spaces.
engineer(s), and building owner simple, but it is essential that key However, usage information is crucial
elements are considered during the to the selection of heating and cooling
design process. equipment, building zoning, and duct
This section offers a system design layout.
Step 2. Define Thermal Zones sequence and discusses application Several publications provide guidance
Involves engineers considerations that, when followed, for properly assessing indoor space
and contractors help avoid system control and comfort. An example is ASHRAE
operational instabilities. (American Society of Heating,
Suggested design steps for unitary Refrigerating and Air Conditioning
zoning systems are summarized in Engineers) Standard 55,Thermal
Step 3. Determine Figure 17. Environmental Conditions for Human
Comfort Zones Occupancy. This standard specifies the
Step 1. Define occupant comfort needs
Involves engineers, combinations of indoor space
contractors, and building owner The design process begins by environments and personal factors
considering the needs of building (activity and clothing) that will produce
occupants and intended building use. thermal environmental conditions
acceptable to 80 percent or more of the
y What is the intended use of the
occupants within a space. Standard 55
Step 4. Size Heating/ building? Is the building usage
addresses temperature, thermal
Cooling Equipment primarily office space? Is there a
radiation, humidity, and air speed.
Involves engineer(s) and contractors
manufacturing operation? Are there
areas that have special requirements ASHRAE Standard 62, Ventilation for
such as computer or electronic rooms, Acceptable Indoor Air Quality, is
video/television production, training another source for occupant comfort
facilities, etc.? and safety issues regarding indoor air
quality. The standard recommends that
Step 5. Size Zone and y What physical activity level is
relative humidity be maintained
Bypass Damper Units expected of the occupants? Seated
between 30 and 60 percent.This
occupants require different indoor
Involves engineer(s) and contractors maximizes comfort and reduces the
temperatures for comfort than
potential for microbial growth.
continuously moving occupants. An
example may be a building with a mix Step 2. Define the Thermal Zones
of office space and light assembly or
A thermal zone is an area with similar
Step 6. Design the Duct system manufacturing.
load profiles and occupant comfort
Involves engineer(s) and contractors y Where will the occupants be requirements. A thermal zone can be a
located and at what times? Pay single room, an area, a group of rooms
particular attention to areas with or an entire building. Defining the
intermittent use, such as conference, thermal zones within a building is
training, and lunchrooms. crucial to designing a comfortable
Step 7. Air Diffuser y How are the occupants expected indoor environment. Each thermal zone
to dress? Give consideration to how is conditioned by a single heating and/
Selection and Placement
the building occupants will dress. Will or cooling unit.The load of the thermal
Involves engineer(s) and contractors
they dress in traditional business attire, zone determines the size of the heating
such as long-sleeved shirts or blouses, and cooling unit.
ties, and jackets? Or, will they dress in
14 VAV-PRC003-EN
Application
Considerations
Cost vs. Comfort Building Example 1 (See Figure 18.) of all areas. It also is not a good
candidate for a zoning system because
First cost can be reduced by limiting Consider an existing single-story office of the simultaneous need for heating
the number of thermal zones. building which is small, poorly and cooling.
Unfortunately, this may impact the insulated, with many large windows
thermal flexibility of the system, and and few interior partitions. On a clear, A similar building with good insulation
result in zone comfort issues. Let’s take cool spring day, the entire building is and fewer shaded windows, on the
a closer look at this important system cool in the morning so heating is other hand, may be a good candidate
decision known as “thermal zoning.” required. By afternoon, however, the for a single thermal zone with individual
south side of the building being comfort zones. The reduction in wall
Characteristics of a building which can glass reduces the solar effect on the
influence thermal load are: influenced by the solar load, is warm
and requires cooling. The north side building resulting in all areas of the
• Orientation of the building (North, remains shaded and continues to building having similar load profiles
South, East, West) require heating. This situation results in throughout the day. In this case, the
• Amount and thermal resistance (R- a simultaneous requirement for heating building has a single thermal zone and
value) of glass (walls, skylights, etc.) and cooling for extended periods. Due is a good candidate for one HVAC unit.
to the varying loads throughout the Individual comfort zones (zone
• Expected occupancy within the area building, controlling the building as a dampers) will be needed to assure
• Interior partitions and doors single thermal zone (with a single HVAC comfortable conditions throughout the
unit) cannot satisfy the comfort needs zone.
• Varying loads from equipment or
processes
Let’s examine a few building examples
and discuss the zoning criteria of each.
Figure 18. Building Example 1 illustrates a small, poorly insulated office on the left, and improved design on the right.
T Thermostat T Thermostat
VAV-PRC003-EN 15
Application
Considerations
Building Example 2 (See Figure 19.) Step 3. Define the Comfort Zones
Consider a strip mall in the spring or fall A primary criteria for defining a thermal
with stores that face both east and Outside
Coffee
zone is that it will not require
Doors
west. In the morning, the east side of Shop simultaneous heating and cooling. An
the building gets full sun and warms up Jewelry HVAC unit with one fan is limited to
Store
while the west side is shaded and supplying either heating or cooling.
requires heating. In the afternoon, the Most applications with larger thermal
east side of the building may need heat Poor Design Elements
• One thermostat for entire space
zones however will have varying
and the west side cooling. Because of • One HVAC unit thermal needs throughout the zone.
the thermal load variation throughout These small variations can easily be
Electronics
the day, this building will not remain Store addressed by properly defining comfort
comfortable if designed with a single Pharmacy zones.
heating and cooling unit. A comfort zone is an area within a
Toy
On the other hand, comfort in this Clothing
Store
thermal zone that is controlled by a
building could be improved by dividing Store zone damper.The amount of
the building into two thermal zones conditioned (heated or cooled) air
(two HVAC units), one serving the east N entering the space varies. This is in
exposure and the other serving the response to a space thermostat.
west. Even with the two systems, ASHRAE Standard 55 recommends
individual occupant comfort is not limiting indoor temperature variations.
necessarily assured. Interior Temperature variations of less than 2°F
partitioning, varying schedules and Figure 19. Building Example 2 in 15 minutes or 4°F in an hour.
number of occupants within the illustrates a poorly insulated store Deviations from this recommendation
thermal zone will drive differing design (above) and an improved design will cause discomfort in 80 percent of
amounts of heating and cooling. The (below) the occupants. Zoning systems can
issues related to comfort zoning are greatly reduce temperature variations
addressed in the next section. caused by shifting occupancy and solar
load conditions in large thermal zones.
Coffee
Outside Jewelry
Shop
Doors Store
Electronics
Store
Pharmacy
Clothing Toy
Store Store
16 VAV-PRC003-EN
Application
Considerations
Diversity =______
17.5 = 90%
19.5
North Zone
Glass
West Zone Interior Zone East Zone
Windows
South Zone
VAV-PRC003-EN 17
Application
Considerations
Step 5. Size Zone and Bypass Dampers located immediately adjacent Step 6. Designing the Duct System
Damper Units to the zone or diffuser may need to be
Low pressure, low velocity air
sized at a lower velocity to avoid sound
Sizing zone damper is relatively distribution systems, such as zoned
and airflow delivery issues.
straightforward. The volume of airflow unitary systems, are usually designed
(in cfm or L/s) for each comfort zone Bypass dampers are typically sized for using the equal friction method.
should be known from the load 80 percent of HVAC unit airflow. Although static regain is the duct
analysis. The designer must select the Recommended velocities are 1600 to design method of choice for medium
duct velocity to be used for the system. 2000 fpm. Bypass dampers should be and high velocity variable air volume
Recommended zone damper velocities located as close to the HVAC unit as systems, the added complexity is
are 1000 to 1600 feet per minute (fpm) possible. (See Bypass Damper difficult to justify with smaller unitary
when applied at the branch level. Operation for additional details.) systems. In addition, the low operating
Sizing dampers in this range will Note: VariTrac systems are designed velocity of most unitary systems makes
minimize damper cost, reduce the risk for HVAC unit static pressures up to the pressure available to “regain”,small
of excessive noise, and ensure 1.75" w.c. and inconsequential.
adequate zone modulation/temperature With the equal friction method, ducts
control. are sized for a constant pressure loss
per given length of duct and fitting(s).
Where low noise levels are especially
critical, the system velocity can be
reduced by enlarging the entering and
leaving ductwork, damper unit or
adding duct liner. A characteristic of the
equal friction method that must be
considered however, is that there is no
natural provision for equalizing
pressure drops in the branch sections.
This results in each branch duct, and
Figure 21. Hand balancing dampers thus the damper units, having different
Hand entering static pressure and airflow
Balancing characteristics.
Damper A robust system and zone unit
controller, like theTrane VariTrac
system, will compensate for system
static changes.The use of manual (or
hand) balancing dampers in the
branches will also ensure that airflow is
appropriately distributed to each
diffuser. (See Figure 21.)The overall
effect is improved acoustical and
system performance.
VariTrac
Damper
Supply
Duct
18 VAV-PRC003-EN
Application
Considerations
Step 7. Air Diffuser Selection and • When the average glass plus wall heat Return Diffusers
Placement loss is less than 250 Btuh/linear foot,
the slot diffuser may be located in Slot-style return diffusers offer some
Supply Diffusers the center of the room with one or acoustical advantages over perforated
more slots blowing toward the grille styles. Perforated drop-in grilles
Many types of supply air diffusers are
perimeter wall. typically offer little attenuation effect
used in variable air volume systems.
and thus allow sound in the plenum to
Performance, and ultimately space • With glass and wall heat loss between break out into the occupied space. This
comfort, can vary greatly depending on 250 and 450 Btuh/linear foot, diffusers is a problem in areas near the unitary
the diffuser selected. Although should be positioned to blow toward heating and cooling unit. Improved
constant-volume diffusers will provide the window and the perimeter wall with ceiling aesthetics is also an advantage
air to the space at full cfm, as air a collision velocity of 75 to 150 fpm. If of slot return diffusers in jobs where
volume delivered to the space using a continuous glass design, slot supply diffusers are used. Within
decreases, so does performance. position diffusers every four feet. the occupied space, they blend with the
Linear slot diffusers are recommended
• If heat loss exceeds 450 Btuh/linear slot supply diffusers.
for most VAV systems.
foot, radiation or floor mounted heated A general rule of thumb is for the return
Linear supply air slot diffusers are air will be required to offset the high air openings to equal the total area of
designed to properly mix variable air wall heat loss. the supply openings. If the ceiling is not
delivery of both heated and cooled air.
tight, such as a drop-in ceiling, the
Linear slot diffusers supply conditioned
return openings can be reduced by up
air which “hugs” the ceiling rather than
to 50% of the supply air openings.
“dumps” air downward on the
occupants.This airflow characteristic is To promote good air distribution, return
known as the “coanda effect”. The diffusers should be positioned to
throw and aspiration characteristics of minimize supply air short-circuiting to
slot diffusers help to evenly distribute the return slot. The returns should be
the air throughout the room or space. either perpendicular to the supply
airflow or parallel and offset from the
Locate linear slot diffusers in the center
supply diffusers.
of the room with the discharge air
pattern perpendicular to a perimeter
wall. To maximize diffuser
performance, placement in which air Figure 22. Proper return diffuser orientation
discharge patterns converge at right
angles should be avoided. (See Diffuser
section of the VariTrane catalog (VAV-
PRC008-EN) for additional diffuser
placement and performance
recommendations.)
The throw characteristics of diffusers is
well-documented. Slot diffusers should
be positioned so that the velocity of the
air striking an obstruction (such as a
wall or column) is 75 feet per minute
(fpm) or less. If airstreams from two
diffusers collide, the collision velocity
should not exceed 150 fpm. Higher
collision velocities result in
uncomfortable drafts in the lower levels
of the room.
In heating applications, linear slot
diffusers must be placed to offset heat
loss and prevent downdraft problems
along perimeter walls. The following
techniques have been proven by test
and experience:
VAV-PRC003-EN 19
Application
Considerations
20 VAV-PRC003-EN
Application
Considerations
VAV-PRC003-EN 21
Application
Considerations
Rooftop
Micro Control
Heating and
Static Pressure
and Supply
Temperature Sensors Return
Bypass
Return Air
Damper
Air Duct
Duct
Supply
Air Duct
Ductwork
22 VAV-PRC003-EN
Application
Considerations
Building Pressure Control In buildings that have a ducted return to • Use an exhaust fan with no exhaust
the fan, bypass air pressurizes the damper. Energize the exhaust fan when
Comfortable, efficient building return air duct. As the return air duct the outdoor air damper opens beyond
operation requires that the air pressure pressure rises, the air flows out of the 25 percent to remove excess outside air
inside the building be slightly higher building through the barometric relief from the building. This method is used
than the atmospheric pressure outside damper in the rooftop unit. Excess with some rooftop units and is
of the building.That is, the building is at bypass air flows into the zones through effective, affordable, and easy to install.
a “positive” pressure with respect to the return air grilles.
the outside environment. If the indoor • Use a back draft damper to prevent
pressure is too low (negative), the Using the following suggestions will airflow to the return air plenum or
doors may be hard to open and cold air help maintain building pressurization grilles. When bypass airflow
may leak in through construction control: pressurizes the return duct, the back
cracks, causing drafts and cold floors. • Use an exhaust fan with a modulated draft damper closes. Pressure in the
On the other hand, if the indoor exhaust damper to remove air from the HVAC unit return air inlet rises, causing
pressure is too high, the doors may return air plenum or duct. Energize the the rooftop barometric relief damper to
stand open and the supply air flow to exhaust fan as the outside air damper open.This method is less effective
the zones may decrease, decreasing opens beyond the minimum position. because the rooftop barometric relief
comfort. Sense building static and maintain damper is sized for a portion of the total
building air pressure at a slightly airflow, not 100 percent of airflow which
Fixed Outside Air Dampers may be seen in economizer mode. As
positive level by modulating the
Achieving appropriate building exhaust damper position. the economizer drives to the maximum
pressure is simple in a system with a position, the building usually becomes
constant volume supply fan and fixed over-pressurized.
outdoor air damper.To maintain a
slightly positive building pressure, size
the exhaust fans to remove slightly Figure 29. Changeover bypass with an economizer. Without proper building
less air than is introduced through the pressurization, bypass air may be forced out of the return duct.
outdoor air damper.
Outside Economizer or Demand- Fan
Economizer
Controlled Ventilation Systems
If the system resets the quantity of
outdoor air in response to occupancy
demands (demand-controlled Outdoor
ventilation), or uses an outdoor air Air Damper
economizer, undesirable changes in
building pressure may result. As the Return
quantity of outdoor air intake varies,
Damper Bypass
the system must exhaust a similar
quantity of air to avoid over or under
pressurizing the building.
When using an economizer in a Return
changeover-bypass VAV system under Opening
low cooling load conditions (reduced
airflow to the zones), the bypass
damper opens to maintain the static
pressure setpoint and airflow through
the supply fan. As the outside air
damper opens to provide economizer
cooling, the return air damper closes.
In buildings with a ceiling plenum
return, the bypass air dumps into the
ceiling plenum since it can no longer
return to the fan. The plenum pressure
rises and plenum air enters the zones
through the return air grilles.
VAV-PRC003-EN 23
Application
Considerations
24 VAV-PRC003-EN
Selection
Procedures
VAV-PRC003-EN 25
Selection
Proceduress
800 160 280 435 630 855 1115 800 160 280 435 630
Velocity (fpm)
1000 200 350 545 785 1070 1395 1000 200 350 545 785
Recommended
1200 235 420 655 940 1280 1675 1200 235 420 655 940
1400 275 490 765 1100
Recommended
1400 275 490 765 1100 1500 1955
1600 315 560 875 1255
1600 315 560 875 1255 1710 2235
1800 350 630 980 1415
Length 12" 12" 16" 16" 20" 20" 2000 390 700 1090 1570
Ship Wt 11 lbs 12 lbs 17 lbs 18 lbs 27 lbs 31 lbs Length 12" 12" 16" 16"
Ship Wt 11 lbs 12 lbs 17 lbs 18 lbs
Recommended
1400 928 1083 1238 1547 1934 2437
1600 1857 2830 4421 6632
1600 1061 1238 1415 1769 2211 2785 1800 2089 3183 4974 7461
Blades 2 2 2 3 3 4 2000 2321 3537 5527 8290
Ship Wt 8 lbs 10 lbs 12 lbs 14 lbs 16 lbs 18 lbs Blades 2 3 3 3
Ship Wt 16 lbs 21 lbs 29 lbs 40 lbs
Notes:
1. Recommended velocity for zone dampers is between 1000 and 1600 fpm. Use
good standard design practices (such as location of duct).
2. Recommended velocity for bypass damper is between 1600 and 2000 fpm.
26 VAV-PRC003-EN
Selection
Procedures
0814=8 x 14 rectangular zone damper 2. Unit Control ELEC is typically used with
electric resistant duct heaters.The
0816=8 x 16 rectangular zone damper auxiliary heat is disabled when the
1016=10 x 16 rectangular zone damper primary heat is activated to protect the
heating coils.
1020=10 x 20 rectangular zone damper
3. Unit Control NCHW is typically used
1418=14 x 18 rectangular zone damper with perimeter heating, hot water,
steam, or electric resistant perimeter. It
is always enabled, regardless of
whether the primary system is heating
or cooling.
VAV-PRC003-EN 27
Selection
Procedures
7R = 8 x 16 zone damper
8R = 10 x 16 zone damper
9R = 10 x 20 zone damper
AR = 14 x 18 zone damper
28 VAV-PRC003-EN
Selection
Procedures
VariTrac dampers Varies air volume to the space to control comfort One per comfort zone
D
Zone sensors Sends space temperature and setpoint One per comfort zone (DDC sensor
E information to the zone damper controller w/ LCD requires 4 VA)
CCP power supply 24V power for the central control panel The CCP must have a dedicated 24V
F power supply
Zone damper power supply(s) 24V power for the zone dampers Power supplies may be shared; each
G zone requires 10VA (plus the load of
optional outputs)
Trane rooftop communications Allows the CCP and Trane rooftop controller to One per controlled Trane rooftop
H interface communicate with each other via simple twisted with ReliaTel controller
shielded wire pair
Optional relay board Provides 24V control of any non-communicating One per controlled non-
J HVAC unit communicating HVAC unit
F
E
A &J
VAV-PRC003-EN 29
Electrical Data
and Connections
Splice
Splice
= Transf
T ormer 1 All customer wiring must be in
accordance with national, state,
= Figure note and local electrical codes.
30 VAV-PRC003-EN
Electrical Data
and Connections
TB1
Rc
1 24 VAC CLASS 2 COOL UNIT
Rh
2 24 VAC CLASS 2 HEAT UNIT
G
3 SUPPLY FAN
2 HEAT/2COOL HEAT PUMP
Y1
4 COOL 1 COMP 1
W1 Y2
5 COOL 2 COMP 2
W2/0
7 HEAT 2 REV VALVE
NO AUX
8
NC
10
11
NOT USED 12
13
14
15
HVAC Unit
TB1
24V Terminal Strip
Rc
1 R
Rh
3
G
G
Y1
4 Y1
5
Y2
Y2
W1
6 W1
W2/0
7
W2
VAV-PRC003-EN 31
32
Figure 35. UCM Comm Link Wiring
VariTrac
Communication Sensor/Bypass Control Termination Board TB2
Zone UCM Address #2 Zone UCM Address #1 Assembly Address #33
Static 1
J1 1 J1 1 J1 1 Pressure Port
J9
J7
J8
J9
J7
J8
J9
J7
J8
J11
J10
J11
J10
J11
J10
TB4–1
TB1–2
TB1–1
TB4–1
TB1–2
TB1–1
TB4–1
TB1–2
TB1–1
ACT ACT ACT
BIP GND 24V BIP GND 24V BIP GND 24V 2
ADDRESS D.D.C.\U.C.M. ADDRESS D.D.C.\U.C.M. ADDRESS D.D.C.\U.C.M.
J3 J3 J3 R
SWITCH SWITCH SWITCH + 3
CONTROL BOARD CONTROL BOARD CONTROL BOARD BK
G
VOUT
PRESS
PRESS
PRESS
1 1 1 –
+ – + – + – + – + – + – + – + – + – Pressure
4
S S S
YEL GRN YEL GRN YEL GRN Transducer
TB3–6
TB3–2
TB3–3
TB3–5
TB3–2
TB3–3
TB3–5
TB3–1
TB3–2
TB3–3
TB3–5
TB3–6
TB2–2
TB2–2
TB3–6
TB2–1
TB2–3
TB2–4
TB2–5
TB2–6
TB2–1
TB2–3
TB2–4
TB2–5
TB2–6
TB3–1
TB2–2
TB2–1
TB2–3
TB2–4
TB2–5
TB2–6
TB3–1
ZONE GND SET A/CO2 GND ZONE GND SET A/CO2 GND ZONE GND SET A/CO2 GND 5
6
Air Supply
7
Temp. Sensor
8
9
10 +
Electrical Data
11 –
COMM 4
12
and Connections
Splice Splice
To Zone Dampers
3 through 24 2 2 13
1 2
14
COMM 5
Figure Notes:
15
1 Shield must be spliced with other
Legend
communication link shields.
= Twisted pair, shielded wire
per Trane specifications 2 Shield must be cut back and taped.
= Shielded ground
VAV-PRC003-EN
Electrical Data
and Connections
CW CLOSE
CCW OPEN
TO NEC CLASS 2
COM HOT 24V TRANSFORMER
LOAD 8 VA
ACTUATOR (WITHOUT ACTUATOR)
{
ACTUATOR
W–HOT
SPARE BK–OPEN
CONNECTOR R–CLOSE
STATIC
2. 24VAC PRESSURE
PORT
ACT BIP GND 24V
FEMALE PLUG END
TB1–1
TB4–1
TB1–2
J11
J10
J1 1
J9
J8
J7
OF BYPASS SENSOR
ASSEMBLY CABLE
HIGH
ADDRESS J3 MALE PLUG END
R
SWITCH +
PRESS
1
+ – + – + –
TB3–2
TB3–5
PRESSURE
TB2–6
TB2–3
TB2–5
TB2–1
TB2–2
TB3–1
TB3–6
TB2–4
YEL GRN
TRANSDUCER AC
T
ZONE GND SET A/CO2 GND
WH
BK R
D.D.C.\U.C.M.
CONTROL BOARD
AIR SUPPLY TEMP SENSOR
COMMUNICATING SENSOR/BYPASS
OUT
OUT
CONTROL BOX
IN
IN
{
SHIELDED
TWISTED PAIR
COMMUNICATIONS
WIRING
VAV-PRC003-EN 33
Electrical Data
and Connections
}
5. R (HOT)
(TB1–1) 24VAC
O (COMMON)
(TB4–1) BIP R
GR (NC CONTACT)
(TB1–1) 24VAC G
BK (RETURN)
(TB1–2) GND W
Y
NOT CONNECTED W
OPTIONAL FIELD INSTALLED
}
OCCUPANCY SENSOR
DAMPER
TO J11 3RD STG. ACTUATOR
HEATER STAGE WIRING
2ND STG. CONTACTOR(S)
TO J10
1ST STG. 24 VAC, 12 VA
TO J9
HOT MAX/COIL
TO J8
OPTIONAL FIELD INSTALLED
ELECTRIC HEATER
ACT BIP GND 24V
TB4–1
TB1–1
TB1–2
J1 1
J11
J10
J9
J7
J8
1
+ – + – + – 1 2 1 2 3 1 2
ON–OFF TB1 TB2 TB3
7.
S
TB2–1
TB2–2
TB2–3
TB2–4
TB2–5
TB2–6
TB3–1
TB3–2
TB3–3
TB3–5
TB3–6
D.D.C. \ U.CM.
MOUNTED
OUT
OUT
WALL
DUCT
6. 9.
IN
IN
(TB1–1) 24V
CONTROL BOARD
24V +
}
5 4 3 2 1
CO2 (TB3–6) GND
GND 0 ZONE SENSOR
SENSOR
OUT V (TB3–5) A/CO2 SHIELDED W/ COMM. JACK
REMOTE MTD.
OPTIONAL FIELD INSTALLED
TWISTED PAIR
3. 4.
CO2 SENSOR COMMUNICATIONS
WIRING OPTIONAL FIELD
TB3–5 TB3–6 INSTALLED DIGITAL ZONE SENSOR
NOTES:
1. Factory Wiring
6. Field Wiring
Optional or Alternate Wiring
OPTIONAL FIELD INSTALLED
AUX TEMP SENSOR 2. ¼" quick connect required for all field connection.
3. Zone sensor terminals 4 and 5 require shielded twisted pair wiring for communications jack equipped zone sensor options
5. The optional binary input connects between TB4–1 (BIP) and 24VAC (HOT) from transformer. The binary input can be
reconfigured as an occupancy input via the communications interface.
6. As shipped, the aux input is configured as an AUX input. The AUX input can be reconfigured as a CO2 sensor input via
the communications interface.
8. If unit mounted transformer is not provided, polarity from unit to unit must be maintained to prevent permanent damage
to control board. If one leg of 24VAC supply is grounded, then ground leg must be connected to TB1–2.
34 VAV-PRC003-EN
Electrical Data
and Connections
24V
–2
GND
TB1–2
TB1–1
TB4–1
J11
1
J10
J1
J9
J7
J8
ACT
BIP GND 24V
TB2–1
Digital Sensor ADDRESS
Temperature J3
Terminal Connection Chart –2 SWITCH D.D.C.\U.C.M.
PRESS
Field Wire CONTROL BOARD
Sensor UCM Color Code Signal Common
–2 1
TB1–1 TB1–1 + – + – + –
Setpoint S
TB1–2 TB1–2 TB2–1
TB2–2
TB2–3
TB2–4
TB2–5
TB2–6
TB3–1
TB3–2
TB3–5
TB3–6
TB3–3
YEL GRN
TB1–1
TB4–1
J11
1
J10
J1
J9
J7
J8
ACT
BIP GND 24V
ADDRESS
J3
SWITCH D.D.C.\U.C.M.
PRESS
CONTROL BOARD
1
+ – + – + –
S
TB2–1
TB2–2
TB2–3
TB2–4
TB2–5
TB2–6
TB3–1
TB3–2
TB3–5
TB3–6
TB3–3
YEL GRN
1
Night Setback
Override Option TB1–1
Sensor
VAV-PRC003-EN 35
Specifications
36 VAV-PRC003-EN
Specifications
Figure 41. VariTrac central control Table 5. VariTrac control panel specifications
panel components
Power Requirements 20–30 Vac, 60 Hz, single-phase, 30 VA minimum. Class 2 transformer
required.
Operating Environment 32°–122°F (0°–50°C), 10–90% relative humidity, non-condensing
Storage Environment -40°F–122°F (-40°–85°C), 5–95% relative humidity, non-condensing
Control Enclosure NEMA 1 resin enclosure, plenum rated
Mounting Mount directly on wall surface or mount on recessed 4" x 4"
(101.6 mm x 101.6 mm) conduit box.
Weight 2.5 lbs. (1.13 kg)
Communication Link Wiring Communication link wiring must be Level 4 22-AWG twisted shielded
pair wire with stranded tinned copper conductors. Maximum total wire
length is 3,500 ft (1066.8 m). Wire must meet Trane specifications.
Binary Input Voltage (provided by VariTrac CCP): 10–14 Vdc
Current (provided by VariTrac CCP): 10–14 mA
Note: Only “dry” contacts may be attached to binary inputs.
UL Approval The VariTrac Central Control Panel is UL approved.
Memory Backup Upon a power loss, all operator-edited data stored in the VariTrac Central
Control Panel is maintained permanently.
VAV-PRC003-EN 37
Specifications
Figure 43. Communicating bypass Table 7. Communicating bypass control assembly specifications
controller
Power Requirements 20–30 Vac, 60Hz, single-phase 15 VA minimum. Class 2 transformer
required.
Operating Environment 32°–120°F (0°–49°C). 10–90% relative humidity, non-condensing
Storage Environment -50°–200°F (-46°–93°C). 5–95% relative humidity, non-condensing
Control Enclosure NEMA 1 metal enclosure, plenum rated
Communication Link Wiring Communication link wiring must be Level 4 22-AWG twisted shielded
pair wire with stranded tinned copper conductors. Maximum total wire is
3,500 ft (1066.8 m). Wire must meet Trane specifications.
Figure 44. Zone occupancy sensor Table 8. Zone occupancy sensor specifications
Power Supply 24 Vac or 24 Vdc, ±10%
Maximum VA Load 0.88 VA @ 24 Vac, 0.722 VA @ 24 Vdc
Isolated Relay Rating 1 A @ 24 Vac or 24 Vdc
Operating Temperature 32°–131°F (0°–55°C)
Storage Temperature -22°–176°F (-30°–80°C)
Humidity Range 0–95% non-condensing
Effective Coverage Area 1200 sq. ft (365.8 m)
Effective Coverage Radius 22 ft (6.7 m)
Housing Material ABS plastic
38 VAV-PRC003-EN
Specifications
Figure 45. DDC zone sensor with Table 9. Digital zone sensor specifications
digital display
Thermistor Resistance Rating 10kW at 77° (25°C)
Accuracy at 77°F (25°C) 0.4°F (0.2°C)
Setpoint Resistance Rating 500 Ohms at 70°F (21.2°F)
Display Zone Temperature Range 40°–99°F (10° to 35°C)
Display Setpoint Range 50°–90°F (10° to 32°C)
Operating Temperature 0°–120°F (–18° to 49°C)
Storage Temperature –20°–130°F (–29° to 54°C)
Humidity Range 5–95% non-condensing
Power Supply 24 VAC
Maximum VA Load 4 VA
Housing Material Rigid vinyl
VAV-PRC003-EN 39
Acoustics
Table 11. Acoustical transfer functions Table 12. Radiated sound data
ARI 885-98 Discharge Transfer
Function Assumptions NC Based on 885-98 Mineral Tile
Size Radiated NC Size
Octave Band
2 3 4 5 6 7 6 in. 33 470
8 in. 26 840
Small Box -24 -28 -39 -53 -59 -40 10 in. 25 1310
(<300 cfm) 12 in. 26 1885
Medium Box -27 -29 240 -51 -53 -39 14 in. 29 2140
(<300–700 cfm) 16 in. 21 2515
Large Box -29 -30 -41 -51 -52 -39
(>700 cfm) NC based on maximum rated airflow
conditions.
Note: Add to terminal unit sound power to
determine discharge sound pressure in the space.
40 VAV-PRC003-EN
Acoustics
Note: NC data based on ARI 885-98 Acoustical transfer functions in Table 11.
VAV-PRC003-EN 41
Dimensions and Weights
Top view
8.75 in.
(22.38 cm)
Bottom view
Note:
1. Central control panel weight is 2.5 lbs.
42 VAV-PRC003-EN
Dimensions and Weights
Mounting holes
See back view for dimensions
6 3/4" 4 1/4"
5"
3 3/8"
Duct Static
Pressure Sensor
0.300"
Notes:
Weight 3 1/4 lbs
Operating Temp 32˚ to 140˚
Humidity 5 to 95% (non-condensing)
Mounting Method Metal screws
VAV-PRC003-EN 43
Dimensions and Weights
Airflow
8.875" 6.625"
Controls Area
4.375"
2.125"
0.50" C
Airflow
2.00"
3.625" Duct Temp Sensor (Optional)
Center of Bead A
N/A on Bypass Control DIA
B
Damper Nominal
A B C Weight
Size CFM
6" 6.375" 12.00" 11.125" 300 6 lbs
44 VAV-PRC003-EN
Dimensions and Weights
16.00" Ref.
Seam
10.00" 16.00"
10.00" 20.00"
14.00" 18.00"
VAV-PRC003-EN 45
Dimensions and Weights
Hub
1.20"
6"
16" Ref
.70" 2"
1.10"
4"
Actuator Dimensions Seam
Dimensions
X Y
14" 12"
16" 16" w Y
Flo
20" 20" Air
30" 20"
Factory Installed
Damper Frame Data Cable Provided
Frame 13 gage galvanized steel
16 gage galvanized steel; blades are
Blades 6" nominal width and 8" maximum
Actuator
Linkage 1/8" rolled steel, zinc plated 5"
Blade Pin 3/8" square steel, zinc plated
Blade Pin 7/16" diameter, 7" long
Extension Included with all dampers
Bearings Self-lubricating acetol
Blade Seals None
Side Seals None
Cable 10"
Weight
46 VAV-PRC003-EN
Dimensions and Weights
3.125" 1.44"
4.25"
˚F
˚C
MAX
2.50"
4.5
ON
Side
View
CANCEL
1.90"
VAV-PRC003-EN 47
Glossary
ABS gears – Gears formed of a Commercial Voyager VAV rooftop unit Non-volatile memory – System
lightweight plastic known for its and VariTrane VAV boxes. memory that retains programming with
toughness, impact strength, and no battery or capacitor back up
Demand control ventilation – A
dimensional stability. required
method of maintaining indoor air
Back draft damper – A one-way quality through intelligent ventilation Normally closed (NC) – Electrical
airflow damper in a parallel fan based on occupancy.The quantity of contacts that are closed (current flows)
powered unit prevents primary flow ventilation is controlled based on in the de-energized condition
from exiting the plenem inlet. indoor CO2 levels, which correlate to Normally open (NO) – Electrical
Binary input – A two-position signal occupancy levels. Demand controlled contacts that are open (no current
indicating on/off status. ventilation saves money by reducing flows) in the de-energized condition
ventilation during periods of low
Binary output – A control output that occupancy. Occupancy sensor – A binary sensor
is either on or off. that transmits a signal upon detection
Direct-expansion (DX) – When the of movement in the coverage area
Built-in time clock –The occupancy refrigerant in the system is either
timer included in the CCP operator condensed or evaporated directly by Outdoor air (OA) –This is fresh air
display. the medium being heated or cooled. drawn in to provide space ventilation.
Bypass damper – The motorized Also see ‘Ventilation air”
Discharge air (DA) – Air discharged
damper ducted between the system from the air handler into the ducts. Outdoor air damper –The damper
supply and return ducts used to that draws fresh air into the air handling
control static pressure in changeover Discharge air control – An air system for ventilation. Also referred to
bypass VAV systems. handling system that provides fixed as the ventilation or fresh air damper
temperature air (either fixed or variable
Central control panel (CCP) – The volume). Other control devices vary the Override – A manual or automatic
system level control device in aTrane actual volume of air delivered to the action taken to bypass normal
changeover bypass or delivered VAV space to maintain occupant comfort. operation
system that gathers data from zone Packaged unitary system – An air
controllers and operates the HVAC unit Economizer – A damper arrangement
and automatic control system that handling system with all the major
to maintain the correct air flow and components contained in a single
temperature. allows a heating, ventilation and air
conditioning (HVAC) system to supply cabinet or installed in a single location
Changeover-bypass VAV – A control up to 100 percent outside air to satisfy PIR – Passive infrared sensing
that provides variable air volume cooling demands, even if additional technology (used in occupancy and
functionality to a constant volume air mechanical cooling is required motion detection sensors)
handling system.
Exception schedule – A one time Polling –The method a VariTrac CCP
CO2 sensor – An analog sensor that only time of day schedule in a system uses to determine the need for heating
detects and measures carbon dioxide that is removed automatically after use or cooling from the air handling system
sensor to determine occupancy level. by examining the zone requirements
Free cooling – Outdoor air introduced
Commissioning –The process of to a system under correct conditions to Positive pressure –The condition that
starting up and verifying correct provided cooling to a space. Also see exists when more air is supplied to a
operation of a building system. also “Economizer” space than is exhausted.
Conditioned air – Air that is heated, HVAC Unit – An air moving device Pressure-dependent VAV control –
cooled, humidified, or dehumidified to that conditions air. An HVAC unit may A VAV unit with airflow quantity
maintain comfort in an interior space. provide cooling, or heating and cooling. dependent upon static pressure.There
Constant volume – An air Typical HVAC units include packaged is no zone flow sensor in pressure
distribution system that varies the rooftop units, split systems, and water dependent VAV boxes.
temperature of a fixed volume of air to source heat pumps.
Pressure-independent VAV
maintain space comfort. LCD – Liquid crystal display control – A VAV unit with airflow
Delivered VAV – A self configuring NDIR – Non-dispersive infrared quantity independent of duct static
system providing true pressure technology pressure. Actual airflow to the space is
independent VAV control to smaller measured and controlled by an airflow
building applications. Delivered VAV Negative pressure –The condition sensor in the pressure independent
requires a CCP with operator display, a that exists when more air is exhausted VAV box.
from a space than is supplied.
48 VAV-PRC003-EN
Glossary
Priority shutdown – An immediate Staged electric reheat – Reheat that Unit control module UCM – ATrane
shutdown of the fan and heating or operates one or more duct mounted microelectronic circuit board that
cooling stages in a VariTrac changeover electric coils in a series in response to controls individual HVAC equipment.
bypass or Delivered VAV system increased space heating demand. May link to an Integrated Comfort
caused by either the loss of critical Staged (or perimeter) hot water System
system information or an external reheat – Reheat that operates duct- Unitary – one or more factory-made
priority shutdown input mounted hot water or space-mounted assemblies which normally include an
Pulse-width modulating reheat – electric or hot water reheat coils in evaporator or cooling coil, an air
Reheat that operates duct mounted response to increased space heating moving device, and a compressor and
electric coils on a 0-100% duty cycle in demand condenser combination
response to increased space heating Static pressure –The difference Variable air volume (VAV) – an air
demand. between the air pressure on the inside handling system that varies the volume
Reheat device – A source of heat of the duct and outside of the duct. (amount) of constant temperature air to
located downstream from a control Static pressure is an indicator of how a space to control comfort
device such as a VAV box to add heat to much pressure the fans are creating VariTrac –TheTrane changeover
air entering a space to provide and how effective they will be at bypass VAV system
occupant comfort distributing the supply air through the
ducts. VariTrane –TheTrane pressure
ReliaTel (RTRM) – The latest independent VAV box
generationTrane factory mounted Supply air (SA) – air which blows out
unitary controller. of the air handler into the ducts. See VAV box – The damper or air valve
also “Discharge air (DA)” (plus associated controller) that
Return air (RA) – Air returned to the controls the zone air volume in a VAV
air handler from the conditioned space, Terminal unit – HVAC equipment that system. Also see “Variable air volume”
to be reconditioned. provides comfort directly to a space.
Ventilation air –The outdoor air
Setpoint –The desired room Thermal requirements –The heating drawn into the HVAC unit to provide
temperature to be achieved and or cooling load requirements for a fresh air to the space. Also see
maintained by an HVAC system. specific area or space in a building. “Outdoor air (OA)”
Setpoint limit – An electronic or Care must be taken to not control areas
with different thermal requirements Voting – See “Polling”
manual constraint imposed on a
setpoint to prevent misadjustment from one air handling system Zone sensor –The device that
Touch-screen operator display – measures a variable (usually
SPDT – A relay with of one set of temperature) in a space and sends it to
normally-open, normally-closed The LCD panel mounted onto a VariTrac
CCP to allow direct user interface and a controller. Commonly referred to as a
contacts thermostat.
time of day programming for the
system
VAV-PRC003-EN 49
50 VAV-PRC003-EN
VAV-PRC003-EN 51
Literature Order Number VAV-PRC003-EN
File Number PL-TD-VAV-000-PRC003-EN-0604
Trane Supersedes VAV-DS-12
A business of American Standard Companies
www.trane.com Stocking Location La Crosse
For more information contact your local district office Trane has a policy of continuous product and product data improvement and reserves the right to change
or email us at comfort@trane.com design and specifications without notice.