08.16
Easy Operation and Configuration Mini BMS Solution with Software and
Intuitive user interface with 10.4” LCD touch screen Hardware Options
Interlock and Emergency Stop for facility management
Flexible
screen views includes the icon view, list
view and layout view for system configurations DI,
DO, Ai, AO points integrated via the
Easy
engineering with use of the Preset Tool and WAGO I/O System
USB port BACnet points (AI, AO, AV. BI, BO. BV, MSI, MSO,
MSV) integrated with the iTM BACnet Client Option
Advanced Control Logic
DIand DO points integration via DIII-Net connected
Independent Cool and Heat setpoints or DI and DIO units
Single setpoint in the occupied period
IndependentSetback setpoints in the BACnet Server Gateway Option
unoccupied period Direct
connection to the VRV system using
WeeklySchedule with Optimum Start and the iTM as a gateway
Timed Override Individual
device ID assigned to each indoor
Auto Changeover with configurable methods unit management point
Seamless control logic integration between
Facility Management and Billing the iTM and BMS
Remote Web access Greatlyreduces the need for BMS
Automatic Error and Alert emails integrator programming
Tenant Billing with iTM PPD option
BACnet/IP BMS
Web access
Ethernet
Integration of Third BACnet® Server Gateway Full Control of Daikin
Party Equipment (DCM014A51) VRV System
Up to 512 groups
Fire alarm (1024 indoor units)
Di/Pi port
kWh meter
Ethernet (BACnet IP)
DIII-NET
DCM601A71
one DIII-NET system
RS485 RS485 Max. 64 indoor unit groups (128 indoor units)
BACnet Client Option
®
(DCM009A51)
iTM Plus Adapter
ter
Max. 64 indoor unit groups
WAGO I/O
Di/Pi portt
up to 30 nodes Up to 7 adaptorss
4 www.daikinac.com
Easy Operation and Configuration
The easy to understand icon and intuitive menu will
enable even a novice user to be proficient in managing
the VRV system.
[Icon view]
Filter sign
OFF
Error
Layout View [Layout view] A special feature utilizes building floor plans to
provide a visual representation of system equipment.
The users can visually locate any installed equipment on the floor
plan without having to memorize equipment names.
Easy Engineering
Icon menus for configurations The system configuration can be done through
the Preset Tool off-site then imported to the iTM
via the USB port at the site. This feature makes
engineering easier and more manageable.
Automatic Control
System Settings
Operation Management
Change to Cool
¢¢ ➂
Change to Cool when
➀ ➁ RT > C_SP + (PCd + SCd)
No change to Change to Cool when (Guard timer initiated in heat mode is ignored)
Cool when RT > C_SP + PCd
RT <= C_SP + PCd (Guard timer is initiated)
76 ➌
75
➋ } SCd
}
➊ PCd
74
Change to Heat
¢¢
71
➍ } PCd
70
➎ }
SCd
69 ➃ ➄
No change to Change to Heat when ➏
Heat when RT < H_SP - PCd ➅
RT >= H_SP - PCd (Guard timer is initiated) Change to Heat when
RT < H_SP - (PCd + SCd)
(Guard timer initiated in cool mode is ignored)
■■ The guard timer prevents another changeover for 15, 30 or 60 minutes (configurable).
■■ When the setpoint is changed manually or by the schedule, the guard timer is not active.
74
73
} SCd
PCd
Differential is 0ºF, at least
}
71 71 2ºF PCd is recommended
PCd
69
} SCd
68
6 www.daikinac.com
Auto Changeover (cont.)
Auto Changeover is applicable to both VRV Heat Pump and Heat Recovery system.
The iTM provides four changeover methods to meet a variety of expectations in your project. Fixed, Individual,
Average or Vote methods can be specified in the changeover group with targeted indoor units as well as
Primary / Secondary Changeover deadbands.
Average method (Weight 0 to 3 on each indoor unit is multiplied in averaging) Changeoveris evaluated with the average of room
temperature and setpoints.
Changeover affects all indoor units.
■ ■ (Average) Goodfor Open office application with Heat Pump
system (or multiple units on the same port of the
■ = Cool Mode ■ = Heat Mode BS Box in Heat Recovery system).
Vote method (Weight 0 to 3 on each indoor unit is multiplied for the demand) Changeover is evaluated based upon total cooling
demand and total heating demand. If the total cooling
demand is greater than the total heating demand
Cool demand (like the figure left), the iTM changes the indoor units
Cool demand
in the changeover group to cooling mode.
No demand When the changeover group is in cooling mode
the total cooling demand will be decreased,
at that point the total heating demand may become
greater than the cooling demand and change
the mode to heating (a guard timer applies).
Schedule Event
Special Day
8 www.daikinac.com
Remote Monitoring / Maintenance
The Web function enables remote management Automatic Alert/Error e-mail enables prompt response
for the Daikin VRV system with other general by service personnel based on timely and precise
equipment integrated into the iTM so they can knowledge of what happened in the system at the
be accessed from your PC (*). remote site.
-- Up to 4 administrators and 60 general users -- Up to 10 e-mail addresses can be set.
can be registered. -- The SMTP server authentication method
-- Screens and operation accessible to is selectable from no authentication, POP
general users can be restricted. before SMTP, and SMTP-AUTH.
Network/Internet
Property Manager/Engineering
(*) Flash Player is required. Indoor icon view via Web Configuration menu via Web
* Pulse power meter that provides an output of 1 pulse per 1 kw and has
a width of 40-400 milliseconds.
Or
Ventilation control
Ventilation equipment is controlled depending on the indoor Stops all indoor units
CO2 levels. Air conditioning losses attributed to unnecessary in localized fire
ventilation are reduced while maintaining appropriate indoor air protection areas
quality and enabling energy savings.
CO 2 level is low Ventilation fan
speed is reduced
Example 2
Ventilation fan
CO 2 level is high speed is increased
10 www.daikinac.com
Mini BMS Solution with
the BACnet® Client Option
DCM009A51 - BACnet® Client Option Features/Benefits
The iTM offers an advanced and cost-effective solution ■■ Cost- effective BMS solution
for Building Management Systems (BMS) applications. ■■ Direct connection on iTM using the
The iTM BACnet Client Option (DCM009A51)
BACnet/IP Protocol
provides more flexibility to enhance the iTM’s
function as a mini BMS. With this new option, the ■■ Integrated control on Daikin VRV system
iTM is able to manage DOAS systems and other third and Daikin Applied System
party equipment through the BACnet/IP protocol. ■■ Monitors and controls third party equipment
By registering equipment connected to a BACnet server
as management points in the iTM, you can now monitor
■■ Easy commissioning with pre-Engineering Preset Tool
and control the equipment via the iTM. ■■ Easy monitoring with preconfigured GUI
MicroTech III
DOAS System
(BACnet/IP)
Ethernet
VRV System
Third Party
devices/equipment
Di/Do/Ai/Ao contacts
750-831
WAGO BACnet/IP Controller
■■ Multi-State Input, Multi-State Output, ■■ The iTM can integrate with the WAGO
BMS
Ethernet (BACnet/IP)
12 www.daikinac.com
Current Solution with BACnet® Gateway (DMS502B71)
Better Solution and Easy integration with iTM BACnet Server Gateway Option
1: 1-00 1: 1-01
Individual Device instance number for
each indoor unit (Configurable) Device ID (1:1-00) = 531100 Device ID (1:1-01) = 531101
Object instance number repeated for Occupancy Mode = MO 1 (All indoor units)
every indoor unit point Unit On Off Status = BI 2 (All indoor units)
Summary of Functions
CATEGORY FUNCTION REMARKS
iTM Plus Adaptor Maximum number of adaptors:7
Maximum number of management points:650
Management points
Maximum number of indoor unit management points:512
Maximum number of areas:650
Areas
Basic Functions Maximum area levels:10
Language English
Icon view Icons show the operation status of equipment
Monitoring screens List view Detailed information of each management point is displayed
Layout view Up to 60 screens can be created
Maximum number of programs:100
Schedule
Up to 20 actions/day can be set
Weekly Schedule 7 day, 5+2,5+1+1,and Everyday weekly patterns can be set
Special days can be specified by specific date or floating date
Yearly Calendar
Automatic DST adjustment
Optimum Start Ensure the room temperature is reached at scheduled start time
Interlock Maximum number of programs:500
Automatic Control
Emergency Stop Maximum number of Programs:31
Auto changeover Maximum number of changeover groups: 512
Independent cooling and heating setpoint range limitation
Temperature Range Limitation
Set between 60-90 °F
Timer Extension Selectable from 36,60,90,120, and 180 minutes
Independent heating and cooling setback setpoint
Setback
Setback recovery temperature range:2-10°F
Up to 500,000 events are recorded in history including malfunctions, operations,
History
automatic control, and system information
Data Control
Up to 13 months of hourly power proportional distribution results are recorded
Power proportional distribution
CSV format data output are supported
Display the same type of screen as the iTM
Web access Up to 4 administrators and 60 general users can be registered
Remote Access
Screens and operation accessible to general users can be restricted
Email Alert Up to 10 email addresses can be set
Automatic Registration Indoor units are automatically detected, and icons for respective models are automatically registered
Screen lock function are available
Security
System Access restriction can be set for each general user
Screen saver time can be set from 1-60 mins
Screen saver
3 patterns are available
14 www.daikinac.com
Options for intelligent Touch Manager
ITEM MODEL DESCRIPTION
DCM002A71 Power Proportional Distribution (PPD)1
Optional Software DCM009A51 BACnet ® IP Client Option2
DCM014A51 BACnet Server Gateway Option3
Interface Adapters KRP928BB2S For connection to Daikin Mini-Split system (connect to Indoor Unit)
Digital input (DI) unit DEC101A51-US2 8 sets of operation status input and alarm input
Digital input/output (DIO) unit DEC102A51-US2 4 sets of control output, operation status input and alarm input
1
The power proportional distribution (PPD) feature supplies the user with a reasonably calculated apportionment of the total power consumption by the Daikin VRV system.
Because input to the PPD includes measured pulses in the refrigerant system and because the VRV system includes a number of variables, including the operating temperatures
and pressures, piping lengths, heat exchange rates, and so forth, no meter-type apportionment of individual user consumption can be made. However, the PPD feature provides
an apportionment methodology that uses highly advanced technology and is applied to the many variables in the VRV system.
2
BACnet IP Client Option can not be activated at the same time with BACnet Server Gateway Option.
3
iTM PPD option and iTM BACnet Client option are not compatible with the iTM BACnet Server Gateway Option.