Professional Documents
Culture Documents
eu/hvac
Frese Application Guide
Valves & Controls for HVAC Applications
1
2
www.frese.eu/hvac
Efficient indoor climate control for buildings
Over 25 years’ experience producing dynamic balancing solutions has positioned Frese as the leading manufacturer of energy saving valves and through our commitment to innovation,
we continue to be at the forefront of technological advancements in our areas of expertise.
Our innovative solutions balance global HVAC systems accurately and efficiently. From cooling systems in the Middle East to heating systems in Scandinavia, our products transform state
of the art technology into everyday solutions.
To support our products, the knowledge, experience and dedication of our employees and partners ensure our solutions are applied correctly to maximise savings and position Frese as the
authoritative voice for energy efficient, pressure independent valve solutions.
Key Icons
DYNAMIC valves from Frese offer the maximum savings in terms of energy consumption and are strongly recommended solutions
DYNAMIC valves for HVAC heating and cooling applications.
STATIC valves STATIC valves from Frese offer effective and reliable flow regulation and verification.
3
Glossary of Terms
Frese Application Guide
4
Heating Systems Page 6
1.0 DYNAMIC and STATIC valve finder
Heating
Air Handling Unit Condensing Boiler - Plant Room Plate Heat Exchanger
3.1 3.8 3.15
with PICV direct control with PICV control with PICV control
Circulation of Minimum Flow- Plant Room Hot Water Tank Stand-alone Terminal Unit
3.6 3.13 3.20
with PICVs and Flow Limiters with PICV control with PICV control
Circulation of Minimum Flow - System End Hot Water Tank Trench Heater
3.7 3.14 3.21
with PICVs and Flow Limiters with PICV control and Self Acting Thermostat with PICV control
Underfloor Heating
3.22
with PICV control - single circuit
Case Study Page 31
4.0 PICV energy savings - Canary Wharf, London
5
Heating Systems
1.0 DYNAMIC and STATIC valve finder Heating
a b c
FOUR PIPE
ONE PIPE SYSTEM TWO PIPE SYSTEM SYSTEM
DYNAMIC valves STATIC valves DYNAMIC valves DYNAMIC valves DYNAMIC valves
Frese SIGMA Compact Frese STBV Range PV-SIGMA Compact PV-STBV PV Compact Frese OPTIMIZER
DN15 to DN150 DN15 to DN500 DN15 to DN50 DN15 to DN50 DN15 to DN150 DN15 & DN25
Dynamic Flow Limiting DRV & VODRV DPCV & Dynamic DPCV & FODRV DPCV Pressure Independent
Valve DN15 to DN300 FODRV Flow Limiting Valve Control Group
6
Cooling Systems
2.0 DYNAMIC and STATIC valve finder Cooling
a b
CONSTANT FLOW VARIABLE FLOW
DYNAMIC valves STATIC valves DYNAMIC valves DYNAMIC valves DYNAMIC valves
STATIC valves
Cartridge Externally
Solution Adjustable
Frese ALPHA Frese SIGMA Compact Frese STBV Range PV-STBV PV-SIGMA Compact PV Compact Frese OPTIMA Compact
DN15 to DN800 DN15 to DN150 DN15 to DN500 DN15 to DN50 DN15 to DN50 DN15 to DN150 DN15 to DN200
Dynamic Flow Limiting Dynamic Flow Limiting DRV & VODRV DPCV & FODRV DPCV & Dynamic DPCV Pressure Independent
Valve Valve DN15 to DN300 FODRV Flow Limiting Valve Control Valve
7
Typical Application Schematics DYNAMIC valves
3.0 For Frese DYNAMIC valves
3.1
Air Handling Unit Function
with PICV direct control
The air temperature of the Air Handling Unit is controlled by a sensor in
the outlet. When the control system calls for higher or lower temperature
on the air outlet, the PICV opens or closes to increase or decrease the flow
through the coil. The power output from the coil follows a parabolic curve
where often an EQ% valve/actuator characteristic is chosen to have a direct
relation between the input control signal and power output.
Benefits
• The PICV ensures balancing of the primary flow and eliminates the use
of both static balancing valves and differential pressure control valves.
• Simple application as only a PICV is required to control flow, temperature
and differential pressure.
Considerations
• At part load, the flow through the coil can be low leading to laminar
AIR HANDLING UNIT flow and reducing the power output.
PRESSURE INDEPENDENT • Larger coils can have different temperatures in different areas of the coil
CONTROL VALVE
F making precise temperature control difficult.
CONTROLLER
• A metering station can be installed if additional flow verification is
R required.
METERING STATION
PRIMARY PUMP
8
Typical Application Schematics
3.0 For Frese DYNAMIC valves DYNAMIC valves
3.2
Air Handling Unit Function
with PICV injection circuit
The air temperature of the Air Handling Unit is controlled by a sensor in the
outlet. The secondary side of the injection circuit circulates a constant flow
through the coil maintaining a uniform temperature throughout the entire
coil.
When the control system calls for higher or lower temperature on the air
outlet, the PICV valve opens or closes to allow heating or cooling water
from the primary side of the injection circuit to enter the secondary side.
The temperature in the coil then changes giving an almost direct relation
between the temperature in the coil and the power output from the coil.
INJECTION CIRCUIT
Benefits
SECONDARY SIDE
• The PICV ensures balancing of the primary flow and eliminates the use
of both static balancing valves and differential pressure control valves.
60˚C
40˚C
40˚C
METERING STATION
Considerations
R
PRIMARY PUMP
• Requires a small circulation pump on the secondary side of the injection
circuit.
CIRCULATION PUMP
PLEASE NOTE: TEMPERATURES ARE SHOWN FOR EXAMPLE ONLY
• A metering station can be installed if additional flow verification is
required.
9
Typical Application Schematics
3.0 For Frese DYNAMIC valves
3.3
Calorifier Function
with PICV control
The room temperature is controlled by a room controller connected to the
PICV actuator. To avoid cold air being blown into the room, when fresh air is
taken from outside, a timer can be inserted to delay the startup of the fan.
The control can either be modulating or On/ Off depending on the system
layout.
Benefits
• The PICV ensures balancing of the flow and eliminates the use of both
static balancing valves and differential pressure control valves.
• Simple installation as only the PICV is required with no need for
additional pressure or flow balancing valves.
• Low total pressure loss in the system due to simple design.
CALORIFIER
• The flow can be set directly on the PICV without the need of a
manometer or a commissioning unit.
CONTROLLER
F • The differential pressure only needs to be checked at the PICV placed at
PRESSURE INDEPENDENT
the index point, or at the end of every branch.
CONTROL VALVE
R
10
Typical Application Schematics
3.0 For Frese DYNAMIC valves
3.4
Chilled Beams Function
with PICV control
The room temperature is controlled by a controller connected to the PICV
actuator. The control can either be modulating or On/Off depending on the
system layout. On/Off control is often selected on passive chilled beams to
avoid laminar flow, which lowers the cooling transfer from the water to the
coil.
Benefits
• The PICV ensures balancing of the flow and eliminates the use of both
static balancing valves and differential pressure control valves.
• Simple installation as only the PICV is required with no need of additional
pressure or flow balancing valves.
• Low total pressure loss in the system due to simple design.
• The flow can be set directly on the PICV without the need of a
manometer or a commissioning unit.
• The differential pressure only needs to be checked at the PICV placed at
the index point, or at the end of every branch.
CHILLED BEAM
PRESSURE INDEPENDENT
CONTROL VALVE Considerations
F R
CONTROLLER
• A metering station can be placed on the branch if additional flow
verification is required by the witness authority.
METERING STATION
• The index valve will, in applications such as this with identical design
PRIMARY PUMP
and coil performance, be the one furthest from the pump, but it can be
elsewhere in other layouts.
• In theory, PT-plugs are only needed on the index PICV, but for
commissioning and diagnostic purposes, it can be useful to have PT-
Frese OPTIMA Compact plugs on every valve.
Pressure Independent Control Valve
11
Typical Application Schematics
3.0 For Frese DYNAMIC valves
3.5
Chilled Ceilings Function
with PICV control
The room temperature is controlled by a controller connected to the PICV
actuator. The control can either be modulating or On/Off depending on the
system layout. On/Off control is often selected on passive chilled ceiling to
avoid laminar flow which lowers the cool transfer from the water to the coil.
Benefits
• The PICV ensures balancing of the flow and eliminates the use of both
static balancing valves and differential pressure control valves.
• Simple installation as only the PICV is required with no need for
additional pressure or flow balancing valves.
• Low total pressure loss in the system due to simple design.
• The flow can be set directly on the PICV without the need of a
manometer or a commissioning unit.
• The differential pressure only needs to be checked at the PICV placed at
the index point, or at the end of every branch.
CHILLED CEILING
Considerations
PRESSURE INDEPENDENT
CONTROL VALVE
• A metering station can be placed on the branch if additional flow
F R
CONTROLLER
verification is required by the witness authority
• The index valve will, in applications such as this with identical design
METERING STATION
and coil performance, be the one furthest from the pump, but it can be
PRIMARY PUMP
elsewhere in other layouts
• In theory, PT-plugs are only needed on the index PICV, but for
commissioning and diagnostic purposes, it can be useful to have PT-
plugs on every valve.
Frese OPTIMA Compact
Pressure Independent Control Valve
12
Typical Application Schematics
3.0 For Frese DYNAMIC valves
3.6
Circulation of Minimum Flow - Plant Room Function
with PICVs and flow limiters
The dynamic flow limiter (Automatic Balancing Valve) ensures a minimum
flow for the cooling or heating devices to prevent from freezing or
overheating. The selected flow rate for the flow limiter is based on the
minimum required flow rate for the heating/cooling device.
Benefits
CHILLER
PRESSURE INDEPENDENT
• The dynamic flow limiter ensures that only the required flow passes
through the bypass and it is not influenced by an increasing pump
CONTROL VALVE
when the flow to the system exceeds the minimum required flow. The
controller must be connected to a flowmeter to control the bypass PICV.
Considerations
CHILLER
• A metering station can be placed on the main line if additional flow
verification is required by the witnessing authority.
PRESSURE INDEPENDENT
CONTROL VALVE
• The minimum bypass flow shall be added to the design flow if a PICV
R
CONTROLLER
with a flow controlled bypass solution is not chosen.
S FLOW SENSOR
S F
PRIMARY PUMP
PRESSURE INDEPENDENT
CONTROL VALVE
Benefits
METERING STATION
• The dynamic flow limiter ensures that only the required flow passes
PRIMARY PUMP
through the bypass and it is not influenced by an increasing pump
F R SYSTEM A - FLOW LIMITING VALVE ON SYSTEM END
FLOW LIMITING VALVE
pressure across the valve.
• With the bypass placed at the end of the line, instant cooling or heating
is ensured at all times, and the circulation of chemicals throughout the
whole system is undertaken.
HEATING OR COOLING
TERMINAL UNIT Considerations
PRESSURE INDEPENDENT
CONTROL VALVE • A metering station can be placed on the main line if additional flow
METERING STATION
verification is required by the witness authority.
PRIMARY PUMP • With the PICV system, the minimum bypass flow shall be added to the
FLOW LIMITING VALVE
design flow.
THREE PORT
CONTROL VALVE • With the 3-way valve replacing the PICV at the end of the branch,
F R SYSTEM B - FLOW LIMITING VALVE AND THREE PORT CONTROL VALVE ON SYSTEM END
pressure independent modulation is not possible.
Benefits
• The PICV ensures balancing of the flow and eliminates the use of both
static balancing valves and differential pressure control valves.
CONDENSING BOILER • Simple installation as only the PICV is required with no need for
R additional pressure or flow balancing valves.
PRESSURE INDEPENDENT
• Low total pressure loss in the system due to simple design.
F CONTROL VALVE
• The flow can be set directly on the PICV without the need of a
CONTROLLER manometer or a commissioning unit.
METERING STATION
• The differential pressure only needs to be checked at the PICV to set the
required flow.
PRIMARY PUMP
Considerations
TEMPERATURE SENSOR
(INDOOR)
15
Typical Application Schematics
3.0 For Frese DYNAMIC valves
INDEX PICV
Benefits
• The PICV ensures balancing of the flow and eliminates the use of both
static balancing valves and differential pressure control valves.
• Simple installation as only the PICV is required with no need for
additional pressure or flow balancing valves.
• Low total pressure loss in the system due to simple design.
• The flow can be set directly on the PICV without the need of a
manometer or a commissioning unit.
FAN COIL UNIT • The differential pressure only needs to be checked at the PICV placed at
INDEX PRESSURE the index point, or at the end of every branch.
INDEPENDENT CONTROL
VALVE
PRESSURE INDEPENDENT
CONTROL VALVE
Considerations
F R
16
Typical Application Schematics DYNAMIC valves
3.0 For Frese DYNAMIC valves
3.10
Fixed Speed Chiller - Plant Room Function
with PICV control The fixed speed chillers are connected to the controller which opens and
closes the flow through each chiller by turning the PICV on and off.
The controller measures the inlet and outlet temperature to maximize Delta
T and regulates the variable speed pump to maintain the required pump
pressure.
For optimal chiller efficiency, the use of cascade control is recommended.
Benefits
1 2 3
• The PICV ensures balancing of the flow and eliminates the use of both
static balancing valves and differential pressure control valves.
• Simple installation as only the PICV is required with no need for
additional pressure or flow balancing valves.
#
FIXED SPEED CHILLER
(# - STAGE)
• Low total pressure loss in the system due to simple design.
R
PRESSURE INDEPENDENT
• The flow can be set directly on the PICV without the need of a
CONTROL VALVE
manometer or a commissioning unit.
F
CONTROLLER • The differential pressure only needs to be checked at the PICV to set the
required flow.
METERING STATION
PRIMARY PUMP
Considerations
FLOW LIMITING VALVE
• A metering station can be placed on the main line if additional flow
verification is required by the witnessing authority.
• A minimum bypass flow controlled by a dynamic flow limiter is required
by the chiller to avoid freezing as they are running at full capacity when
switched on.
17
Typical Application Schematics
3.0 For Frese DYNAMIC valves
3.11
Variable Speed Chiller - Plant Room Function
with PICV control
The variable speed chillers are connected to the controller, which controls
the flow through each chiller by the PICV.
The controller measures the inlet and outlet temperatures to maximize
Delta T and regulate the variable speed pump to maintain the required
pump pressure.
For optimal chiller efficiency, the use of multiple chillers at lower capacity
or cascade control at part load shall be selected, depending on the chiller
design and control philosophy.
Benefits
• The PICV ensures balancing of the flow and eliminates the use of both
static balancing valves and differential pressure control valves.
R
• Simple installation as only the PICV is required with no need for
CHILLER
additional pressure or flow balancing valves.
F
PRESSURE INDEPENDENT
CONTROL VALVE • Low total pressure loss in the system due to simple design.
CONTROLLER
• The flow can be set directly on the PICV without the need of a manometer
or a commissioning unit.
METERING STATION
• The differential pressure only needs to be checked at the PICV to set the
PRIMARY PUMP required flow.
TEMPERATURE SENSOR
(INDOOR)
Considerations
• A metering station can be placed on main line if additional flow
verification is required by the witnessing authority.
18
Typical Application Schematics
3.0 For Frese DYNAMIC valves
Benefits
• The PICV ensures balancing of the flow and eliminates the use of both
static balancing valves and differential pressure control valves.
• Simple installation as only the PICV is required with no need for additional
R
pressure or flow balancing valves.
HEAT PUMP
• Low total pressure loss in the system due to simple design.
F
PRESSURE INDEPENDENT • The flow can be set directly on the PICV without the need of a manometer
CONTROL VALVE
or a commissioning unit.
CONTROLLER • The differential pressure only needs to be checked at the PICV to set the
required flow.
METERING STATION
19
Typical Application Schematics
3.0 For Frese DYNAMIC valves
Benefits
• The PICV ensures balancing of the flow and eliminates the use of both
static balancing valves and differential pressure control valves.
• Simple installation.
• Low total pressure loss in the system due to simple design.
• The flow can be set directly on the PICV without the need of a
manometer or a commissioning unit.
HOT WATER TANK • The flow limiting feature of the PICV ensures a minimum Delta T for the
F
water heating up the tank.
CONTROLLER
• Legionella heating up cycles can be performed automatically.
R
PRESSURE INDEPENDENT
CONTROL VALVE
Considerations
METERING STATION
• A metering station can be installed if additional flow verification is
PRIMARY PUMP required by the witnessing authority.
TEMPERATURE SENSOR
20
Typical Application Schematics
3.0 For Frese DYNAMIC valves
3.14
Hot Water Tank Function
with PICV control and Self Acting Thermostat
The hot water temperature in the tank is controlled by a self-acting
thermostat with a remote sensor placed in a sensor pocket located in the
tank.
The self-acting thermostat is mounted directly on the PICV.
Benefits
• The PICV ensures balancing of the flow and eliminates the use of both
static balancing valves and differential pressure control valves.
• Simple installation with no need of any control system.
• Low total pressure loss in the system due to simple design.
• The flow can be set directly on the PICV without the need of a
manometer or a commissioning unit.
F
REMOTE SENSOR
• The flow limiting feature of the PICV ensures a minimum Delta T for the
water heating up the tank.
R
HOT WATER TANK
PRESSURE INDEPENDENT
Considerations
CONTROL VALVE
WITH SELF ACTING • Legionella heating up cycles cannot be performed automatically.
THERMOSTAT
21
Typical Application Schematics
3.0 For Frese DYNAMIC valves
SECONDARY PUMP
• Secondary pump is switched off when no demand.
TEMPERATURE SENSOR
(INDOOR)
Considerations
• Minimum differential pressure required for the PICV must be available
at design flow.
22
Typical Application Schematics
3.0 For Frese DYNAMIC valves
DIFFERENTIAL PRESSURE
CONTROL VALVE
Benefits
PRESSURE INDEPENDENT
CONTROL VALVE • Prevents noise in the system.
CONTROLLER
• Provides good modulation for the radiator valves.
60˚C
30˚C
TEMPERATURE SENSOR
• All sections will have a defined DP available.
70˚C
30˚C
(INDOOR)
TEMPERATURE SENSOR • With the correct radiator valve pre-setting, the flow will be controlled in
(OUTDOOR)
every part of the system.
F METERING STATION
SECONDARY PUMP
PLEASE NOTE: TEMPERATURES ARE SHOWN FOR EXAMPLE ONLY Considerations
• If the radiator valves are without pre-setting or they are not set correctly,
the flow in the system will not be in balance.
DIFFERENTIAL PRESSURE
Benefits
CONTROL VALVE
• The flow rate through the dynamic balancing valve is independent of
PRESSURE INDEPENDENT
CONTROL VALVE
the differential pressure across it.
• The flow can be set without the use of a manometer/commissioning
CONTROLLER
device.
60˚C
30˚C
TEMPERATURE SENSOR
• Only 1 dynamic balancing valve in series.
70˚C
30˚C
(INDOOR)
TEMPERATURE SENSOR
(OUTDOOR) • If the system is expanded, it will not need to be rebalanced.
F METERING STATION
• No straight lengths of pipe before or after the dynamic balancing valve
R PRIMARY PUMP are required.
SECONDARY PUMP • Prevents noise in the system and provides good modulation to the
PLEASE NOTE: TEMPERATURES ARE SHOWN FOR EXAMPLE ONLY
radiator valves.
• All sections will have a defined DP available.
Considerations
Frese PV-SIGMA Compact Frese OPTIMA Compact
• Higher cost from both DP control valve and dynamic balancing valve
DPCV & Dynamic Flow Pressure Independent
Limiting Valve Control Valve • A metering station can be installed if additional flow verification is
required by the witnessing authority.
24
Typical Application Schematics
3.0 For Frese DYNAMIC valves
30˚C
30˚C
(INDOOR)
TEMPERATURE SENSOR
(OUTDOOR) • Only 1 dynamic balancing valve in series.
F METERING STATION
• If the system is expanded, it will not need to be rebalanced.
R PRIMARY PUMP
• No straight lengths of pipe before or after the dynamic balancing valve
PLEASE NOTE: TEMPERATURES ARE SHOWN FOR EXAMPLE ONLY
SECONDARY PUMP
are required.
Considerations
• Minimum differential pressure required for the dynamic balancing valve
Frese OPTIMA Compact must be available at design flow.
Frese SIGMA Compact
Pressure Independent • The differential pressure in the different sections of the system cannot be
Dynamic Flow Limiting Valve
Control Valve controlled.
25
Typical Application Schematics
3.0 For Frese DYNAMIC valves
Benefits
• The PICV ensures balancing of the flow and eliminates the use of both
static balancing valves and differential pressure control valves.
• Simple installation as only the PICV is required with no need for
additional pressure or flow balancing valves.
• Low total pressure loss in the system due to simple design.
• The flow can be set directly on the PICV without the need of a
manometer or a commissioning unit.
TERMINAL UNIT
F • The differential pressure only needs to be checked at the PICV placed at
PRESSURE INDEPENDENT
the index point, or at the end of every branch.
CONTROL VALVE
R
26
Typical Application Schematics
3.0 For Frese DYNAMIC valves
Benefits
• The PICV ensures balancing of the flow and eliminates the use of both
static balancing valves and differential pressure control valves.
• Simple installation as only the PICV is required with no need for
TERMINAL UNIT
additional pressure or flow balancing valves.
F PRESSURE INDEPENDENT • Low total pressure loss in the system due to simple design.
CONTROL VALVE
• The flow can be set directly on the PICV without the need of a
R CONTROLLER manometer or a commissioning unit.
METERING STATION
• The differential pressure only needs to be checked at the PICV placed at
the index point, or at the end of every branch.
PRIMARY PUMP
TEMPERATURE SENSOR
(INDOOR) Considerations
• Minimum differential pressure required for the PICV must be available
at design flow.
• A metering station can be placed on the branch if additional flow
verification is required by the witnessing authority.
27
Typical Application Schematics
3.0 For Frese DYNAMIC valves
Benefits
• The PICV ensures balancing of the flow and eliminates the use of both
INDEX PICV
static balancing valves and differential pressure control valves.
• Simple installation as only the PICV is required with no need for
additional pressure or flow balancing valves.
• Low total pressure loss in the system due to simple design.
• The flow can be set directly on the PICV without the need of a
TRENCH HEATER
manometer or a commissioning unit.
INDEX PRESSURE
INDEPENDENT CONTROL
VALVE
• The differential pressure only needs to be checked at the PICV placed at
PRESSURE INDEPENDENT
the index point, or at the end of every branch.
CONTROL VALVE
CONTROLLER Considerations
METERING STATION • A metering station can be placed on the branch if additional flow
PRIMARY PUMP verification is required by the witnessing authority.
F R
• The index valve will, in applications such as this with identical design
and coil performance, be the one furthest from the pump, but it can be
elsewhere in other layouts.
• In theory, PT-plugs are only needed on the index PICV, but for
commissioning and diagnostic purposes, it can be useful to have PT-
plugs on each valve.
Frese OPTIMA Compact
Pressure Independent Control Valve
28
Typical Application Schematics
3.0 For Frese DYNAMIC valves
Benefits
• The PICV ensures balancing of the flow and eliminates the use of both
UNDERFLOOR HEATING
static balancing valves and differential pressure control valves.
PRESSURE INDEPENDENT • Simple installation as only the PICV is required with no need for
CONTROL VALVE
additional pressure or flow balancing valves.
30˚C
25˚C
CONTROLLER
• Low total pressure loss in the system due to simple design.
70˚C
25˚C
TEMPERATURE SENSOR • The flow can be set directly on the PICV without the need of a
(INDOOR)
TEMPERATURE SENSOR
manometer or a commissioning unit.
F
(OUTDOOR)
R METERING STATION
Considerations
PRIMARY PUMP
• Minimum differential pressure required for the PICV must be
SECONDARY PUMP
available at design flow.
PLEASE NOTE: TEMPERATURES ARE SHOWN FOR EXAMPLE ONLY
29
Types of Projects
4.0 For Frese DYNAMIC valves
Shopping
Malls
Sports Education
Please visit
www.frese.eu/
Commercial
Hotels Residential
HVAC
for more details
Buildings
30
Case Study
5.0 PICV energy savings - Canary Wharf, London a
Overview
We installed a DN65 pressure independent control valve on an air handling unit together with a
variety of sensors and data collection equipment to monitor the performance of the valve and the
associated air handling unit.
We were also able to compare the performance of the air handling unit with a pressure independent
control valves fitted to the same air handling unit with a conventional 2 port modulating control valve
fitted.
Findings
•
a
The off coil air temperature is controlled much more tightly by the pressure independent b
control valve compared to the conventional two port modulating valve
• With the relative flow control through the air handling unit when fitted with pressure
b
independent control valve or fitted with a conventional two port control valve. Again, the
amplitude and frequency of the oscillations are higher when the air handling unit is fitted with
a conventional two port modulating valve
• Compare the relative cooling output of the air handling unit when fitted with a pressure
c
independent control valve and two port modulating valve, we can see once again the power
output from the coil is much more stable when fitted with a pressure independent control valve
Conclusion
The actual energy saving was calculated using the pump affinity laws and the coil power output c
equation to compare the energy performance of the air handling unit when fitted with a pressure
independent control valve and a conventional two port modulating valve.
The results showed that when the system was fitted with a PICV, the same AHU can satisfy the same
cooling load with 35% less pump energy consumption and in increased ∆T.
www.frese.eu/hvac
Denmark - Main Office United Kingdom China Australia & New Zealand
Frese A/S Frese Ltd Frese Valves (Ningbo) Co., Ltd. Frese Asia Pacific
Tel: +45 58 56 00 00 Tel: +44 (0) 1704 896 012 Tel: +86 (21) 5110 3212 Tel: +61431 794 414