Professional Documents
Culture Documents
APPENDIX 6-1
Residential Unit
Maximum Population 315
(1)
Unit Flow Factor 0.37 m3/head/d
0.37 x 315
Design Average Dry Weather Flow
116.55 m3/d
Peaking Factor 8 (for population < 1,000)
8 x 116.55
Design Flow
932.40 m3/d (10.79 l/s)
Employees
No. of employees 30
(1)
Unit Flow Factor 0.28 m3/head/d
0.28 x 30
Design Average Dry Weather Flow
8.40 m3/d
Peaking Factor 8 (for population < 1,000)
8 x 8.40
Design Flow for Employees
67.20 m3/d (0.77 l/s)
Privileged and Confidential Comprehensive Development and Wetland Protection
Near Yau Mei San Tsuen
Employees
Pool Area 930 m2
Pool Depth 1.3 m
930 x 1.3
Pool Volume
1209 m3
Turnover Rate 4 hrs
Surface Loading Rate of Filter 20 m3/m2/hr
1209/4/20
Filter Areas Required
15.11 m2
Backwash Duration 3 min/d
Backwash Flow Rate 30 m3/m2/hr
30 x 15.11 x 3 / 60
Design Flow for Swimming Pool Backwashing
22.67 m3/d (0.26 l/s)
Swimming
Items Units Resident Employee Total
Pool
Overall Design
Average Dry Weather m3/d 116.55 8.40 22.67 147.62
Flow (ADWF)