Professional Documents
Culture Documents
Servo Drive
(Catalog Numbers
2094-AC05-MP5, -AC05-M01, -AC09-M02,
-AC16-M03, -AC32-M05
2094-BC01-MP5, -BC01-M01, -BC02-M02,
-BC04-M03, -BC07-M05
2094-BC01-MP5-S, -BC01-M01-S,
-BC02-M02-S, -BC04-M03-S, -BC07-M05-S
2094-PRF
2094-AL09, -AL75S
2094-BL02, -BL75S
2094-XL75S-C1
2094-XL75S-C2
2094-BSP2)
Installation Manual
Important User Information Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application,
Installation and Maintenance of Solid State Controls (Publication SGI-1.1
available from your local Rockwell Automation sales office or online at
http://www.rockwellautomation.com/literature) describes some important
differences between solid state equipment and hard-wired electromechanical
devices. Because of this difference, and also because of the wide variety of
uses for solid state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this
equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for
indirect or consequential damages resulting from the use or application of
this equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with
any particular installation, Rockwell Automation, Inc. cannot assume
responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to
use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without
written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of
safety considerations.
Allen-Bradley, A-B, ControlLogix, Kinetix, and Rockwell Automation are registered trademarks of Rockwell Automation.
RSLogix, RSLogix 5000, SoftLogix, and SCANport are trademarks of Rockwell Automation.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Table of Contents
Preface
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Who Should Use this Manual . . . . . . . . . . . . . . . . . . . . . . . P-1
Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Contents of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . P-2
Product Receiving and Storage Responsibility . . . . . . . . . . . P-2
Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . P-3
Conventions Used in this Manual . . . . . . . . . . . . . . . . . . . . P-4
Chapter 1
Install Your Kinetix 6000 Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Comply with European Union Directives . . . . . . . . . . . . . . 1-2
EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Low Voltage Directive. . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Kinetix 6000 System Component Overview. . . . . . . . . . . . . 1-4
Before Mounting Your System . . . . . . . . . . . . . . . . . . . . . . 1-7
Unpack Your Kinetix 6000 . . . . . . . . . . . . . . . . . . . . . . 1-7
System Mounting Requirements. . . . . . . . . . . . . . . . . . 1-10
Ventilation Requirements . . . . . . . . . . . . . . . . . . . . . . 1-11
Size an Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-15
Size a Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-17
Circuit Breaker/Fuse Selection. . . . . . . . . . . . . . . . . . . 1-18
HF Bonding Your System. . . . . . . . . . . . . . . . . . . . . . . . . 1-19
Bonding Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-19
Bonding Multiple Subpanels . . . . . . . . . . . . . . . . . . . . 1-21
Plan Your Panel Layout . . . . . . . . . . . . . . . . . . . . . . . . . . 1-21
Establish Noise Zones . . . . . . . . . . . . . . . . . . . . . . . . . 1-22
Cable Categories for the Kinetix 6000 . . . . . . . . . . . . . 1-29
Mounting Guidelines to Reduce Electrical Noise . . . . . 1-31
Bulletin 2094 Mounting Brackets . . . . . . . . . . . . . . . . . 1-35
Mount Your Kinetix 6000 Drive System. . . . . . . . . . . . . . . 1-37
Install 2094 Mounting Brackets . . . . . . . . . . . . . . . . . . 1-37
Mount Your Power Rail . . . . . . . . . . . . . . . . . . . . . . . 1-38
Mount Your Integrated Axis Module . . . . . . . . . . . . . . 1-40
Mount Your Axis Module(s) . . . . . . . . . . . . . . . . . . . . 1-43
Mount Your Shunt Module . . . . . . . . . . . . . . . . . . . . . 1-45
Mount Your Slot Filler Module(s) . . . . . . . . . . . . . . . . 1-46
Install 2094 Mounting Brackets . . . . . . . . . . . . . . . . . . 1-47
Mount Your Line Interface Module . . . . . . . . . . . . . . . 1-48
Mount Your External Shunt Resistor Kit . . . . . . . . . . . . 1-49
Replace Kinetix 6000 System Components . . . . . . . . . . 1-49
Chapter 2
Kinetix 6000 Connector Data Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Locate IAM Connectors and Indicators . . . . . . . . . . . . . . . . 2-2
Locate AM Connectors and Indicators . . . . . . . . . . . . . . . . . 2-3
IAM and AM Connector Pin-outs. . . . . . . . . . . . . . . . . . . . . 2-4
Integrated Axis Module/Axis Module Connectors . . . . . . 2-4
Safe-Off Connector Pin-out . . . . . . . . . . . . . . . . . . . . . . 2-4
I/O Connector Pin-out . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Motor Feedback Connector Pin-outs . . . . . . . . . . . . . . . 2-6
Auxiliary Feedback Connector Pin-outs . . . . . . . . . . . . . 2-8
IAM Input Connector Pin-outs . . . . . . . . . . . . . . . . . . . . 2-9
IAM and AM Motor Power and Brake Connector
Pin-outs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Understand IAM/AM Signal Specifications . . . . . . . . . . . . . 2-11
Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
SERCOS Connections . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Contactor Enable Relay . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Motor/Resistive Brake Relay . . . . . . . . . . . . . . . . . . . . 2-15
Control Power Input . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Understand Feedback Specifications . . . . . . . . . . . . . . . . . 2-17
Motor and Auxiliary Feedback Specifications . . . . . . . . 2-17
Locate SM Connectors and Indicators . . . . . . . . . . . . . . . . 2-19
Shunt Module Connectors . . . . . . . . . . . . . . . . . . . . . . 2-19
Shunt Module Connector Pin-outs . . . . . . . . . . . . . . . . 2-19
Locate LIM Connectors and Indicators. . . . . . . . . . . . . . . . 2-20
LIM Connector Pin-outs . . . . . . . . . . . . . . . . . . . . . . . . . . 2-22
Line Interface Module Connectors . . . . . . . . . . . . . . . . 2-22
I/O Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-23
Auxiliary Power Input Connector. . . . . . . . . . . . . . . . . 2-24
Control Power Output Connector . . . . . . . . . . . . . . . . 2-25
24V dc Brake Supply Connector . . . . . . . . . . . . . . . . . 2-25
VAC LINE Connector. . . . . . . . . . . . . . . . . . . . . . . . . . 2-26
VAC LOAD Connector. . . . . . . . . . . . . . . . . . . . . . . . . 2-27
Auxiliary Power Connector . . . . . . . . . . . . . . . . . . . . . 2-27
Understand LIM Signal Specifications . . . . . . . . . . . . . . . . 2-28
LIM I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-28
LIM Brake Power Supply (2094-AL09 and -BL02) . . . . . 2-35
LIM Control Power . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-36
Auxiliary Power Output . . . . . . . . . . . . . . . . . . . . . . . 2-37
Auxiliary Power Input . . . . . . . . . . . . . . . . . . . . . . . . . 2-37
Chapter 3
Connect Your Kinetix 6000 Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Understand Basic Wiring Requirements . . . . . . . . . . . . . . . 3-1
Build Your Own Cables . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Route Power and Signal Wiring. . . . . . . . . . . . . . . . . . . 3-2
Determine Your Type of Input Power . . . . . . . . . . . . . . . . 3-3
Grounded Power Configurations . . . . . . . . . . . . . . . . . . 3-3
Ungrounded Power Configurations . . . . . . . . . . . . . . . . 3-5
DC Common Bus Configurations . . . . . . . . . . . . . . . . . . . . 3-6
Common Bus Fusing Requirements . . . . . . . . . . . . . . . . 3-7
Set the Ground Jumper in Ungrounded Power
Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Remove the IAM from the Power Rail . . . . . . . . . . . . . . 3-8
Set the Ground Jumper . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Ground Your Kinetix 6000 . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Ground Your System to the Subpanel . . . . . . . . . . . . . 3-11
Ground Multiple Subpanels. . . . . . . . . . . . . . . . . . . . . 3-12
Motor Power Cable Shield Termination . . . . . . . . . . . . 3-12
Power Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . 3-17
IAM Power Wiring Requirements. . . . . . . . . . . . . . . . . 3-17
IAM/AM Power Wiring Requirements . . . . . . . . . . . . . 3-18
LIM Power Wiring Requirements . . . . . . . . . . . . . . . . . 3-19
Shunt Module Power Wiring Requirements . . . . . . . . . 3-20
Connect Input Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22
Connect the Braided Ground Strap . . . . . . . . . . . . . . . 3-22
Connect Input Power (IAM with LIM) . . . . . . . . . . . . . 3-22
Connect Input Power (IAM without LIM) . . . . . . . . . . . 3-29
Connect Input Power (Common Bus) . . . . . . . . . . . . . 3-31
Safe-Off Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-33
Wire the Contactor Enable Connector . . . . . . . . . . . . . . . . 3-34
Connect Motor Power and Brakes . . . . . . . . . . . . . . . . . . 3-35
Understand Feedback and I/O Cable Connections . . . . . . 3-40
Motor Feedback Connector Pin-outs . . . . . . . . . . . . . . 3-41
Wire Feedback and I/O Connectors . . . . . . . . . . . . . . 3-44
Understand External Shunt Connections . . . . . . . . . . . . . . 3-48
Understand Resistive Brake Module Connections . . . . . . . 3-49
Connect Your SERCOS Fiber-Optic Cables . . . . . . . . . . . . 3-50
Chapter 4
Troubleshoot Status Indicators Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
General Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Troubleshoot IAM/AM Status LEDs . . . . . . . . . . . . . . . . . . . 4-7
Drive Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Comm Status LED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Bus Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Troubleshoot SM Status LEDs . . . . . . . . . . . . . . . . . . . . . . . 4-9
Appendix A
Specifications and Dimensions Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Power Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Integrated Axis Module (converter) 230V Power
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Integrated Axis Module (converter) 460V Power
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3
Axis Module (inverter) 230V Power Specifications . . . . . A-4
Axis Module (inverter) 460V Power Specifications . . . . . A-5
Line Interface Module Power Specifications . . . . . . . . . . A-6
Shunt Module Specifications . . . . . . . . . . . . . . . . . . . . . A-7
Shunt Module (230V) System Specifications . . . . . . . . . . A-8
Shunt Module (460V) System Specifications . . . . . . . . . . A-9
Circuit Breaker/Fuse Specifications . . . . . . . . . . . . . . . A-11
Contactor Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-13
Input Transformer for Control Power . . . . . . . . . . . . . . A-13
Power Dissipation Specifications . . . . . . . . . . . . . . . . . A-14
General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . A-15
Environmental Specifications . . . . . . . . . . . . . . . . . . . . A-15
Maximum Feedback Cable Lengths . . . . . . . . . . . . . . . A-16
AC Line Filter Specifications . . . . . . . . . . . . . . . . . . . . . . . A-17
External Shunt Module Specifications . . . . . . . . . . . . . . . . A-18
External Passive Shunt Module Specifications . . . . . . . . A-18
External Active Shunt Module Specifications . . . . . . . . A-18
Resistive Brake Module Specifications . . . . . . . . . . . . . . . . A-19
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-19
Integrated Axis Module Dimensions. . . . . . . . . . . . . . . A-20
Axis Module Dimensions. . . . . . . . . . . . . . . . . . . . . . . A-22
Shunt Module Dimensions. . . . . . . . . . . . . . . . . . . . . . A-24
Slot Filler Module Dimensions . . . . . . . . . . . . . . . . . . . A-25
Power Rail Dimensions . . . . . . . . . . . . . . . . . . . . . . . . A-25
Line Interface Module Dimensions. . . . . . . . . . . . . . . . A-28
Mounting Bracket Dimensions. . . . . . . . . . . . . . . . . . . A-31
Appendix B
Interconnect Diagrams Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Kinetix 6000 Interconnect Diagram Notes . . . . . . . . . . . . . . B-1
Power Interconnect Diagrams . . . . . . . . . . . . . . . . . . . . . . B-3
DC Common Bus Interconnect Diagrams . . . . . . . . . . . . . . B-8
Shunt Module Interconnect Diagrams . . . . . . . . . . . . . . . . B-13
1336 Active Shunt Input Fuse Specifications. . . . . . . . . B-14
1336 Active Shunt Fault Relay Specifications . . . . . . . . B-14
Resistive Brake Module Interconnect Diagrams . . . . . . . . . B-16
AM/Motor Interconnect Diagrams. . . . . . . . . . . . . . . . . . . B-17
Controlling a Brake Example . . . . . . . . . . . . . . . . . . . . . . B-25
System Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . B-27
IAM/AM Inverter Block Diagram . . . . . . . . . . . . . . . . . B-27
IAM Converter Block Diagram. . . . . . . . . . . . . . . . . . . B-28
Safe-Off Feature Block Diagram . . . . . . . . . . . . . . . . . B-29
SM Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . B-29
LIM Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . B-30
RBM Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . B-35
Appendix C
Catalog Numbers and Accessories Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
Integrated Axis Modules. . . . . . . . . . . . . . . . . . . . . . . .. . . C-2
Axis Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . C-2
Shunt Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . C-3
Power Rails . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . C-3
Power Rail Slot Filler . . . . . . . . . . . . . . . . . . . . . . . . . .. . . C-3
RSLogix 5000 Software . . . . . . . . . . . . . . . . . . . . . . . . .. . . C-3
Line Interface Modules. . . . . . . . . . . . . . . . . . . . . . . . .. . . C-4
Resistive Brake Modules. . . . . . . . . . . . . . . . . . . . . . . .. . . C-4
AC Line Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . C-4
External Shunt Resistor Kits . . . . . . . . . . . . . . . . . . . . .. . . C-5
Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . C-5
Motor Power Cables . . . . . . . . . . . . . . . . . . . . . . . .. . . C-5
Motor Feedback Cables. . . . . . . . . . . . . . . . . . . . . .. . . C-6
Motor Brake Cable . . . . . . . . . . . . . . . . . . . . . . . . .. . . C-6
RBM to Drive Interface Cable . . . . . . . . . . . . . . . . .. . . C-6
SERCOS Interface Fiber-Optic Cables. . . . . . . . . . . .. . . C-7
Connector Kits and Miscellaneous Accessories . . . . . . .. . . C-7
Low Profile Connector Kits . . . . . . . . . . . . . . . . . . .. . . C-7
Mounting Bracket . . . . . . . . . . . . . . . . . . . . . . . . . .. . . C-7
Panel-Mounted Breakout Boards, Cables, and Kits . .. . . C-8
Drive End Connector Kits . . . . . . . . . . . . . . . . . . . .. . . C-8
Motor End Connector Kits. . . . . . . . . . . . . . . . . . . .. . . C-9
Module Connector Sets . . . . . . . . . . . . . . . . . . . . . .. . C-10
Introduction Read this preface to familiarize yourself with the rest of the manual.
This preface contains the following topics:
Who Should Use this Use this manual for designing, installing, and wiring your Kinetix 6000
Multi-Axis Servo Drive. The manual is intended for engineers or
Manual technicians directly involved in the installation and wiring of the
Kinetix 6000.
Purpose of this Manual This manual provides the mounting, wiring, and connecting
procedures for the Kinetix 6000 and standard Rockwell Automation/
Allen-Bradley motors recommended for use with the Kinetix 6000.
ControlLogix Motion
Interface Module SoftLogix PCI Card
Contents of this Manual Refer to the following listing for the descriptive contents of this
installation manual.
Chapter 2 Kinetix 6000 Connector Data Provides IAM, AM, SM, and LIM connector
locations, signal descriptions, and specifications.
Chapter 3 Connect Your Kinetix 6000 Provides connection and wiring information for
the Kinetix 6000 drive components.
Provides troubleshooting tables that define the
Chapter 4 Troubleshoot Status Indicators Kinetix 6000 status LED error codes.
Provides mounting dimensions, and power,
Appendix A Specifications and Dimensions weight, environmental, and functional
specifications for the Kinetix 6000.
Provides power and drive/motor interconnect
Appendix B Interconnect Diagrams diagrams for the Kinetix 6000. Also provides
Kinetix 6000 system component block diagrams.
Catalog Numbers and Provides catalog numbers and descriptions of the
Appendix C Accessories Kinetix 6000 and related products.
Product Receiving and You, the customer, are responsible for thoroughly inspecting the
equipment before accepting the shipment from the freight company.
Storage Responsibility Check the item(s) you receive against your purchase order. If any
items are obviously damaged, it is your responsibility to refuse
delivery until the freight agent has noted the damage on the freight
bill. Should you discover any concealed damage during unpacking,
you are responsible for notifying the freight agent. Leave the shipping
container intact and request that the freight agent make a visual
inspection of the equipment.
Kinetix 6000 user documentation and CAD files Kinetix 6000 User Documentation and CAD Files CD 2094-CL001
More detailed information on the use of ControlLogix motion ControlLogix Motion Module Programming Manual 1756-RM086
features and application examples
ControlLogix SERCOS interface Module Installation
ControlLogix SERCOS interface module installation instructions Instructions 1756-IN572
SoftLogix SERCOS interface PCI card installation instructions 16 Axis PCI SERCOS interface Card Installation 1784-IN041
Instructions
The instructions needed to program a motion application Logix5000 Controllers Motion Instructions 1756-RM007
Reference Manual
Information on configuring and troubleshooting your ControlLogix
SERCOS and analog motion modules Logix5000 Motion Modules User Manual 1756-UM006
Information on configuring and troubleshooting your SoftLogix PCI SoftLogix Motion Card Setup and Configuration 1784-UM003
card Manual
Information on proper handling, installing, testing, and Fiber-Optic Cable Installation and Handling
troubleshooting fiber-optic cables Instructions 2090-IN010
Information, examples, and techniques designed to minimize system System Design for Control of Electrical Noise GMC-RM001
failures caused by electrical noise Reference Manual
For declarations of conformity (DoC) currently available from www.ab.com/
Rockwell Automation Rockwell Automation Product Certification website certification/ce/docs
Published by the National
An article on wire sizes and types for grounding electrical equipment National Electrical Code Fire Protection Association
of Boston, MA.
A glossary of industrial automation terms and abbreviations Allen-Bradley Industrial Automation Glossary AG-7.1
Conventions Used in this The conventions starting below are used throughout this manual.
Manual • Bulleted lists such as this one provide information, not procedural
steps
• Numbered lists provide sequential steps or hierarchical
information
• Words that you type or select appear in bold
• When we refer you to another location, the section or chapter
name appears in italics
• Acronyms for the Kinetix 6000 components, shown in the table
below, are used throughout this manual.
Chapter Objectives This chapter provides system installation guidelines and procedures
for mounting your Kinetix 6000. This chapter covers the following
topics:
Comply with European If this product is installed within the European Union or EEC regions
and has the CE mark, the following regulations apply.
Union Directives
Meeting CE requires a grounded system, and the
ATTENTION
method of grounding the AC line filter and drive
must match. Failure to do this renders the filter
ineffective and may cause damage to the filter. For
grounding examples, refer to Grounded Power
Configurations on page 3-3.
EMC Directive
Kinetix 6000 System This section provides an overview of the Kinetix 6000 system
components and a typical installation.
Component Overview
IMPORTANT Acronyms for the Kinetix 6000 components, as
described in the table below, are used throughout
this manual.
Line Interface 2094-xLxx The Line Interface Module (LIM) contains the circuit breakers, AC line filter (2094-AL09 and -BL02 only),
Module 2094-xLxxS power supplies, and safety contactor required for Kinetix 6000 operation. This module does not mount to
2094-XL75S-Cx the power rail. Individual components can be purchased separately in place of the LIM.
The Kinetix 6000 shunt module (SM) mounts to the power rail and provides additional shunting
Shunt Module 2094-BSP2 capability in regenerative applications.
ControlLogix/ 1756-MxxSE module The SERCOS interface module/PCI card serves as a link between the ControlLogix/SoftLogix platform
SoftLogix Platforms 1784-PM16SE PCI card and Kinetix 6000 system. The communication link uses the IEC 61491 SErial Real-time COmmunication
System (SERCOS) protocol over a fiber-optic cable.
RSLogix 5000 RSLogix 5000 provides support for programming, commissioning, and maintaining the Logix family of
software 9324-RLD300ENE controllers.
MP-Series, 1326AB, The MP-Series (Low Inertia, Integrated Gear, Food Grade, and Stainless Steel) 230 and 460V motors;
Servo Motors TL-Series, F-, H-, N-, and TL-Series motors; 1326AB (M2L/S2L) and 1326AB (resolver) motors; F-, H-, N-, and Y-Series motors are
Y-Series available for use with the Kinetix 6000.
Motor power, feedback, and brake cables include integral molded, bayonet style, quick connect/
quick-release connectors at the motor. Power and brake cables have flying leads on the drive end and
Motor Power, Feedback, straight connectors that connect to servo motors. Standard feedback cables have angled connectors
and Brake cables (45º) on the drive end and straight connectors that connect to servo motors. Optional feedback cables
Cables have a straight connector on the motor end and flying leads that wire to a low-profile connector on the
drive end.
SERCOS fiber-optic cables are available in enclosure only, PVC, nylon, and glass with connectors at both
Fiber-Optic cables ends.
AC Line Filters 2090-XXLF-xxxx The 2090-XXLF-xxxx three-phase AC line filters are available for 230V and 460V systems.
1394-SRxxxx The Bulletin 1394 external passive shunt modules are available when the IAM/AM internal shunt and
External Shunt power rail mounted shunt module (2094-BSP2) capability is exceeded.
Modules The Bulletin 1336 external active shunt modules are available when the internal shunt resistor (IAM/
1336-MOD-Kxxxx AM) capability is exceeded.
The Resistive Brake Module (RBM) includes a safety contactor for use in a control circuit. Contactors and
Resistive Brake 2090-XBxx-xx resistors reside in this module such that the motor leads can be disconnected from the drive with the
Module permanent magnet motor brought to an immediate stop. This module does not mount to the power rail.
1
Refer to the Kinetix Safe-Off Feature Safety Reference Manual (publication GMC-RM002) for more information.
Note: Refer to Appendix C for a complete list of catalog numbers for the Kinetix 6000 components listed above.
Figure 1.1
Typical Three-Phase AC System Installation
SERCOS interfaceTM
CP OK
RBM I/O
ControlLogix Chassis
Tx (rear)
Rx (front)
Resistive Resistive
Brake Brake
Kinetix 6000 Multi-Axis Servo Drive Modules Modules
(optional (optional
components) components)
SERCOS fiber-optic ring
AC Line
Filter
Three-Phase Shunt Module
Input Power (optional
component)
MAIN VAC
Slot Filler
Integrated Module
Line Interface Axis
(required
Module Module
to fill any
(optional unused slot)
component)
Power Rail
To Input Sensors
and Control String Axis Modules (5)
Refer to Appendix B for System Block Diagrams of the IAM, SM, LIM,
and RBM.
Figure 1.2
Typical DC Common Bus System Installation
ControlLogix Controller Programming Network
SERCOS interfaceTM
ControlLogix Chassis
CP OK
Tx (rear)
Rx (front)
AC Line
Filter SERCOS fiber-optic ring
Three-Phase Shunt Module
Input Power (optional
component)
MAIN VAC
Kinetix 6000
Line Interface Leader IAM Slot Filler
Module (6 axis system) Module
(optional (required
component) to fill any
unused slot)
Power Rail
Axis Modules (5)
DC Common Bus
SERCOS Fiber Optic Ring
Kinetix 6000
Follower IAM Slot Filler
(7 axis system) Module
(required
to fill any
unused slot)
Power Rail
Axis Modules (6)
Note: Motors and other details common to both three-phase AC and DC Common Bus configurations are removed.
Before Mounting Your Before you mount your Kinetix 6000 system make sure you
understand the following:
System
• Unpack Your Kinetix 6000
• System Mounting Requirements
• Ventilation Requirements
• Size an Enclosure
• Size a Transformer
• Circuit Breaker/Fuse Selection
Remove all packing material, wedges, and braces from within and
around the components. After unpacking, check the item(s) name
plate catalog number against the purchase order.
There are several things that you need to take into account when
preparing to mount the Kinetix 6000:
ATTENTION
Plan the installation of your system so that you can
perform all cutting, drilling, tapping, and welding
with the system removed from the enclosure.
Because the system is of the open type construction,
be careful to keep any metal debris from falling into
it. Metal debris or other foreign matter can become
lodged in the circuitry, which can result in damage to
components.
Ventilation Requirements
Figure 1.3
Minimum Clearance Requirements
IAM (2094-AC05, -AC09, -BC01, -BC02)
AM (2094-AMP5, -AM01, -AM02, -BMP5, -BM01, -BM02)
SM (2094-BSP2)
50.8 mm (2.0 in.) clearance DO NOT mount Kinetix 6000 system on its side.
for airflow and installation
1 The power rail (slim), catalog number 2094-PRSx, does not extend left or right of the first or last module
(respectively). When using power rail (catalog number 2094-PRx) the power rail extends approximately 25.4 mm
(1.0 in.) left of the IAM and right of the last module mounted on the rail.
Figure 1.4
Minimum Clearance Requirements
IAM (2094-AC16, -AC32, -BC04, -BC07)
AM (2094-AM03, -AM05, -BM03, -BM05)
305 mm (12.0 in.) clearance DO NOT mount Kinetix 6000 system on its side.
for airflow and installation
Power Rail
2094-PRSx is shown
Note: The LIM is not mounted on the Kinetix 6000 power rail.
Figure 1.5
Minimum Clearance Requirements
LIM (2094-AL75S, -BL75S, and -XL75S-Cx)
MAIN VAC
MAIN VAC
Clearance left of Clearance right of
Module is not required Module is not required
Figure 1.6
Minimum Clearance Requirements
LIM (2094-AL09 and -BL02)
Size an Enclosure
Size the Kinetix 6000 servo drive and LIM and use the results to
predict the amount of heat dissipated into the enclosure. You will also
need heat dissipation data from other equipment inside the enclosure
(such as ControlLogix). Once the total amount of heat dissipation (in
watts) is known, the minimum enclosure size can be calculated.
Heat dissipation for the Kinetix 6000 example system is shown in the
table below.
Heat Dissipation 1
Enclosure Component Description Loading 1 watts
Figure 1.7
ControlLogix Real Power
75
1756-P B72 Backplane 60
1756-P B75 Power Load 45
dc (watts) 30
15
0
0 20 40 60 80 100
0.38Q 4.08Q
A = ------------------------ A = ----------------
1.8T – 1.1 T – 1.1
The maximum ambient rating of the Kinetix 6000 is 50° C (122° F) and
if the maximum environmental temperature is 30° C (86° F) then
Q=606 and T=20 in the equation below.
0.38 ( 606 )
A = -------------------------------- ≈ 6.59m 2
1.8 ( 20 ) – 1.1
Since the minimum cabinet depth to house the 230V drive (selected
for this example) is 200 mm (7.9 in.), then the cabinet needs to be
approximately 2100 mm (high) x 1250 mm (wide) x 200 mm (deep).
Size a Transformer
This section describes the fuse and circuit breaker requirements for
your Kinetix 6000 system.
The Kinetix 6000 utilizes internal short circuit output protection and is
suitable for use on a circuit capable of delivering up to 100,000
amperes, when protected by class CC, J, L, and R fuses. Circuit
breakers with adequate widthstand and interrupt ratings, as defined in
NEC 2002, article 110.9 and 110.10, are also allowed.
Size Fuses
In most cases, fuses selected to match the drive input current rating
will meet the NEC requirements and provide the full drive capabilities.
Dual element, time delay (slow acting) fuses should be used to avoid
nuisance trips during the inrush current of power initialization. Refer
to Power Specifications on page A-2 for input current and inrush
current specifications for your IAM.
HF Bonding Your System Bonding is the practice of connecting metal chassis, assemblies,
frames, shields and enclosures to reduce the effects of electromagnetic
interference (EMI). For more information on the concept of
high-frequency (HF) bonding, the ground plane principle, and
electrical noise reduction, refer to System Design for Control of
Electrical Noise Reference Manual (publication GMC-RM001).
Bonding Modules
Unless specified, most paints are not conductive and they act as
insulators. To achieve a good bond between power rail and the
subpanel, surfaces need to be paint-free or plated. Bonding metal
surfaces creates a low-impedance return path for high-frequency
energy.
Figure 1.8
Recommended Bonding Practices for Painted Panels
Star washer
Flat washer Scrape paint
Nut Welded
stud Nut Flat washer
Use a wire brush to remove paint from If the mounting bracket is coated with
threads to maximize ground a non-conductive material (anodized,
connection. painted, etc.), scrape the material
Use plated panels or scrape paint on Star washer around the mounting hole.
front of panel.
Subpanel
Bolt
Tapped hole
Ground bus or
Nut
mounting bracket
Star washer
Scrape paint on both sides of
panel and use star washers.
Flat washer
Star washer
Nut
Flat washer
Figure 1.9
Multiple Subpanels and Cabinet
Recommended:
Bond the top and bottom of each subpanel to the cabinet using
25.4 mm (1.0 in.) by 6.35 mm (0.25 in.) wire braid.
Bonded cabinet
ground bus to
subpanel
Plan Your Panel Layout This section outlines the practices which minimize the possibility of
noise-related failures as they apply specifically to Kinetix 6000
installations. For more information on the concept of electrical noise
reduction, refer to System Design for Control of Electrical Noise
Reference Manual (publication GMC-RM001).
• The clean zone (C) is to the right and beneath the Kinetix 6000
(grey wireway).
• The dirty zone (D) is to the left and above the Kinetix 6000, and
above and below the LIM (black wireway).
• The very dirty zone (VD) is from the filter output to IAM. Shielded
cable is required on the EMC filter (LOAD side) and the braided
shield attached to the clamp provided.
• The SERCOS fiber optic cables are immune to electrical noise.
Figure 1.10
Establishing Noise Zones (LIM mounted left of IAM)
Dirty Wireway Clean Wireway
D VD
AC Line Filter Motor Power Cables
D D D
VAC LOAD Very dirty Filter/IAM connections
segregated (not in wireway)
Fiber-Optic Cable
D VD
VAC LINE D
No sensitive
MAIN VAC
equipment within
150 mm (6.0 in.) 2
Kinetix 6000
1
If IAM/AM I/O cable contains (dirty) relay wires, route cable with LIM I/O cable in dirty wireway.
2
When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples,
refer to the System Design for Control of Electrical Noise Reference Manual (publication GMC-RM001).
• The clean zone (C) is to the left and beneath the Kinetix 6000
(grey wireway).
• The dirty zone (D) is to the right and above the Kinetix 6000, and
above and below the LIM (black wireway).
• The very dirty zone (VD) is from the filter output to IAM. Shielded
cable is required on the EMC filter (LOAD side) and the braided
shield attached to the clamp provided.
• The SERCOS fiber optic cables are immune to electrical noise.
Figure 1.11
Establishing Noise Zones (LIM with EMC Filter behind IAM)
Clean Wireway Dirty Wireway
equipment within
150 mm (6.0 in.) 2 D
AC Line Filter
Kinetix 6000
Line Interface Module
1
If IAM/AM I/O cable contains (dirty) relay wires, route cable with LIM I/O cable in dirty wireway.
2 When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples,
refer to the System Design for Control of Electrical Noise Reference Manual (publication GMC-RM001).
• The clean zone (C) is to the left and beneath the drive system
(grey wireway).
• The dirty zone (D) is to the right and above the drive, and above
and below the LIM (black wireway).
• The very dirty zone (VD) is from the filter output to drive.
Shielded cable is required on the EMC filter (LOAD side) and the
braided shield attached to the clamp (when provided).
Figure 1.12
Establishing Noise Zones (EMC Filter behind LIM)
Clean Wireway Dirty Wireway
D D D Control VAC
Very dirty Filter/Drive connections Auxiliary VAC
segregated (not in wireway) VAC LINE 24V dc Brake
VAC LOAD
PR/PRS
VD
PRS
PR
PR
LIM LIM
No sensitive D LIM
I/O
equipment within MAIN VAC
AC (EMC)
Line Filter
Kinetix 6000
PR/PRS
PRS
PR
PR
LIM LIM
1
If drive system I/O cable contains (dirty) relay wires, route cable with LIM I/O cable in dirty wireway.
2
When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples,
refer to the System Design for Control of Electrical Noise Reference Manual (publication GMC-RM001).
3
Only the 2094-AL75S and -XL75S-Cx Line Interface Modules are compatible with the 2094 Mounting Brackets.
The 2094-BL75S, -AL09, and -BL02 models are not compatible.
• Keep the DC common bus cable (very dirty) segregated from all
other cables (not in a wireway).
Figure 1.13
Establishing Noise Zones (DC Common Bus)
Dirty Wireway Clean Wireway
D VD
AC Line Filter Motor Power Cables
D D D
VD
Fiber-Optic Cable
Very dirty DC Bus connections
segregated (not in wireway)
No sensitive
equipment within
150 mm (6.0 in.) 2
1
If IAM/AM I/O cable contains (dirty) relay wires, route cable with LIM I/O cable in dirty wireway.
2
When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples,
refer to the System Design for Control of Electrical Noise Reference Manual (publication GMC-RM001).
Note: This layout is preferred due to the reduced size of the very dirty
zone.
• The clean zone (C) is to the right and beneath the Kinetix 6000
(grey wireway).
• The dirty zone (D) is to the left and above the Kinetix 6000, and
above and below the LIM (black wireway).
• The very dirty zone (VD) is limited to where the LIM VAC output
jumpers over to the IAM. Shielded cable is required only if the
very dirty cables enter a wireway.
• The SERCOS fiber optic cables are immune to electrical noise.
Figure 1.14
Establishing Noise Zones (LIM mounted left of IAM)
D Fiber-Optic Cable
D
VD
No sensitive
equipment within
150 mm (6.0 in.) 2
Kinetix 6000
1 If IAM/AM I/O cable contains (dirty) relay wires, route cable with LIM I/O cable in dirty wireway.
2
When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples,
refer to the System Design for Control of Electrical Noise Reference Manual (publication GMC-RM001).
• The clean zone (C) is to the right and beneath the Kinetix 6000
(grey wireway).
• The dirty zone (D) is to the left and above the Kinetix 6000, and
above and below the LIM (black wireway).
• The LIM VAC output is very dirty (VD). Use shielded cable with a
braid clamp attached at both ends of the cable to reduce the rating
to dirty (D).
• The SERCOS fiber optic cables are immune to electrical noise.
Figure 1.15
Establishing Noise Zones (LIM mounted above IAM)
Dirty Wireway Clean Wireway
D VD
Very dirty LIM/IAM
connections must be
shielded with braid
clamp at both ends. 1
D
Motor Power Cables
D Fiber-Optic Cable
No sensitive
equipment within
150 mm (6.0 in.) 3
Kinetix 6000
C C
D
I/O 2 and Feedback Cables
Route Encoder/Analog/Registration
Shielded Cable
Route 24V dc I/O
Shielded Cable
1
For examples of shield clamp attachment, refer to the System Design for Control of Electrical Noise Reference
Manual (publication GMC-RM001)
2 If IAM/AM I/O cable contains (dirty) relay wires, route cable in dirty wireway.
3
When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples,
refer to the System Design for Control of Electrical Noise Reference Manual (publication GMC-RM001).
• The clean zone (C) is beneath the Kinetix 6000 and includes the
I/O wiring, feedback cable, and DC filter (grey wireway).
• The dirty zone (D) is above the Kinetix 6000 (black wireway) and
includes the circuit breakers, transformer, 24V dc power supply,
contactors, AC line filter, and motor power cables.
• The very dirty zone (VD) is limited to where the AC line (EMC)
filter VAC output jumpers over to the IAM. Shielded cable is
required only if the very dirty cables enter a wireway.
• The SERCOS fiber optic cables are immune to electrical noise.
Figure 1.16
Establishing Noise Zones (No LIM)
D D 2
VD
Contactors
Circuit
Breaker 24V Motor AC
Brake PS Line Filter
4
XFMR
DC
Kinetix 6000
Filter
2
3
C I/O 1 and Feedback Cables C
1
If IAM/AM I/O cable contains (dirty) relay wires, route cable in dirty wireway.
2
When space to the right of the IAM does not permit 150 mm (6.0 in.) segregation, use a grounded steel shield
instead. For examples, refer to the System Design for Control of Electrical Noise Reference Manual (publication
GMC-RM001).
3
This is a clean 24V dc available for any device that may require it. The 24V enters the clean wireway and exits to
the right.
4
This is a dirty 24V dc available for motor brakes and contactors. The 24V enters the dirty wireway and exits to the
left.
• The clean zone (C) is beneath the less noisy modules (I/O, analog,
encoder, registration, etc. (grey wireway).
• The dirty zone (D) is above and below the power supply and
noisy modules (black wireway).
• The SERCOS fiber optic cables are immune to electrical noise.
Figure 1.17
Establishing Noise Zones (ControlLogix)
Dirty Wireway Clean Wireway
EMC
Filter
Spare Slot(s)
D C
Zone Method
Wire/Cable Connector Very Ferrite Shielded
Dirty Dirty Clean Sleeve Cable
CTRL 1 and 2 CPD X
DC-/DC+ (unshielded cable) X
L1, L2, L3 (shielded cable) IPD X X
L1, L2, L3 (unshielded cable) X
CONT EN- and CONT EN+ (M1 contactor) CED X
DPI DPI X X
Zone Method
Wire/Cable Connector Very Ferrite Shielded
Dirty Clean
Dirty Sleeve Cable
U, V, W (motor power) MP X X
MBRK-, MBRK+ (motor brake) X
MBRK-, MBRK+ (motor brake) X X
1326AB motors with resolver feedback
BC
DBRK-, DBRK+ (resistive brake) X
COM, PWR (24V dc), filtered1 X
2
COM, PWR (24V dc), unfiltered X
COM, PWR (24V dc), safety enable, and SO X
feedback signals for Safe-Off feature
Motor Feedback MF X X
Auxiliary Feedback AF X X
Registration and Analog Outputs X X
IOD
Others X
Fiber-Optic Rx and Tx No Restrictions
1
Refer to Footnote 3 on page 1-28.
2
Refer to Footnote 4 on page 1-28.
Zone Method
Wire/Cable Connector Very Ferrite Shielded
Dirty Clean
Dirty Sleeve Cable
VAC LINE (main input) IPL X
230V ac input APL X
VAC LOAD (shielded option) X X
OPL
VAC LOAD (unshielded option) X
Control Power Output CPL X
MBRK PWR, MBRK COM P1L/PSL X
Status I/O IOL X
Auxiliary 230V ac P2L X
Zone Method
Wire/Cable Connector Very Ferrite Shielded
Dirty Dirty Clean Sleeve Cable
COL, DC+ (shielded option) X X
RC
COL, DC+ (unshielded option) X
Thermal Switch TS X X
Fan (if present) N/A X
Zone Method
Wire/Cable Connections Very Ferrite Shielded
Dirty Clean
Dirty Sleeve Cable
Resistive Brake Module Coil Power TB3-6 and TB3-7 X
TB1-1 thru -5
Resistive Brake Module I/O and TB3-8 X
AC Line Filters
• Mount the AC line filter on the same panel as the Kinetix 6000 and
as close to the Kinetix 6000 Power Rail as possible.
• Good HF bonding to the panel is critical. For painted panels, refer
to Figure 1.8.
• Segregate input and output wiring as far as possible.
Customer-supplied
metal enclosure
minimum
CAT. PART SER.
INPUT DC INPUT AC
FOR FUSE REPLACEMENT USE:
BUSSMAN CAT. NO.
FOR USE WITH 1394-SJT22-X SYSTEM MODULE
by local code)
D 2094-BSP2
D Shunt Module
VD
No sensitive
equipment within
150 mm (6.0 in.)
Kinetix 6000
D
I/O and Feedback Cables
When mounting your shunt module inside the enclosure, follow these
additional guidelines (refer to Figure 1.19 and for an example).
minimum
BULLETIN 1394 300W SHUNT MODULE
CAT. PART SER.
INPUT DC INPUT AC
FOR FUSE REPLACEMENT USE:
BUSSMAN CAT. NO.
FOR USE WITH 1394-SJT22-X SYSTEM MODULE
2094-BSP2
D D
Shunt Module
VD
No sensitive
equipment within
150 mm (6.0 in.)
Kinetix 6000
RBM D
I/O
D VD
No sensitive
equipment within
150 mm (6.0 in.)
Kinetix 6000
D
IAM/AM Feedback and
(clean) I/O
LIM and IAM/AM (dirty) I/O
The thermal switch and brake are mounted inside the motor, but how
you connect to the axis module depends on the motor series. Refer to
Connect Motor Power and Brakes in Chapter 3 for wiring guidelines
specific to your drive/motor combination. Refer to AM/Motor
Interconnect Diagrams in Appendix B for the interconnect diagram for
your drive/motor combination.
The number of brackets required for use with the power rail and LIM
are shown in the table below.
Figure 1.21
Mounting Bracket Features
PRS
PR
LIM LIM
Mounting Bracket
(2094-XNBRKT-1)
For use when mounting LIM For use when mounting For use when mounting LIM
Power Rail (2094-PRx)
For use when mounting
Power Rail (2094-PRSx or PRx)
For use when mounting 2094-PRS1 Power Rail
(bracket in right most position)
Figure 1.22
Mounting Brackets used with Power Rail
LIM
LIM
LIM
PR/PRS PR/PRS PR/PRS
Power Rail
Space for AC Line Filter
(2094-PRS8 shown)
beneath brackets and Power Rail.
PR PR PR
LIM
LIM
Mounting Bracket (2094-XNBRKT-1)
Use M6 (1/4 in.) bolts (2 places typical)
to mount each bracket to panel.
Figure 1.23
Mounting Brackets used with Power Rail and LIM PR/PRS
PRS
PR
PR
LIM LIM
LIM
LIM
LIM
AC Line Filter
beneath brackets, Line Interface Module
Power Rail Power Rail, and LIM.
(2094-PRS8 shown) PR PR PR
(2094-AL75S shown)
LIM
LIM
PR/PRS
PRS
PR
PR
LIM LIM
Mount Your Kinetix 6000 The procedures in this section assume you have prepared your panel
and understand how to bond your system. For installation instructions
Drive System regarding equipment and accessories not included here, refer to the
instructions that came with those items.
ATTENTION
This drive contains ESD (Electrostatic Discharge)
sensitive parts and assemblies. You are required to
follow static control precautions when you install,
test, service, or repair this assembly. If you do not
follow ESD control procedures, components can be
damaged. If you are not familiar with static control
procedures, refer to Allen-Bradley publication
8000-4.5.2, Guarding Against Electrostatic Damage
or any other applicable ESD Protection Handbook.
Bulletin 2094 mounting brackets can be used to mount the power rail
over the AC line filter.
If Then
1. Layout the position for your AC line filter
You are using the 2094 Mounting Brackets and (refer to Establish Noise Zones for panel
plan to mount the power rail over the AC line layout recommendations).
filter 2. Mount your AC line filter on the panel.
3. Go to Install 2094 Mounting Brackets.
You are not using the 2094 Mounting Brackets Go to Mount Your Power Rail.
4. Remove braided grounding strap from 2094 power rail (save nut
and washer). Refer to Figure 1.25 for location of strap.
Figure 1.24
Mounting Orientation
LIM
LIM
LIM
PR/PRS PR/PRS PR/PRS
AC Line Filter
(2090-XXLF-3100 shown)
LIM
LIM
The Kinetix 6000 power rail comes in lengths to support one IAM, and
up to seven additional axes (AM) or shunt module (SM). The
connector pins for each slot are covered by a protective boot. The
boot is designed to protect the pins from damage and ensure that no
foreign objects lodge between the pins during installation.
ATTENTION
To avoid damage to Power Rail during
installation, do not remove the protective boots
until the module for each slot is ready for
mounting.
1. Layout the position for your power rail in the enclosure (refer to
Establish Noise Zones for panel layout recommendations).
Mounting hole dimensions for the power rail are shown in
Appendix A.
4.
If your 2094 power Then
rail is mounted
Attach the braided grounding strap from
Directly to the panel right side grounding stud to the bonded
cabinet ground, as shown in Figure 1.25.
Go to Install 2094 Mounting Brackets and
To 2094 mounting verify proper installation of grounding
brackets
strap, as shown in Figure 1.24.
Figure 1.25
Attaching Braided Ground Strap (2094-PRSx and -PRx)
1
For more information on bonding subpanels, refer to the System Design for Control of Electrical Noise Reference
Manual (publication GMC-RM001).
This procedure assumes you have mounted your power rail to the
panel. Each power rail accommodates one Integrated Axis Module
(IAM) and up to seven additional modules (either axis or shunt). You
must mount a slot filler in any slot not occupied by another module.
Note: Although this procedure is written for the IAM, figures 1.26
through 1.29 apply to any module mounting on the power rail.
1. Prepare to mount your IAM in the left most slot by removing the
protective boots from the power rail connectors (refer to Figure
1.26 for the IAM position on the power rail).
3. Hang the mounting bracket from the slot on the power rail (as
shown in Figure 1.26).
Figure 1.26
Mounting Kinetix 6000 Components on the Power Rail
Mounting Bracket
4. Pivot module downward and align the guide pins on the power
rail with the guide pin holes in the back of the IAM. Refer to
Figure 1.27 for alignment of pins and holes.
Note: The IAM can have two or three power rail connectors and
guide pins, the AM can have one or two, all others have
only one.
Figure 1.27
Guide Pin Alignment
Guide Pin
Hole(s)
Guide Pin(s)
Power Rail
(side view)
in upright Integrated Axis Module
vertical position (side view)
Integrated Axis Module
(rear view)
5. Gently push the module against the power rail connectors. Refer
to the figure below for final mounting position.
Figure 1.28
Kinetix 6000 Component Mounted on the Power Rail
Power Rail
6. Use 2.26 N-m (20 lb-in.) torque to tighten the mounting screw(s)
located as shown in the figure below.
Figure 1.29
Tightening the Mounting Screws
Mounting Screws
Figure 1.30
Axis Module Mounting Order
Highest Power Utilization or Amp Rating Lowest Power Utilization or Amp Rating
Integrated Axis Module Axis Module Axis Module Axis Module Axis Module Axis Module Shunt Module Slot Filler Module
2094-AC09-M02 2094-AM02 2094-AM02 2094-AM02 2094-AM01 2094-AM01 2094-BSP2 2094-PRF
This procedure assumes you have mounted your power rail and
integrated axis module.
1. Determine the next available slot (to the right of the IAM) for
positioning your axis module.
ATTENTION
To avoid damage to the pins located on the back
of each module (IAM, AM, SM, and PRF) and to
ensure that module pins mate properly with the
power rail, hang modules as shown in steps 4-7.
5. Pivot module downward and align the guide pins on the power
rail with the guide pin holes in the back of the AM. Refer to Figure
1.27 for alignment of pins and holes.
6. Gently push the module against the power rail connectors. Refer
to Figure 1.28 for an example of Kinetix 6000 components
mounted on the power rail.
7. Use 2.26 N-m (20 lb-in.) torque to tighten the mounting screw(s).
Refer to Figure 1.29 for the location of the mounting screw(s) on
Kinetix 6000 components.
8.
If you Do this
Have another 2094-AMxx or -BMxx Go to step 1 (above) and complete
axis module to mount installation on your next axis module.
Do not have another 2094-AMxx or
Go to Mount Your Shunt Module.
-BMxx axis module to mount
1. Determine the next available slot (to the right of the last axis
module) for positioning your shunt module.
ATTENTION
To avoid damage to the pins located on the back
of each module (IAM, AM, SM, and PRF) and to
ensure that module pins mate properly with the
power rail, hang modules as shown in steps 4-7.
5. Pivot module downward and align the guide pins on the power
rail with the guide pin holes in the back of the shunt module.
Refer to Figure 1.27 for alignment of pins and holes.
6. Gently push the module against the power rail connectors. Refer
to Figure 1.28 for an example of Kinetix 6000 components
mounted on the power rail.
7. Use 2.26 N-m (20 lb-in.) torque to tighten the mounting screw(s).
Refer to Figure 1.29 for the location of the mounting screw(s) on
Kinetix 6000 components.
ATTENTION
To avoid damage to the pins located on the back
of each module (IAM, AM, SM, and PRF) and to
ensure that module pins mate properly with the
power rail, hang modules as shown in steps 4-7.
4. Hang the slot filler mounting bracket into the corresponding slot
on the power rail. Refer to Figure 1.26 for an example.
5. Pivot module downward and align the guide pins on the power
rail with the guide pin holes in the back of the slot filler module.
Refer to Figure 1.27 for alignment of pins and holes.
6. Gently push the module against the power rail connectors. Refer
to Figure 1.28 for an example of Kinetix 6000 components
mounted on the power rail.
7. Use 2.26 N-m (20 lb-in.) torque to tighten the mounting screw(s).
Refer to Figure 1.29 for the location of the mounting screw(s) on
Kinetix 6000 components.
8.
If you Then
Have additional
Go to step 1 (above) and complete
empty slot(s) in
installation on your next slot filler.
your power rail
Do not have empty
slot(s) in your You have completed mounting your power
rail components.
power rail
Bulletin 2094 mounting brackets can be used to mount the LIM over
the AC line filter. Refer to Figure 1.31 for an illustration of the 2094
mounting bracket orientation when used with the LIM.
If Then
1. Layout the position for your AC line filter
(refer to Establish Noise Zones for panel
You are using the 2094 Mounting Brackets and layout recommendations).
plan to mount the LIM over the AC line filter
2. Mount your AC line filter on the panel.
3. Go to main step 1 below.
You are not using the 2094 Mounting Brackets Go to Mount Your Line Interface Module.
Figure 1.31
Mounting Orientation
Mounting Brackets
(2094-XNBRKT-1)
PR/PRS
PRS
PR
LIM LIM
AC Line Filter
(2090-XXLF-3100 shown)
PR/PRS
PRS
PR
LIM LIM
Mounting Brackets
(2094-XNBRKT-1)
1. Layout the position for your shunt resistor in the enclosure (refer
to Establish Noise Zones for panel layout recommendations).
Chapter Objectives This chapter provides power, feedback, and I/O connector locations
and signal descriptions for your Kinetix 6000. This chapter includes:
Switch and LED locations are shown, however for switch and LED
configuration, refer to the Kinetix 6000 Multi-Axis Servo Drive
Integration Manual (publication 2094-IN002).
Locate IAM Connectors and Use the figure below to locate the Integrated Axis Module connectors
and indicators. Although the physical size of the 2094-BCxx-Mxx
Indicators (460V) IAM is larger than the 2094-ACxx-Mxx (230V) IAM, the location
of the connectors and indicators is identical.
Figure 2.1
Kinetix 6000 Integrated Axis Modules (2094-ACxx-Mxx and -BCxx-Mxx)
1 2 3 4
DC- Motor Power
1 2 3 4 5 6
W
DC+ (MP) Connector
V
DC Bus / AC Input Power
U
(IPD) Connector L3
1 2 3 4 5 6 7 8 9
MBRK -
L2
1 2 3 4 5 6
MBRK +
L1 COM
Motor/Resistive Brake
PWR (BC) Connector
Contactor Enable CONT EN- DBRK -
1 2
Safe-Off RX TX BAUD
(SO) Connector DPI RATE
Seven Segment
Fault Status LED
Mounting Screw
Note: Switch and LED locations are shown, however for switch and
LED configuration, refer to the Kinetix 6000 Multi-Axis Servo
Drive Integration Manual (publication 2094-IN002).
Locate AM Connectors and Use the figure below to locate the Axis Module connectors and
indicators. Although the physical size of the 2094-BMxx (460V) AM is
Indicators larger than the 2094-AMxx (230V) AM, the location of the connectors
and indicators is identical.
Figure 2.2
Kinetix 6000 Axis Modules (2094-AMxx and -BMxx)
1 2 3 4
W Motor Power
V (MP) Connector
U
1 2 3 4 5 6 7 8 9
MBRK -
1 2 3 4 5 6
MBRK +
Safe-Off COM Motor/Resistive Brake
(SO) Connector PWR (BC) Connector
DBRK -
(present only on the 2094-BMxx-S) DBRK +
RX TX
BAUD
RATE
Seven Segment
Fault Status LED
Mounting Screw
IAM and AM Connector The IAM and AM connectors are described in the table below. IAM/
AM connector pin-outs and signal descriptions follow.
Pin-outs
Integrated Axis Module/Axis Module Connectors
Figure 2.3
Motion Allowed Jumper (2090-XNSS-MA)
The following table and figure below provides the signal descriptions
and pin-out for the IAM and AM I/O (26-pin) IOD connector. Refer to
Digital Inputs on page 2-11 and Analog Outputs on page 2-13 for I/O
signal specifications.
Figure 2.4
Pin Orientation for 26-pin I/O (IOD) Connector
26-pin IAM/AM
I/O Connector
Pin 18
Pin 9
Pin 26
Pin 19 Pin 1
Pin 10
The following table provides the signal descriptions and pin-out for
the IAM and AM motor feedback (15-pin) MF connectors. Motor and
auxiliary feedback specifications begin on page 2-17.
Figure 2.5
Pin Orientation for 15-pin Motor Feedback (MF) Connector
15-pin IAM/AM
Motor Feedback Connector
Pin 10
Pin 15 Pin 5
Pin 11 Pin 1
Pin 6
The following tables provide the signal descriptions and pin-outs for
the IAM and AM auxiliary feedback (15-pin) AF connectors when used
with different feedback devices. Motor and auxiliary feedback
specifications begin on page 2-17.
Note: For TTL devices, the position count will increase when A leads
B. For sinusoidal devices, the position count will increase when
cosine leads sine.
Figure 2.6
Pin Orientation for 15-pin Auxiliary Feedback (AF) Connector
15-pin IAM/AM
Auxiliary Feedback Connector
Pin 6
Pin 11 Pin 1
Pin 15 Pin 5
Pin 10
The following tables provide the signal descriptions and pin-outs for
the Integrated Axis Module input connectors.
The following table provides the signal descriptions and pin-outs for
the Control power (2-pin) CPD connector. Refer to Control Power
Input on page 2-16 for signal specifications.
The following table provides the signal descriptions and pin-outs for
the DC bus and input power (6-pin) IPD connector.
3 Chassis ground
4 L3
5 3-phase input power L2
6 L1
The following table provides the signal descriptions and pin-outs for
the contactor enable (2-pin) CED connector. Refer to Contactor
Enable Relay on page 2-14 for signal specifications.
The following tables provide the signal descriptions and pin-outs for
the Integrated Axis Module and Axis Module motor power and brake
connectors. Refer to Motor/Resistive Brake Relay on page 2-15 for
signal specifications.
The following table provides the signal descriptions and pin-outs for
the IAM and AM motor power (4-pin) MP connector.
The following table provides the signal descriptions and pin-outs for
the IAM and AM motor and resistive brake (6-pin) BC connector.
Digital Inputs
Two fast registration inputs and four other inputs are available for the
machine interface on the Integrated Axis Modules (IAM) and Axis
Modules (AM). Each IAM and AM supplies 24V dc @ 500 mA for the
purpose of registration, home, enable, over-travel positive, and
over-travel negative inputs. These are sinking inputs that require a
sourcing device. A 24V power and common connection is provided
for each input.
OFF State Voltage Voltage applied to the input, with respect to -1.0V 3.0V
IOCOM, to guarantee an OFF state.
Figure 2.7
Enable, Home, and Overtravel Digital Input Circuits
24V dc 1
I/O SUPPLY IOD-1, -4, -7, -10
Figure 2.8
Registration Digital Input Circuits
+24V dc
IOD-13, -16
I/O SUPPLY
VCC
IOD-14, -17
INPUT
3k Ω 1k Ω
SERCOS Connections
Specification Description
Data Rates 2, 4, and 8 MBd
Node Addresses 01-99 1
1 Node address selection is done on the Integrated Axis Module (IAM). Node addresses for additional axes on the
same power rail are assigned by incrementing from left to right (starting with the IAM address).
Analog Outputs
The Kinetix 6000 includes two analog outputs (IOD-23 and -25) that
can be configured through software to represent drive variables.
Figure 2.9 shows the configuration of the analog outputs. The table
below provides a description of the analog outputs.
Figure 2.9
Analog Output Configuration
Oscilloscope
2.5V = 0 ref
DAC
ATTENTION
Wiring the Contactor Enable relay is required. To
avoid injury or damage to the drive, wire the
Contactor Enable relay into your safety control string
so that:
• Three-phase power is removed from the drive in
the event of shutdown fault conditions.
• Drive operation is prevented when the Power Rail
is not fully populated.
• Control power is applied to the drive prior to
three-phase power.
Refer to Power Interconnect Diagrams on page B-3
for wiring examples.
Figure 2.10
Contactor Enable Relay
CONT EN+
Normally
Open
Relay
CONT EN-
IAM
An active signal releases the motor brake (BC-5 and -6). The brake
signal is the same as the contactor enable signal, with the addition of
the turn-on and turn-off delays specified by the brake active delay and
brake inactive delay (software configurable in RSLogix 5000). Refer to
AM/Motor Interconnect Diagrams beginning on page B-17 and
Controlling a Brake Example (page B-25) for wiring examples.
The resistive brake relay (BC-1 and -2) controls the Resistive Brake
Module (RBM) contactor. The RBM is wired between the drive and
motor, using an internal contactor to switch the motor between the
drive and a resistive load. The RBM contact delay is the time it takes
to fully close the contactor across the motor power input lines, and
must be configured in RSLogix 5000. Refer to Resistive Brake Module
Interconnect Diagrams on page B-16 for wiring examples.
Figure 2.11
Motor Brake Relay
1 1
1
Noise suppression device.
1
For motors requiring more than the maximum current specified, a relay must be added.
Specification Description
1 This number does not include the axis module (inverter section) that resides inside the integrated axis module.
Understand Feedback The Kinetix 6000 can accept motor and auxiliary feedback signals
from the following types of encoders:
Specifications
• Stegmann Hiperface
• TTL or Sine/Cosine with index pulse and Hall commutation
• Resolver Transmitter TR = 0.25 (motor feedback only)
Note: Auto-configuration in RSLogix 5000 software of intelligent
absolute, high-resolution, and incremental encoders is possible
only with Allen-Bradley motors.
AM, BM, and IM Input encoder signals are filtered using analog and
digital filtering. The inputs also include illegal state change detection.
Refer to Figure 2.12 for a schematic of the AM, BM, and IM inputs.
Figure 2.12
Schematic of the Motor Encoder Inputs
+5 V
1k Ω
10k Ω
+
56 pF 1k Ω
+
1k Ω
1k Ω 56 pF
-
56 pF 100 pF
1k Ω
1k Ω 1k Ω 10k Ω
-
56 pF
56 pF
1k Ω 1k Ω 10k Ω
56 pF
10k Ω
100 pF
Drive Drive
Specification Description
Incremental, A quad B, Sine/Cosine, Intelligent, Resolver, and
Encoder Types Absolute
5.0 MHz (TTL input) per channel
Maximum Input Frequency
250 kHz (Sine/Cosine input)
Commutation Feedback Hall sensor
The IAM and AM power circuit board generates the +5V and +9V dc
for the motor and auxiliary feedback power supplies. Short circuit
protection and separate common mode filtering for each channel is
included. Refer to the table below for specifications.
Voltage Current mA
Supply Reference
Minimum Nominal Maximum Minimum Maximum
+5V dc EPWR_5V 5.13 5.4 5.67 10 400 1, 3
+9V dc EPWR_9V 8.3 9.1 9.9 10 275 2, 3
1
400 mA on the 5 volt supply split in any manner between the channels with no load on the 5 volt supply.
2 275 mA on the 9 volt supply split in any manner between the channels with no load on the 9 volt supply.
3
300 mA on the 5 volt supply on one channel with 150 mA on the 9 volt supply on the second channel.
Locate SM Connectors and Use the figure below to locate the Shunt Module connectors and
indicators. Refer to Understand External Shunt Connections on page
Indicators 3-48 when wiring the RC and TC connectors.
Figure 2.13
Kinetix 6000 Shunt Modules (2094-BSP2)
COL
1 2 3
INT
External Shunt Resistor
DC+ (RC) Connector
TS2 External Thermal Switch
1 2
Mounting Screw
The following table provides the signal descriptions and pin-outs for
the Shunt Module (3-pin) RC connector.
The following table provides the signal descriptions and pin-outs for
the Shunt Module (2-pin) TS connector.
Locate LIM Connectors and Use figures 2.14 and 2.15 to locate the Line Interface Module
connectors and indicators.
Indicators
Figure 2.14
Kinetix 6000 Line Interface Modules (2094-AL09 and -BL02)
1 2
L2/N (CPL) Connector
1
PE PE
1 2 3 4
1 2 3 4
VAC Line
50/60 Hz
50/60 Hz
L3 MBRK PWR L3
VAC Load
4321
Figure 2.15
Kinetix 6000 Line Interface Modules (2094-AL75S, -BL75S, and -XL75S-Cx)
1 2
L1
(APL) Connector 1 L2N
CONTROL VAC
CTRL2
Control Power Output (CPL) Connector
1 2
CTRL1
1
VAC Line
1 2 3 4
AUX2
(IPL) Connector L2
AUX2
230V ac Auxiliary Power Output (P2L) Connector
3
AUX1
AUX1
L1
12 3 4 5 6
I/O_COM
195-265 VAC LOAD, 50/60 Hz
24 VDC SUPPLY
1 I/O_PWR
I/O_COM
I/O_PWR 24V dc Brake Power Output (P1L) Connector
VAC Load
2
L3' I/O_COM
L1'
4
I/O Power
Status LED
Main VAC
OFF
CB1
ON
MAIN VAC
CB3 CB2
1
Auxiliary Power Input (APL) connector is only present on the 2094-XL75S-Cx model.
LIM Connector Pin-outs The LIM (2094-xLxxSx and xLxx) connectors are described in the table
below. LIM connector pin-outs and signal descriptions follow.
I/O Connector
The following table provides the signal descriptions and pin-outs for
the I/O (21-pin) IOL connector (2094-AL75S, -BL75S, and -XL75S-Cx).
Figure 2.16
Pin Orientation for 21-pin I/O (IOL) Connector
IOL
IOL
1 IO_PWR1
2 IO_COM1
3 IO_PWR1
1 IO_PWR1
4
6
IO_COM1
5 IO_PWR1
IO_COM1
2 IO_COM1
7 COIL_E1
8 COIL_E2
9 ALRM_M
3 IO_PWR1
10
12
SHIELD
11 ALRM_B
ALRM_COM
4 IO_COM1
13 CONSTAT_11
14 CONSTAT_12
15 CONSTAT_21
5 IO_PWR1
16
18
CONSTAT_22
17 CONSTAT_31
CONSTAT_32
6 IO_COM1
19 CONSTAT_53
20 CONSTAT_54
21 SHIELD
7 COIL_E1
8 COIL_E2
9 ALRM_M
10 SHIELD 21-pin I/O
11 ALRM_B (IOL) Connector
12 ALRM_COM
13 CONSTAT_11
14 CONSTAT_12
15 CONSTAT_21
16 CONSTAT_22
17 CONSTAT_31
18 CONSTAT_32
19 CONSTAT_53
20 CONSTAT_54
21 SHIELD
Line Interface Module
(2094-AL75S is shown)
The following table provides the signal descriptions and pin-outs for
the I/O (26-pin) IOL connector (2094-AL09 and -BL02).
Figure 2.17
Pin Orientation for 26-pin I/O (IOL) Connector
26-pin LIM
I/O Connector
Pin 18
Pin 9
Pin 26
Pin 19 Pin 1
Pin 10
The following table provides the signal descriptions and pin-outs for
the Auxiliary Power Input (2-pin) APL connector (2094-XL75S-Cx).
The following table provides the signal descriptions and pin-outs for
the Control Power (2-pin) CPL connector (2094-AL75S, -BL75S, and
-XL75S-Cx).
The following table provides the signal descriptions and pin-outs for
the Control Power LOAD (2-pin) CPL connector (2094-AL09 and
-BL02).
The +24V supply is intended for use with mechanical motor brake or
Bulletin 2090 resistive brake module (RBM) applications.
The following table provides the signal descriptions and pin-outs for
the 24V dc brake supply (6-pin) P1L connector (2094-AL75S, -BL75S,
and -XL75S-Cx).
The following table provides the signal descriptions and pin-outs for
the 24V dc brake supply (4-pin) PSL connector (2094-AL09 and
-BL02).
The following table provides the signal descriptions and pin-outs for
the 3-phase input power (4-pin) IPL connector (2094-AL75S, -BL75S,
and -XL75S-Cx).
The following table provides the signal descriptions and pin-outs for
the 3-phase input power (4-pin) IPL connector (2094-AL09 and
-BL02).
IPL Pin
Description Signal
2094-AL09 2094-BL02
1 4 Chassis ground PE
2 3 L3
3 2 3-phase input power L2
4 1 L1
The following table provides the signal descriptions and pin-outs for
the 3-phase output power (4-pin) OPL connector (2094-AL75S,
-BL75S, and -XL75S-Cx).
The following table provides the signal descriptions and pin-outs for
the 3-phase output power (4-pin) OPL connector (2094-AL09 and
-BL02).
OPL Pin
Description Signal
2094-AL09 2094-BL02
4 1 Chassis ground PE’
3 2 L3’
2 3 3-phase output power L2’
1 4 L1’
The following table provides the signal descriptions and pin-outs for
the 230V auxiliary power (4-pin) P2L connector. This connector is
only present with catalog numbers 2094-AL75S, -BL75S, and
-XL75S-Cx.
1 AUX1_L1
110V ac power supply. For use as needed.
2 AUX1_L2
2094-XL75S-C1
3 AUX2_L1
110V ac power supply. For use as needed.
4 AUX2_L2
Understand LIM A description of the Kinetix 6000 LIM I/O (IOL), brake power (P1L/
PSL), control power (CPL), and 230V power (P2L) signals and circuit
Signal Specifications specifications is provided on the following pages.
Note: Block diagrams for the Line Interface Modules (230V and 460V)
begin on page B-34.
LIM I/O
The LIM I/O (IOL) signals (2094-AL09 and -BL02) include the
contactor coil, status contacts, and I/O power supply. The following
table provides a description of the IOL connector signals. Refer to Line
Interface Module Power Specifications on page A-6 for auxiliary
contactor specifications.
For safety reasons, the internal wiring (figures 2.18 and 2.19) is
arranged so that if the control power (CPL) circuit breaker (CB2) trips,
the opening contact will interrupt the coil voltage and remove main
input power to the IAM (IPD) connector (refer to Figure 2.18).
Figure 2.18
IOL Contactor Coil (2094-AL75S, -BL75S, and -XL75S-Cx)
CB2_AUX CR1
A1 A2
1 2 DC Interface Module
IOL-7
E1 COIL_E1
A1 E2
IOL-8
COIL_E2
1 2 1 2
FB1
3 4 3 4
CB2
Figure 2.19
IOL Contactor Coil (2094-AL09 and -BL02)
CB2_AUX
CR1
IOL-13 1 2 A1 A2 IOL-4
COIL_A1 COIL_A2
1 2
CB2 D1
3 4
Line Interface Module
The LIM safety contactor (figures 2.20 and 2.21) includes three main
contacts (normally open) that close when coil power is applied.
Figure 2.20
IOL Contactor Status (2094-AL75S, -BL75S, and -XL75S-Cx)
CR1
1 2
3 4
5 6
IOL-13 IOL-14
CONSTAT_11 CONSTAT_12
IOL-15 IOL-16
CONSTAT_21 CONSTAT_22
IOL-17 IOL-18
CONSTAT_31 CONSTAT_32
IOL-19 IOL-20
CONSTAT_53 CONSTAT_54
A1 A2
Figure 2.21
IOL Contactor Status (2094-AL09 and -BL02)
CR1
1 2
3 4
5 6
IOL-15 IOL-6
CONSTAT_11 CONSTAT_12
IOL-16 IOL-7
CONSTAT_21 CONSTAT_22
IOL-17 IOL-8
CONSTAT_31 CONSTAT_32
IOL-18 IOL-9
CONSTAT_41 CONSTAT_42
A1 A2
PLC I/O power is available to the user via the IOL (21-pin) terminal
block connector (as shown in Figure 2.22).
Motor brakes and the RBM I/O power is available to the user via the
P1L (6-pin) connector. Each P1L output contains an LC circuit to
prevent electrical noise contamination of the 24V supply and an MOV
to prevent current surges from the motor brake (as shown in Figure
2.22).
IMPORTANT Use the P1L +24V dc supply with devices that can
potentially generate flyback currents (brake coils,
relays, etc.).
Figure 2.22
IOL Power Supply (2094-AL75S, -BL75S, and -XL75S-Cx)
P1L-1
P1L-3
IO_PWR2
P1L-5
P1L-2
P1L-4
IO_COM2
P1L-6
Interface PCB
Figure 2.23
IOL Power Supply (2094-AL09 and -BL02)
Note: The PSL brake power supply is rated at 2A. If more current is
required, consider using the IOL power supply.
IMPORTANT Use the PSL +24V dc supply with devices that can
potentially generate flyback currents (brake coils,
relays, etc.). This supply requires external flyback
protection with either a diode or MOV.
Figure 2.24
PSL Power Supply (2094-AL09 and -BL02)
3 2 PSL-2
MBRK COM
PSL-4
Figure 2.25
CPL Power Supply (2094-AL75S, -BL75S, and -XL75S-Cx)
1 2 1 2 CPL-2
CTRL 2
Single-Phase
FB1 CB2
4 3 4 AC Line Filter CPL-1
3 CTRL 1
Figure 2.26
CPL Power Supply (2094-AL09 and -BL02)
CB2_AUX
1 2 CPL-2
L1
Single-Phase
CB2
AC Line Filter 4 CPL-1
3
L2/N
An auxiliary 230V ac output is provided for use with the Bulletin 2090
Resistive Brake Module (RBM) or other customer requirement as
needed on the P2L connector. This supply is present with catalog
numbers 2094-AL75S, -BL75S, and -XL75S-C2. The supply is protected
by circuit breaker CB2.
3 4 3 4 P2L-2
AUX1_L2
P2L-3
AUX2_L1
P2L-4
AUX2_L2
Refer to Figure B.29 (on page B-32) for the 2094-XL75S-Cx block
diagram.
Chapter Objectives This chapter provides procedures for wiring your Kinetix 6000 and
making cable connections. This chapter includes:
Understand Basic Wiring This section contains basic wiring information for the Kinetix 6000.
Requirements
ATTENTION Plan the installation of your system so that you can
perform all cutting, drilling, tapping, and welding
with the system removed from the enclosure.
Because the system is of the open type construction,
be careful to keep any metal debris from falling into
it. Metal debris or other foreign matter can become
lodged in the circuitry, which can result in damage
to components.
When building your own cables, follow the guidelines listed below.
Be aware that when you route power and signal wiring on a machine
or system, radiated noise from nearby relays, transformers, and other
electronic drives, can be induced into motor or encoder feedback,
communications, or other sensitive low voltage signals. This can cause
system faults and communication problems.
Determine Your Type of Before wiring input power to your Kinetix 6000 system you must
determine the type of input power you are connecting to. The IAM is
Input Power designed to operate in both grounded and ungrounded environments.
ATTENTION When using a LIM with your Kinetix 6000, the VAC
LINE input power must come from a grounded
configuration (refer to Figure 3.1).
When not using a LIM with your Kinetix 6000,
ungrounded configurations are allowed, but you
must set the jumper to prevent high electrostatic
build-up (refer to Set the Ground Jumper in
Ungrounded Power Configurations on page 3-7).
Figure 3.1
Grounded Power Configuration (WYE Secondary)
CTRL 2
1 2
1 2 3 4
DC-
1 2 3 4 5 6
L3 W
DC+
V
Transformer U
L3
L2
1 2 3 4 5 6 7 8 9
MBRK -
L2
1 2 3 4 5 6
MBRK +
L1 COM
3-Phase L1 CONT EN-
PWR
DBRK -
1 2
RX TX BAUD
DPI RATE
Phase Ground
Bonded cabinet
ground
Figure 3.2
Grounded (B-Phase) Power Configuration (Delta Secondary)
CTRL 2
1 2
CTRL 1
1 2 3 4
Transformer (Delta) Secondary DC-
1 2 3 4 5 6
W
DC+
V
Transformer L3 U
L3
1 2 3 4 5 6 7 8 9
MBRK -
L2
1 2 3 4 5 6
MBRK +
L1 COM
PWR
CONT EN- DBRK -
1 2
CONT EN+ DBRK +
L2
RX TX BAUD
DPI RATE
L1
Ground grid or
power distribution ground
Figure 3.3
Ungrounded Power Configuration
CTRL 2
1 2
CTRL 1
1 2 3 4
DC-
1 2 3 4 5 6
L3 DC+
W
Transformer V
U
L2 L3 1 2 3 4 5 6 7 8 9
MBRK -
L2
1 2 3 4 5 6
3-Phase MBRK +
L1
Input VAC COM
L1 CONT EN-
PWR
DBRK -
1 2
RX TX BAUD
DPI RATE
Chassis Ground
Bonded cabinet
ground
ATTENTION
Ungrounded systems do not reference each
phase potential to a power distribution ground.
This can result in an unknown potential to
earth ground.
DC Common Bus When an IAM is used in a DC common bus configuration, the IAM is
known as a Leader IAM or Follower IAM. The IAM (non-common bus)
Configurations and Leader IAM have identical three-phase input power connections.
The Leader IAM is responsible for discharging the DC bus, and for
providing common bus follower drives with DC bus pre-charge, bus
regulation, phase-loss detection, and ground fault detection. Follower
IAMs do not have three-phase input power connections, but have DC
bus connections from a Leader IAM (refer to Figure 3.4).
The Kinetix 6000 Leader IAM can operate with non-Kinetix 6000
follower drives, as can the Kinetix 6000 Follower IAM operate with
(non-Kinetix 6000) common bus leader drives. However, non-Kinetix
6000 leader and follower drives must meet the same functional
requirements as the Kinetix 6000 Leader and Follower IAMs.
Figure 3.4
Typical DC Common Bus Configuration
Integrated Axis Module Axis Modules Integrated Axis Module Axis Modules
(2094-BCxx-Mxx) (2094-BMxx) (2094-BCxx-Mxx) (2094-BMxx)
Common Bus Leader IAM Common Bus Follower IAM
CTRL 2
1 2
CTRL 1
1 2 3 4
1 2 3 4
CTRL 1
1 2 3 4
1 2 3 4
ground W W W W
1 2 3 4
1 2 3 4
DC- V V DC- V V
1 2 3 4 5 6
1 2 3 4 5 6
W W
DC+ U U DC+ U U
V V
U MBRK - MBRK -
U MBRK - MBRK -
L3
1 2 3 4 5 6
1 2 3 4 5 6
L3
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
MBRK + MBRK +
1 2 3 4 5 6 7 8 9
MBRK + MBRK +
MBRK -
L2
1 2 3 4 5 6
MBRK -
L2
1 2 3 4 5 6
CONT EN-
Input Power
DBRK -
1 2
RX TX RX TX RX TX RX TX
BAUD BAUD RX TX BAUD
BAUD BAUD
RX TX BAUD
RATE RATE DPI RATE RATE RATE
DPI RATE
When using a Kinetix 6000 Leader IAM, DC bus fuses are only
required when wiring to more than one Kinetix 6000 Follower IAM.
When wiring multiple Follower IAMs, terminal blocks are required to
extend the DC common bus power to additional drives. Fuses should
be installed in both lines of the DC bus between the DC bus terminal
block and each Follower IAM. These fuses should be rated based on
the DC input current of each Follower IAM.
When using a non-Kinetix 6000 common bus leader, DC bus fuses are
required in both lines of the DC bus, between the common bus leader
and Follower IAM. These fuses should be rated based on the leader’s
DC output current. When using more than one Follower IAM, fuses
should be installed in both lines of the DC bus between the
non-Kinetix 6000 common bus leader and the terminal block as well
as between the DC bus terminal block and each Follower IAM.
Set the Ground Jumper in Setting the ground jumper is only necessary when using an
ungrounded power configuration (as shown in Figure 3.3). Setting the
Ungrounded Power jumper involves removing the IAM from the power rail, opening the
Configurations IAM, and moving the jumper.
Setting the ground jumper is best done with the IAM removed from
the power rail and placed face-up on a solid surface equipped as a
grounded static safe workstation.
1. Verify that all control and input power has been removed from the
system.
3. Grasp top and bottom of IAM with both hands and gently pull the
IAM away from the connectors enough to clear the guide pins
(IAM will pivot on top bracket). Lift the bracket out of the power
rail slot and remove IAM from the power rail. Refer to figures 1.28,
1.29, and 1.30 for illustrations.
4. Place the IAM (with front panel facing up) on a grounded static
safe workstation.
1. Remove the top and bottom front panel screws. Use the table
below to locate the front panel screws and ground jumper.
Figure 3.5
Setting the 230V Ground Jumper
Top Screw
P17
Figure 3.6
Setting the 460V Ground Jumper
Top Screw
2. Swing the front panel open to the right, as shown, and locate the
ground jumper.
3.
And move the
For this IAM Refer to ground jumper
from
2094-ACxx-Mxx Figure 3.5 P16 to P17
(230V)
2094-BCxx-Mxx
Figure 3.6 P14 to P12
(460V)
4. Replace the IAM front panel and two screws. Apply 1.6 N-m (14
lb-in.) torque.
5. Mount the IAM back on the power rail. Refer to Mount Your
Integrated Axis Module in Chapter 1 for instructions.
Ground Your Kinetix 6000 We recommend that all equipment and components of a machine or
process system have a common earth ground point connected to their
chassis. A grounded system provides a ground path for short circuit
protection. Grounding your modules and panels minimize shock
hazard to personnel and damage to equipment caused by short
circuits, transient overvoltages, and accidental connection of
energized conductors to the equipment chassis. For CE grounding
requirements, refer to Chapter 1.
In the figure below, the power rail is shown properly grounded to the
bonded cabinet ground on the subpanel.
Figure 3.7
Chassis Ground Configuration
Kinetix 6000
Power Rail
Braided
Ground Strap Ground grid or power
distribution ground
Motors with power cables that include only the 3-phase motor power
wires are listed in the table below.
For this Motor Catalog Number Use this Motor Power Cable
MP-Series Low Inertia MPL-A/BxxxxS/M
MP-Series Integrated Gear MPG-A/BxxxxS/M 2090-XXNPMP-xxSxx
1326AB (M2L/S2L) 1326AB-Bxxxx-M2L/S2L
TL-Series TL-Axxxx-H 2090-XXNPT-16Sxx
H- or F-Series H-xxxx or F-xxxx 2090-XXNPH/HF-xxSxx
N-Series N-xxxx 2090-XXNPN-16Sxx
Figure 3.9
Motor Power Terminations (3-phase wires only)
Motor Cable
Shield Clamp Cable Clamp
(with tie wrap)
DC-
3
W
DC+
2
V
1
U
L3
MBRK -
L2
MBRK +
L1 COM
PWR
CONT EN- DBRK -
CONT EN+ DBRK +
RX TX BAUD
DPI RATE
Motors with power cables that include the 3-phase motor power and
brake wires are listed in the table below.
For this Motor Catalog Number Use this Motor Power Cable
MP-Series Food Grade MPF-A/BxxxxS/M
2090-XXNPMF-xxSxx
MP-Series Stainless Steel MPS-A/BxxxxS/M
Y-Series Y-xxxx 2090-XXNPY-16Sxx
The MP-Series brake wires have a shield braid (shown below as gray)
that folds back under the cable clamp before the conductors are
attached to the motor brake (BC) connector. Y-Series brake wires are
not shielded and do not require routing under the cable clamp.
Note: The thermal switch wires for the MP-Series motors are included
in the feedback cable. Refer to AM/Motor Interconnect
Diagrams beginning on page B-17 for the interconnect diagram.
Figure 3.10
Motor Power Terminations (3-phase and brake wires)
Motor Cable
Y-Series brake wires are not Shield Clamp
shielded and do not require routing (with tie wrap)
under the cable clamp.
CTRL 2
CTRL 1
1 2 3 4
DC-
W Motor Power
DC+ (MP) Connector
V
U
L3
MBRK -
L2
1 2 3 4 5 6
MBRK +
L1 COM
PWR Resistive/Motor Brake
CONT EN-
CONT EN+
DBRK - (BC) Connector
DBRK +
RX TX BAUD
DPI RATE
Motors with power cables that include the 3-phase motor power,
brake wires, and thermal switch wires are listed in the table below.
For this Motor Catalog Number Use this Motor Power Cable
1326AB (resolver) 1326AB-Bxxxx-21 1326-CPx1-xxx
Figure 3.11
Motor Power Terminations (3-phase, brake, and thermal switch wires)
Cable Clamp
Thermal Switch Wires (with tie wrap)
CTRL 1
CTRL 2
1 2 3 4
DC- Motor Power
W
DC+ (MP) Connector
V
U
L3
MBRK -
L2
1 2 3 4 5 6
MBRK +
L1 COM
PWR Resistive/Motor Brake
CONT EN- DBRK - (BC) Connector
CONT EN+ DBRK +
TL- and Y-Series motors have a short pigtail cable which connects to
the motor, but is not shielded. The preferred method for grounding
the TL- and Y-Series motor power cable on the motor side is to
expose a section of the cable shield and clamp it directly to the
machine frame. The motor power cable also has a 150 mm (6.0 in.)
shield termination wire with a ring lug that connects to the closest
earth ground. Use this method in addition to the cable clamp. The
termination wire may be extended to the full length of the motor
pigtail if necessary, but it is best to connect the supplied wire directly
to ground without lengthening. Refer to Figure 3.12 for an illustration.
Figure 3.12
TL- and Y-Series Motor Power Cable Connection
Cable Braid Clamped
to Machine Frame1 Connectors
Motor Power Cable Pigtail Cable
TL-Series or
Y-Series
Motor
150 mm (6.0) Termination
Machine Frame 1 1
1
Remove paint from machine frame to ensure proper HF-bond between machine frame and motor case, shield
clamp, ground stud, etc.
Power Wiring Power wiring requirements are given in the tables below. Wire should
be copper with 75° C (167° F) minimum rating. Phasing of main AC
Requirements power is arbitrary and earth ground connection is required for safe
and proper operation.
Use the table below to determine the recommended wire size and
torque value when wiring the Line Interface Modules (2094-AL75S,
-BL75S, and -XL75S-Cx).
P2L-1 AUX1_L1
P2L-2 AUX1_L2 0.2-4.0 0.5 - 0.6
Auxiliary Power Output 7 (0.28)
P2L-3 AUX2_L1 (24-10) (4.4 - 5.3)
P2L-4 AUX2_L2
P1L-1 IO_PWR2
P1L-2 IO_COM2
Brake and I/O Power P1L-3 IO_PWR2 0.08-1.5
7 (0.28) 0.22-0.25 (2)
Output P1L-4 IO_COM2 (28-16)
P1L-5 IO_PWR2
P1L-6 IO_COM2
Status I/O 0.5-1.5
IOL-1 thru IOL-21 6 (0.25) 1.13 (10)
(21 pin terminal block) (22-14)
1
The Auxiliary Power Input (APL) connector is only present on catalog number 2094-XL75S-Cx.
Use the table below to determine the recommended wire size and
torque value when wiring the Line Interface Modules (2094-AL09 and
-BL02)
IPL-1
IPL-2 L3
VAC LINE
IPL-3 L2
IPL-4 L1
LIM (230V) 0.5 - 0.6
2.5 (14) 10 (0.38)
2094-AL09 (4.4 - 5.3)
OPL-4
OPL-3 L3’
VAC LOAD
OPL-2 L2’
OPL-1 L1’
IPL-4
IPL-3 L3
VAC LINE
IPL-2 L2
IPL-1 L1
LIM (460V) 1.5 - 1.8
4.0 (12) 10 (0.38)
2094-BL02 (13.2 - 15.9)
OPL-1
OPL-2 L3’
VAC LOAD
OPL-3 L2’
OPL-4 L1’
ATTENTION
This drive contains ESD (Electrostatic Discharge)
sensitive parts and assemblies. You are required to
follow static control precautions when you install,
test, service, or repair this assembly. If you do not
follow ESD control procedures, components can be
damaged. If you are not familiar with static control
procedures, refer to Allen-Bradley publication
8000-4.5.2, Guarding Against Electrostatic Damage
or any other applicable ESD Protection Handbook.
Connect Input Power These procedures assume you have mounted your Kinetix 6000 drive
components and are ready to wire the AC input power.
2. Connect the other end of your braided ground strap to the bonded
cabinet ground bus. For more information on bonding, refer to
Chapter 1.
3.
If Your System Then Go To
Includes the Line Interface Connect Input Power (IAM
Module (LIM) with LIM)
Does not include the Line Connect Input Power (IAM
Interface Module (LIM) without LIM)
This procedure assumes you have an IAM or Leader IAM and LIM
mounted on your panel and are ready to wire the AC input power.
2. Route the single-phase power wires (L1 and L2/N) to your LIM.
3.
Into this terminal on the
Insert this wire from the APL connector
single-phase supply 2094-XL75S-Cx (LIM)
APL Pin Signal
L1 1 L1
L2 2 L2/N
5. Gently pull on each wire to make sure it does not come out of its
terminal. Re-insert and tighten any loose wires.
2. Route the 3-phase power wires (L1, L2, L3 and ground) to your
LIM.
3.
Into this terminal on the IPL connector (LIM)
Insert this wire from 2094-AL09, -AL75S,
2094-BL02
the 3-phase supply -BL75S, and -XL75S-Cx
IPL Pin Signal IPL Pin Signal
L1 4 L1 1 L1
L2 3 L2 2 L2
L3 2 L3 3 L3
1 4
4. Tighten the IPL connector screws (IPL-1, -2, -3, and -4).
5. Gently pull on each wire to make sure it does not come out of its
terminal. Re-insert and tighten any loose wires.
1. Prepare one end of the 3-phase power wires for attachment to the
OPL connector by removing insulation equal to the recommended
strip length (refer to figures 2.14 and 2.15 for connector location).
2.
Into this terminal on the OPL connector (LIM)
Insert this wire from 2094-BL02, -AL75S
2094-AL09
the 3-phase supply -BL75S, or -XL75S-Cx
OPL Pin Signal OPL Pin Signal
L1 1 L1’ 4 L1’
L2 2 L2’ 3 L2’
L3 3 L3’ 2 L3’
4 1
3. Tighten the OPL connector plug screws (OPL-1, -2, -3, and -4).
4. Gently pull on each wire to make sure it does not come out of its
terminal. Re-insert and tighten any loose wires.
5.
If you have this LIM Then Do this
The AC line filter is not included
2094-AL75S, -BL75S or Go to Wire the AC Line
-XL75S-Cx with your LIM. You must install Filter.
one external to the LIM.
The AC line filter is wired as an Go to Wire the Input
2094-AL09 or -BL02
internal component of your LIM. Power Connector (IAM).
2. Route the 3-phase power wires (L1, L2, L3, and ground) from the
LIM (OPL connector) to the LINE side of your AC line filter and
attach to terminals L1, L2, L3, and E (respectively).
4. Route the 3-phase power wires (L1, L2, L3 and ground) from the
IAM to the LOAD side of your AC line filter and attach to terminals
L1, L2, L3, and E (respectively).
5. Tighten the LINE and LOAD terminal screws (L1, L2, L3 and E).
6. Gently pull on each wire to make sure it does not come off of its
terminal. Re-insert and tighten any loose wires.
1. Prepare the other end of the 3-phase power wires (from the LIM
or line filter) for attachment to the IPD connector plug by
removing insulation equal to the recommended strip length.
2. Route the 3-phase power wires (L1, L2, L3 and ground) to your
IAM.
3.
Insert this wire from the OPL connector (LIM)
Into this terminal on the
2094-BL02, -AL75S IPD connector (IAM)
2094-AL09
-BL75S, or -XL75S-Cx
OPL Pin Signal OPL Pin Signal IPD Pin Signal
1 L1’ 4 L1’ 6 L1
2 L2’ 3 L2’ 5 L2
3 L3’ 2 L3’ 4 L3
4 1 3
4. Tighten the IPD connector plug screws (IPD-6, -5, -4, and -3).
5. Gently pull on each wire to make sure it does not come out of its
terminal. Re-insert and tighten any loose wires.
6. Insert the IPD connector plug into the IPD connector (refer to
Figure 2.1 for connector location).
2.
Insert this Control
Into the Control Power (CPL) connector (LIM)
Power LOAD wire
CPL Pin CPL Pin
Signal Signal
(2094-AL75S, -BL75S, -XL75S-Cx) (2094-AL09 and -BL02)
L1 1 2 L1
L2 2 1 L2/N
3. Tighten the two CPL connector plug screws (CPL-1 and -2).
4. Gently pull on each wire to make sure it does not come out of its
terminal. Re-insert and tighten any loose wires.
5. Insert the CPL connector plug into the CPL connector (refer to
figures 2.14 and 2.15 for connector location).
1. Prepare the other end of the single-phase power wires (from the
previous procedure) for attachment to the CPD connector plug by
removing insulation equal to the recommended strip length.
2. Route the single-phase power wires (L1 and L2) to your IAM.
3.
Insert this wire from the Control Power (CPL) connector Into this terminal on the
(LIM) CPD connector (IAM)
CPL Pin
CPL CPL Pin/Signal CPL
(2094-AL75S, -BL75S, CPD Pin Signal
Signal (2094-AL09 and -BL02) Signal
-XL75S-Cx)
1 CTRL 1 2 L1 1 CTRL 2
2 CTRL 2 1 L2/N 2 CTRL 1
5. Gently pull on each wire to make sure it does not come out of its
terminal. Re-insert and tighten any loose wires.
6. Insert the CPD connector plug into the CPD connector (refer to
Figure 2.1 for connector location).
This procedure assumes you have an IAM or Leader IAM and separate
power supply/line filter components mounted on your panel and are
ready to wire the AC input power to the IAM.
1. Prepare your 3-phase power wires from the AC line filter for
attachment to the IPD connector plug by removing insulation
equal to the recommended strip length.
2. Route the 3-phase power wires (L1, L2, L3 and ground) to your
IAM.
3.
Into this terminal on the IPD
Insert this wire from your connector (IAM)
3-phase supply
IPD Pin Signal
6 L1
3-phase supply 5 L2
(phasing arbitrary)
4 L3
Bonded ground bus or (Ground)
3
Terminal E on AC line filter 1
1
Refer to Appendix B (page B-6) for an interconnect diagram of the Kinetix 6000 without a
LIM.
4. Tighten the IPD connector plug screws (IPD-6, -5, -4, and -3).
5. Gently pull on each wire to make sure it does not come out of its
terminal. Re-insert and tighten any loose wires.
6. Insert the IPD connector plug into the IPD connector (refer to
Figure 2.1 for connector location).
1. Prepare the single-phase power wires from the AC line filter for
attachment to the CPD connector plug by removing insulation
equal to the recommended strip length.
3.
Into this terminal on the CPD
Insert this wire from the connector (IAM)
single-phase supply
CPD Pin Signal
Single-phase supply 1 CTRL 2
(phasing arbitrary) 2 CTRL 1
5. Gently pull on each wire to make sure it does not come out of its
terminal. Re-insert and tighten any loose wires.
6. Insert the CPD connector plug into the CPD connector (refer to
Figure 2.1 for connector location).
4. Gently pull on each wire to make sure it does not come out of its
terminal. Re-insert and tighten any loose wires.
5. Insert the IPD connector plug into the IPD connector on the
Leader IAM (refer to Figure 2.1 for connector location).
1. Prepare your DC bus and ground wires for attachment to the IPD
connector plug by removing insulation equal to the recommended
strip length.
2. Insert the DC Bus and ground wires as shown in the table below.
Insert the DC bus and ground wires from the Leader IAM
into these terminals on the IPD connector (Follower IAM)
IPD Pin Signal
1 DC-
2 DC+
3
4 N.C.
5 N.C.
6 N.C.
3. Tighten the IPD connector plug screws (IPD-1, -2, and -3).
4. Gently pull on each wire to make sure it does not come out of its
terminal. Re-insert and tighten any loose wires.
5. Insert the IPD connector plug into the IPD connector on the
Follower IAM (refer to Figure 2.1 for connector location).
Safe-Off Connections Each IAM (2094-BCxx-Mxx-S) and AM (2094-BMxx-S) ships with the
(9-pin) wiring plug header (2090-XNSS-WP) and motion allowed
jumper (2090-XNSS-MA) installed in the Safe-Off (SO) connector. With
the motion allowed jumper installed, the safe-off feature is not used.
Pin orientation for the motion allowed jumper is shown on page 2-4.
Wire the Contactor Enable These procedures assume you have wired your single-phase and
three-phase input power and are ready to wire the Contactor Enable
Connector connector.
Figure 3.13
Wire Preparation
Strip Length 10 mm (0.38 in.)
CONT EN-
CONT EN+
2. Insert the CED connector wires into the CED connector plug and
tighten the connector plug screws.
3. Gently pull on each wire to make sure it does not come out of its
terminal. Re-insert and tighten any loose wires.
4. Insert the CED connector plug into the CED connector (refer to
Figure 2.1 for connector location).
Connect Motor Power and These procedures assume you have wired your single-phase and
three-phase input power, the contactor enable connector, and are
Brakes ready to wire the motor power and brake connectors.
1.
If you have this Use this Motor
Do this
motor Power Cable
MPL-A/B or MPG-A/B
2090-XXNPMP-xxSxx
1326AB (M2L/S2L)
MPF-A/B or MPS-A/B 2090-XXNPMF-xxSxx
TL-Axxxx-H 2090-XXNPT-16Sxx
2090-XXNPH-xxSxx or Go to main step 2.
H-Series
2090-XXNPHF-xxSxx
F-Series 2090-XXNPHF-xxSxx
N-Series 2090-XXNPN-16Sxx
Y-Series 2090-XXNPY-16Sxx 1
4. Cut the motor power cable, removing any existing
motor power preparation from the drive end of the
cable.
5. Remove 130 mm (5.1 in.) of outer insulation from the
cable, as shown in Figure 3.14.
1326AB (resolver) 1326-CPx1-xxx 2
6. Remove all but 25.4 mm (1.0 in.) of the cable braid.
7. Trim each of the wires to 105 mm (4.1 in.) as shown
in Figure 3.14.
8. Go to main step 2.
1 The brake wires for Y-Series motors are included in the motor power cable and require no additional preparation.
2
The brake wires for 1326AB (resolver) motors are included in the motor power cable, but require preparation for
use with the Kinetix 6000.
Figure 3.14
Shield Clamp Cable Preparation (1326-CPx1-xxx, 2090-XXNPY-16Sxx, and
2090-XXNPMF-xxSxx)
Strip Length 10 mm (0.375 in.)
Exposed Braid
105 mm (4.1 in.)
25.4 mm (1.0 in.)
130 mm (5.1 in.)
4.
Insert the motor power wires from this servo Into this terminal on the MP
motor connector (IAM/AM)
1326AB (resolver), 1326AB (M2L/S2L), F-, H-
MP Pin Signal
and Y-Series N-, and MP-Series
1 / Black U / Brown 1 U
2 / Black V / Black 2 V
3 / Black W / Blue 3 W
Green/Yellow Green/Yellow 4
5. Tighten the MP connector plug screws (MP-1, -2, -3, and -4).
6. Gently pull on each wire to make sure it does not come out of its
terminal. Re-insert and tighten any loose wires.
8.
If your motor is Then
1. Connect the 152.4 mm (6.0 in.)
termination wire to the closest earth
TL- or Y-Series ground (refer to Figure 3.12 for pigtail
location).
2. Go to Wire the Motor Brake Connector.
Not TL- or Y-Series Go to Wire the Motor Brake Connector.
The procedure for wiring your motor brake varies slightly, depending
on the motor series you are using. Refer to the table below to
determine where the brake wires for your servo motor are located and
for the appropriate brake cable or connector kit catalog number.
For this Motor Series The Brake Wires Cable Catalog Number
MPL-A/B and MPG-A/B
2090-UXNBMP-18Sxx brake cable
1326AB (M2L/S2L)
Are in a separate brake cable
TL-Axxxx-H (the motor has a brake 2090-DANBT-18Sxx
connector)
H/F-Series Straight brake connector kit 9101-0330
N-Series Straight brake connector kit 9101-1698
MPF-A/B and MPS-A/B 2090-XXNPMF-xxSxx power cable
Are included in the power
1326AB (resolver) cable (the motor does not have 1326-CPx1-xxx power cable
a brake connector)
Y-Series 2090-XXNPY-16Sxx power cable
1.
If your system Then your +24V dc brake power Do this
1. Wire +24V dc power from the LIM
Is available from the 24V Brake Power to BC-3 and -4 on your IAM/AM.
Includes a LIM
Connector (P1L/PSL) on the LIM.
2. Go to step 2.
1. Wire +24V dc power from your
Does not include a LIM Is user-supplied. user-supplied +24V.
2. Go to step 2.
2.
If you have this Refer to
Do this
motor this figure
1. Remove 105 mm (4.1 in.) of outer insulation and shield from
the cable as shown in Figure 3.15.
MPL-A/B, MPG-A/B, 2. Prepare your brake conductors by removing insulation equal
1326AB (M2L/S2L), to the recommended strip length.
Figure 3.15
TL-Axxxx-H, or 3. Route the motor brake cable to your AM or IAM (inverter
H-, F-, and N-Series section). For the location of motor/resistive brake connector,
refer to figures 2.1 or 2.2).
4. Go to main step 3.
MPF-A/B and Figures 3.14 1. Prepare your brake conductors by removing insulation equal
MPS-A/B and 3.10 to the recommended strip length.
Figures 3.14 2. Go to main step 3.
1326AB (resolver)
and 3.11
Figures 3.14
Y-Series
and 3.10
Figure 3.15
Brake Cable Preparation
Outer Insulation
Strip Length 10 mm (0.375 in.)
BR+
Brake Cable
BR-
3.
Into this terminal on the
Insert the motor brake wires from this servo motor
BC connector (IAM/AM)
1326AB (M2L/S2L), H-, 1326AB
Y-Series MP Pin Signal
F-, N-, and MP-Series (resolver)
A / BR+ 6 / B1 7 / BR+ 5 MBRK+
C / BR- 4 / B2 9 / BR- 6 MBRK-
5. Gently pull on each wire to make sure it does not come out of its
terminal. Re-insert and tighten any loose wires.
Figure 3.16
Depressing the Spring Clamp
Flat Blade Screwdriver
3.5 mm (0.14 in.) tip
Cable Clamp
Screwdriver
tip in slot
3. Release the spring, making sure the cable and cable braid are held
secure by the clamp.
4. Attach tie wrap around cable and clamp, if additional strain relief
is required (refer to Figure 3.17 for examples).
Figure 3.17
Motor Cable and Clamp
5.
If you Do this
Have more axis 1. Move to the next axis module.
modules to wire 2. Go to Wire the Motor Power Connector.
Have wired all your Go to Understand Feedback and I/O Cable
axis modules Connections.
Understand Feedback and Factory made cables with premolded connectors are designed to
minimize EMI and are recommended over hand-built cables to
I/O Cable Connections improve system performance. However, other options are available
for building your own feedback and I/O cables. Refer to the table
below for the available options.
Connector Kit
This Connection Option Is Available for this Cable Using this Type of Cable
Catalog Number
Refer to the table below for the
Premolded Connectors N/A Motor Feedback premolded motor feedback cable
available for your motor.
Refer to the table below for the flying
2090-K6CK-D15M
Motor Feedback lead cable available for your motor.
Refer to the table below for motor feedback cable catalog numbers
available for specific motor/feedback combinations.
The following table provides the signal descriptions and pin-outs for
the motor feedback (15-pin) connector to MP-Series Low Inertia (MPL)
and Integrated Gear (MPG), 1326AB (M2L/S2L), and N-Series motors.
Incremental Encoder
High Resolution Feedback Signals for
Feedback Signals for
Motor Drive MF
Connector MPL-Bxxx-M/-S MPL-A3xx-M/-S Connector
MPL-A5xx-M/-S and MPL-A4xx-M/-S MPL-Axxx-H
Pin MPL-Bxxx-H and Pin
1326AB-Bxxx-M2L/-S2L MPL-A45xx-M/-S
Motors MPG-A/Bxxx-M/-S Motors N-Series Motors
The following table provides the signal descriptions and pin-outs for
the motor feedback (15-pin) connector to MP-Series (resolver-based)
motors.
The following table provides the signal descriptions and pin-outs for
the motor feedback (15-pin) connector to MP-Series Food Grade
(MPF) and MP-Series Stainless Steel (MPS) motors.
1 Sine+ Sine+ 1
2 Sine- Sine- 2
3 Cos+ Cos+ 3
4 Cos- Cos- 4
5 Data+ Data+ 5
6 Data- Data- 10
9 Reserved EPWR_5V 14
10 Reserved ECOM 6
11 EPWR_9V Reserved 7
12 ECOM Reserved 6
13 TS+ TS+ 11
14 TS- TS- 6
The following table provides the signal descriptions and pin-outs for
the motor feedback (15-pin) premolded connector to TL-Series
motors.
Motor Drive MF
Incremental Encoder Feedback
Connector Connector
Signals for TL-Axxxx-H Motors
Pin Pin
1 AM+ 1
2 AM- 2
3 BM+ 3
4 BM- 4
5 IM+ 5
6 S1 12
7 EPWR_5VM 14
8 ECOMM 6
Connector
9 Shield
Housing
10 IM- 10
11 S2 13
15 S3 8
The following table provides the signal descriptions and pin-outs for
the motor feedback (15-pin) connector to H-, F-, and Y-Series (230V)
motors.
P S3 8 Reserved Reserved 7
R TS+ 11 Reserved Reserved 9
S TS- 6 Reserved Reserved 11
T S1 12 Reserved Reserved 15
The following table provides the signal descriptions and pin-outs for
the motor feedback (15-pin) connector to 1326AB (resolver-based)
460V motors.
Motor Resolver Feedback for Drive MF Motor Resolver Feedback for Drive MF
Connector 1326AB-Bxxxx-21 Connector Power 1326AB-Bxxxx-21 Connector
Pin 460V Motors Pin 1 Cable 460V Motors Pin 2
A R1 5 5 TS+ 16
B R2 10 9 TS- 17
C – – – Shield S
D S1 3
E S3 4
F – –
G S2 1
H S4 2
1
For termination of individual drain wires, use Low Profile connector kit (2090-K6CK-D15MF) and reference Figure
3.19.
2
Thermal switch wires (5 and 9) are in the motor power cable (1326-CPx1-xxx). Use Low Profile connector kit
(2090-K6CK-D15MF) and reference Figure 3.19.
Refer to Figures 2.1 and 2.2 for the location of your motor feedback
connector(s).
6. Route the cable and wires, as shown in figures 3.18 and 3.19 (for
15-pin feedback cables) or Figure 3.20 (for 26-pin I/O cables) and
tighten the terminal screws to 0.2 N-m (2.1 lb-in.). Refer to
Appendix B for the motor feedback pin-out for your motor/drive
combination. Refer to Chapter 2 for I/O and auxiliary feedback
cable pinouts.
7. Gently pull on each wire to make sure it does not come out of its
terminal. Re-insert and tighten any loose wires.
8. Provide stress relief for wires by securing them with a tie wrap as
shown in figures 3.18, 3.19, and 3.20.
9. Position the cable shield (braid) in the clamp, replace the two
screws, and tighten clamp screws to 0.4 N-m (3.5 lb-in.). Refer to
figures 3.18 and 3.19 to see how the cable shield clamps to the
connector.
11. Insert the Low Profile connector into the appropriate IAM/AM/LIM
connector. Refer to Figures 2.1 (IAM), 2.2 (AM), and 2.14 (LIM) for
the location of your feedback and I/O connectors.
Figure 3.18
Wiring (15-Pin) Flying-Lead Feedback Cable Connections
15-pin (male) Motor Feedback 15-pin (female) Auxiliary Feedback
Low Profile Connector Low Profile Connector
Bare wires
Figure 3.19
Wiring (15-Pin) 1326-CCUx-xxx Motor Feedback Cable Connector
15-pin (male) Motor Feedback 15-pin (female) Auxiliary Feedback
Bare wires
Low Profile Connector Low Profile Connector
Drain wire
Wire insulation
Pin 10 Pin 6
Foil shield
Pin 5 Pin 15 Pin 1 Pin 11
Mounting
Braided shield Screws
Pin 1 Pin 11 Pin 5 Pin 15
1326-CCUx-xxx
Outer insulation Pin 6 Pin 10
0 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Drain wire (only with 1326-CCUx-xxx
Refer to Chapter 2 for feedback
cable) folded back under clamp
signal descriptions.
Tie
Wrap Refer to Appendix B for the motor
feedback interconnect drawing for
your application.
Shield Clamp
17 16 S
Pins S, 16, and 17 are only included on
Exposed Braid under clamp 2090-K6CK-D15MF Low Profile connectors and
used for thermal switch connections to 1326AB
(resolver-based) motors. After filtering, these pins
connect to MF-11 and -6.
Turn clamp over to hold
small wires secure 1326-CCUx-xxx cable Feedback
Thermal Switch Wires
Figure 3.20
Wiring (26-Pin) I/O Cable Connector
Pin 18
Pin 9 Pin 26
Mounting
Screws
Pin 1 Pin 19
Pin 10
S 26 25 24 S 23 22 21 20 19 18 17 16 15 14 13
12 11 10
Tie Wrap
Slot
Understand External Shunt Follow these guidelines when wiring your external active or passive
shunt resistor kit.
Connections
IMPORTANT When tightening screws to secure the wires, refer to
the tables beginning on page 3-17 for torque values.
Figure 3.21
Shunt Module Jumper Settings
1 2 3
COL
Shunt Module, top view INT
(2094-BSP2) Cable Shield
Clamp
DC+ Jumper 1
TS2
1 2
Understand Resistive Brake Follow these guidelines when wiring your Bulletin 2090 Resistive
Brake Module (RBM).
Module Connections
IMPORTANT To ensure system performance, run wires and cables
in the wireways as established in Chapter 1.
Figure 3.22
Resistive Brake Module Connections
I/O
(TB3) Connections
DC-
W
(TB1) Connector (TB2) Connector
DC+
V
U
L3
MBRK -
L2
MBRK +
L1 COM
PWR
CONT EN- DBRK -
CONT EN+ DBRK +
Connect Your SERCOS This procedure assumes you have your ControlLogix chassis with
1756-MxxSE interface module or personal computer with
Fiber-Optic Cables 1784-PM16SE PCI card and Kinetix 6000 SERCOS interface system(s)
mounted and are ready to connect the fiber-optic cables.
SERCOS interfaceTM
ControlLogix
1756-MxxSE SERCOS
CP OK
interface Module 0
F 1
ABCDE
23 6 7
45
RSLogix 5000 89
SoftLogix
OK 1784-PM16SE SERCOS interface PCI Card
(as viewed from the back of your PC)
CP
TX
SERCOS Transmit Connector, Tx
Tx (rear)
Figure 3.24
Fiber-Optic Ring Connection (Example 1)
0 SoftLogix
ABCDE
3456 72
F 1
1784-PM16SE SERCOS
89
OK
CP
RX
Receive
Refer to figures 3.25, 3.26, and 3.27 for examples of fiber-optic ring
connections between the Kinetix 6000 drive(s) (IAM or AM) and the
1756-MxxSE interface module.
Figure 3.25
Fiber-Optic Ring Connection (Example 2)
SERCOS interfaceTM
CP OK
ControlLogix Chassis
Tx (rear)
Rx (front)
Transmit Receive
Figure 3.26
Fiber-Optic Ring Connection (Example 3)
CP OK CP OK
ControlLogix
Chassis
Tx (rear) Tx (rear)
Rx (front) Rx (front)
Transmit Receive
Receive Transmit
Kinetix 6000
Note: You can mount the two 1756-MxxSE SERCOS interface modules in two separate ControlLogix chassis (as
shown above) or you can mount them in the same chassis.
Cable lengths of 32 m (105 ft) for plastic cable and 200 m (656.7 ft) for
glass cable are possible for each transmission section (point A to B).
In Figure 3.27, the second Kinetix 6000 system is located in a separate
cabinet and connected with bulkhead adapters.
Figure 3.27
Fiber-Optic Ring Connection (Example 3)
1756-MxxSE SERCOS
Interface Module
SERCOS interfaceTM
CP OK
ControlLogix Chassis
SERCOS Fiber-Optic
Tx (rear)
B A B A
SERCOS Fiber-Optic
Bulkhead Adapter
Figure 3.28
Kinetix 6000 Drive-to-Drive Example
1756-M16SE SERCOS
Interface Module SERCOS Fiber-Optic Ring
SERCOS interfaceTM
CP OK
Rx (front)
Kinetix 6000
(5 axis power rail)
2. Insert the other end of the cable (from step 1) into the Transmit
SERCOS connector on the ControlLogix module/SoftLogix PCI
Card and thread the connector on finger tight.
4. Insert the other end of the cable (from step 3) into the Receive
SERCOS connector on the ControlLogix module/SoftLogix PCI
Card and thread the connector on finger tight.
Chapter Objectives This chapter provides a troubleshooting activities for the Kinetix 6000.
This chapter includes:
• General Troubleshooting
• Troubleshoot IAM/AM Status LEDs
• Troubleshoot SM Status LEDs
• Troubleshoot LIM Status LEDs
• Troubleshoot RBM Status LEDs
• Troubleshoot General System Problems
General Troubleshooting Refer to the Error Codes section to identify problems, potential causes,
and appropriate actions to resolve the problems. If problems persist
after attempting to troubleshoot the system, please contact your
Allen-Bradley representative for further assistance. To determine if
your Kinetix 6000 drive has an error, refer to the table below.
Actively cycling segments in a full circle Your Kinetix 6000 drive is ready, but SERCOS
2094-xCxx-Mxx-x IAM communications is not available.
Displaying a fixed 4 Your Kinetix 6000 drive is ready.
Your Kinetix 6000 drive has an error. Proceed
All drives Flashing an E followed by two numbers to the section Error Codes.
Error Codes
OverSpeedFault Motor speed has exceeded 150% of maximum rated speed. The 100% • Check cables for noise.
E18 trip point is dictated by the lesser of the user velocity limits or the
(Overspeed Fault) motor rated base speed. • Check tuning.
SERCOSFault The SERCOS ring is not Check that fiber-optic cable is present and
E38 active after being active Cable disconnected. connected properly.
(SERCOS Ring Flt) and operational.
• Verify that there are no impediments to
motion at startup, such as hard limits.
E39
DriveHardFault Self-sensing Commutation Motion required for self-sensing startup • Increase self-sensing current if high
(Self Sense Flt) Startup Error commutation was obstructed. friction or load conditions exist.
• Check motor or encoder wiring using
wiring diagnostics.
• An attempt was made to enable the • Disable the Drive Enable Input fault.
axis through software while the Drive
DriveEnableInput Enable hardware input was inactive. • Verify that Drive Enable hardware input
E43 Fault Missing Drive Enable Input is active whenever the drive is enabled
Signal • The Drive Enable input transitioned through software.
(Drive Enable Flt)
from active to inactive while the axis
was enabled.
DriveHardFault For symptom, cause, and resolution of this error code, refer to the Kinetix Safe-Off Feature Safety Reference Manual
E49 (publication GMC-RM002). Applies to IAM (2094-xCxx-Mxx-S) and AM (2094-xMxx-S) with Safe-Off feature.
(Safe-Off HW Flt)
The airflow access to the Kinetix 6000 is Check airflow and re-route cables away
limited or blocked. from the Kinetix 6000.
Power rail CAN communications failed. Check module for proper mount.
Communicate
E73 Check power rail and module for foreign
(Backplane Comm) Power rail connection shorted or open. objects.
• Check for proper motor sizing.
Steady Red Drive faulted Seven-segment LED displays error code Refer to the section Error Codes and continue
troubleshooting.
Use the table below for troubleshooting the Bus Status LED on your
Kinetix 6000 IAM (2094-xCxx-Mxx) or AM (2094-xMxx).
Troubleshoot SM Status Each of the shunt module LEDs provide specific troubleshooting
information, as described in Bus Status LED, Temperature Fault LED,
LEDs and Shunt Fault LED.
The following table applies when all three SM LEDs are flashing.
Use the table below for troubleshooting the Bus Status LED on your
Kinetix 6000 SM (2094-BSP2).
Flashing Normal condition when control power is applied and bus voltage is less than N/A
60V dc.
Normal condition when control power is applied and bus voltage is greater
Steady Green than 60V dc. N/A
Off Control power is not present Internal power supply failure Replace shunt module.
Use the table below for troubleshooting the Temperature Fault LED on
your Kinetix 6000 SM (2094-BSP2).
Use the table below for troubleshooting the Shunt Fault LED on your
Kinetix 6000 SM (2094-BSP2).
Troubleshoot LIM Status The following troubleshooting table applies to the following Line
Interface Module status LEDs:
LEDs
• 24V Power status LED (2094-AL75S, -BL75S, and -XL75S-Cx)
• Brake Power status LED (2094-AL09 and -BL02)
• I/O Power status LED (2094-AL09 and -BL02)
Troubleshoot RBM Status The Resistive Brake Module (RBM) contactor status LED is visible from
the front of the RBM. Use the table below for troubleshooting the
LEDs RBM status LEDs.
If the Status LED is RBM Contactor Status is Potential Cause is Possible Resolution is
Contactor engaged
(direct connection between drive and No faults or failures N/A
motor)
Steady Green
Contactor disengaged • Monitor CONSTAT_41/42 status to verify lack of
(no connection between drive and Contactor failure drive/motor power (output is NC).
motor) • Contact A-B representative.
• Verify ground wiring.
Recommended grounding • Route wires away from noise sources.
not followed
Blinking Green Contactor rapidly engaging/ • Refer to System Design for Control of Electrical Noise
(audible clicking) disengaging Reference Manual (publication GMC-RM001).
Control circuit improperly Verify control wiring and programming.
wired
Off No faults or failures N/A
(intended)
• +24V supply is off.
Contactor disengaged
(connection open between drive and +24V not applied between • Verify wiring.
Off motor) COIL_A1 and COIL_A2 • Drive not enabled.
(unintended)
• Contact A-B representative.
T1 (Fault) thermostat open Duty cycle exceeded, allow RBM to cool.
Troubleshoot General Use the tables below for troubleshooting general system faults. For a
list of Bulletin 1756 product manuals, refer to Related Documentation
System Problems in the Preface.
Motor Select limit is incorrectly set (servo motor is not matched • Check setups.
to axis module). • Run Tune in RSLogix 5000.
Notch filter or output filter may be required
Mechanical resonance (refer to Axis Properties window, Output tab
in RSLogix 5000).
Torque Limit limits are set too low. Verify that current limits are set properly.
Select the correct motor and run Tune in
Incorrect motor selected in configuration. RSLogix 5000 again.
• Check motor size vs. application need.
The system inertia is excessive.
• Review servo system sizing.
You cannot obtain the motor
acceleration/deceleration The system friction torque is excessive. Check motor size vs. application need.
that you want • Check motor size vs. application need.
Available current is insufficient to supply the correct accel/decel
rate. • Review servo system sizing.
Verify limit settings and correct them, as
Acceleration limit is incorrect. necessary.
Verify limit settings and correct them, as
Velocity Limit limits are incorrect. necessary.
The axis cannot be enabled for 1.5 seconds after disabling. Disable the axis, wait for 1.5 seconds, and
enable the axis.
Enable signal has not been applied or the enable wiring is • Check the controller.
incorrect. • Check the wiring.
The motor wiring is open. Check the wiring.
The motor connections are loose or open. Check motor wiring and connections.
Foreign matter is lodged in the motor. Remove foreign matter.
The motor load is excessive. Verify the servo system sizing.
No Rotation The bearings are worn. Return the motor for repair.
• Check brake wiring and function.
The motor brake is engaged (if supplied).
• Return the motor for repair.
The motor is not connect to the load. Check coupling.
Change the command profile to reduce accel/
The duty cycle is excessive. decel or increase time.
Motor Overheating
The rotor is partially demagnetized causing excessive motor Return the motor for repair.
current.
Motor tuning limits are set too high. Run Tune in RSLogix 5000 again.
• Remove the loose parts.
Loose parts are present in the motor. • Return motor for repair.
• Replace motor.
Abnormal Noise
Through bolts or coupling is loose. Tighten bolts.
The bearings are worn. Return motor for repair.
Notch filter may be required (refer to Axis
Mechanical resonance Properties window, Output tab in RSLogix
5000).
Motor power phases U and V, U and W, or V and W reversed. Check and correct motor power wiring.
Erratic Operation - Motor
locks into position, runs Sine, Cosine or Rotor leads are reversed in the feedback cable
without control or with connector. Check and correct motor feedback wiring.
reduced torque
Sine, Cosine, Rotor lead sets of resolver feedback are reversed. Check and correct motor feedback wiring.
• Certifications
• Power Specifications
• General Specifications
• AC Line Filter Specifications
• External Shunt Module Specifications
• Resistive Brake Module Specifications
• Dimensions
Certifications The Kinetix 6000 is certified for the following when the product or
package is marked.
Power Specifications This section contains power specifications for the Kinetix 6000 system
components.
Description
Specification
2094-AC05-MP5 2094-AC05-M01 2094-AC09-M02 2094-AC16-M03 2094-AC32-M05
Description
Specification
2094-BC01-MP5 2094-BC01-M01 2094-BC02-M02 2094-BC04-M03 2094-BC07-M05
AC Input Voltage 324-528Vrms Three-Phase (360/480V nominal)
AC Input Frequency 47 - 63 Hz
The tables below list the power specifications for the Kinetix 6000
(230V) Axis Modules. These specifications apply to the Axis Module
specified in the column heading by catalog number and the same Axis
Module (inverter section) that resides within an Integrated Axis
Module.
Description
Specification 2094-AMP5 2094-AM01 2094-AM02 2094-AM03 2094-AM05
(2094-AC05-MP5) (2094-AC05-M01) (2094-AC09-M02) (2094-AC16-M03) (2094-AC32-M05)
Bandwidth 1
Velocity Loop 500 Hz
Current Loop 1300 Hz
PWM Frequency 8 kHz 4 kHz
Nominal Input Voltage 325V dc
Continuous Current (rms) 3.7A 6.0A 10.6A 17.3A 34.6A
Continuous Current (sine)
0-peak 5.2A 8.5A 15.0A 24.5A 48.9A
Peak Current (rms) 2 7.4A 12.0A 21.2A 34.6A 51.9A
Peak Current (0-peak) 2 10.5A 17.0A 30.0A 48.9A 73.4A
Continuous Power Out (nominal) 1.2 kW 1.9 kW 3.4 kW 5.5 kW 11.0 kW
Internal Shunt
Continuous Power N/A 50W
Peak Power N/A 1400W
Internal Shunt Resistor N/A 115 Ω
Shunt On N/A 405V dc
Shunt Off N/A 375V dc
Efficiency 98%
Capacitance 390µF 660µF 780µF 1320µF 2640µF
Capacitive Energy Absorption 15 Joules 25 Joules 29 Joules 50 Joules 99 Joules
1 Bandwidth values vary based on tuning parameters and mechanical components.
2
Peak current duration equals 2.5 seconds.
The tables below list the power specifications for the Kinetix 6000
(460V) Axis Modules. These specifications apply to the Axis Module
specified in the column heading by catalog number and the same Axis
Module (inverter section) that resides within an Integrated Axis
Module.
Description
Specification 2094-BMP5 2094-BM01 2094-BM02 2094-BM03 2094-BM05
(2094-BC01-MP5) (2094-BC01-M01) (2094-BC02-M02) (2094-BC04-M03) (2094-BC07-M05)
Bandwidth 1
Velocity Loop 500 Hz
Current Loop 1300 Hz
PWM Frequency 8 kHz 4 kHz
Nominal Input Voltage 650V dc
Continuous Current (rms) 2.8A 6.1A 10.3A 21.2A 34.6A
Continuous Current (sine)
0-peak 4.0A 8.6A 14.6A 30.0A 48.9A
Peak Current (rms) 2 4.2A 9.2A 15.5A 31.8A 51.9A
Peak Current (0-peak) 2 5.9A 12.9A 21.8A 45.0A 73.4A
Continuous Power Out (nominal) 1.8 kW 3.9 kW 6.6 kW 13.5 kW 22.0 kW
Internal Shunt
Continuous power 50W 200W
Peak power 5600W 22300W
Internal Shunt Resistor 115 Ω 28.75 Ω
Shunt On 805V dc
Shunt Off 755V dc
Efficiency 97%
Capacitance 75µF 150µF 270µF 840µF 1175µF
Capacitive Energy Absorption 10 Joules 19 Joules 35 Joules 108 Joules 152 Joules
1 Bandwidth values vary based on tuning parameters and mechanical components.
2
Peak current duration equals 2.5 seconds.
Description
Designator Specification 2094-XL75S-C1 2094-XL75S-C2
2094-AL75S (230V) 2094-BL75S (460V)
(230/460V) (230/460V)
195-265Vrms 380-520Vrms 195-520Vrms Three-Phase
VAC Line AC Input Voltage Three-Phase Three-Phase (230-460V nominal)
(IPL) Connector (230V nominal) (460V nominal)
AC Input Frequency 47 - 63 Hz 47 - 63 Hz
VAC Load 75Arms 75Arms
(OPL) Connector Main AC Output Current
Description
Designator Specification
2094-AL09 2094-BL02
195-265Vrms Three-Phase 380-520Vrms Three-Phase
VAC Line AC Input Voltage
(230V nominal) (460V nominal)
(IPL) Connector
AC Input Frequency 47 - 63 Hz
VAC Load Main AC Output Current 20Arms 30Arms
(OPL) Connector
Auxiliary AC Output Current 3A
Control Power Output
(CPL) Connector 195-265Vrms Three-Phase 190-260Vrms Three-Phase
Auxiliary AC Output Voltage
(230V nominal) (230V nominal)
The table below lists the power specifications for the Kinetix 6000
Shunt Modules.
Specifications
Shunt Module Drive Peak Peak Continuous Fuse Replacement
Kinetix 6000 Drives Catalog Number Resistance Power
Voltage Current Power
V ac Ohms kW Amps Watts
2094-ACxx-Mxx 230 5.7 14
or 2094-BSP2 28.75 200 N/A (no internal fuse)
2094-BCxx-Mxx 460 22.5 28
In the table below, the 230V system specifications are given for the
IAM internal shunt resistors, the Kinetix 6000 (2094-BSP2) SM, and the
Bulletin 1394 external shunt modules.
In the example below, the continuous shunt power is 300W. The 50W
resistor in the IAM is disabled when used in combination with the
(2094-BSP2) SM. This example is unique to the 2094-AC09-M02 IAM.
Figure A.1
230V Shunt Power Example (2094-AC09-M02)
In the table below, the 460V system specifications are given for the
IAM internal shunt resistors, the Kinetix 6000 (2094-BSP2) SM, and the
Bulletin 1394 external shunt modules.
BC01-MP5 – – – – 50 plus 3
BC01-M01 – – – – 50 plus 3
BC02-M02 0 to 7 N/A 2 – – – – N/A 2 50 plus 3
BC04-M03 – – – –
200 plus 4
BC07-M05 – – – –
BCxx-Mxx 1 to 6 BSP2 28.75 28 22.5 200 N/A 2 200 plus 5
BCxx-Mxx 300 1394-SR9A 300 6
BCxx-Mxx 900 1394-SR9AF 900 6
1 to 6 BSP2 4 201.3 162
BCxx-Mxx 1800 1394-SR36A 1800 6
BCxx-Mxx 3600 1394-SR36AF 3600 6
1
Refer to on page A-17 for shunt module specifications.
2 Module not part of system configuration.
3
50 plus the sum of the AM internal shunt ratings.
4
200 plus the sum of the AM internal shunt ratings.
5 200 plus the sum of the IAM and AM internal shunt ratings.
6
Use of external shunt disables shunts internal to IAM and AM.
In the example below, the sum of the IAM, AMs, and SM equal 500W
of continuous shunt power.
Kinetix 6000 (230V) Shunt Power Example Bulletin 1394 External Shunt Module
900W Continuous Shunt Power ALLEN-BRADLEY
Shunt Module
(1394-SR9AF) 900W external shunt
R
Figure A.4
Circuit Protection under NEC 1999 110-10 (preferred fully rated devices)
Breakers Selected
for Device Protection Breakers Selected
Fully Rated Short Circuit for Device Protection
Interrupt Capability Fully Rated Short Circuit
Interrupt Capability
Drive Drive Drive
Figure A.5
Circuit Protection under NEC 1999 110-10 (allowed but no longer preferred)
Contactor Ratings
You can use any general purpose transformer with the following
ratings. Refer to Control Power Input on page 2-16 for more
information.
Specification Rating
Input volt-amperes 750 VA (up to 8 axis)
Output voltage 120-240V ac
General Specifications The following sections provide weight, environmental, AC line filter,
external shunt, and maximum feedback cable length specifications for
the Kinetix 6000 system.
Weight Specification
Kinetix 6000 Catalog Number Description Kinetix 6000 Catalog Number Description
Module Module
2094-AC05-MP5 2.23 kg (4.9 lbs) 2094-BC01-MP5 4.98 kg (11.0 lbs)
2094-AC05-M01 2.27 kg (5.0 lbs) 2094-BC01-M01 5.03 kg (11.1 lbs)
IAM IAM
(230V) 2094-AC09-M02 2.31 kg (5.1 lbs) (460V) 2094-BC02-M02 5.08 kg (11.2 lbs)
2094-AC16-M03 4.71 kg (10.4 lbs) 2094-BC04-M03 9.60 kg (21.1 lbs)
2094-AC32-M05 7.43 kg (16.4 lbs) 2094-BC07-M05 10.12 kg (22.3 lbs)
2094-AMP5 1.46 kg (3.2 lbs) 2094-BMP5 2.44 kg (5.4 lbs)
2094-AM01 1.50 kg (3.3 lbs) 2094-BM01 2.49 kg (5.5 lbs)
AM 2094-AM02 1.54 kg (3.4 lbs) AM 2094-BM02 2.54 kg (5.6 lbs)
(230V) (460V)
2094-AM03 3.13 kg (6.9 lbs) 2094-BM03 4.58 kg (10.1 lbs)
2094-AM05 3.18 kg (7.0 lbs) 2094-BM05 4.98 kg (11.0 lbs)
2094-AL09 11.33 kg (25 lbs) LIM 2094-BL02 18.14 kg (40 lbs)
LIM (460V) 2094-BL75S 17.15 kg (37.8 lbs)
(230V) 2094-AL75S 10.70 kg (23.6 lbs) LIM 2094-XL75S-Cx 10.70 kg (23.6 lbs)
(230/460V)
2094-PRS1 1.05 kg (2.3 lbs) 2094-PR1 1.04 kg (2.3 lbs)
2094-PRS2 1.59 kg (3.5 lbs) 2094-PR2 1.41 kg (3.1 lbs)
2094-PRS3 2.14 kg (4.7 lbs) Power Rails 2094-PR4 2.18 kg (4.8 lbs)
Power Rails 2094-PRS4 2.67 kg (5.9 lbs) 2094-PR6 2.90 kg (6.4 lbs)
(Slim) 2094-PRS5 3.11 kg (6.8 lbs) 2094-PR8 3.63 kg (8.0 lbs)
2094-PRS6 3.55 kg (7.8 lbs)
2094-PRS7 3.99 kg (8.8 lbs) SM (460V) 2094-BSP2 3.1 kg (6.8 lbs)
2094-PRS8 4.43 kg (9.7 lbs) Slot Filler Module 2094-PRF 0.45 kg (1.0 lbs)
Environmental Specifications
The maximum feedback cable lengths for Kinetix 6000 drives with
MP-Series Low Inertia (MPL) and Integrated Gear (MPG) motors are
given in the table below.
The maximum feedback cable lengths for Kinetix 6000 drives with
MP-Series Food Grade (MPF) and Stainless Steel (MPS) motors are
given in the table below.
The maximum feedback cable lengths for Kinetix 6000 drives with
1326AB, TL-Series, and F-, H-, N-, and Y-Series motors are given in the
table below.
AC Line Filter The table below contains specifications for AC Line Filters available
for use with all 230V and 460V systems.
Specifications
Specifications
AC Line Filter
Catalog Number Voltage Phase Current Power Weight Humidity Vibration Operating
Loss kg (lb) Temperature
30A @ 50° C 2.7
2090-XXLF-X330B 38W
(122° F) (5.9)
2090-XXLF-375 500V ac 75A @ 50° C 5.2 10-200 Hz -25 to 85° C
Three 57W 90% RH
2090-XXLF-375B 50/60 Hz (122° F) (11.4) @ 1.8 g (-13 to 185 ° F)
Use the table below to determine which AC line filter is best suited for
your Kinetix 6000 drive.
External Shunt Module The following sections provide external passive and active shunt
module specifications. These shunt modules are compatible with the
Specifications Kinetix 6000 drives with regenerative loads that exceed the capacity of
the internal shunt resistor (IAM/AM).
These external passive shunt modules wire to the Kinetix 6000 Shunt
Module (2094-BSP2).
Specifications
External Shunt Drive
Voltage Resistance Peak Peak Cont. Shipping Bussmann
Catalog Number Range Power Current Power Weight Replacement Fuse
VAC
Ohms kW Amps Watts kg (lbs)
230 1 41.0 101.25 FNQ-R-20-R1 1
1394-SR9A 4 300 3.63 (8)
460 160.0 20.0 FWP50A14F
1
230 41.0 101.25 FNQ-R-20-R11
1394-SR9AF 4 900 3.63 (8)
460 160.0 20.0 FWP50A14F
1
230 41.0 101.25 FNQ-R-20-R1 1
1394-SR36A 4 1800 8.6 (19)
460 160.0 20.0 FWP50A14F
1 FNQ-R-25-R1 1
230 41.0 101.25
1394-SR36AF 4 3600 9.0 (20)
460 160.0 20.0 FWP50A14F
1 Requires the use of an FNQ fuse with an adapter to allow the smaller body fuse to fit the larger FWP fuse holder.
These Bulletin 1336 external active shunt modules wire directly to the
DC bus.
Specifications
Shunt Module Drive Continuous Shipping
Kinetix 6000 Drives Catalog Number Resistance Peak Peak
Voltage Ohms Power Current Power Weight Fuse Replacement
VAC kW Amps Watts kg (lbs)
1336-MOD-KA005 28.0 6 15 375 A50P10
2094-ACxx-Mxx 230V
1336-MOD-KA010 13.2 12 30 750 A50P20
6.8 (15)
1336-MOD-KB005 104.0 6 7.5 375 A60Q
2094-BCxx-Mxx 1336-MOD-KB010 460V 52.0 12 15 750 A60Q
1336-MOD-KB050 10.0 60 76 3750 33.8 (75) A70QS35
Resistive Brake Module The following resistive brake modules are compatible with the Kinetix
6000 drive system.
Specifications
Drive Peak Drive Current Continuous
Catalog Number Voltage Resistance 1 Peak Energy
Power
Weight
Ohms Joules Amps 0-pk Amps rms kg (lb)
Volts Watts
2090-XB33-32 32
150 33 23 30 1.91 (4.22)
2090-XB33-16 16
2090-XB120-06 230 or 460 6
2090-XB120-03 3 290 120 85 45 2.75 (6.06)
2090-XB120-01 1
1 Tolerance = ± 10%.
Dimensions Within this section you will find dimension drawings for the following
Kinetix 6000 system components:
Figure A.6
2094-AC05-MP5, AC05-M01, and -AC09-M02 (230V)
2094-BC01-MP5, -BC01-M01, and -BC02-M02 (460V)
F
2094-AC05-M01 (230V) shown
62
Important: Additional clearance below the connector
(2.45)
is necessary to provide the recommended cable bend
This view illustrates the radius.
additional clearance required for
premolded cable connectors.
Note: Modules are shown mounted to the power rail and the
dimensions reflect that in the depth of the module.
Figure A.7
2094-AC16-M03 and -AC32-M05 (230V)
2094-BC04-M03 and -BC07-M05 (460V)
B C
8.9
(0.35)
62
Important: Additional clearance below the connector
(2.45)
is necessary to provide the recommended cable bend
This view illustrates the radius.
additional clearance required for
premolded cable connectors.
Modules are shown mounted to the power rail and the dimensions
reflect that in the depth of the module.
Figure A.8
2094-AMP5, -AM01, and -AM02 (230V)
2094-BMP5, -BM01, and -BM02 (460V)
A
B
Dimensions are in millimeters (inches) 70
20 (2.76)
(0.8) 8.9
(0.35)
F
2094-AM01 (230V) shown
Power Rail
Note: Modules are shown mounted to the power rail and the
dimensions reflect that in the depth of the module.
A B D E F
Kinetix 6000 AM mm (in.) mm (in.) mm (in.) mm (in.) mm (in.)
2094-AMP5
2094-AM01 198 (7.8) 176 (7.0) 51 (2.0) 206 (8.2) 231 (9.1)
2094-AM02
2094-BMP5
2094-BM01 272 (10.7) 249 (9.8) 0 (0) 256 (10.1) 281 (11.0)
2094-BM02
Figure A.9
2094-AM03 and -AM05 (230V)
2094-BM03 and -BM05 (460V)
A Dimensions are in millimeters (inches)
B C
8.9
(0.35)
Modules are shown mounted to the power rail and the dimensions
reflect that in the depth of the module.
Kinetix 6000 AM A B C E F
mm (in.) mm (in.) mm (in.) mm (in.) mm (in.)
2094-AM03
198 (7.8) 176 (7.0) 70 (2.8) 302 (11.9) 420 (16.5)
2094-AM05
2094-BM03 256 (10.1) 374 (14.7)
272 (10.7) 249 (9.8) 141 (5.5)
2094-BM05 318 (12.5) 436 (17.2)
Figure A.10
2094-BSP2
263
(10.3) 70
249 Dimensions are in millimeters (inches) (2.76)
(9.8)
123 43
20 (4.8) 20 (1.7)
(0.8) (0.8)
281
(11.0)
256
(10.1)
Power Rail
Note: Modules are shown mounted to the power rail and the
dimensions reflect that in the depth of the module.
Figure A.11
2094-PRF
62.1
2.45
70.1
56.4 2.76
2.22
206.2
8.12
Figure A.12
2094-PRS1 (Slim)
134.6
22.9 (5.3)
(0.90) 88.9
(3.5) ∅ 7.95 25.4
(O.313) TYP. (1.0)
25.4
241.3 (1.0)
Dimensions are in millimeters (inches) (9.5)
190.5
(7.5)
∅ 15.88 12.4
69.9 (O.625) TYP.
(2.75) (0.49)
Figure A.13
2094-PRS2, -PRS3, -PRS4, -PRS5, -PRS6, -PRS7, and -PRS8 (Slim)
22.9 A
(0.90) B ∅ 7.95
C Dimensions are in millimeters (inches) (O.313) TYP. 25.4
(1.0)
25.4
241.3 (1.0)
(9.5)
190.5
(7.5)
∅ 15.88
(O.625) TYP. 12.4
(0.49)
Figure A.14
2094-PR1, -PR2, -PR4, -PR6, and -PR8
A
12.7 B
(0.50)
C Dimensions are in millimeters (inches) 25.4
(1.0)
∅ 7.95
(O.313) TYP.
198.1 25.4
(7.80) (1.0)
146.05
(5.75)
∅ 15.88
(O.625) TYP.
12.2
(0.48)
Figure A.15
2094-AL09 (230V)
325
(12.8)
197
(7.75)
3x Ø 16 6x Ø 7.9 12.7 22
(0.63) (0.31) 187.7
(0.5) (0.87)
(7.39)
3x 28.7 (1.13)
8.9
225 (0.35)
(8.86)
253.1
(9.97)
286.8
(11.29)
28
30.9 142.5 12.7 (1.1)
(1.22) (5.61) (0.5)
20 285 Flying-Lead I/O Cable
(0.79) (11.22) with 2090-K6CK-D26Mxx
Low Profile Connector Kit
Figure A.16
2094-BL02 (460V)
400
(15.75)
100
(3.9)
2x 206
(8.11)
280 Dimensions are in millimeters (inches)
(11.02)
277
(10.9)
2x 28.5 (1.2)
2x 40.4 27.6
280 (1.59) (1.09)
(11.02)
3x Ø 16 6x Ø 7.9
(0.63) (0.31) 289
12.7
(11.37)
(0.50)
3x 28.7 (1.13)
8.9
(0.35)
252.2
(9.93)
312
(12.28) 197 278.4
(7.8) 250 (10.96)
(9.84)
Figure A.17
2094-AL75S (230V), -BL75S (460V), and -XL75S-Cx (230/460V)
259.8
(10.23)
CONTROL VAC
CTRL2
CTRL1
195-265 VAC LINE, 50/60 Hz
AUX2
L1
AUX1
I/O_COM
24 VDC SUPPLY
I/O_PWR
I/O_COM
L3' I/O_PWR
I/O_COM
I/O_PWR
L2'
L1'
(14.80)
2x 352.4 309.9
309.9 (13.87) (12.20)
(12.20)
2x 33 (1.30) 220
(8.66)
Figure A.18
Mounting Bracket Dimensions
Ø 7.9 (0.31) TYP. REF 4.2
12.7
(0.16) REF
Ø 15.9 (0.62) TYP. (0.50) TYP.
M6 x 1 holes
(6 Locations) 23.4
(0.92)
40.6
55.3
(1.60)
(2.18)
LIM
PR/PRS
301 ±0.5
(11.86 ±0.020)
PRS
LIM
Ground
Stud
76.2 89.3 ±0.5
(3.0) (3.51 ±0.020)
Figure A.19
LIM on 2094 Mounting Brackets
PR/PRS
PRS
PR
PR
LIM LIM
Mounting Bracket
(2094-XNBRKT-1)
428.6
(16.87) MAIN VAC
276.2
(10.87)
PRS
PR
PR
LIM LIM
Mounting Bracket
(2094-XNBRKT-1)
Note: Only the 2094-AL75S and -XL75S-Cx models are compatible with the 2094 Mounting brackets. The
2094-BL75S, -AL09, and -BL02 models are not compatible.
Interconnect Diagrams
Kinetix 6000 Interconnect This section provides interconnect diagram notes to assist you in
wiring the Kinetix 6000 system. The notes apply to the interconnect
Diagram Notes diagrams on the pages that follow.
ATTENTION
The National Electrical Code and local electrical
codes take precedence over the values and methods
provided. Implementation of these codes is the
responsibility of the machine builder.
Note Information
1 For power wiring specifications, refer to Power Wiring Requirements on page 3-17.
2 For input fuse and circuit breaker sizes, refer to Circuit Breaker/Fuse Specifications on page A-11.
3 For AC line filter specifications, refer to AC Line Filter Specifications on page A-17.
4 Terminal block is required to make connections.
5 2094-BCxx-Mxx (460V) IAM requires step down transformer for single-phase control power input. Source 2094-ACxx-Mxx (230V) IAM control
power from the three-phase input power (line-to-line). Supplying 230V control power from any other source requires an isolation transformer. If
used, do not ground either leg of the isolation transformer output.
6 LIM models 2094-AL75S and -BL75S can supply a maximum of eight axes. LIM models 2094-XL75S-Cx can supply a maximum of sixteen axes. For
common bus systems with more than sixteen axes, multiple LIMs (or control power transformers) are required.
7 Contactor coil (M1) needs integrated surge suppressors for AC coil operation. Refer to Contactor Ratings on page A-13.
8 Drive Enable input must be opened when main power is removed, or a drive fault will occur. A delay of at least 1.0 second must be observed
before attempting to enable the drive after main power is restored.
9 Cable shield clamp must be used in order to meet CE requirements. No external connection to ground required.
10 Jumper is factory set, indicating grounded system at user site. Ungrounded sites must jumper the bleeder resistor to prevent high electrostatic
buildup. Refer to Determine Your Type of Input Power on page 3-3 for more information.
11 Implementation of safety circuits and risk assessment is the responsibility of the
ATTENTION
machine builder. Please reference international standards EN 1050 and EN 954
estimation and safety performance categories. For more information refer to
Understanding the Machinery Directive (publication SHB-900).
12 Wiring the Contactor Enable relay is required. To avoid injury or damage to the
ATTENTION
drive, wire the Contactor Enable relay into your safety control string. Refer to
Contactor Enable Relay on page 2-14. The recommended minimum wire size for
wiring the safety circuit to the contactor enable connector is 1.5 mm2 (16 AWG).
13 The Kinetix 6000 axis module referenced is either an individual axis module (2094-xMxx) or the same axis module that resides within an
integrated axis module (2094-xCxx-Mxx).
14 For motor cable specifications, refer to the Kinetix Motion Control Selection Guide (publication GMC-SG001).
15 Wire colors are for flying lead cable (2090-XXNFxx-Sxx) and may vary from the premolded connector cable (2090-UXNFBxx-Sxx).
16 Y-Series feedback cables have a drain wire that must be folded back under the Low Profile connector clamp.
17 Only the MPG-Bxxx encoder uses the +5V dc supply. MPL-Bxxx encoders use the +9V dc supply.
18 Brake wires on MPF/MPS-A/B5xx motors are labeled plus (+) and minus (-). All other MP-Series Food Grade and Stainless Steel motor brake
wires are labeled F and G.
19 Refer to 1336 Active Shunt Input Fuse Specifications for input fuse specifications. Current requirements are for master only shunt applications as
shown in Figure B.11. For master/slave applications (Figure B.12) you must multiply the current requirement by the number of shunt units.
20 Refer to 1336 Active Shunt Fault Relay Specifications for fault relay specifications. This normally closed contact (TTL compatible) is closed when
115V ac is applied and opens when a shunt fault or loss of power occurs.
21 TB3-2 (TS_22) can be wired to ControlLogix input as overtemp warning in user program.
22 Firmware version 1.071 (or higher) is required to use the DBRK outputs on the Kinetix 6000 IAM or AM.
23 The safety relay time delay should be set beyond the time required to stop and disable the axis when running at full speed.
24 Drive Enable Input Checking must be selected in Axis Properties.
Power Interconnect The interconnect wiring for an IAM is shown beginning below.
Diagrams In the configuration below the IAM has input power, brake power,
and the start/stop string wired from a LIM (2094-AL09 or -BL02). The
2094-xLxx LIM contains an AC line filter, so an external filter is not
required.
Figure B.1
IAM Power Interconnect Diagram (IAM with LIM)
Kinetix 6000
INTEGRATED AXIS MODULE
2094-ACxx-Mxx or -BCxx-Mxx
Power Rail
Bonded Cabinet Ground Stud
Ground Bus*
Note 9
1
MBRK_PWR
2
24V dc Output MBRK_COM
3
(PSL) Connector MBRK_PWR
4 6
MBRK_COM BR-
MBRK - Motor Brake
5 BR+ Connections
MBRK +
4
COM
24-26 Motor/Resistive 3
IO_PWR Brake (BC) Connector PWR
2 BR-
I/O (IOL) STOP * DBRK - Resistive Brake
Connector 1 BR+
13 DBRK + Connections
Note 11, 12 COIL_A1
20-22 1
IO_COM CONT EN- Contactor Enable
4 2 (CED) Connector
COIL_A2 CONT EN+
Note 12
* INDICATES USER SUPPLIED COMPONENT
In the configuration below two IAMs have input power, brake power,
and the start/stop string wired from the same LIM (2094-AL75S,
-BL75S, or -XL75S-Cx). The 2094-xL75S-xx LIM does not contain an AC
line filter, so an external filter is added between the LIM and IAM.
Refer to Appendix C for catalog numbers of available AC line filters.
Figure B.2
IAM Power Interconnect Diagram (IAM with LIM)
Kinetix 6000
INTEGRATED AXIS MODULE
2094-ACxx-Mxx or -BCxx-Mxx
(IAM_1)
Kinetix 6000 4
LINE INTERFACE MODULE 3 Three-Phase
Motor Power W Motor Power
2094-AL75S, -BL75S, or -XL75S-Cx (MP) Connector 2 Connections
V
1 Note 14
Note 4 1 U
Control Power CTRL 2 1 CTRL 2 Control Power
Single-Phase (CPL) Output 2 2 (CPD) Connector
195-264V ac RMS CTRL 1 CTRL 1
Note 1
To CPD connector,
IAM_2
Note 6
1
DC-
2 DC Bus
DC+ and
1 1 Note 4 3
VAC LOAD 3-Phase
VAC LINE 2 3-Phase (OPL) Output 2 Three-Phase 4 Input (IPD)
L3 L3' L3
3-Phase (IPL) Input 3 195-264V ac RMS 3 AC Line Filter 5 Connector
195-264V ac RMS L2 or 324-528V ac RMS L2' Note 3 L2
4 4 6
or 324-528V ac RMS L1 Note 1 L1' L1
Note 1
To IPD connector,
IAM_2
Auxiliary Power 1
L1
Single-Phase (APL) Input 2
93-121V ac RMS L2/N 1
IO_PWR2
or 196-253V ac RMS 2 To BC connector, IAM_2
(This connector is present IO_COM2
only on the 2094-XL75S-Cx) 3
24V dc (P1L) Output IO_PWR2
Note 1 4
IO_COM2
5
IO_PWR2
6
IO_COM2 Motor Brake
Connections
6 BR-
MBRK -
5 BR+
MBRK +
4
COM
Motor/Resistive 3
Brake (BC) Connector PWR
2 BR-
1, 3, 5 DBRK -
IO_PWR1
1 BR+
DBRK +
I/O (IOL) STOP *
Connector Resistive Brake
7 Connections
Note 11, 12 COIL_E1
2, 4, 6 1
IO_COM1 CONT EN- Contactor Enable
8 2 (CED) Connector
COIL_E2 CONT EN+
Note 12
Kinetix 6000
INTEGRATED AXIS MODULE
2094-ACxx-Mxx or -BCxx-Mxx
(IAM_2)
4
Three-Phase
3 Motor Power
Motor Power W
(MP) Connector 2 Connections
V Note 14
1
1 U
CTRL 2 Control Power
From CPL connector, LIM 2 (CPD) Connector
CTRL 1
1
DC-
2 DC Bus
DC+ and
3
3-Phase
Three-Phase 4 Input (IPD)
L3
From OPL connector, LIM AC Line Filter 5 Connector
Note 3 L2
6
L1
6 BR-
MBRK - Motor Brake
5 BR+ Connections
MBRK +
4
COM
Motor/Resistive 3 From P1L connector, LIM
Brake (BC) Connector PWR
2 BR-
DBRK - Resistive Brake
1 BR+
DBRK + Connections
1
From IOL connector, LIM CONT EN- Contactor Enable
2 (CED) Connector
and CED connector, IAM_1 CONT EN+
Note 12
The configuration on this page does not include a LIM. You must
supply input power components. The diagram below is preferred
because one three-phase line filter is utilized by both control power
and main input power connections. The three-phase line filter is wired
upstream of fusing and the M1 contactor.
Figure B.3
IAM Power Interconnect Diagram (IAM without LIM - Preferred)
Kinetix 6000
INTEGRATED AXIS MODULE
2094-ACxx-Mxx or -BCxx-Mxx
The configuration on this page does not include a LIM. You must
supply input power components. The diagram below is not preferred
because two line filters are required. The single-phase and
three-phase line filters are wired downstream of fusing and the M1
contactor.
Figure B.4
IAM Power Interconnect Diagram (IAM without LIM - Alternate)
Kinetix 6000
INTEGRATED AXIS MODULE
2094-ACxx-Mxx or -BCxx-Mxx
1 Note 9
Single-Phase CTRL 2 Control Power
Single-Phase Input 2 Cable Shield
AC Line Filter CTRL 1 (CPD) Connector
95-264V ac RMS Clamp
Note 3
Notes 1, 2
Input Fusing *
Isolation 4
Transformer * 3 Three-Phase
Note 5 Motor Power W Motor Power
2
(MP) Connector V Connections
1 1 Note 14
DC- U
2 DC Bus
DC+
Note 4 3 and
3-Phase
Three-Phase 4
Three-Phase Input L3 Input (IPD)
195-264V ac RMS AC Line Filter 5 Connector 6 BR-
L2 MBRK -
or 324-528V ac RMS Note 3 6 Motor Brake
L1 5 BR+
Notes 1, 2 MBRK + Connections
Input Fusing * M1 * 4
COM User Supplied
Notes 7, 8 Motor/Resistive 3
Brake (BC) Connector PWR 24V dc (1.2A maximum)
2 BR-
DBRK -
Resistive Brake
1 BR+
Notes 7, 12 1 DBRK + Connections
CONT EN- Contactor Enable
2
CONT EN+ (CED) Connector
STOP * START * Note 12
24V ac/dc CR1 *
or
120V ac
50/60 Hz M1 * CR1 * Ground Jumper
Note 10
CR1 *
* INDICATES USER SUPPLIED COMPONENT
Refer to Attention statement (Note 11)
Kinetix 6000
COMMON BUS FOLLOWER IAM
Bonded Cabinet 2094-ACxx-Mxx or -BCxx-Mxx
Ground Bus*
DC Common Bus
Ground Bus*
Power Rail 1
Interconnect Diagrams
1
CONT EN- Contactor Enable * INDICATES USER SUPPLIED COMPONENT
2 (CED) Connector
CONT EN+
Note 12
CR1*
Kinetix 6000 (460V) Follower IAM are shown.
IMPORTANT Use a push-button circuit (instead of a SPST toggle switch) in series with the contactor enable string
(between the 8720MC-RPS and Kinetix 6000) to allow a drive fault to remove the DC bus power, and
Non-Kinetix 6000 Leader Drive with Single Follower IAM Power Diagram
to prevent the drive from applying DC bus power without the user’s input after clearing a drive fault.
In the figure below, the 8720MC-RPS regenerative power supply and
B-9
Figure B.7
Leader IAM with Multiple Follower IAM Diagram
To Follower
DC Bus Connections
To Follower
Control Power
Connections
Kinetix 6000
COMMON BUS LEADER IAM
2094-ACxx-Mxx or -BCxx-Mxx
Bonded Cabinet
Ground Bus *
Power Rail
Ground Stud Note 9
Cable Shield
Clamp
Single-Phase Input 1
CTRL 2 Control Power
95-264V ac RMS 2 (CPD) Connector
Notes 1, 2 CTRL 1 4
Note 4 Three-Phase
3
1 Motor Power W Motor Power
DC- 2
2 (MP) Connector V Connections
DC+ DC Bus 1 Note 14
3 and U
4 3-Phase
Three-Phase Input from LIM L3 Input (IPD)
or input power contactor (M1) 5 Connector
195-264V ac RMS L2
6 6
or 324-528V ac RMS L1 MBRK -
Notes 1, 2, 7, 8 5
MBRK +
4
COM
Motor/Resistive 3
Brake (BC) Connector PWR
2
DBRK -
1
DBRK +
1
CONT EN- Contactor Enable
2 (CED) Connector
CONT EN+
Note 12
To Follower
Control Circuit
Connections
Wire the Leader and Follower IAM
contactor enable terminals in series
with the safety control string or LIM I/O.
Kinetix 6000
COMMON BUS FOLLOWER IAM
2094-ACxx-Mxx or -BCxx-Mxx
Bonded Cabinet
Ground Bus *
Power Rail
Ground Stud Note 9
Cable Shield
Clamp
Note 4
From Leader 1
CTRL 2 Control Power
Control Power 2 (CPD) Connector
Connections CTRL 1 4
Note 4 Three-Phase
3
From Leader 1 Motor Power W Motor Power
DC- (MP) Connector 2 Connections
DC Bus Connections 2 DC Bus V
DC+ 1 Note 14
3 and U
DC Bus Fusing * 4 3-Phase
Note 2 N.C. L3 Input (IPD)
5 Connector
N.C. L2
6 6
N.C. L1 MBRK -
5
MBRK +
4
COM
Motor/Resistive 3
Brake (BC) Connector PWR
2
DBRK -
1
DBRK +
1 Contactor Enable
CONT EN-
2 (CED) Connector
CONT EN+
Note 12
Kinetix 6000
COMMON BUS FOLLOWER IAM
2094-ACxx-Mxx or -BCxx-Mxx
Bonded Cabinet
Ground Bus *
Power Rail
Ground Stud Note 9
Cable Shield
Clamp
1
CTRL 2 Control Power
2 (CPD) Connector
CTRL 1 4
3 Three-Phase
1 Motor Power W Motor Power
DC- 2
2 (MP) Connector V Connections
DC+ DC Bus 1 Note 14
3 and U
DC Bus Fusing * 4 3-Phase
Note 2 N.C. L3 Input (IPD)
5 Connector
N.C. L2
6 6
N.C. L1 MBRK -
5
MBRK +
4
COM
Motor/Resistive 3
Brake (BC) Connector PWR
2
DBRK -
1
DBRK +
From Leader
Control Circuit 1
CONT EN- Contactor Enable
Connections 2 (CED) Connector
CONT EN+
Note 12
In the figure below, a non-Kinetix 6000 leader drive and Kinetix 6000
Follower IAM are shown.
Figure B.8
Non-Kinetix 6000 Leader Drive with Single Follower IAM Power Diagram
Kinetix 6000
COMMON BUS FOLLOWER IAM
Bonded Cabinet 2094-ACxx-Mxx or -BCxx-Mxx
Ground Bus*
Power Rail
Non-Kinetix 6000 Ground Stud Note 9
COMMON BUS LEADER Cable Shield
Bonded Cabinet Clamp
Ground Bus*
Ground Stud Single-Phase Input 1
CTRL 2 Control Power
95-264V ac RMS 2
CTRL 1 (CPD) Connector
Notes 1, 2 4
Three-Phase
3
1 Motor Power W Motor Power
DC Bus DC- Pre-charge DC- DC Bus (MP) Connector 2 Connections
Circuitry* 2 Connections V
Connections DC+ DC+ 1 Note 14
3 U
DC Bus Fusing* 4 Ground
N.C. L3 3-Phase
5
N.C. L2 Input (IPD)
6 Connector 6
N.C. L1 MBRK -
5
MBRK +
Three-Phase Input L3 4
COM
from LIM or input L2 Motor/Resistive 3
power contactor (M1) Brake (BC) Connector PWR
Notes 1, 2, 7, 8 L1 2
DBRK -
1
DBRK +
1
CONT EN- Contactor Enable
2 (CED) Connector
CONT EN+
Note 12
DRIVE OK-
Contactor Enable * INDICATES USER -SUPPLIED COMPONENT
DRIVE OK+
Shunt Module Interconnect In the figure below, the Kinetix 6000 Shunt Module is shown wired for
internal shunt operation. This is the factory default jumper setting.
Diagrams
Figure B.9
Internal Shunt Module Interconnect Diagram
Kinetix 6000
SHUNT MODULE
2094-BSP2
3
External Shunt Resistor COL
2
(RC) Connector INT
1
DC+
2
External Thermal Switch TS2 1
(TS) Connector TS1
In the figure below, the Kinetix 6000 shunt module is shown wired
with an external passive shunt resistor. Refer to Appendix C for a list
of external shunt resistor catalog numbers available for the Kinetix
6000.
Figure B.10
External Passive Shunt Module Interconnect Diagram
3
External Shunt Resistor COL COL
2
(RC) Connector INT Resistor
1 DC+
DC+
In the figure below, the Kinetix 6000 IAM (without the LIM) is shown
wired with a Bulletin 1336 external active shunt. Refer to Appendix C
for a list of external shunt resistor catalog numbers available for the
Kinetix 6000.
Figure B.11
External Active Shunt Module Interconnect Diagram
Contactor Enable 1
CONT EN- Refer to Attention statement (Note 11)
(CED) Connector 2
CONT EN+ CR1*
Note 12
CR1*
M1* 24V ac/dc
or
CR1* 120V ac
50/60 Hz
* INDICATES USER SUPPLIED COMPONENT START* STOP*
Notes 7, 12
Kx005 or Kx010 Input current requirement to power logic for fault 0.05A
contact operation.
KB050 Input current requirement to power fan and logic for 0.65A
fault contact operation.
In the figure below, the Kinetix 6000 IAM is shown (without a LIM)
wired with a Bulletin 1336 external active shunt (master) and two
slave units. Refer to Appendix C for a list of external shunt resistor
catalog numbers available for the Kinetix 6000.
Figure B.12
External Active Shunt Module Interconnect Diagram
1
Contactor Enable CONT EN- EXTERNAL ACTIVE SHUNT
(CED) Connector 2
CONT EN+ RESISTOR (1336-MOD-Kxxxx)
Note 12
1
(+) Slave In
Notes 7, 12 2
(–) Slave In
3
STOP* START* (–) Master Out
24V ac/dc CR1* 4
or (+) Master Out
120V ac 5
M1* (–) DC Bus
50/60 Hz CR1* TB1
CR1* 6
(+) DC Bus
Note 4
Refer to Attention statement (Note 11)
1
TB3
2
3
Fault Relay Note 20
4
Shunt chassis 1336 Slave
ground screw
Single-Phase Input 1
115V ac RMS TB3
2
50/60 Hz
Note 4 3
Input Fusing* Fault Relay Note 20
Note 19 4
Shunt chassis 1336 Slave
ground screw
* INDICATES USER SUPPLIED COMPONENT
Resistive Brake Module An example diagram of the Resistive Brake Module (RBM) wired to a
Kinetix 6000 IAM/AM is shown in the figure below. Refer to Appendix
Interconnect Diagrams C for a list of RBM catalog numbers available for the Kinetix 6000.
Figure B.13
Resistive Brake Module Interconnect Diagram
Safety
Relay * Safety Relay Monitor *
or
PLC Input Device * * INDICATES USER-SUPPLIED COMPONENT
Gate Interlock*
Input Safety Output Time Delay
or
Channel Channel Channel
Light Curtain Device*
Note 23
Notes 7, 12
STOP* START*
24V AC/DC CR1*
or
120V AC, M1*
50/60 HZ CR1*
CR1*
Refer to Attention statement (Note 11)
AM/Motor Interconnect This section contains the motor power, brake, and feedback signal
interconnect diagrams between an Axis Module and MP-Series,
Diagrams 1326AB, or F-, H-, N-, and Y-Series servo motors.
In the figure below, the Kinetix 6000 axis module (460V) is shown
connected to MP-Series Low Inertia and Integrated Gear (460V)
motors.
Figure B.14
Axis Module to MP-Series (460V) Motor Interconnect Diagram
Cable Shield
0 Clamp
Note 9
1
4 Green/Yellow D Motor Feedback
2
3 1/Blue C W (MF) Connector
3 Motor Power W GND
(IAM/AM)
4 (MP) Connector 2 2/Black B V
V Three-Phase
5 1 3/Brown A U Motor Power A BLACK SIN+ 1
6 Motor Feedback U WHT/BLACK SIN- 2
2090-XXNPMP-xxSxx
B
7 (MF) Connector COS+
Motor Power Cable C RED 3
8 Note 14
D WHT/RED COS- 4
9
10 Motor Feedback E GREEN DATA+ 5
11 Motor/Resistive 2090-UXNBMP-18Sxx Brake Cable F WHT/GREEN DATA- 10
12 Brake (BC) Connector Note 14
14
K GRAY +5VDC
13 6 Black C BR- L WHT/GRAY ECOM 6
MBRK -
14 5 White A Motor Brake N +9VDC 7
MBRK + BR+ ORANGE
15 R WHT/ORANGE TS+ 11
4
COM User Supplied Thermostat
3 24V dc (1.2A max.) S Refer to Low Profile Connector
PWR illustration (lower left)
2 BR- for proper grounding technique.
DBRK - Resistive Brake P
1 BR+ Connections
DBRK +
2090-XXNFMP-Sxx
(flying-lead) Feedback Cable
Notes 14, 15, 17
In the figure below, the Kinetix 6000 axis module (230V) is shown
connected to MP-Series Low Inertia (MPL) and Integrated Gear (MPG)
230V servo motors.
Figure B.15
Axis Module to MP-Series (230V) Motor Interconnect Diagram
Cable Shield
Clamp
0 Note 9
1
4 Green/Yellow D
2
3 1/Blue C W Motor Feedback
3 Motor Power W GND
(MF) Connector
4 (MP) Connector 2 2/Black B V
V Three-Phase (IAM/AM)
5 1 3/Brown A U Motor Power
6 U SIN+ 1
A BLACK
7 2090-XXNPMP-xxSxx
Motor Feedback Motor Power Cable B WHT/BLACK SIN- 2
8 (MF) Connector Note 14 COS+
C RED 3
9
D WHT/RED COS- 4
10
11 Motor/Resistive 2090-UXNBMP-18Sxx Brake Cable E GREEN DATA+ 5
Brake (BC) Connector Motor Feedback
12 Note 14 F WHT/GREEN DATA- 10
13 6 Black C BR- K GRAY +5VDC 14
MBRK -
14 5 White A Motor Brake L WHT/GRAY ECOM 6
MBRK + BR+
15 N ORANGE – 7
4
COM User Supplied R WHT/ORANGE TS+ 11
3 24V dc (1.2A max.)
PWR Thermostat
2 BR- S Refer to Low Profile Connector
DBRK - Resistive Brake illustration (lower left)
1 BR+ for proper grounding technique.
DBRK + Connections P
2090-XXNFMP-Sxx
(flying-lead) Feedback Cable
Notes 14, 15
Motor Feedback
MPL-A (230V) SERVO MOTORS (MF) Connector
WITH INCREMENTAL FEEDBACK (IAM/AM)
D A BLACK AM+ 1
B WHT/BLACK AM- 2
Grounding Technique for C W GND
Feedback Cable Shield B V C RED BM+ 3
Low Profile Connector Three-Phase D WHT/RED BM- 4
(2090-K6CK-D15M shown) A U Motor Power
E GREEN IM+ 5
F WHT/GREEN IM- 10
Motor Feedback K GRAY +5VDC 14
L WHT/GRAY ECOM 6
Clamp N ORANGE – 7
Exposed shield secured R WHT/ORANGE TS+ 11
under clamp.
Thermostat
Clamp screws (2) S BLUE –
Turn clamp over to hold C BR- T WHT/BLUE S1 12
small cables secure.
Motor Brake U YELLOW S2 13
A BR+ V WHT/YELLOW S3 8
P
Refer to Low Profile Connector
illustration (lower left)
for proper grounding technique.
2090-XXNFMP-Sxx
(flying-lead) Feedback Cable
Notes 14, 15
In the figure below, the Kinetix 6000 axis module is shown connected
to MP-Series Food Grade (MPF) and MP-Series Stainless Steel (MPS)
servo motors.
Figure B.16
Axis Module to MP-Series Food Grade and Stainless Steel Motors
2090-XXNFMF-Sxx
(flying-lead) Feedback Cable
Notes 14, 15
In the figure below, the Kinetix 6000 axis module (230V) is shown
connected to TL-Series (230V) servo motors.
Figure B.17
Axis Module to TL-Series (230V) Motor Interconnect Diagram
In the figure below, the Kinetix 6000 axis module (460V) is shown
connected to 1326AB-Bxxxx (460V) servo motors.
Figure B.18
Axis Module to 1326AB Motor Interconnect Diagram
Cable Shield
0 Clamp
Note 9
1
4 Green/Yellow D Motor Feedback
2
3 1/Blue W (MF) Connector
3 Motor Power W C GND (IAM/AM)
4 (MP) Connector 2 2/Black B V
V Three-Phase
5 1 3/Brown A U A BLACK SIN+ 1
6 U Motor Power WHT/BLACK 2
B SIN-
2090-XXNPMP-xxSxx
7 Motor Feedback COS+ 3
Motor Power Cable C RED
8 (MF) Connector Note 14 WHT/RED COS-
D 4
9
10 Motor Feedback E GREEN DATA+ 5
11 Motor/Resistive 2090-UXNBMP-18Sxx Brake Cable F WHT/GREEN DATA- 10
12 Brake (BC) Connector Note 14
K – 14
GRAY
13 6 Black C BR- L WHT/GRAY ECOM 6
MBRK -
14 5 White A BR+ Motor Brake N ORANGE +9VDC– 7
15 MBRK +
4 R WHT/ORANGE TS+ 11
COM User Supplied Thermostat
3 24V dc (1.2A max.) S
PWR
2 BR- Refer to Wire Low Profile
DBRK - Resistive Brake P Connectors beginning on page 3-45
1 BR+ Connections for proper grounding technique.
DBRK +
2090-XXNFMP-Sxx
(flying-lead) Feedback Cable
Note 14, 15
1
Wiring the thermal switch on 1326AB (resolver-based) motors requires the use of the Low Profile connector kit
(2090-K6CK-D15MF) and wire extension to the power connector. Pins 16, 17, and S are filtered to prevent noise
transmission back to the drive. Refer to Wire Low Profile Connectors beginning on page 3-45 for wiring
instructions and a diagram.
In the figure below, the Kinetix 6000 axis module (230V) is shown
connected to H- and F-Series (230V) servo motors.
Figure B.19
Axis Module to H/F-Series Motor Interconnect Diagram
Cable Shield
0 Clamp
Note 9
1
4 Green/Yellow D
2
3 1/Blue C W Motor Feedback
3 Motor Power W GND
(MF) Connector
4 (MP) Connector 2 2/Black B V
V Three-Phase (IAM/AM)
5 1 3/Brown A U Motor Power
6 U A BLACK AM+ 1
2090-XXNPH/HF-xxSxx
7 Motor Power Cable B WHT/BLACK AM- 2
8 Motor Feedback Note 14
C RED BM+ 3
9 (MF) Connector
D WHT/RED BM- 4
10
11 9101-0330 Brake Cable Connector Kit E GREEN IM+ 5
Motor Feedback
12 Note 14 F WHT/GREEN IM- 10
13 6 Black B BR- R WHT/BROWN TS+ 11
MBRK -
14 5 White A Motor Brake P BROWN S3 8
BR+
15 MBRK +
K
4 GRAY +5VDC 14
COM User Supplied J
3 24V dc (1.2A max.) L
PWR WHT/GRAY ECOM 6
2 BR- M
DBRK - Resistive Brake
1 BR+ N BLUE S2 13
DBRK + Connections
T WHT/BLUE S1 12
Motor/Resistive H VIOLET –
Brake (BC) Connector Thermostat
S WHT/VIOLET TS- 6
Refer to Low Profile Connector
illustration (below)
for proper grounding technique.
2090-XXNFHF-Sxx
(flying-lead) Feedback Cable
Note 14, 15
Clamp
Exposed shield secured
under clamp.
Clamp screws (2)
Turn clamp over to hold
small cables secure.
In the figure below, the Kinetix 6000 axis module (230V) is shown
connected to N-Series (230V) servo motors.
Figure B.20
Axis Module to N-Series Motor Interconnect Diagram
Cable Shield
0 Clamp
Note 9 E N/C
1
4 Green/Yellow D
2
3 1/Blue C W Motor Feedback
3 Motor Power W GND
(MF) Connector
4 (MP) Connector 2 2/Black B V
V Three-Phase (IAM/AM)
5 1 3/Brown A U Motor Power
6 U A BLACK AM+ 1
2090-XXNPN-xxSxx
7 Motor Power Cable B WHT/BLACK AM- 2
8 Motor Feedback Note 14
C RED BM+ 3
9 (MF) Connector
D WHT/RED BM- 4
10
11 9101-1698 Brake Cable Connector Kit E GREEN IM+ 5
Motor Feedback
12 Note 14 F WHT/GREEN IM- 10
13 6 Black B BR- R WHT/BROWN TS+ 11
MBRK -
14 5 White A Motor Brake V BROWN S3 8
BR+
15 MBRK +
K
4 GRAY +5VDC 14
COM User Supplied C N/C J
3 24V dc (1.2A max.) L
PWR WHT/GRAY ECOM 6
2 BR- M
DBRK - Resistive Brake
1 BR+ U BLUE S2 13
DBRK + Connections
T WHT/BLUE S1 12
Motor/Resistive H VIOLET –
Brake (BC) Connector Thermostat
S WHT/VIOLET TS- 6
Refer to Low Profile Connector
illustration (below)
for proper grounding technique.
2090-XXNFN-Sxx
(flying-lead) Feedback Cable
Note 14, 15
Clamp
Exposed shield secured
under clamp.
Clamp screws (2)
Turn clamp over to hold
small cables secure.
In the figure below, the Kinetix 6000 axis module (230V) is shown
connected to Y-Series (230V) servo motors.
Figure B.21
Axis Module to Y-Series Motor Interconnect Diagram
Cable Shield
0 Clamp
Note 9
1 4 Green/Yellow 4
2 Motor Feedback
3 3/Black 3 W GND
3 Motor Power W (MF) Connector
4 (MP) Connector 2 2/Black 2 V (IAM/AM)
V Three-Phase
5 1 1/Black 1 U Motor Power
6 U 9 BLACK AM+ 1
7 Motor Feedback 10 WHT/BLACK AM- 2
8 (MF) Connector Pigtail
2090-XXNPY-xxSxx 11 RED BM+ 3
9 Motor Power and Brake Cable Motor 12 WHT/RED BM- 4
Note 14
10 Feedback
13 GREEN IM+ 5
11
14 WHT/GREEN IM- 10
12 Pigtail
Black 9 BR- 15 WHT/BLUE S1 12
13 Motor
14 Motor/Resistive 7 17 BLUE S2 13
Black BR+ Brake
15 Brake (BC) Connector 8
19 BROWN S3
6 – WHT/BROWN –
MBRK -
5 22 GRAY +5VDC 14
MBRK +
4 23 WHT/GRAY ECOM 6
COM User Supplied 24 DRAIN
3 24V dc (1.2A max.)
PWR
2 Refer to Low Profile Connector
BR- illustration (below)
DBRK - Resistive Brake
1 for proper grounding technique.
BR+ Connections
DBRK +
2090-XXNFY-Sxx
(flying-lead) Feedback Cable
Notes 14, 15, 16
Clamp
Exposed shield and drain wire
secured under clamp.
Clamp screws (2)
Turn clamp over to hold
small cables secure.
Controlling a Brake The relay output of the Kinetix 6000 (MBRK± BC-5 and -6) is suitable
for directly controlling a motor brake, subject to the relay voltage limit
Example of 30V dc, and the relay current limit as shown in the table below.
The following tables list Allen-Bradley motors and brake coil current
ratings.
Coil Currents Rated at < 1.0A Coil Currents Rated at < 1.0A
Compatible Brake Motors Coil Current Compatible Brake Motors Coil Current
F-4030, -4050, and -4075 0.69A MPL/MPF/MPS-x310, -x320, -x330 1 0.50A
1
H-3007 and -3016 0.60A MPL-x420, -x430, -x4520, -x4530, -x4540
0.64A
H-4030, -4050, and -4075 0.69A MPF-x430, -x4530, -x4540 1
N-2302, and -2304 0.28A MPG-x004 1 0.33A
N-3406, -3412, -4214, and -4220 0.36A MPG-x010 1
0.45A
N-5630, -5637, and -5647 0.71A MPG-x025 1
Y-1002 and -1003 0.26A MPG-x050 1 0.50A
Y-2006 and -2012 0.31A MPG-x110 1 1.0A
Y-3023 0.37A
TL-A110P-H, -A120P-H, and -A130P-H 0.208A
TL-A220P-H and -A230P-H 0.375A 1326AB-B4xxx 0.88A
TL-A2530P-H and -A2540P-H 0.396A
TL-A410P-H 0.746A
1
Applies to 230V and 460V motors.
Coil Currents Rated > 1.0A and ≤1.3A Coil Currents Rated > 1.0A and ≤1.3A
Compatible Brake Motors Coil Current Compatible Brake Motors Coil Current
F-6100, -6200, and -6300 1.30A MPL-x520, -x540, -x560, -x580 1
1.05 to 1.28A
MPF-B540
H-6100, -6200, and -6300 1.13A
1326AB-B5xxx, and -B7xxx 1.20A
1Applies to 230V and 460V motors.
Coil Currents Rated > 1.3A and ≤3.0A Coil Currents Rated > 1.3A and ≤3.0A
Compatible Brake Motors Coil Current Compatible Brake Motors Coil Current
MPL-B640, -B660, -B680, -B860, -B880,
H-8350 and -8500 2.20A 1.91 to 2.19A
-B960, -B980
Figure B.22
Example Configuration Controlling a Motor Brake
Kinetix 6000
IAM (inverter) or AM
Note 13
6
MBRK -
5 CR1
MBRK +
4
COM User Supplied
3 24V dc (3.0A max.)
PWR
2
DBRK -
1 BR-
DBRK +
CR1 BR+ Brake
Motor/Resistive 1 SERVO
Brake (BC) Connector Feedback MOTOR
Power
1
For Motor/Resistive Brake (BC) connector specifications, refer to Motor/Resistive Brake Relay on page 2-15.
PWR U V W
System Block Diagrams
DBRK MBRK
Motor Shield
FUSE_OK
Figure B.23
DC+
Common Mode
Choke
(460V only)
Inverter Block Diagram
POWER
RAIL DC-
SYSOK
Inverter Section Shunt Circuit
CONV_ID (5)
CTRL 1 (460V only)
SMPS
GSHUNT (2)
+/-12V (Control)
CTRL 2
IAM/AM Inverter Block Diagram
DC+
DCL1 DCL2
Common Bus
Three-Phase Power Connections DC-
AC Input DC+
L1
L1
Interconnect Diagrams
CHASSIS
L2 DC Link
Gnd Flt CT
Vcc
Ground Jumper 4 120K Shunt Circuit 2 Vsns
CONV_OT
Figure B.24
95C POWER
Chassis RAIL
CTRL-
DC+
DC-
Control Power CTRL+
Converter Block Diagram
AC Input
CTRL1
SYS_OK
CTRL2
EMC Filter1 GSHUNT
IAM Converter Block Diagram
Control Power
Loss Detector
DROK/
CONT_EN Rectifier Circuit 2
CONT_EN1
1
CONT_EN2 EMC filter present only on 460V converters.
2
Rectifier and shunt circuits present only on 230V converters.
3
Internal DC link inductor present on 460V converters.
Connectors for external DC link inductor present on 230V
converters.
4
Ground jumper shown in factory default position (grounded
facility power).
Interconnect Diagrams B-29
The Kinetix 6000 Safe-Off drives ship with the wiring header and
motion allowed jumper installed, as shown in the figure below. With
the motion allowed jumper installed, the safe-off feature is not used.
Figure B.25
Safe-Off Feature Block Diagram
Safe-Off Option
Safe-Off (SO) Gate Control
9-pin Connector Power Supply
K1-C
8 +24V
9 +24V_COM
3 FDBK1+
4 FDBK1-
K1-A
7 ENABLE1+
K1 Gate Control
6 ENABLE- Safety Monitor
K2 uC Circuit (CCP)
5 ENABLE2+
K2-A
1 FDBK2+
2 FDBK2-
SM Block Diagram
Figure B.26
Shunt Module Block Diagram
DC+
Internal
or External
Shunt
Resistor
POWER
RAIL DC-
SYSOK
Shunt Circuit
CTRL 1 SMPS
GSHUNT (2)
+5V (Control)
CTRL 2 +/-15V (IGBT)
24V (Control)
Chassis
Interface PCB
OPL
OPL
1 CONSTAT_12
1 Interface PCB
2 L3' CONSTAT_22
2
3 L2' CONSTAT_32
3 24V Status LED
4 L1' CONSTAT_54 IOL: STATUS I/O
4 IOL
COIL_A2 IOL Pin 1 IO_PWR1
OPL: VAC LOAD Pin 2 IO_COM1
1 1
Pin 1 PE N/C 2 2 Pin 3 IO_PWR1
COIL_E2
Pin 2 L3' 2 4 6 12 22 32 42 54 A2 E2 3 Pin 4 IO_COM1
COIL_E1
Pin 3 L2' E1 4 Pin 5 IO_PWR1
CR1 5 Pin 6
Interconnect Diagrams
4
L1 1 2 Single Phase, 1-Stage 3 Pin 3 AUX1_L1
14
L2 Line Filter (230VAC) 2 3 Pin 2
1 2 AUX2_L2
L2 3 4 1
L1 1 3 L1' 2 Pin 1 AUX2_L1
3 4 CTRL1
L2 2 4 L2'
5 PE CTRL2 1
OPL
OPL
1 CONSTAT_12
1 Interface PCB
2 L3' CONSTAT_22
2
3 L2' CONSTAT_32 24V Status LED
3
4 L1' CONSTAT_54 IOL IOL: STATUS I/O
4
COIL_A2 IOL Pin 1 IO_PWR1
OPL: VAC LOAD 1 Pin 2 IO_COM1
1
N/C 2 2 Pin 3 IO_PWR1
Pin 1 PE COIL_E2
2 4 6 12 22 32 42 54 A2 E2 3 Pin 4 IO_COM1
Pin 2 L3' COIL_E1
E1 4 Pin 5 IO_PWR1
Pin 3 L2' CR1 100-JE 5 Pin 6 IO_COM1
Pin 4 L1' CONSTAT_54
6 Pin 7 COIL_E1
1 3 5 11 21 31 41 53 A1 A1 CONSTAT_32
7 Pin 8 COIL_E2
IPL CONSTAT_22
IPL N/C 8
CB1 CONSTAT_12 Pin 9 ALRM_M
1 9
1 ALRM_COM Pin 10 SHIELD
10
2 L1 1 2 ALRM_B Pin 11 ALRM_B
11
2 COIL_E1 Pin 12
L2 3 4 12 ALRM_COM
3 CONSTAT_53 CONSTAT_53
3 13 Pin 13 CONSTAT_11
4 L3 5 6 CONSTAT_31 CONSTAT_31
14 Pin 14 CONSTAT_12
4 CONSTAT_21 CONSTAT_21
15 Pin 15
Figure B.28
Interface PCB
OPL
OPL
1 CONSTAT_12
1 Interface PCB
2 L3' CONSTAT_22
2
3 L2' CONSTAT_32 24V Status LED
3
4 L1' CONSTAT_54 IOL IOL: STATUS I/O
4
COIL_A2 IOL Pin 1 IO_PWR1
OPL: VAC LOAD 1 Pin 2 IO_COM1
1
Pin 1 PE N/C 2 2 Pin 3 IO_PWR1
COIL_E2
Pin 2 L3' 2 4 6 12 22 32 42 54 A2 E2 3 Pin 4 IO_COM1
COIL_E1
E1 4 Pin 5 IO_PWR1
Pin 3 L2'
CR1 5
Interconnect Diagrams
IPL
18
1 2 Pin 10 N/C
26
COIL_A1
19
10
Pin 25 IO_PWR
Pin 26 IO_PWR
Single-Phase, 1-Stage
Line Filter (230VAC)
1 2
IO_PWR
L1 L1' L1 24+
3 4 6A Power Supply IO_COM
L2 L2' L2 24-
PE PSL
PE
CB3 1 PSL: I/O 24V DC OUTPUT
PS2
LF2
2 Pin 1 MBRK_PWR
MBRK_PWR Pin 2 MBRK_COM
L1 24+ 3 Pin 3 MBRK_PWR
2A Power Supply MBRK_COM Pin 4 MBRK_COM
L2 24- 4
PE
PS1
Interconnect Diagrams
CPL
CPL: CONTROL POWER
1 2 L2/N
1 Pin 1 L2/N
3 4 L1 Pin 2 L1
2
CB2
B-33
Pin 1 PE
CONSTAT_22
Pin 2 L3'
OPL Pin 3 L2' CONSTAT_32 24V Status LEDs
Pin 4 L1'
1
CONSTAT_42
L3_OUT
2
L2_OUT COIL_A2
3
L1_OUT
4
2 4 6 12 22 32 42 A2
IOL: STATUS I/O
CR1 D1 Pin 1 N/C
IPL: VAC LINE INPUT 100S-C85 Pin 2 N/C
Pin 4 PE Pin 3 N/C
5 31 Pin 4 COIL_A2
Pin 3 L3 1 3 11 21 41 A1
Interconnect Diagrams
Pin 5 N/C
Pin 2 L2
IOL Pin 6 CONSTAT_12
Pin 1 L1 COIL_A1
Pin 7 CONSTAT_22
L1_IN 1 2 CONSTAT_31
26 Pin 10 N/C
CONSTAT_31
1 L1 L1' Pin 11 N/C
CONSTAT_22
L2_IN 3 4 CONSTAT_21 Pin 12 N/C
2 CONSTAT_21
L2 L2' Pin 13 COIL_A1
CONSTAT_12
3 5 6 Pin 14
Figure B.31
COIL_A1
19
10
Pin 25 IO_PWR
Pin 26 IO_PWR
Single-Phase, 1-Stage
Line Filter (230VAC)
1 2
IO_PWR
L1 L1' L1 24+
3 4 6A Power Supply IO_COM
L2 L2' L2 24-
460V to 230V PE PSL
750VA XFMR PE
CB3 1 PSL: I/O 24V DC OUTPUT
PS2
TX1 LF2
2 Pin 1 MBRK_PWR
MBRK_PWR Pin 2 MBRK_COM
L1 24+ 3 Pin 3 MBRK_PWR
2A Power Supply MBRK_COM Pin 4 MBRK_COM
L2 24- 4
PE
PS1
CPL
CPL: CONTROL POWER
1 2 L2/N
1 Pin 1 L2/N
3 4 L1 Pin 2 L1
2
CB2
Drive Connections RBM Enclosure Motor Connections
(TB1) Connector (TB2) Connector
CR1
GROUND 4 4 GROUND
3 1 2
W DRIVE 3 W MTR
2 3 4
V DRIVE 2 V MTR
1 5 6
U DRIVE 1 U MTR
W BRAKE 11 12
V BRAKE 21 22
Figure B.32
I/O Connections
D1 (TB3) Connector
RBM Block Diagrams
R1 R2 R3 1 TS_21
2 TS_22
T1 (fault) 3 CONSTAT_41
RBM Block Diagram (2090-XB33-xx)
4 CONSTAT_42
5 SHIELD
T2 (warning)
6 COIL_A1
7 COIL_A2
8 SHIELD
Interconnect Diagrams
B-35
4 GROUND
3 1 2
W DRIVE 3 W MTR
3 4
CONSTAT_42
T2 (warning)
5 SHIELD
6 COIL_A1
7 COIL_A2
8 SHIELD
Interface PCB
Appendix C
Chapter Objectives This appendix lists the Kinetix 6000 drives and accessory items in
tables by catalog number providing detailed descriptions of each
component. This appendix describes catalog numbers for:
Integrated Axis Modules Use the following table to identify Kinetix 6000 230V Integrated Axis
Modules with converter power ratings of between 3.0 kW to 23.0 kW.
Use the following table to identify Kinetix 6000 460V Integrated Axis
Modules with converter power ratings of between 6.0 kW to 45.0 kW.
Axis Modules Use the following table to identify Kinetix 6000 230V Axis Modules
with output current ratings of between 5A and 49A (continuous).
Use the following table to identify Kinetix 6000 460V Axis Modules
with output current ratings of between 4A and 49A (continuous).
Shunt Module Use the following table to identify the Bulletin 2094 Shunt Module for
your Kinetix 6000 application.
Power Rails Use the following table to identify the Power Rail for your Kinetix
6000 application.
Power Rail Slot Filler Use the following table to identify the Power Rail Slot Filler for your
Kinetix 6000 application.
RSLogix 5000 Software The Kinetix 6000 drives are configured using RSLogix 5000 software.
RSLogix 5000 is a Windows based application that allows drive
configuration to be done off-line and saved to disk.
Line Interface Modules Use the following table to identify the Line Interface Module for your
Kinetix 6000 application.
Line Interface Module, 230V, 20A • 24V dc power output with 8A current capacity 2094-AL09
Line Interface Module, 460V, 30A • Internal Line Filter 2094-BL02
Resistive Brake Modules Use the following table to identify the Bulletin 2090 Resistive Brake
Module for your Kinetix 6000 application.
AC Line Filters Use the following table to identify the Bulletin 2090 AC Line Filter for
your Kinetix 6000 application.
External Shunt Resistor Kits Use the following table to identify the Bulletin 1394 and 1336 External
Shunt Resistor Kit for your Kinetix 6000 application.
Cables Use the following tables to identify motor power, feedback, interface,
and brake cables for your Kinetix 6000 with 230/460V motors. For
standard available cable lengths, refer to the Kinetix Motion Control
Selection Guide (publication GMC-SG001)
IMPORTANT Low Profile connector kits are required for use with
2090-XXNFxx-Sxx. or 2090-CDNFDMP-Sxx feedback
cables.
Mounting Bracket
Use the following table to identify the drive end (mating) connector
kit for your Kinetix 6000 motor feedback connectors. Refer to Chapter
2 for pin, description, and signal information.
The following table lists Amp mating connectors that are not available
from Rockwell Automation. Please contact Amp at 1-800-522-6752 or a
distributor for additional information.
Connector I/O Signals (IOD/IOL) Motor Feedback (MF) Auxiliary Feedback (AF)
Components 26-Pin 15-Pin Male 15-Pin Female
High-Density, D-Shell High-Density, D-Shell High-Density, D-Shell
Mating Connector 748365-1 748364-1 748565-1
Crimp Pin
Contacts 748333-4 1 748333-4 1 748610-4 1
Unshielded
748678-2 748678-1 748678-1
Backshell Kit
Shielded
745172-1 745171-5 745171-5
Backshell Kit
Installation Assistance
Rockwell tests all of its products to ensure that they are fully operational
when shipped from the manufacturing facility. However, if your product is
not functioning and needs to be returned:
United States Contact your distributor. You must provide a Customer Support case
number (see phone number above to obtain one) to your distributor in
order to complete the return process.
Outside United Please contact your local Rockwell Automation representative for
States return procedure.