You are on page 1of 7

DIESEL ENGINE GENERATION APPLICATIONS ON

SHIPS AND MOORED FLOATING FACILITIES


Copyright Material IEEE
PCIC-2008-24

Donald A. Voltz, PE Moni Islam Christopher N. Chaney, PE


Senior Member, IEEE Member, IEEE Mustang Engineering, L.P.
Mustang Engineering, L.P. L-3 Communications 16001 Park Ten Place
16001 Park Ten Place 5700 Citrus Blvd Houston, TX, USA 77084
Houston, TX, USA 77084 New Orleans, LA, USA chris.chaney@mustangeng.com
dvoltz@ieee.org moni.islam@ieee.org

Abstract – The rules and regulations for ships and moored Periodically Unmanned Machinery Space, NVR-Naval Vessel
floating facilities regarding electrical power generation are the Rules, GMDSS-Global Maritime Distress, Safety System,
same with a few exceptions, though the service requirements Main Generation, Auxiliary Generation, and Emergency
are very different. The commonalities of regulation Generation
applicability for different applications along with there
challenges are presented in this paper. I. INTRODUCTION
The Integrated Power System (IPS) with high power and
high voltage for ships and moored floating facilities bring Traditional shipboard electrical power generation and
additional regulation challenges with many unknowns in the distribution systems are for ship service power under normal
electrical generation and power distribution grid. operating conditions and emergency power for emergency
This paper addresses the differences between the situation. The IPS system is required to supply power for
application of diesel engine generators and their affects on the electrical propulsion requirements that is in addition to ship
power distribution systems of ships and floating facilities service power and emergency power.
including the challenges of IPS applications. Moored floating platforms include drilling, production, and
This paper addresses design and regulation issues and pipeline transportation facilities associated with oil and gas
challenges and recommends the following; exploration and production. The floating platforms require
1. Systematic overview of the power system power for topsides process facilities including production and
requirements and their differences. compression and marine facilities included in the hull. At the
2. Systematic overview of the IPS requirements, discretion of the owner, a diesel engine generator can be
applicability of the present rules and regulations. used for services such as auxiliary, black start and emergency
3. Systematic approach to develop awareness in the power. The USCG (United States Coast Guard) requires a
technical community. dedicated source of power for emergency service thus
4. Establish liaison with the authorities having requiring a dedicated diesel engine generator.
jurisdiction of directing, policy making and rule In general, regulations related to high power generation and
implementation. distribution systems for floating platforms are supported by the
5. In view of the above, the IEEE-45 Working Group rules and regulations for ship service power generation due to
should take the lead to develop additional insufficient regulations for high power application.
recommendations, standards for power generation, Reference is made to Figures 1 through 5 for overview of
distribution, and management for ships and moored the electrical power generation for ships and moored floating
floating platforms design in line with industrial platforms. Figures 1 and 2 illustrate the transition of shipboard
practices (for ex. API RP-14F, AFI RP-14FZ, NFPA mechanical propulsion directly connecting the propulsion
70, etc.) and electrical safety requirements. prime mover to the propeller with mechanical shaft. The
6. The Naval Vessel Rules are to be reviewed for electric drive system is shown as the propeller is driven by an
proper application of standard design and electric motor where the prime movers are generating electric
development practices and recommend changes to power for the propulsion motor. Figure 3 is for typical ship
the rules. service power generation for ship service loads and
7. Develop recommended practice to lead Naval Ship emergency generation in case of ship service power failure.
design, commercial ship design and floating platform Figure 4 is for typical electrical propulsion system where in
design. addition to the ship service and emergency power generation,
8. Establish liaison among the regulatory bodies to propulsion power is generated for propulsion loads.
consider new recommendations to IEEE-45 as Figure 5 is for moored floating production platforms,
guides for rule making for commercial ships, naval showing the power generation with two generators for
ships, and floating platforms. production module, compression module and other related
services as topside power, dedicated auxiliary generator
Index Terms – IPS-Integrated Power System, MCR- provides auxiliary power, fire fighting services. The auxiliary
Maximum Continuous Rating of prime mover, ACCU- generator provides marine habitable loads, black start power
and firewater power. Additionally, the platforms require The Ship’s electric power requirements are outlined in A1
dedicated diesel generator for dedicated fire pumps to support for ship service requirements and in A2 for IPS requirements.
fire fighting. This dedicated firewater power distribution
system is completely isolated from the remaining system.
Gen Gen

6.6KV SWITCHBOARD
Prime Mover
Prime Mover
Prime Mover Gen
Gen

Cable
DRIVE DRIVE

Cable
Switchboard

M M
Mechanical Shaft

Cable PROPULSION DRIVE

Drive SHIP SERVICE SWITCHBOARD


480V BUS 120V BUS

Motor
Load
Mechanical Shaft
Power Panel Load MCC TRANSFORMER

Propellor EMERGENCY SWITCHBOARD


Figure-1:Direct Mechanical Drive System
Propellor 120V EMERGENCY BUS 480V EMERGENCY BUS
Figure-2:Electrical Drive System

Load Shore Power


Power Panel
TRANSFORMER EG
Figure-4: Typical Electrical One Line Diagram For IPS System Generation and Distribution
Gen Gen

SHIP SERVICE SWITCHBOARD


A. Ships
480V BUS 120V BUS

The USCG, and ABS (American Bureau of Shipping) rules


and regulations, for electrical power generation are mostly for
ship service electric loads and emergency power
Load
Power Panel Load MCC TRANSFORMER requirements. However, the IPS electrical power generation
and distribution requirements are well beyond the ship service
requirements, and challenges are to understand those
requirements in the context of electrical power generation and
distribution for ship service as well as propulsion power
EMERGENCY SWITCHBOARD
requirements.
120V EMERGENCY BUS 480V EMERGENCY BUS
The ABS has requirements for the electrical power
generation redundancy are known as R1, R1+S, R2, R2+S
etc. and control system related requirements are ACC, ACCU
TRANSFORMER Load Shore Power
etc. [3]
Power Panel EG The MCR (maximum continuous rating) requirements are in
general for direct drive prime movers. The MCR requirements
Figure-3: Typical Electrical One Line Diagram with Ship Service and Emergency Power for electrical power generating prime movers should be
Generation and Distribution different. This is applicable for ships and platforms.
The ship service electric power generation related number
of prime mover requirement falls under N+1 requirements
II. ELECTRICAL LOAD CALCULATION which may not be the optimum solution for IPS type power
CHALLENGES generation and distribution.

The ship service electric load calculation is performed for A1. Ship Service Power:
the operating scenarios such as port loading, ship underway,
cruise, and other special operational loadings, particularly for 1. Ship Service Generator
sizing ship service and emergency generators. 2. Emergency Power
The floating platform electric load calculations are 3. Standby Power
performed for the topside processing modules and hull loads 4. Uninterruptable Power System (UPS)
for at least equal to the highest expected system operating
load. This requirement is met by using all generators or The ship service power is provided to power vital and
sometimes with one additional generator as stand-by. The non-vital electrical equipment onboard a ship. The ship
auxiliary generator size is also calculated for the highest service power requirement is generally at the range of 10
expected load. The emergency generator size is calculated for Megawatts supported by multiple generators. By
100% emergency loads except the duplicate loads. The fire regulation the ship service power must be available for
pump dedicated generator size is also calculated the same vital loads under all operational conditions including the
way. back-out recovery. The emergency generator is provided
to start it and take emergency load under ship service
2
black-out conditions. By regulation, the emergency loads power utilization is considered for 80% maximum
are; (a) Navigation lights, emergency lights, continuous rating of the engine. This is considered MCR
Communication system, daylight signaling light, smoke rating by regulation.
detection, electric whistle, fire detection system, and The electrical propulsion system electrical power is
general alarm, (b) Emergency bilge pump, fire fighting generated by using multiple generators and delivering
system, GMDSS, Navigational equipment, steering gear, power at synchronous speed. Multiple generators can be
vital automation system etc. The UPS is required to used in parallel to meet the load demand. The generators
support automated system and vital system in case of can be added to the service or taken out of service to
temporary loss of power. Refer to figures 1, 2, and 3 for meet the load demand. The generators usually run 90 to
typical service scenario for ship service power generation 95 percent load to meet maximum demand load. For that
and distribution. reason there is no need to use 80% MCR for electric
There are additional requirements for periodically drive prime movers.
unmanned engine room such as ACCU (per ABS) for
normal and alternate UPS power. A5. N+1 Redundancy Requirements: For ship service
power and IPS power N+1 rules are contained in
A2. IPS Power: References [3], [5], [6] and [7]. The N+1 requirement
basically leads to the generator size and number of
1. Main Propulsion Power generator selection, keeping one of the largest
2. Ship Service Power generators in stand-by. The generator rating selection
3. Emergency Power also includes 80% MCR of the prime mover. In addition,
4. Standby power the generator loading requirements are around 90%
5. Uninterruptable Power continuous. This requirement is mainly for periodically
unmanned engine room. This excessive power
The IPS electrical power generation, distribution, and generation requirement leads to oversize generator size.
management for electrical propulsion system is in The total power generation could be reduced
addition to the ship service power and emergency power substantially leading to design optimization.
requirements for ships. There are many variations to the
IPS power requirements. Typical electrical one line A6. Black Starting Of Prime Movers-IPS: “Per ABS
representation is shown in Figure 4. The cruise ship IPS 4-9-4/13.5 [3] for “Automatic Start and Changeover – In
requirement is different from the icebreakers, tankers etc. the event of detecting low or the loss of system pressure
The propulsion power requirement can be at the range of automatic startup of and change the standby pumps,
75 megawatts. The high power requirement leads to which are essential to maintain propulsion machinery, is
voltage level higher than 460V such as 4160V, 6600V, provided.”
11KV etc. These higher voltage power generation and “Per ABS 4-9-3/13/9/1 [3] under ACC/ACCU continuity
distribution leads to electrical system design with many of power it is required that the standby electric power is to
features which are not in the 460V system design be available in no more than 30 seconds.”
requirements. The challenges are namely, number of
generators, HV and LV switchboards, propulsion B. Moored Floating Facilities
transformers, propulsion drives and propulsion motors as
well as maximum continuous rating requirement of the With oil exploration moving farther offshore and production
prime mover, overall ship electrical grounding system, rates increasing a whole new class of facilities with complex
personnel and equipment electrical safety hazard etc. electrical systems with numerous generators have been
developed. A list of those is shown below with their primary
A3. ACC/ACCU REQUIREMENTS: Per ABS, for function and loading based on recent installation of moored
vessels whose propulsion machinery spaces are intended floating platforms in the Gulf of Mexico. Even though these
for centralized control, attended or periodically facilities are stationary (i.e. moored) they are subject to the
unattended are classes as ACC, and ACCU respectively. same USCG regulations [6] and if classed, ABS, DNV, etc
There are strict requirements must be adhered to and rules as those on ships. Any discrepancies or issues with the
specific ABD certification must be obtained. The Ship regulation are noted under the individual generator(s).
propulsion system and associated vital auxiliaries must
have redundant capability to make sure of continuity of B1. Main Generation: As previously mentioned
power under all possible operational condition as well as generation must be provided for the highest expected
emergency condition. The shipboard propulsion system electrical load from the topsides processing modules and
related electric vital system usually known as vital the utility load in the hull. In order to determine the
system, vital auxiliaries, redundant standby vitals and electrical load, a driver study can be conducted to
emergency vitals. The basic classifications are in determine the proper mix of machines used for
section 2. For specific requirements refer to ABS Part 4, mechanical drives and generation [1]. In many cases, an
Chapter 9 [3]. all electric platform case is selected where the total
For US Navy ships refer to appropriate Naval Vessel electrical load generally ranges from 15 megawatts for
Rules [3]. smaller production facilities to a level now approaching
100 megawatts plus for larger production facilities.
A4. MCR: The mechanical drive system, propulsion In order to supply this load, two to six or more main
power is transmitted through mechanical shaft to the power generators are required to meet the electrical
propeller and the propeller speed variation is mainly done demand of the platform depending upon throughput and
by varying the speed of the engine. Due to the power whether the N or N+1 sizing criteria is used. These
generation speed variation and engine performance generators will typically range in size from 10 MVA (8

3
MW) to 45 MVA (36 MW). In either the N or N+1 case, differential in fuel consumption between it and the main
some form of load shedding is required upon loss of one turbine generator, running on diesel. Note: this sizing
of the operating generators to reduce production upsets and economic exercise should be performed early in the
and losses. The most reliable and convenient method is project.
to shed a small number of relatively large loads.
These units are normally dual fueled with the primary B3. Emergency Generator: A diesel engine generator
source being fuel gas and the back-up or secondary is typically used to satisfy the USCG requirement for an
source being diesel. They are usually equipped with an emergency source of power. The purpose of the
automatic transfer system such that the units switch to emergency generator is to provide power to maintain
diesel upon the loss of fuel gas without affecting the critical life support systems in the event that main
platform load. This provides for redundancy at the fuel generation is lost. The loads that are required to be
source level. connected to the Emergency Generator are outlined in
Most of the main turbine-generators are regulatory 46CFR 112.15 [6].
compliant with the exception of the larger aircraft As required by the ABS 4-3-2/5.3 [4], the emergency
derivatives having duel shaft designs. These machines generator is to be sized to 1.0 service factor of the
cannot meet the speed regulation requirements of the connected load. If the connected load is greater than the
regulatory bodies (i.e. USCG 46CFR, ABS MODU, etc.) emergency generator rating, a load shed system is
and require a waiver to be acceptable for marine service. required to shed any non-emergency type loads
One method to prove the speed regulation capability is to connected to the emergency bus. The requirement to
run a parallel test [2]. size the generator at 1.0 service factor of connected load
can lead to a generator sized to approximately 200% to
B2. Auxiliary Generator: An auxiliary generator can 300% of the amount of power required by the demand
be applied at the discretion of the owner or operator of factor of all the loads connected to the emergency bus.
the floating facility. It is not a required regulatory machine In the case of a moored floating platform, the emergency
unless it can be used to supply regulatory loads such as load remains constant whether it’s running in emergency
electric fire pumps. However, it still is required to meet mode or if the platform is operating in normal mode.
the design, installation and testing requirements of the Review of ABS MODU 4-3-2/5.3 [4] should be considered
applicable regulatory standards. This unit can be used to in regard to the emergency load demand factor on
for a different number of loading tasks depending upon modern moored floating platforms.
what mode it is operating. For instance the unit can be With the approval of the USCG, the emergency diesel
used as follows: engine generator can be made to operate in different
modes with the use of a PLC (programmable logic
1) To support full living conditions and power controller). One possible additional use of the emergency
requirements during hookup commissioning, generator is as a hurricane generator to provide power to
installation, start-up and turn around activities. The the control system to remotely monitor the state of the
load requirement would be in the range of 5 to 10 platform, feed main turbine generators’ and large motors’
MW. Multiple units could be required (auxiliary space heaters and other loads such as food preservation
mode) units, etc., during a hurricane event. See section III for
2) To support minimal living conditions and power detailed operation.
requirements during hookup commissioning,
installation, start-up and turn around activities. The B4. Firewater Generator: A diesel engine generator
load requirement would be in the range of 1.5 to 2.5 can be used to satisfy the USCG power requirement for
MW (auxiliary mode) firewater service. The dedicated diesel engine generator
3) To feed electric fire pumps upon loss of main is used to provide power solely to electric motor driven
generation (fire mode) firewater pumps as shown in Figure 5. Typically, the
4) To provide black start capabilities for main Firewater power distribution system is isolated from the
generation (auxiliary/black start mode) Normal Power distribution system to ensure power
5) To provide back-up power to the emergency bus in system integrity.
the cases where the emergency generator fails to
start. This can be accomplished through the power B5. Hurricane Generator: As discussed in section 3
and control system configuration. See Figure 5 as (Emergency Generator), a diesel engine generator can
an example. be used for multiple modes of service. The service
requirements of a hurricane generator are limited to either
Through the use of a PLC, this unit can be made to a hurricane or if the platform has to be completely
operate in different modes thus alleviating the need for abandoned. At the discretion of the owner, the hurricane
additional generators. See Section III for detailed generator can be used as a mode of service on another
operation. diesel engine generator such as an auxiliary generator or
The sizing of this unit can have a significant impact an emergency generator. However, it is imperative to
upon the economics of the facility. If the offshore hook- keep in mind that USCG approval will be required to add
up and commissioning requires a significant time before an additional mode of service to an emergency generator.
start-up the owner or operator has a choice to either run
one of the main turbine generators on diesel or provide B6. Rental Generators: Normally, rental generators
an auxiliary per Item 1 above. A fuel consumption study are not required to meet regulatory installation standards
should be conducted to determine the optimum condition. (i.e. fire and gas, fuel systems, etc.) unless these units
From the results of the study, it can be shown that the will be connected into the power system and used to
auxiliary generator can easily be upsized for the provide additional main power such as that required

4
during offshore installation, hook-up, commissioning and are open and the tie-breaker between buses A and B is
start-up. In these cases, the units are run individually or closed, hence providing a normal power feed to bus A. In this
are run in parallel with either the auxiliary or emergency mode, the two main breakers and the tiebreaker connecting
generation. Under such conditions of use, the regulatory buses B and C are arranged in a main-tie-main automatic
enforcement may require the owner or operator to comply transfer configuration, referred to as a “Secondary Selective
with full regulatory requirements. System”.
The Auxiliary Generator is designed to provide three critical
III. CASE STUDY OF A RECENT MOORED FLOATING services: (1) black start power to start a Turbine Generator,
PRODUCTION FACILITY INSTALLED IN THE GULF (2) power for two electrically driven firewater pumps in the
OF MEXICO event of a fire and (3) auxiliary power to habitable loads in the
event that main generation is un-available.
On today’s modern oil and gas platforms, diesel engine The Auxiliary Generator is rated at 1825kW and provides
generators are commonly used for emergency and back-up sufficient black start power to the auxiliaries of a Turbine
systems including hurricane, firewater, auxiliary and black- Generator in addition to powering marine loads and habitable
start service. With the utilization of a Programmable Logic loads in the living quarters. The auxiliaries required to start a
Controller (PLC), a diesel engine generator can be used for Turbine Generator require approximately 400kW of available
more than one service. The following is a case study on how power. Therefore, the habitable and marine loads have to be
three diesel generators were used on a recent floating limited to no more than approximately 1400kW as to allow the
platform installation in the Gulf of Mexico. 400kW of power required for starting a main Turbine
Generator.
A. Normal Power Distribution System The Auxiliary Generator is also designed to operate in
“Firewater” mode to provide sufficient power to two electrically
The main marine (hull) distribution bus of the floating driven firewater pumps. In the event of a fire call from the
platform is a 4.16kV switchgear line up consisting of three HESS (Hull Emergency Safety System), the auxiliary
main buses, A, B and C normally fed from topsides generation generator automatically starts. There are two inputs that
as shown in Figure 5. Bus A is connected to the Auxiliary initiate a fire call from HESS: low ring main pressure and fire
Generator and busses B and C receive their normal power detected. Even though the Auxiliary Generator starts
from Topsides main generation through two (2) 10 MVA dry- automatically on a fire call from HESS, it does not necessarily
type transformers. In normal operation, the incoming main close to the bus immediately. The auxiliary Generator breaker
breakers are closed, the tie-breaker between buses B and C closes to the bus when dead bus is detected on Bus A. The

Gen Gen

TOPSIDES MAIN GENERATION SWITCHBOARD

13.8kV BUS A BUS B

TOPSIDES COMPRESSION TOPSIDES COMPRESSION


AND PRODUCTION LOADS AND PRODUCTION LOADS

BLACK
START
AG
LOADS

MARINE MAIN DISTRIBUTION SWITCHBOARD

BUS A 4.16kV BUS B BUS C

MARINE LOADS MARINE LOADS


DEDICATED FIRE DEDICATED FIREWATER FWG
WATER PUMPS SYSTEM

EG

DEDICATED FIREWATER
SWITCHBOARD
EMERGENCY 4.16kV
SWITCHBOARD

480V

DEDICATED FIRE
WATER PUMPS
EMERGENCY LOADS

FIGURE 5: TYPICAL ELECTRICAL ONE LINE DIAGRAM FOR MOORED FLOATING PRODUCTION FACILITY

5
philosophy is that Main Generation will continue to provide Generator may also be operated to serve “Hurricane” loads in
power to the fire pumps as long as it is available. In the event the event that the platform is abandoned for a hurricane.
that main generation is not available, the auxiliary generator The Emergency Generator has two distinct modes of
will close to Bus A and the A-B tie breaker will trip to island operation, “Emergency” and “Hurricane” mode. Normal
Bus A ensuring that the Auxiliary Generator is providing operation of the dual mode Emergency/Hurricane Generator
dedicated power to the firewater pumps. is Emergency mode. A key switch wired to the PLC, controls
The Auxiliary Generator is also utilized to provide power to the operating mode of the emergency/hurricane generator.
marine and minimal habitable loads in the event that Main The hurricane mode of operation is only used in the event that
Power Generation is not available. Operation in this the platform is evacuated due to a hurricane. Just prior to
circumstance is referred to as “Auxiliary” mode. The habitable evacuating the platform, the key switch is placed in hurricane
loads include HVAC, normal and emergency lighting and mode.
power to the platform’s control systems. In “Auxiliary” mode, Essentially, modes of operation are defined by the
the A-B and B-C tie-breakers are in the closed position to engine/generator protection that is required in each mode.
distribute power from the Auxiliary Generator to the rest of the According to USCG 46CFR [6], there are only four permissible
electrical distribution system. Once main power generation is shutdowns allowed on an emergency generator: Low Lube
restored, it is imperative to re-connect the Hull’s distribution Oil Pressure, Overspeed, CO2 Release and Differential
system to main power generation. The Auxiliary Generator is Current (86). In addition to the four shut downs in emergency
designed to synchronize across five different points to perform mode, numerous other alarms can be programmed and
a closed transition transfer back to main power generation. monitored in the control room. In Hurricane mode, the
The five points that can be synchronized across are: Auxiliary platform is evacuated (i.e. unmanned). As such, it is
Generator Breaker, A-B tie breaker, Bus B Main Incomer, B-C imperative to utilize a conservative engine/generator
tie breaker and Bus C Main Incomer. protection scheme with more than just the shut downs allowed
As described, the Auxiliary Generator has two distinct by USCG 46CFR [6] in emergency mode.
modes of operation: “Auxiliary” and “Firewater”. Its normal The generator protection relay also has two modes of
mode of operation is “Auxiliary”. A signal from the platform operation, which is controlled from a PLC output. The
control system wired to the PLC, controls the operating mode hurricane mode set-points are programmed to provide
of the auxiliary/firewater generator. Essentially, modes of maximum generator protection. However, the emergency
operation are defined by the engine/generator protection that mode set-points are programmed to provide the most
is required in each mode. According to USCG 46CFR [6], operating time before the machine is irreversibly damaged.
there are only three permissible shutdowns allowed on a
firewater generator: Overspeed, CO2 Release and Differential C. Firewater Pump Power Distribution System
Current (86). In addition to the three shut downs in firewater
mode, numerous other alarms can be programmed and In addition to the normal and emergency distribution
monitored in the control room. The Auxiliary mode of system, there is also a “Dedicated Firewater Pump” power
operation utilizes a conservative engine/generator protection distribution system provided in the Hull. It is completely
scheme with additional shut downs as typically recommended separate from the main and emergency power distribution
by the manufacturer for engine and generator protection. systems. Its only purpose is to provide 4.16kV power to two
The generator protection relay also has two modes of electrically driven firewater pumps. The 4.16kV bus is
operation, which is controlled from a PLC output. The connected to a dedicated firewater pump diesel engine
“auxiliary” mode set-points are programmed to provide generator. In the event of a fire, the generator automatically
maximum generator protection. However, the “firewater” starts and closes to the bus providing power to the firewater
mode set-points are programmed to provide the most pump motors.
operating time for fire fighting before the machine is To allow for periodic maintenance operation, the Firewater
irreversibly damaged. Generator also has a “Manual/Test” mode of operation. In
this mode, maximum generator protection is utilized.
B. Emergency Power Distribution System
IV. CONLUSIONS AND RECOMMENDATIONS
The Emergency 480V distribution system provides power to
USCG 46CFR [6] designated emergency loads as well as This paper addresses some of the challenging design
other loads required for minimal habitability. It is connected to issues between ships and moored floating platforms as
the normal power distribution system through the referenced to regulatory standards.
4.16kV/480V emergency service transformer, which feeds IEEE-45 should take lead for defining these challenging
power from the 4.16kV main distribution system to the issues properly and provide necessary recommendations in
emergency bus. The emergency bus is normally powered view of reliability, redundancy, safety of equipment and
through the emergency service transformer. The Emergency operations.
diesel engine generator is connected to the emergency bus as In a recent shipboard electrical system safety workshop, it
well. In the event of loss of topsides power generation was recommended to initiate a new standard for electrical
resulting in no power on the Emergency bus, a dead bus relay safety (on shipboard). This safety standard should be under
picks up and automatically starts the diesel emergency the leadership of an IEEE-45 related working group.
generator. Once the emergency generator reaches rated Using diesel driven electric generators for multiple tasks
speed and 95% rated voltage, the emergency generator main can improve the operational characteristics and reliability of
breaker closes thus re-establishing power to the emergency auxiliary, black start, fire water, emergency and hurricane
distribution system. The Emergency Generator is capable of electrical systems on moored floating platforms. They also
providing power for at least 18 hours for all emergency loads can provide economic savings during commissioning and start
as required by the USCG 46CFR [6]. The Emergency up.

6
The understanding of regulatory requirements and good Mr. Islam is the “Senior Systems Integration Engineer” for L-
communications with the regulatory agencies are valuable 3Communications.
assets when applying diesel driven electric generation on
ships and moored floating platforms. Donald A. Voltz received his B.S.E.E. from Michigan
Technological University in 1975. He has been with Mustang
V. ACKNOWLEDGEMENTS Engineering L.P. for 10.5 years and is currently a Principal
Electrical Consultant. His responsibilities include the design
The authors would like to acknowledge the contributions of and installation of electrical systems for petroleum and
the following: Emil Shtaygrud of ABS and Mr. Akhter Hossain chemical plants including floating offshore oil and gas
of USCG for directing the authors to appropriate sections of producing platforms. Prior to joining Mustang Engineering
rules and regulations. L.P., he was employed by The Dow Chemical Company for
22½ years. He is a senior member of IEEE. His
VI. REFERENCES memberships in IEEE include the IAS and PES. He presently
serves as Vice Chair of the Marine Industry Subcommittee
[1] Voltz, Donald A., Beaver, Stan C., McDonald Charles, and as Chair of the Standard IEEE 1242. He has presented
“Are All Electric Platforms Viable in the Gulf of Mexico,” several technical papers to the IAS, PES and PCIC. He has
Petroleum and Chemical Industry Technical Conference, served on various API, IEEE, National Electrical Code,
2002, Industrial Applications Society, 49th Annual. Chemical Manufacturers Association and Texas A&M
[2] Voltz, Donald A., Bankes Jr., Gerald, Beaver, Stan C., committees and task groups. He is presently a member of
“Are There Risks Associated with Testing Turbine- API RP-14F and 14FZ (Recommended Practice for Design
Generator Sets Prior to Acceptance? “Mr. Murphy Thinks and Installation of Electrical Systems for Fixed and Floating
So,” Petroleum and Chemical Industry Technical Offshore Petroleum Facilities Using Division or Zone
Conference, 2004, Industrial Applications Society, 51st Classifications), IEEE 45 (Electrical Installations on Ships)
Annual. various Underwriters Laboratory committees and a member of
[3] American Bureau of Shipping (ABS), Naval Vessel Rules National Electrical Code Panel 6. He holds Professional
[4] American Bureau of Shipping (ABS), Rules for Building Engineering Licenses in Alaska and Michigan. He has
and Classing Mobile Offshore Drilling Units (MODU) recently joined BP as a Senior Electrical Engineer in the Gulf
[5] American Bureau of Shipping (ABS), Steel Vessel Rules of Mexico Exploration and Production Unit, Central
[6] Code of Federal Regulation (CFR) Title 46, Shipping, Operations.
Subchapter J Electrical Engineering”
[7] Institute of Electrical and Electronics Engineers (IEEE),
Standard 45-1983, IEEE Recommended Practice for
Electrical Installations on Shipboard
[8] U.S. Department of Transportation United States Coast
Guard Navigation and Inspection Circular No. 2-89,
Guide for Electrical Installations on Merchant Vessels
and Mobile Offshore Drilling Units

VII. VITA

Christopher N. Chaney received his B.S.E.E. from Texas


A&M University in 2002. He has been employed with
Mustang Engineering, L.P. for 6 years and is currently an
Electrical Technical Professional. His responsibilities include
the design and installation of electrical systems for petroleum
and chemical plants including floating offshore oil and gas
producing platforms. He has co-authored and presented one
technical paper to PCIC. He holds professional licenses in
Alaska and Texas.

Moni Islam has thirty-five years diversified electrical


engineering experience in planning, designing, developing,
and implementing new shipbuilding and ship modernization
programs. Mr. Islam was the Chair of IAS-PCIC- Marine
Industry Sub-Committee (2005- 2007), Chair of IEEE
Standard 45 central committee and working group member of
IEEE Standard-P1662, 1709, 1713. He has been involved in
“All Electric Ship” R&D programs for many years and has
authored many technical papers on shipboard electrical
power. Mr. Islam authored “Handbook to IEEE Standard 45, A
Guide to Electrical Installation on Shipboard (August 2004
Release)”. Mr. Islam received his Bachelor of Marine
Engineering Technology with distinction from the Merchant
Marine Academy, Bangladesh in 1969, and Bachelor of
Electrical Engineering Degree with Honors from Fort Schuyler,
Maritime College, and State University of New York in 1975.

You might also like