ATTACHMENTS
Attachment-1 Heat Gain and Heat Loss Calculations
Attachment-2 Air Balance Tables
Attachment-3 Psychometric Diagrams
Attachment-4 Fancoil Selection Tables
Attachment-5 Duct Pressure Loss Calculations
Attachment-6 Boiler Circulation Pump Hydraulic Calculation
Attachment-7 Block A Main Heating Circulation Pump Hydraulic Calculation
Attachment-8 Block C Main Heating Circulation Pump Hydraulic Calculation
Attachment-9 Block B Fancoil Heating Circulation Pump Hydraulic Calculation
Attachment-10 Block B Hygienic AHU Heating Circulation Pump Hydraulic Calc.
Attachment-11 Block B Ventilation AHU Heating Circulation Pump Hydraulic Calc.
Attachment-12 Block B DHW Exchanger Heating Circulation Pump Hydraulic Calc.
Attachment-13 Block D Fancoil Heating Circulation Pump Hydraulic Calculation
Attachment-14 Block A Fancoil Heating Circulation Pump Hydraulic Calculation
Attachment-15 Block A Ventilation AHU Heating Circulation Pump Hydraulic Calc
Attachment-16 Block C Fancoil Heating Circulation Pump Hydraulic Calculation
Attachment-17 Block C Ventilation AHU Heating Circulation Pump Hydraulic Calc
Attachment-18 Block B Fancoil Cooling Circulation Pump Hydraulic Calculation
Attachment-19 Block B Ventilation AHU Cooling Circulation Pump Hydraulic Calc.
Attachment-20 Block B Hygienic AHU Cooling Circulation Pump Hydraulic Calc.
Attachment-21 Block D Fancoil Cooling Circulation Pump Hydraulic Calculation
Attachment-22 Block A Fancoil Cooling Circulation Pump Hydraulic Calculation
Attachment-23 Block A Ventilation AHU Cooling Circulation Pump Hydraulic Calc.
Attachment-24 Block C Fancoil Cooling Circulation Pump Hydraulic Calculation
Attachment-25 Block C Ventilation AHU Cooling Circulation Pump Hydraulic Calc.
1.0 GENERAL INFORMATION
Gdyel Hospital consists of 4 Blocks. Hospital is designed for 240 beds capacity.
Gdyel hospital also includes operation theaters, intensive care, sterilization,
examination rooms, monitoring services (Radiology, IRM, etc.), offices, patient
rooms, laundry, kitchen and restaurant.
1.1 DESIGN PARAMETERS
Design Parameters
Winter Summer
Offices: 21ºC 25 ºC
Operation Theaters 18ºC (+Elec. Heater) 24 ºC
Meeting Room 21ºC 25 ºC
Patients Rooms: 21 ºC 25 ºC
Restaurant 21 ºC 25 ºC
Corridor: 19 ºC 27 ºC
Entrance Hall: 17 ºC 29 ºC
Toilet: 18 ºC -
1.1.2 Transfer Coefficients
UWALL1 : 0,433 W/m2.K → Selected U Value U: 0,45 W/m2.K
UWALL2 : 0,417 W/m2.K → Selected U Value U: 0,45 W/m2.K
UROOF : 0,728 W/m2.K → Selected U Value U: 0,728 W/m2.K
UWINDOW : 1,4 W/m2.K → Selected U Value U: 1,4 W/m2.K
UBLOCK D WINDOW: 1,0 W/m2.K → Selected U Value U: 1,0 W/m2.K
2.0 CENTRAL HEATING & COOLING SYSTEM
Quantity of Boilers are selected according to heating loads of fancoil system ,air
handling units and domestic hot water system. In the Building, there will be 3
Boiler with duel fuel burner (natural gas and Diesel). Boiler will be placed in
penthouse technical room of the Block-B. Primer heating water of Building
shall be 80/60°C. Heating system water distribution shall be from the header
placed in Block-B technical room. Each block shall have their own heating water
distribution header placed in technical rooms. Secondery heating water
distribution of the Block-A and C shall be from these headers. 60°C Domestic
hot water will be produced by plate type heat exchangers.
Heating of the Block-A and B are provided by fancoil system. Fancoil system
operation temperature is selected 60/50°C. 3 way control valve is placed at the
inlet of the fancoil heating circulation pump to produce 60/50°C heating water.
Ventilation units only supply the outdoor air at room condition. In Block-B
heating of the hygienic areas provide by air handling units. In other spaces heat
loss of the areas provide by fan-coil units. Ventilation units coil capacities are
selected to supply the fresh air at room condition as in other blocks.
GP-A1 21,0 kW
GP-A2 14,0 kW
GP-A3 13,0 kW
GP-A4 90,0 kW
Sum of Block-A 138,0 kW
GP-OP-1 25,0 kW
GP-OP-2 25,0 kW
GP-OP-3 41,0 kW
GP-OP-4 41,0 kW
GP-OP-5 55,0 kW
GP-OP-6 21,0 kW
GP-OP-7 (GP-B11) 78,0 kW
GP-B1 40,0 kW
GP-B2 31,0 kW
GP-B3 14,0 kW
GP-B4 32,0 kW
GP-B5 47,0 kW
GP-B6 43,0 kW
GP-B7 32,0 kW
GP-B8 30,0 kW
GP-B9 11,0 kW
GP-B10 11,0 kW
GP-B12 36,0 kW
GP-B13 85,0 kW
GP-B14 28,0 kW
Sum of Block-B 726,0 kW
GP-C1 26,0 kW
GP-C2 28,0 kW
GP-C3 31,0 kW
GP-C4 68,0 kW
Sum of Block-C 153,0 kW
Type : Inline
Capacity : 25 m3/h
Head : 5 mWg
Quantity :3
Electrical Capacity : 0,75 kW
Expansion Tank :
Type : Cylindrical-Vertical Type
Capacity : 1.000 litre
Operation Pressure : 6 bar
Quantity :2
Type : Twin-Inline
Capacity : 13.0 m3/h
Head : 8 mWg
Quantity : 1 Set
Electrical Capacity : 0.75 kW
Type : Cylindrical
Capacity : 15.000 litre
Diameter : 1600 mm
Length : 8.570 mm
Quantity :2
Chimney Selection
Q + 10.000
FΑ = (cm²)
√h x (25 + 2 √Q )
4
FΑ: πD²/4
FΑ: Chimney Section Area
h : Chimney Hight
D: Chimney Diameter
D= √(4x FΑ/π)
D= √(4x 2461/π)
D= 56 cm = 600 mm (Stainless Steel w/ Rockwool Insulation)
2.2 COOLING SYSTEM & CHILLER GROUPS
Chilled water demand of the hospital building shall be prepared by air cooled
chillers. Two air cooled chiller shall be placed outside of the building,
determined by architecture. Primary circulation pumps of the chiller groups
shall be placed in the basement floor. Secondary circulation pumps and
chilled water distribution header shall be placed in the penthouse floor
technical room of the Block-B.
In summer operation, operation theaters and most of the Block-B spaces will
be conditioned by air handling units. Radiology and laboratory spaces shall
be conditioned by suspended ceiling type fan-coil units.
Primary and secondary circuit of the chilled water system shall be 7/12°C.
2.2.1 Block B Chilled Water System
GP-OP-1 35,0 kW
GP-OP-2 35,0 kW
GP-OP-3 50,0 kW
GP-OP-4 50,0 kW
GP-OP-5 66,0 kW
GP-OP-6 28,0 kW
GP-OP-7 (GP-B11) 105,0 kW
GP-B1 42,0 kW
GP-B3 11,0 kW
GP-B4 25,0 kW
GP-B5 44,0 kW
GP-B6 34,0 kW
GP-B7 25,0 kW
GP-B8 24,0 kW
GP-B9 8,0 kW
GP-B10 9,0 kW
GP-B12 38,0 kW
GP-B13 83,0 kW
GP-B14 29,0 kW
Sum of Block-B 741 kW
Block B Air Handling Units Total Cooling Load : 741.000 Watt
Fan –Coil Units Total Cooling Load (w/0,8 Diversity) : 238.163 Watt
(297.703 W x 0,8: 238.163 W)
Two equal capacity air cooled chiller selected for Block-B and Block-D
Chiller Unit
Type : Air Cooled Chiller, w/Hydronic Module
Capacity : 535 kW ( Outside Air Temp. 41.5°C )
Cooling Water : 7/12 C
Electrical Capacity : 205 kw
Quantity :2
Contraction Tank
Capacity : 1000 liter - 6 bar
Quantity : 1 ea
GP-A1 16,0 kW
GP-A2 11,0 kW
GP-A3 10,0 kW
GP-A4 71,0 kW
Sum of Block-A 108,0 kW
Fan –Coil Units Total Cooling Load (w/0,8 Diversity) : 283.984 Watt
(354.980 W x 0,8: 283.984 W)
Air cooled w/Hydronic module chiller unit selected and placed at Block A
roof.
Chiller Unit
Type : Air Cooled Chiller, w/Hydronic Module
Capacity : 400 kW ( Outside Air Temp. 38°C )
Cooling Water : 7/12 C
Electrical Capacity : 150 kw
Quantity :1
Contraction Tank
Capacity : 300 liter - 8 bar
Quantity : 1 ea
GP-C1 20,0 kW
GP-C2 22,0 kW
GP-C3 24,0 kW
GP-C4 53,0 kW
Sum of Block-C 119,0 kW
Fan –Coil Units Total Cooling Load (w/0,8 Diversity) : 310.368 Watt
(387.960 W x 0,8: 310.368 W)
Air cooled w/Hydronic module chiller unit selected and placed at Block C
roof.
Chiller Unit
Type : Air Cooled Chiller, w/Hydronic Module
Capacity : 430 kW ( Outside Air Temp. 38°C )
Cooling Water : 7/12 C
Electrical Capacity : 155 kw
Quantity :1
Contraction Tank
Capacity : 300 liter - 8 bar
Quantity : 1 ea
2.2.3.3 Block C Seconder Chilled Water Circulation Pumps
Air Handling Unit capacity shall be designed according to 5,5°C supply air
temperature difference.
7.192 x 0,86
Vsupply fan : = 3.878 m³/h ≈ 4.000 m³/h
0,29 x 5,5
SUMMER OPERATION
563 x 0.86
T3 = 18 + = 18.4°C
0.29 x 4.000
Air Handling Unit capacity shall be designed according to 5,5°C supply air
temperature difference.
7.192 x 0,86
Vsupply fan : = 3.878 m³/h ≈ 4.000 m³/h
0,29 x 5,5
SUMMER OPERATION
563 x 0.86
T3 = 18 + = 18.4°C
0.29 x 4.000
Air Handling Unit capacity shall be designed according to 3,5°C supply air
temperature difference.
7.010 x 0,86
Vsupply fan : = 5.940 m³/h ≈ 6.650 m³/h
0,29 x 3,5
SUMMER OPERATION
406 x 0.86
T3 = 18 + = 18.2°C
0.29 x 6.650
Air Handling Unit capacity shall be designed according to 3,5°C supply air
temperature difference.
7.192 x 0,86
Vsupply fan : = 6.094 m³/h ≈ 6.650 m³/h
0,29 x 3,5
SUMMER OPERATION
563 x 0.86
T3 = 18 + = 18.3°C
0.29 x 6.650
Air Handling Unit capacity shall be designed according to 3°C supply air
temperature difference.
8.378 x 0,86
Vsupply fan = 8.282 m³/h ≈ 9.000 m³/h
:
0,29 x 3
SUMMER OPERATION
1.726 x 0.86
T3 = 18 + = 18.7°C
0.29 x 9.000
Air Handling Unit capacity shall be designed according to 5°C supply air
temperature difference.
6.047 x 0,86
Vsupply fan : = 3.587 m³/h ≈ 3.300 m³/h
0,29 x 5
SUMMER OPERATION
156 x 0.86
T3 = 18 + = 18.2°C
0.29 x 3.300
Air Handling Unit capacity shall be designed according to 8°C supply air
temperature difference.
27.289 x 0,86
Vsupply fan = 10.116 m³/h ≈ 10.550 m³/h
:
0,29 x 8
SUMMER OPERATION
3.929 x 0.86
T3 = 21 + = 22.1°C
0.29 x 10.550
Air Handling Unit capacity shall be designed according to 8°C supply air
temperature difference.
9.339 x 0,86
Vsupply fan : = 3.462 m³/h ≈ 4.500 m³/h
0,29 x 8
SUMMER OPERATION
7.626 x 0.86
T3 = 21 + = 26.1°C
0.29 x 4.500
Buanderie Air Handling Unit designed as ventilation unit. Heat loss of the
space shall be provided by air handling unit.
WINTER OPERATION
6.137 x 0.86
T3 = 18 + = 22.4°C
0.29 x 4.150
Air Handling Unit capacity shall be designed according to supply 25°C fresh
air at room temperature. Spaces, served by the GP-B3 air handling unit, heat
gain and heat losses are provided by fancoil units.
SUMMER OPERATION
Magasin Air Handling Unit designed as ventilation unit. Heat loss of the space
shall be provided by fancoil units.
WINTER OPERATION
Vs = 2.000 m³/h
Restaurant Air Handling Unit designed as ventilation unit. Air Handling Unit
capacity shall be designed according to supply 25°C fresh air at room
temperature. Spaces, served by the GP-B4 air handling unit, heat gain and heat
losses are provided by fancoil units.
SUMMER OPERATION
Restaurant Air Handling Unit designed as ventilation unit. Heat loss of the
space shall be provided by fancoil units.
WINTER OPERATION
Vs = 4.600 m³/h
SUMMER OPERATION
WINTER OPERATION
Radiologie Air Handling Unit designed as ventilation unit. Air Handling Unit
capacity shall be designed according to supply 25°C fresh air at room
temperature. Spaces, served by the GP-B6 air handling unit, heat gain and heat
losses are provided by fancoil units.
SUMMER OPERATION
Radiologie Air Handling Unit designed as ventilation unit. Heat loss of the
space shall be provided by fancoil units.
WINTER OPERATION
Urgencies Air Handling Unit designed as ventilation unit. Air Handling Unit
capacity shall be designed according to supply 25°C fresh air at room
temperature. Spaces, served by the GP-B7 air handling unit, heat gain and heat
losses are provided by fancoil units.
SUMMER OPERATION
Urgencies Air Handling Unit designed as ventilation unit. Heat loss of the
space shall be provided by fancoil units.
WINTER OPERATION
Laboratories Air Handling Unit designed as ventilation unit. Air Handling Unit
capacity shall be designed according to supply 25°C fresh air at room
temperature. Spaces, served by the GP-B8 air handling unit, heat gain and heat
losses are provided by fancoil units.
SUMMER OPERATION
Laboratories Air Handling Unit designed as ventilation unit. Heat loss of the
space shall be provided by fancoil units.
WINTER OPERATION
Logements Air Handling Unit designed as ventilation unit. Air Handling Unit
capacity shall be designed according to supply 25°C fresh air at room
temperature. Spaces, served by the GP-B9 air handling unit, heat gain and heat
losses are provided by fancoil units.
SUMMER OPERATION
Logements Air Handling Unit designed as ventilation unit. Heat loss of the
space shall be provided by fancoil units.
WINTER OPERATION
Dialyse Air Handling Unit designed as ventilation unit. Air Handling Unit
capacity shall be designed according to supply 25°C fresh air at room
temperature. Spaces, served by the GP-B10 air handling unit, heat gain and
heat losses are provided by fancoil units.
SUMMER OPERATION
Dialyse Air Handling Unit designed as ventilation unit. Heat loss of the space
shall be provided by fancoil units.
WINTER OPERATION
Air Handling Unit capacity shall be designed according to 8°C supply air
temperature difference.
11.584 x 0,86
Vsupply fan : = 4.294 m³/h ≈ 4.000 m³/h
0,29 x 8
SUMMER OPERATION
7.379 x 0.86
T3 = 21 + = 26.5°C
0.29 x 4.000
Air Handling Unit capacity shall be designed according to 7°C supply air
temperature difference.
22.761 x 0,86
Vsupply fan : = 9.643 m³/h ≈ 9.400 m³/h
0,29 x 7
SUMMER OPERATION
18.009 x 0.86
T3 = 21 + = 26.7°C
0.29 x 9.400
Air Handling Unit capacity shall be designed according to 7,5°C supply air
temperature difference.
7.955 x 0,86
Vsupply fan = 2.950 m³/h ≈ 3.150 m³/h
:
0,29 x 7,5
SUMMER OPERATION
5.143 x 0.86
T3 = 21 + = 25.5°C
0.29 x 3.150
Air Handling Unit capacity shall be designed according to supply 25°C fresh
air at room temperature. Spaces, served by the GP-A1 air handling unit, heat
gain and heat losses are provided by fancoil units.
Air Handling shall be %100 fresh air unit.
V: 3000 m3/h
SUMMER OPERATION
Revelidation Air Handling Unit designed as ventilation unit. Heat loss of the
space shall be provided by fancoil units.
WINTER OPERATION
Air Handling Unit capacity shall be designed according to supply 25°C fresh
air at room temperature. Spaces, served by the GP-A2 air handling unit, heat
gain and heat losses are provided by fancoil units.
Air Handling shall be %100 fresh air unit.
V: 2000 m3/h
SUMMER OPERATION
Pharmacy Air Handling Unit designed as ventilation unit. Heat loss of the
space shall be provided by fancoil units.
WINTER OPERATION
Air Handling Unit capacity shall be designed according to supply 25°C fresh
air at room temperature. Spaces, served by the GP-A3 air handling unit, heat
gain and heat losses are provided by fancoil units.
Air Handling shall be %100 fresh air unit.
V: 1850 m3/h
SUMMER OPERATION
Autopsie Air Handling Unit designed as ventilation unit. Heat loss of the space
shall be provided by fancoil units.
WINTER OPERATION
Air Handling Unit capacity shall be designed according to supply 25°C fresh
air at room temperature. Spaces, served by the GP-A4 air handling unit, heat
gain and heat losses are provided by fancoil units.
Air Handling shall be %100 fresh air unit.
V: 13.200 m3/h
SUMMER OPERATION
Revelidation Air Handling Unit designed as ventilation unit. Heat loss of the
space shall be provided by fancoil units.
WINTER OPERATION
SUMMER OPERATION
Bureaux Air Handling Unit designed as ventilation unit. Heat loss of the space
shall be provided by fancoil units.
WINTER OPERATION
SUMMER OPERATION
WINTER OPERATION
SUMMER OPERATION
Consultation Air Handling Unit designed as ventilation unit. Heat loss of the
space shall be provided by fancoil units.
WINTER OPERATION
SUMMER OPERATION
Unites de Soins Air Handling Unit designed as ventilation unit. Heat loss of
the space shall be provided by fancoil units.
WINTER OPERATION
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A4-0242-Soins '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.7 °C / 20.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 502 - 3 m² - -
Wall Transmission 33 m² 145 - 33 m² 287 -
Roof Transmission 24 m² 120 - 24 m² 333 -
Window Transmission 3 m² 28 - 3 m² 70 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 45 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 114 0
>> Total Zone Loads - 1803 120 - 1257 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A4-0242-Soins '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 12 0.452 - 37 - 103
S EXPOSURE
WALL 21 0.452 - 108 - 184
WINDOW 1 3 1.400 0.820 28 502 70
H EXPOSURE
ROOF 24 0.731 - 120 - 333
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' A4-0241-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 468 - 3 m² - -
Wall Transmission 10 m² 58 - 10 m² 90 -
Roof Transmission 24 m² 308 - 24 m² 333 -
Window Transmission 3 m² 37 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 94 0
>> Total Zone Loads - 1777 70 - 1037 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' A4-0241-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 10 0.452 - 58 - 90
WINDOW 1 3 1.400 0.820 37 468 67
H EXPOSURE
ROOF 24 0.731 - 308 - 333
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' A4-0240-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 468 - 3 m² - -
Wall Transmission 10 m² 58 - 10 m² 90 -
Roof Transmission 24 m² 308 - 24 m² 333 -
Window Transmission 3 m² 37 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 94 0
>> Total Zone Loads - 1777 70 - 1037 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' A4-0240-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 10 0.452 - 58 - 90
WINDOW 1 3 1.400 0.820 37 468 67
H EXPOSURE
ROOF 24 0.731 - 308 - 333
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' A4-0239-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 468 - 3 m² - -
Wall Transmission 10 m² 58 - 10 m² 90 -
Roof Transmission 24 m² 308 - 24 m² 333 -
Window Transmission 3 m² 37 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 94 0
>> Total Zone Loads - 1777 70 - 1037 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' A4-0239-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 10 0.452 - 58 - 90
WINDOW 1 3 1.400 0.820 37 468 67
H EXPOSURE
ROOF 24 0.731 - 308 - 333
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' A4-0238-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 468 - 3 m² - -
Wall Transmission 10 m² 58 - 10 m² 90 -
Roof Transmission 24 m² 308 - 24 m² 333 -
Window Transmission 3 m² 37 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 94 0
>> Total Zone Loads - 1777 70 - 1037 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' A4-0238-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 10 0.452 - 58 - 90
WINDOW 1 3 1.400 0.820 37 468 67
H EXPOSURE
ROOF 24 0.731 - 308 - 333
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' A4-0237-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 468 - 3 m² - -
Wall Transmission 10 m² 58 - 10 m² 90 -
Roof Transmission 24 m² 308 - 24 m² 333 -
Window Transmission 3 m² 37 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 94 0
>> Total Zone Loads - 1777 70 - 1037 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' A4-0237-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 10 0.452 - 58 - 90
WINDOW 1 3 1.400 0.820 37 468 67
H EXPOSURE
ROOF 24 0.731 - 308 - 333
TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' A4-0236-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 468 - 3 m² - -
Wall Transmission 10 m² 58 - 10 m² 90 -
Roof Transmission 24 m² 308 - 24 m² 333 -
Window Transmission 3 m² 37 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 13 m² 52 - 13 m² 52 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 94 0
>> Total Zone Loads - 1777 70 - 1037 0
TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' A4-0236-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 10 0.452 - 58 - 90
WINDOW 1 3 1.400 0.820 37 468 67
H EXPOSURE
ROOF 24 0.731 - 308 - 333
TABLE 1.8.A. COMPONENT LOADS FOR SPACE '' A4-0235-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 468 - 3 m² - -
Wall Transmission 10 m² 58 - 10 m² 90 -
Roof Transmission 24 m² 308 - 24 m² 333 -
Window Transmission 3 m² 37 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 94 0
>> Total Zone Loads - 1777 70 - 1037 0
TABLE 1.8.B. ENVELOPE LOADS FOR SPACE '' A4-0235-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 10 0.452 - 58 - 90
WINDOW 1 3 1.400 0.820 37 468 67
H EXPOSURE
ROOF 24 0.731 - 308 - 333
TABLE 1.9.A. COMPONENT LOADS FOR SPACE '' A4-0234-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 468 - 3 m² - -
Wall Transmission 10 m² 58 - 10 m² 90 -
Roof Transmission 24 m² 308 - 24 m² 333 -
Window Transmission 3 m² 37 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 94 0
>> Total Zone Loads - 1777 70 - 1037 0
TABLE 1.9.B. ENVELOPE LOADS FOR SPACE '' A4-0234-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 10 0.452 - 58 - 90
WINDOW 1 3 1.400 0.820 37 468 67
H EXPOSURE
ROOF 24 0.731 - 308 - 333
TABLE 1.10.A. COMPONENT LOADS FOR SPACE '' A4-0233-Bureau Medecin '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 468 - 3 m² - -
Wall Transmission 34 m² 157 - 34 m² 296 -
Roof Transmission 24 m² 308 - 24 m² 333 -
Window Transmission 3 m² 37 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 115 0
>> Total Zone Loads - 1984 120 - 1264 0
TABLE 1.10.B. ENVELOPE LOADS FOR SPACE '' A4-0233-Bureau Medecin '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 10 0.452 - 58 - 90
WINDOW 1 3 1.400 0.820 37 468 67
N EXPOSURE
WALL 24 0.452 - 98 - 206
H EXPOSURE
ROOF 24 0.731 - 308 - 333
TABLE 1.11.A. COMPONENT LOADS FOR SPACE '' A4-0232-Bureu Secretaria '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0700 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.2 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 388 - 3 m² - -
Wall Transmission 34 m² 172 - 34 m² 296 -
Roof Transmission 24 m² 240 - 24 m² 333 -
Window Transmission 3 m² 11 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 115 0
>> Total Zone Loads - 1826 120 - 1264 0
TABLE 1.11.B. ENVELOPE LOADS FOR SPACE '' A4-0232-Bureu Secretaria '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 64 - 90
WINDOW 1 3 1.400 0.820 11 388 67
N EXPOSURE
WALL 24 0.452 - 108 - 206
H EXPOSURE
ROOF 24 0.731 - 240 - 333
TABLE 1.12.A. COMPONENT LOADS FOR SPACE '' A4-0231-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0700 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.2 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 388 - 3 m² - -
Wall Transmission 10 m² 64 - 10 m² 90 -
Roof Transmission 24 m² 240 - 24 m² 333 -
Window Transmission 3 m² 11 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 94 0
>> Total Zone Loads - 1609 70 - 1037 0
TABLE 1.12.B. ENVELOPE LOADS FOR SPACE '' A4-0231-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 64 - 90
WINDOW 1 3 1.400 0.820 11 388 67
H EXPOSURE
ROOF 24 0.731 - 240 - 333
TABLE 1.13.A. COMPONENT LOADS FOR SPACE '' A4-0230-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0700 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.2 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 388 - 3 m² - -
Wall Transmission 10 m² 64 - 10 m² 90 -
Roof Transmission 24 m² 240 - 24 m² 333 -
Window Transmission 3 m² 11 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 94 0
>> Total Zone Loads - 1609 70 - 1037 0
TABLE 1.13.B. ENVELOPE LOADS FOR SPACE '' A4-0230-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 64 - 90
WINDOW 1 3 1.400 0.820 11 388 67
H EXPOSURE
ROOF 24 0.731 - 240 - 333
TABLE 1.14.A. COMPONENT LOADS FOR SPACE '' A4-0229-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0700 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.2 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 388 - 3 m² - -
Wall Transmission 10 m² 64 - 10 m² 90 -
Roof Transmission 24 m² 240 - 24 m² 333 -
Window Transmission 3 m² 11 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 94 0
>> Total Zone Loads - 1609 70 - 1037 0
TABLE 1.14.B. ENVELOPE LOADS FOR SPACE '' A4-0229-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 64 - 90
WINDOW 1 3 1.400 0.820 11 388 67
H EXPOSURE
ROOF 24 0.731 - 240 - 333
TABLE 1.15.A. COMPONENT LOADS FOR SPACE '' A4-0228-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0700 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.2 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 388 - 3 m² - -
Wall Transmission 10 m² 64 - 10 m² 90 -
Roof Transmission 24 m² 240 - 24 m² 333 -
Window Transmission 3 m² 11 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 94 0
>> Total Zone Loads - 1609 70 - 1037 0
TABLE 1.15.B. ENVELOPE LOADS FOR SPACE '' A4-0228-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 64 - 90
WINDOW 1 3 1.400 0.820 11 388 67
H EXPOSURE
ROOF 24 0.731 - 240 - 333
TABLE 1.16.A. COMPONENT LOADS FOR SPACE '' A4-0227-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0700 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.2 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 388 - 3 m² - -
Wall Transmission 10 m² 64 - 10 m² 90 -
Roof Transmission 24 m² 240 - 24 m² 333 -
Window Transmission 3 m² 11 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 94 0
>> Total Zone Loads - 1609 70 - 1037 0
TABLE 1.16.B. ENVELOPE LOADS FOR SPACE '' A4-0227-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 64 - 90
WINDOW 1 3 1.400 0.820 11 388 67
H EXPOSURE
ROOF 24 0.731 - 240 - 333
TABLE 1.17.A. COMPONENT LOADS FOR SPACE '' A4-0226-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0700 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.2 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 388 - 3 m² - -
Wall Transmission 10 m² 64 - 10 m² 90 -
Roof Transmission 24 m² 240 - 24 m² 333 -
Window Transmission 3 m² 11 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 94 0
>> Total Zone Loads - 1609 70 - 1037 0
TABLE 1.17.B. ENVELOPE LOADS FOR SPACE '' A4-0226-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 64 - 90
WINDOW 1 3 1.400 0.820 11 388 67
H EXPOSURE
ROOF 24 0.731 - 240 - 333
TABLE 1.18.A. COMPONENT LOADS FOR SPACE '' A4-0225-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0700 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.2 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 388 - 3 m² - -
Wall Transmission 10 m² 64 - 10 m² 90 -
Roof Transmission 24 m² 240 - 24 m² 333 -
Window Transmission 3 m² 11 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 94 0
>> Total Zone Loads - 1609 70 - 1037 0
TABLE 1.18.B. ENVELOPE LOADS FOR SPACE '' A4-0225-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 64 - 90
WINDOW 1 3 1.400 0.820 11 388 67
H EXPOSURE
ROOF 24 0.731 - 240 - 333
TABLE 1.19.A. COMPONENT LOADS FOR SPACE '' A4-0224-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0700 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.2 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 388 - 3 m² - -
Wall Transmission 10 m² 64 - 10 m² 90 -
Roof Transmission 24 m² 240 - 24 m² 333 -
Window Transmission 3 m² 11 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 94 0
>> Total Zone Loads - 1609 70 - 1037 0
TABLE 1.19.B. ENVELOPE LOADS FOR SPACE '' A4-0224-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 64 - 90
WINDOW 1 3 1.400 0.820 11 388 67
H EXPOSURE
ROOF 24 0.731 - 240 - 333
TABLE 1.20.A. COMPONENT LOADS FOR SPACE '' A4-0223-Bureau Chef Med '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.7 °C / 20.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 502 - 3 m² - -
Wall Transmission 33 m² 148 - 33 m² 287 -
Roof Transmission 24 m² 120 - 24 m² 333 -
Window Transmission 3 m² 28 - 3 m² 70 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 45 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 114 0
>> Total Zone Loads - 1806 120 - 1257 0
TABLE 1.20.B. ENVELOPE LOADS FOR SPACE '' A4-0223-Bureau Chef Med '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 12 0.452 - 40 - 103
S EXPOSURE
WALL 21 0.452 - 108 - 184
WINDOW 1 3 1.400 0.820 28 502 70
H EXPOSURE
ROOF 24 0.731 - 120 - 333
TABLE 1.21.A. COMPONENT LOADS FOR SPACE '' A4-0279-Corridor '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2000 HEATING DATA AT DES HTG
COOLING OA DB / WB 32.5 °C / 20.1 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 56 m² 260 - 56 m² 481 -
Roof Transmission 210 m² 2986 - 210 m² 2918 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 293 - 4 m² 106 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4536 W 4536 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 1868 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 537 0
>> Total Zone Loads - 8748 352 - 5911 0
TABLE 1.21.B. ENVELOPE LOADS FOR SPACE '' A4-0279-Corridor '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 30 0.452 - 129 - 258
S EXPOSURE
WALL 26 0.452 - 131 - 223
DOOR GLASS 4 1.400 0.820 43 250 106
H EXPOSURE
ROOF 210 0.731 - 2986 - 2918
TABLE 1.22.A. COMPONENT LOADS FOR SPACE '' A4-0263-Menage '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 19.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 8 m² 114 - 8 m² 111 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 26 m² 104 - 26 m² 104 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 173 W 173 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 150 W 150 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 22 0
>> Total Zone Loads - 676 70 - 237 0
TABLE 1.22.B. ENVELOPE LOADS FOR SPACE '' A4-0263-Menage '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 8 0.731 - 114 - 111
TABLE 1.23.A. COMPONENT LOADS FOR SPACE '' A4-0271-Unite Probre '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 19.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 143 - 10 m² 139 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 44 - 11 m² 240 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 38 0
>> Total Zone Loads - 846 120 - 416 0
TABLE 1.23.B. ENVELOPE LOADS FOR SPACE '' A4-0271-Unite Probre '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 10 0.731 - 143 - 139
TABLE 1.24.A. COMPONENT LOADS FOR SPACE '' A4-0272-Infirmerie '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 19.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 143 - 10 m² 139 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 21 m² 84 - 21 m² 84 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 22 0
>> Total Zone Loads - 886 120 - 245 0
TABLE 1.24.B. ENVELOPE LOADS FOR SPACE '' A4-0272-Infirmerie '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 10 0.731 - 143 - 139
TABLE 1.25.A. COMPONENT LOADS FOR SPACE '' A4-0273-Preparation '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 19.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 143 - 10 m² 139 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 21 m² 84 - 21 m² 84 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 150 W 150 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 22 0
>> Total Zone Loads - 736 120 - 245 0
TABLE 1.25.B. ENVELOPE LOADS FOR SPACE '' A4-0273-Preparation '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 10 0.731 - 143 - 139
TABLE 1.26.A. COMPONENT LOADS FOR SPACE '' A4-0274-Unite Sale '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1900 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.1 °C / 20.5 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 140 - 10 m² 139 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² -30 - 11 m² 185 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 32 0
>> Total Zone Loads - 769 120 - 357 0
TABLE 1.26.B. ENVELOPE LOADS FOR SPACE '' A4-0274-Unite Sale '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 10 0.731 - 140 - 139
TABLE 1.27.A. COMPONENT LOADS FOR SPACE '' A4-0275-Office '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 19.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 15 m² 214 - 15 m² 208 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 109 - 11 m² 240 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 324 W 324 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 45 0
>> Total Zone Loads - 1091 120 - 493 0
TABLE 1.27.B. ENVELOPE LOADS FOR SPACE '' A4-0275-Office '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 15 0.731 - 214 - 208
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A4-0279-Corridor '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2000 HEATING DATA AT DES HTG
COOLING OA DB / WB 32.5 °C / 20.1 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 56 m² 209 - 56 m² 431 -
Roof Transmission 210 m² 2679 - 210 m² 2611 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 281 - 4 m² 95 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4536 W 4536 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 1671 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 481 0
>> Total Zone Loads - 8379 352 - 5288 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A4-0279-Corridor '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 30 0.452 - 102 - 231
S EXPOSURE
WALL 26 0.452 - 108 - 200
DOOR GLASS 4 1.400 0.820 32 250 95
H EXPOSURE
ROOF 210 0.731 - 2679 - 2611
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' A4-0263-Menage '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 19.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 8 m² 102 - 8 m² 99 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 26 m² 0 - 26 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 173 W 173 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 150 W 150 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 10 0
>> Total Zone Loads - 560 70 - 109 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' A4-0263-Menage '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 8 0.731 - 102 - 99
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' A4-0271-Unite Probre '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 19.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 128 - 10 m² 124 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 0 - 11 m² 196 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 32 0
>> Total Zone Loads - 788 120 - 352 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' A4-0271-Unite Probre '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 10 0.731 - 128 - 124
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' A4-0272-Infirmerie '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 19.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 128 - 10 m² 124 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 21 m² 0 - 21 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 12 0
>> Total Zone Loads - 788 120 - 137 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' A4-0272-Infirmerie '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 10 0.731 - 128 - 124
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' A4-0273-Preparation '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 19.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 128 - 10 m² 124 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 21 m² 0 - 21 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 150 W 150 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 12 0
>> Total Zone Loads - 638 120 - 137 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' A4-0273-Preparation '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 10 0.731 - 128 - 124
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' A4-0274-Unite Sale '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1900 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.1 °C / 20.5 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 125 - 10 m² 124 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² -74 - 11 m² 142 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 27 0
>> Total Zone Loads - 711 120 - 293 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' A4-0274-Unite Sale '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 10 0.731 - 125 - 124
TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' A4-0275-Office '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 19.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 15 m² 192 - 15 m² 186 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 65 - 11 m² 196 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 324 W 324 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 38 0
>> Total Zone Loads - 1025 120 - 421 0
TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' A4-0275-Office '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 15 0.731 - 192 - 186
TABLE 1.8.A. COMPONENT LOADS FOR SPACE '' A4-0222 Stair Hall '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.9 °C / 21.1 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 33 m² 5909 - 33 m² - -
Wall Transmission 68 m² 284 - 68 m² 519 -
Roof Transmission 88 m² 587 - 88 m² 1094 -
Window Transmission 33 m² 355 - 33 m² 774 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 950 W 950 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 675 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 306 0
>> Total Zone Loads - 8085 0 - 3368 0
TABLE 1.8.B. ENVELOPE LOADS FOR SPACE '' A4-0222 Stair Hall '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 17 0.452 - 69 - 133
WINDOW 1 9 1.400 0.820 96 1037 208
W EXPOSURE
WALL 16 0.452 - 57 - 123
WINDOW 1 10 1.400 0.820 109 2013 238
S EXPOSURE
WALL 34 0.452 - 158 - 263
WINDOW 1 8 1.400 0.820 82 1560 179
WINDOW 2 6 1.400 0.820 68 1300 149
H EXPOSURE
ROOF 88 0.731 - 587 - 1094
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A3-0165-Bureau Chef Med. '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.0 °C / 18.3 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 629 - 3 m² - -
Wall Transmission 33 m² 92 - 33 m² 287 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 15 - 3 m² 70 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 22 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 81 0
>> Total Zone Loads - 1720 120 - 890 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A3-0165-Bureau Chef Med. '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 12 0.452 - 16 - 103
S EXPOSURE
WALL 21 0.452 - 76 - 184
WINDOW 1 3 1.400 0.820 15 629 70
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' A3-0166-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 18.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 396 - 3 m² - -
Wall Transmission 10 m² 63 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 14 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1377 70 - 670 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' A3-0166-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 63 - 90
WINDOW 1 3 1.400 0.820 14 396 67
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' A3-0167-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 18.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 396 - 3 m² - -
Wall Transmission 10 m² 63 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 14 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1377 70 - 670 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' A3-0167-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 63 - 90
WINDOW 1 3 1.400 0.820 14 396 67
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' A3-0168-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 18.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 396 - 3 m² - -
Wall Transmission 10 m² 63 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 14 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1377 70 - 670 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' A3-0168-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 63 - 90
WINDOW 1 3 1.400 0.820 14 396 67
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' A3-0169-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 18.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 396 - 3 m² - -
Wall Transmission 10 m² 63 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 14 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1377 70 - 670 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' A3-0169-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 63 - 90
WINDOW 1 3 1.400 0.820 14 396 67
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' A3-0170-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 18.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 396 - 3 m² - -
Wall Transmission 10 m² 63 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 14 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1377 70 - 670 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' A3-0170-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 63 - 90
WINDOW 1 3 1.400 0.820 14 396 67
TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' A3-0171-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 18.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 396 - 3 m² - -
Wall Transmission 10 m² 63 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 14 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1377 70 - 670 0
TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' A3-0171-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 63 - 90
WINDOW 1 3 1.400 0.820 14 396 67
TABLE 1.8.A. COMPONENT LOADS FOR SPACE '' A3-0172-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 18.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 396 - 3 m² - -
Wall Transmission 10 m² 63 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 14 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1377 70 - 670 0
TABLE 1.8.B. ENVELOPE LOADS FOR SPACE '' A3-0172-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 63 - 90
WINDOW 1 3 1.400 0.820 14 396 67
TABLE 1.9.A. COMPONENT LOADS FOR SPACE '' A3-0173-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 18.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 396 - 3 m² - -
Wall Transmission 10 m² 63 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 14 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1377 70 - 670 0
TABLE 1.9.B. ENVELOPE LOADS FOR SPACE '' A3-0173-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 63 - 90
WINDOW 1 3 1.400 0.820 14 396 67
TABLE 1.10.A. COMPONENT LOADS FOR SPACE '' A3-0174-Bureu Secretaria '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 18.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 396 - 3 m² - -
Wall Transmission 34 m² 169 - 34 m² 296 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 14 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 82 0
>> Total Zone Loads - 1593 120 - 897 0
TABLE 1.10.B. ENVELOPE LOADS FOR SPACE '' A3-0174-Bureu Secretaria '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 63 - 90
WINDOW 1 3 1.400 0.820 14 396 67
N EXPOSURE
WALL 24 0.452 - 106 - 206
TABLE 1.11.A. COMPONENT LOADS FOR SPACE '' A3-0175-Bureau Medecin '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 468 - 3 m² - -
Wall Transmission 34 m² 157 - 34 m² 296 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 37 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 82 0
>> Total Zone Loads - 1676 120 - 897 0
TABLE 1.11.B. ENVELOPE LOADS FOR SPACE '' A3-0175-Bureau Medecin '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 10 0.452 - 58 - 90
WINDOW 1 3 1.400 0.820 37 468 67
N EXPOSURE
WALL 24 0.452 - 98 - 206
TABLE 1.12.A. COMPONENT LOADS FOR SPACE '' A3-0176-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 468 - 3 m² - -
Wall Transmission 10 m² 58 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 37 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1469 70 - 670 0
TABLE 1.12.B. ENVELOPE LOADS FOR SPACE '' A3-0176-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 10 0.452 - 58 - 90
WINDOW 1 3 1.400 0.820 37 468 67
TABLE 1.13.A. COMPONENT LOADS FOR SPACE '' A3-0177-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 468 - 3 m² - -
Wall Transmission 10 m² 58 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 37 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1469 70 - 670 0
TABLE 1.13.B. ENVELOPE LOADS FOR SPACE '' A3-0177-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 10 0.452 - 58 - 90
WINDOW 1 3 1.400 0.820 37 468 67
TABLE 1.14.A. COMPONENT LOADS FOR SPACE '' A3-0178-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 468 - 3 m² - -
Wall Transmission 10 m² 58 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 37 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1469 70 - 670 0
TABLE 1.14.B. ENVELOPE LOADS FOR SPACE '' A3-0178-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 10 0.452 - 58 - 90
WINDOW 1 3 1.400 0.820 37 468 67
TABLE 1.15.A. COMPONENT LOADS FOR SPACE '' A3-0179-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 468 - 3 m² - -
Wall Transmission 10 m² 58 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 37 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1469 70 - 670 0
TABLE 1.15.B. ENVELOPE LOADS FOR SPACE '' A3-0179-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 10 0.452 - 58 - 90
WINDOW 1 3 1.400 0.820 37 468 67
TABLE 1.16.A. COMPONENT LOADS FOR SPACE '' A3-0180-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 468 - 3 m² - -
Wall Transmission 10 m² 58 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 37 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1469 70 - 670 0
TABLE 1.16.B. ENVELOPE LOADS FOR SPACE '' A3-0180-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 10 0.452 - 58 - 90
WINDOW 1 3 1.400 0.820 37 468 67
TABLE 1.17.A. COMPONENT LOADS FOR SPACE '' A3-0181-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 468 - 3 m² - -
Wall Transmission 10 m² 58 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 37 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1469 70 - 670 0
TABLE 1.17.B. ENVELOPE LOADS FOR SPACE '' A3-0181-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 10 0.452 - 58 - 90
WINDOW 1 3 1.400 0.820 37 468 67
TABLE 1.18.A. COMPONENT LOADS FOR SPACE '' A3-0182-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 468 - 3 m² - -
Wall Transmission 10 m² 58 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 37 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1469 70 - 670 0
TABLE 1.18.B. ENVELOPE LOADS FOR SPACE '' A3-0182-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 10 0.452 - 58 - 90
WINDOW 1 3 1.400 0.820 37 468 67
TABLE 1.19.A. COMPONENT LOADS FOR SPACE '' A3-0183-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 468 - 3 m² - -
Wall Transmission 10 m² 58 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 37 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1469 70 - 670 0
TABLE 1.19.B. ENVELOPE LOADS FOR SPACE '' A3-0183-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 10 0.452 - 58 - 90
WINDOW 1 3 1.400 0.820 37 468 67
TABLE 1.20.A. COMPONENT LOADS FOR SPACE '' A3-0184-Soins '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.0 °C / 18.3 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 629 - 3 m² - -
Wall Transmission 33 m² 90 - 33 m² 287 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 15 - 3 m² 70 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 22 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 81 0
>> Total Zone Loads - 1718 120 - 890 0
TABLE 1.20.B. ENVELOPE LOADS FOR SPACE '' A3-0184-Soins '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 12 0.452 - 14 - 103
S EXPOSURE
WALL 21 0.452 - 76 - 184
WINDOW 1 3 1.400 0.820 15 629 70
TABLE 1.21.A. COMPONENT LOADS FOR SPACE '' A3-0205-Menage '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 26 m² 104 - 26 m² 104 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 173 W 173 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 150 W 150 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 10 0
>> Total Zone Loads - 562 70 - 114 0
TABLE 1.21.B. ENVELOPE LOADS FOR SPACE '' A3-0205-Menage '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.22.A. COMPONENT LOADS FOR SPACE '' A3-0213-Unite Probre '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT May 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.0 °C / 17.8 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 44 - 11 m² 240 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 24 0
>> Total Zone Loads - 703 120 - 264 0
TABLE 1.22.B. ENVELOPE LOADS FOR SPACE '' A3-0213-Unite Probre '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.23.A. COMPONENT LOADS FOR SPACE '' A3-0214-Infirmerie '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 21 m² 84 - 21 m² 84 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 8 0
>> Total Zone Loads - 744 120 - 92 0
TABLE 1.23.B. ENVELOPE LOADS FOR SPACE '' A3-0214-Infirmerie '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.24.A. COMPONENT LOADS FOR SPACE '' A3-0215-Preparation '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 21 m² 84 - 21 m² 84 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 150 W 150 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 8 0
>> Total Zone Loads - 594 120 - 92 0
TABLE 1.24.B. ENVELOPE LOADS FOR SPACE '' A3-0215-Preparation '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.25.A. COMPONENT LOADS FOR SPACE '' A3-0216-Unite Sale '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.6 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² -26 - 11 m² 185 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 19 0
>> Total Zone Loads - 634 120 - 204 0
TABLE 1.25.B. ENVELOPE LOADS FOR SPACE '' A3-0216-Unite Sale '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.26.A. COMPONENT LOADS FOR SPACE '' A3-0217-Office '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT May 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.0 °C / 17.8 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 109 - 11 m² 240 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 324 W 324 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 24 0
>> Total Zone Loads - 876 120 - 264 0
TABLE 1.26.B. ENVELOPE LOADS FOR SPACE '' A3-0217-Office '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.27.A. COMPONENT LOADS FOR SPACE '' A3-0221-Corridor '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 33.4 °C / 19.6 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 56 m² 182 - 56 m² 481 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 1157 - 4 m² 106 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4536 W 4536 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 1868 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 246 0
>> Total Zone Loads - 6549 352 - 2701 0
TABLE 1.27.B. ENVELOPE LOADS FOR SPACE '' A3-0221-Corridor '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 30 0.452 - 52 - 258
S EXPOSURE
WALL 26 0.452 - 130 - 223
DOOR GLASS 4 1.400 0.820 36 1121 106
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A3-0221-Corridor '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 33.4 °C / 19.6 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 56 m² 132 - 56 m² 431 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 1146 - 4 m² 95 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4536 W 4536 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 1671 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 220 0
>> Total Zone Loads - 6488 352 - 2416 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A3-0221-Corridor '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 30 0.452 - 25 - 231
S EXPOSURE
WALL 26 0.452 - 106 - 200
DOOR GLASS 4 1.400 0.820 25 1121 95
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' A3-0164 Stair Hall '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.3 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 33 m² 6228 - 33 m² - -
Wall Transmission 68 m² 216 - 68 m² 519 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 33 m² 238 - 33 m² 774 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 950 W 950 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 675 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 197 0
>> Total Zone Loads - 7633 0 - 2164 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' A3-0164 Stair Hall '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 17 0.452 - 40 - 133
WINDOW 1 9 1.400 0.820 64 877 208
W EXPOSURE
WALL 16 0.452 - 36 - 123
WINDOW 1 10 1.400 0.820 73 1560 238
S EXPOSURE
WALL 34 0.452 - 140 - 263
WINDOW 1 8 1.400 0.820 55 2067 179
WINDOW 2 6 1.400 0.820 46 1723 149
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' AR-0000 Bureau '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.7 °C / 20.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 962 - 5 m² - -
Wall Transmission 36 m² 153 - 36 m² 308 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 5 m² 55 - 5 m² 137 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 45 - 13 m² 52 -
Ceiling 23 m² -23 - 23 m² 531 -
Overhead Lighting 497 W 497 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 450 W 450 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 493 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 152 0
>> Total Zone Loads - 2354 180 - 1674 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' AR-0000 Bureau '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 14 0.452 - 44 - 124
WINDOW 1 3 1.400 0.820 27 460 67
S EXPOSURE
WALL 21 0.452 - 108 - 184
WINDOW 1 3 1.400 0.820 28 502 70
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' AR-0001-Preparations '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 937 - 5 m² - -
Wall Transmission 27 m² 150 - 27 m² 232 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 5 m² 73 - 5 m² 134 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 48 m² 0 - 48 m² 1109 -
Overhead Lighting 1037 W 1037 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 1029 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 250 0
>> Total Zone Loads - 2441 120 - 2754 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' AR-0001-Preparations '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 27 0.452 - 150 - 232
WINDOW 1 5 1.400 0.820 73 937 134
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' AR-0002-Preparation '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.8 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 937 - 5 m² - -
Wall Transmission 27 m² 150 - 27 m² 232 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 5 m² 73 - 5 m² 134 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 48 m² 0 - 48 m² 1109 -
Overhead Lighting 1037 W 1037 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 4 287 240 0 0 0
Infiltration - 0 0 - 1029 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 250 0
>> Total Zone Loads - 3485 240 - 2754 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' AR-0002-Preparation '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 27 0.452 - 150 - 232
WINDOW 1 5 1.400 0.820 73 937 134
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' AR-0003-Bureau D'exp '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 469 - 3 m² - -
Wall Transmission 24 m² 132 - 24 m² 210 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 35 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 1249 - 5 m² 133 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 44 m² 0 - 44 m² 1016 -
Overhead Lighting 950 W 950 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 943 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 237 0
>> Total Zone Loads - 3651 180 - 2607 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' AR-0003-Bureau D'exp '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 24 0.452 - 132 - 210
WINDOW 1 3 1.400 0.820 35 469 67
DOOR GLASS 5 1.400 0.800 69 1180 133
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' AR-0010-Bureau Medecin '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 0 - 15 m² 89 -
Ceiling 14 m² 0 - 14 m² 323 -
Overhead Lighting 302 W 302 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 41 0
>> Total Zone Loads - 746 120 - 454 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' AR-0010-Bureau Medecin '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' AR-0005-Medecin Legale '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 24 m² 95 - 24 m² 143 -
Ceiling 39 m² 0 - 39 m² 901 -
Overhead Lighting 842 W 842 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 450 W 450 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 104 0
>> Total Zone Loads - 1603 180 - 1148 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' AR-0005-Medecin Legale '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' AR-0014-Sas de Dist. '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.0 °C / 21.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 8 m² 30 - 8 m² 64 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 153 - 4 m² 266 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 33 m² 0 - 33 m² 762 -
Overhead Lighting 713 W 713 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 377 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 147 0
>> Total Zone Loads - 1340 120 - 1617 0
TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' AR-0014-Sas de Dist. '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 8 0.452 - 30 - 64
DOOR 4 4.000 - 153 - 266
TABLE 1.8.A. COMPONENT LOADS FOR SPACE '' AR-0004-Pharmacie '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 44 m² 0 - 44 m² 1016 -
Overhead Lighting 950 W 950 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 102 0
>> Total Zone Loads - 1287 176 - 1118 0
TABLE 1.8.B. ENVELOPE LOADS FOR SPACE '' AR-0004-Pharmacie '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.9.A. COMPONENT LOADS FOR SPACE '' AR-0026 Accueil '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.7 °C / 20.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 502 - 3 m² - -
Wall Transmission 32 m² 145 - 32 m² 278 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 28 - 3 m² 70 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 122 - 4 m² 304 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 50 m² -51 - 50 m² 1155 -
Overhead Lighting 1080 W 1080 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 150 W 150 - 0 0 -
People 15 1011 528 0 0 0
Infiltration - 0 0 - 572 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 238 0
>> Total Zone Loads - 2987 528 - 2617 0
TABLE 1.9.B. ENVELOPE LOADS FOR SPACE '' AR-0026 Accueil '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 21 0.452 - 108 - 184
WINDOW 1 3 1.400 0.820 28 502 70
E EXPOSURE
WALL 11 0.452 - 37 - 95
DOOR 4 4.000 - 122 - 304
TABLE 1.10.A. COMPONENT LOADS FOR SPACE '' AR-0016-Reserve '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 16 m² 0 - 16 m² 192 -
Ceiling 10 m² 0 - 10 m² 231 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 1 67 35 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 42 0
>> Total Zone Loads - 383 35 - 465 0
TABLE 1.10.B. ENVELOPE LOADS FOR SPACE '' AR-0016-Reserve '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.11.A. COMPONENT LOADS FOR SPACE '' AR-0017-Reserve '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 16 m² 0 - 16 m² 192 -
Ceiling 10 m² 0 - 10 m² 231 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 1 67 35 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 42 0
>> Total Zone Loads - 383 35 - 465 0
TABLE 1.11.B. ENVELOPE LOADS FOR SPACE '' AR-0017-Reserve '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.12.A. COMPONENT LOADS FOR SPACE '' AR-0030-Bureau '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 18.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 396 - 3 m² - -
Wall Transmission 45 m² 221 - 45 m² 391 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 14 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 16 m² 64 - 16 m² 64 -
Ceiling 23 m² 0 - 23 m² 531 -
Overhead Lighting 497 W 497 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 450 W 450 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 493 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 155 0
>> Total Zone Loads - 1857 180 - 1701 0
TABLE 1.12.B. ENVELOPE LOADS FOR SPACE '' AR-0030-Bureau '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 12 0.452 - 74 - 107
WINDOW 1 3 1.400 0.820 14 396 67
N EXPOSURE
WALL 33 0.452 - 146 - 284
TABLE 1.13.A. COMPONENT LOADS FOR SPACE '' AR-0031-Salle de traitme '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 18.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 792 - 5 m² - -
Wall Transmission 27 m² 161 - 27 m² 232 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 5 m² 27 - 5 m² 134 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 33 m² 132 - 33 m² 132 -
Ceiling 48 m² 0 - 48 m² 1109 -
Overhead Lighting 1037 W 1037 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 4 287 240 0 0 0
Infiltration - 0 0 - 1029 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 264 0
>> Total Zone Loads - 3436 240 - 2899 0
TABLE 1.13.B. ENVELOPE LOADS FOR SPACE '' AR-0031-Salle de traitme '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 27 0.452 - 161 - 232
WINDOW 1 5 1.400 0.820 27 792 134
TABLE 1.14.A. COMPONENT LOADS FOR SPACE '' AR-0032-Salle de trait '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 18.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 792 - 5 m² - -
Wall Transmission 27 m² 161 - 27 m² 232 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 5 m² 27 - 5 m² 134 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 33 m² 132 - 33 m² 132 -
Ceiling 48 m² 0 - 48 m² 1109 -
Overhead Lighting 1037 W 1037 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 4 287 240 0 0 0
Infiltration - 0 0 - 1029 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 264 0
>> Total Zone Loads - 3436 240 - 2899 0
TABLE 1.14.B. ENVELOPE LOADS FOR SPACE '' AR-0032-Salle de trait '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 27 0.452 - 161 - 232
WINDOW 1 5 1.400 0.820 27 792 134
TABLE 1.15.A. COMPONENT LOADS FOR SPACE '' AR-0033 Kinesitherapi '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 10 m² 40 - 10 m² 40 -
Ceiling 8 m² 0 - 8 m² 185 -
Overhead Lighting 173 W 173 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 22 0
>> Total Zone Loads - 785 60 - 247 0
TABLE 1.15.B. ENVELOPE LOADS FOR SPACE '' AR-0033 Kinesitherapi '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.16.A. COMPONENT LOADS FOR SPACE '' AR-0034 Kinesitherapi '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 18.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 396 - 3 m² - -
Wall Transmission 13 m² 80 - 13 m² 116 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 14 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 10 m² 0 - 10 m² 231 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 214 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 63 0
>> Total Zone Loads - 1350 120 - 691 0
TABLE 1.16.B. ENVELOPE LOADS FOR SPACE '' AR-0034 Kinesitherapi '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 13 0.452 - 80 - 116
WINDOW 1 3 1.400 0.820 14 396 67
TABLE 1.17.A. COMPONENT LOADS FOR SPACE '' AR-0035 Kinesitherapi '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 18.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 396 - 3 m² - -
Wall Transmission 13 m² 80 - 13 m² 116 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 14 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 10 m² 0 - 10 m² 231 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 214 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 63 0
>> Total Zone Loads - 1350 120 - 691 0
TABLE 1.17.B. ENVELOPE LOADS FOR SPACE '' AR-0035 Kinesitherapi '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 13 0.452 - 80 - 116
WINDOW 1 3 1.400 0.820 14 396 67
TABLE 1.18.A. COMPONENT LOADS FOR SPACE '' AR-0036 Kinesitherapi '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 10 m² 40 - 10 m² 40 -
Ceiling 8 m² 0 - 8 m² 185 -
Overhead Lighting 173 W 173 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 22 0
>> Total Zone Loads - 785 60 - 247 0
TABLE 1.18.B. ENVELOPE LOADS FOR SPACE '' AR-0036 Kinesitherapi '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.19.A. COMPONENT LOADS FOR SPACE '' AR-0037 Kinesitherapi '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 10 m² 40 - 10 m² 40 -
Ceiling 8 m² 0 - 8 m² 185 -
Overhead Lighting 173 W 173 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 22 0
>> Total Zone Loads - 785 60 - 247 0
TABLE 1.19.B. ENVELOPE LOADS FOR SPACE '' AR-0037 Kinesitherapi '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.20.A. COMPONENT LOADS FOR SPACE '' AR-0038 Kinesitherapi '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 18.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 396 - 3 m² - -
Wall Transmission 13 m² 80 - 13 m² 116 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 14 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 10 m² 0 - 10 m² 231 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 214 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 63 0
>> Total Zone Loads - 1350 120 - 691 0
TABLE 1.20.B. ENVELOPE LOADS FOR SPACE '' AR-0038 Kinesitherapi '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 13 0.452 - 80 - 116
WINDOW 1 3 1.400 0.820 14 396 67
TABLE 1.21.A. COMPONENT LOADS FOR SPACE '' AR-0039-Kinesitherapi '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 18.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 396 - 3 m² - -
Wall Transmission 13 m² 80 - 13 m² 116 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 14 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 10 m² 0 - 10 m² 231 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 214 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 63 0
>> Total Zone Loads - 1350 120 - 691 0
TABLE 1.21.B. ENVELOPE LOADS FOR SPACE '' AR-0039-Kinesitherapi '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 13 0.452 - 80 - 116
WINDOW 1 3 1.400 0.820 14 396 67
TABLE 1.22.A. COMPONENT LOADS FOR SPACE '' AR-0040 Kinesitherapi '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 7 m² 28 - 7 m² 28 -
Ceiling 8 m² 0 - 8 m² 185 -
Overhead Lighting 173 W 173 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 21 0
>> Total Zone Loads - 773 60 - 234 0
TABLE 1.22.B. ENVELOPE LOADS FOR SPACE '' AR-0040 Kinesitherapi '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.23.A. COMPONENT LOADS FOR SPACE '' AR-0041 Kinesitherapi '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 8 m² 0 - 8 m² 185 -
Overhead Lighting 173 W 173 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 18 0
>> Total Zone Loads - 745 60 - 203 0
TABLE 1.23.B. ENVELOPE LOADS FOR SPACE '' AR-0041 Kinesitherapi '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.24.A. COMPONENT LOADS FOR SPACE '' AR-0042 Kinesitherapi '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 8 m² 0 - 8 m² 185 -
Overhead Lighting 173 W 173 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 18 0
>> Total Zone Loads - 745 60 - 203 0
TABLE 1.24.B. ENVELOPE LOADS FOR SPACE '' AR-0042 Kinesitherapi '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' AR-0028 Corridor '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0200 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.3 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 75 m² -4 - 75 m² 1418 -
Overhead Lighting 1620 W 1620 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 142 0
>> Total Zone Loads - 1953 176 - 1559 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' AR-0028 Corridor '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' AR-0047 Hall de Recept '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.3 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 24 m² 5351 - 24 m² - -
Wall Transmission 102 m² 317 - 102 m² 786 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 24 m² 174 - 24 m² 565 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 430 - 4 m² 95 -
Floor Transmission 88 m² 0 - 88 m² 374 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 950 W 950 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 675 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 250 0
>> Total Zone Loads - 8197 352 - 2746 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' AR-0047 Hall de Recept '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 31 0.452 - 72 - 238
DOOR GLASS 4 1.400 0.820 29 401 95
W EXPOSURE
WALL 25 0.452 - 56 - 192
WINDOW 1 10 1.400 0.820 73 1560 238
S EXPOSURE
WALL 46 0.452 - 189 - 356
WINDOW 1 6 1.400 0.820 46 1723 149
WINDOW 2 8 1.400 0.820 55 2067 179
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' AR-0047 Hall de Recept '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.3 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 29.0 °C OCCUPIED T-STAT 17.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 24 m² 5351 - 24 m² - -
Wall Transmission 102 m² 225 - 102 m² 694 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 24 m² 108 - 24 m² 499 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 419 - 4 m² 84 -
Floor Transmission 88 m² 0 - 88 m² 330 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 950 W 950 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 596 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 220 0
>> Total Zone Loads - 8026 352 - 2423 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' AR-0047 Hall de Recept '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 31 0.452 - 44 - 210
DOOR GLASS 4 1.400 0.820 18 401 84
W EXPOSURE
WALL 25 0.452 - 33 - 170
WINDOW 1 10 1.400 0.820 45 1560 210
S EXPOSURE
WALL 46 0.452 - 147 - 314
WINDOW 1 6 1.400 0.820 28 1723 131
WINDOW 2 8 1.400 0.820 34 2067 158
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' OP-1 Chirrugie Majeure-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 23 m² 278 - 23 m² 269 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 24 m² 144 - 24 m² 0 -
Ceiling 20 m² 87 - 20 m² 115 -
Overhead Lighting 907 W 719 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5000 W 4537 - 0 0 -
People 6 384 800 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 38 0
>> Total Zone Loads - 6148 800 - 423 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' OP-1 Chirrugie Majeure-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 23 0.731 - 278 - 269
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' OP-1 Unite Propre-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT May 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.8 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 14 m² 84 - 14 m² 0 -
Ceiling 8 m² 35 - 8 m² 46 -
Overhead Lighting 156 W 123 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 91 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 5 0
>> Total Zone Loads - 439 120 - 51 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' OP-1 Unite Propre-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' OP-1 Scrub-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT May 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.8 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 36 m² 193 - 36 m² 81 -
Overhead Lighting 272 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 91 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 8 0
>> Total Zone Loads - 605 120 - 89 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' OP-1 Scrub-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' OP-2 Chirrugie Gyneco-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 23 m² 278 - 23 m² 269 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 24 m² 144 - 24 m² 0 -
Ceiling 20 m² 87 - 20 m² 115 -
Overhead Lighting 907 W 719 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5000 W 4537 - 0 0 -
People 6 384 800 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 38 0
>> Total Zone Loads - 6148 800 - 423 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' OP-2 Chirrugie Gyneco-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 23 0.731 - 278 - 269
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' OP-2 Scrub-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT May 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.8 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 36 m² 193 - 36 m² 81 -
Overhead Lighting 272 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 91 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 8 0
>> Total Zone Loads - 605 120 - 89 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' OP-2 Scrub-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' OP-2 Unite Propre-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT May 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.8 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 14 m² 84 - 14 m² 0 -
Ceiling 8 m² 35 - 8 m² 46 -
Overhead Lighting 156 W 123 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 91 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 5 0
>> Total Zone Loads - 439 120 - 51 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' OP-2 Unite Propre-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' OP-3-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT May 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.8 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 24 m² 144 - 24 m² 0 -
Ceiling 42 m² 182 - 42 m² 242 -
Overhead Lighting 907 W 719 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5000 W 4537 - 0 0 -
People 6 384 800 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 24 0
>> Total Zone Loads - 5966 800 - 266 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' OP-3-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' OP-3 Scrub '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT May 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.8 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 36 m² 193 - 36 m² 81 -
Overhead Lighting 272 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 91 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 8 0
>> Total Zone Loads - 605 120 - 89 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' OP-3 Scrub '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' OP-3 Unite Propre '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT May 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.8 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 14 m² 84 - 14 m² 0 -
Ceiling 8 m² 35 - 8 m² 46 -
Overhead Lighting 156 W 123 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 91 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 5 0
>> Total Zone Loads - 439 120 - 51 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' OP-3 Unite Propre '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' OP-4 Chirrugie Majeur-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 23 m² 278 - 23 m² 269 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 24 m² 144 - 24 m² 0 -
Ceiling 20 m² 87 - 20 m² 115 -
Overhead Lighting 907 W 719 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5000 W 4537 - 0 0 -
People 6 384 800 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 38 0
>> Total Zone Loads - 6148 800 - 423 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' OP-4 Chirrugie Majeur-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 23 0.731 - 278 - 269
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' OP-4 Scrub-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT May 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.8 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 36 m² 193 - 36 m² 81 -
Overhead Lighting 272 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 91 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 8 0
>> Total Zone Loads - 605 120 - 89 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' OP-4 Scrub-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' OP-4 Unite Propre-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT May 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.8 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 14 m² 84 - 14 m² 0 -
Ceiling 8 m² 35 - 8 m² 46 -
Overhead Lighting 156 W 123 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 91 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 5 0
>> Total Zone Loads - 439 120 - 51 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' OP-4 Unite Propre-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' OP-5 Chirurgie Majeure-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.0 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 72 m² 420 - 72 m² 521 -
Roof Transmission 57 m² 687 - 57 m² 667 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 14 m² 84 - 14 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1231 W 976 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5000 W 4537 - 0 0 -
People 6 384 800 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 119 0
>> Total Zone Loads - 7088 800 - 1307 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' OP-5 Chirurgie Majeure-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 31 0.452 - 155 - 224
E EXPOSURE
WALL 41 0.452 - 265 - 297
H EXPOSURE
ROOF 57 0.731 - 687 - 667
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' OP-5 Unite Propre-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 8 m² 97 - 8 m² 94 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 66 - 11 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 156 W 123 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 91 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 9 0
>> Total Zone Loads - 483 120 - 103 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' OP-5 Unite Propre-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 8 0.731 - 97 - 94
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' OP-5 Scrub-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.0 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 15 m² 94 - 15 m² 105 -
Roof Transmission 14 m² 169 - 14 m² 164 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 22 m² 132 - 22 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 272 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 91 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 27 0
>> Total Zone Loads - 807 120 - 296 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' OP-5 Scrub-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 15 0.452 - 94 - 105
H EXPOSURE
ROOF 14 0.731 - 169 - 164
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' B.2-0213 Attente '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 203 - 1 m² - -
Wall Transmission 8 m² 45 - 8 m² 66 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 20 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 22 m² 88 - 22 m² 88 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 302 W 240 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 17 849 598 0 0 0
Infiltration - 0 0 - 200 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 39 0
>> Total Zone Loads - 1444 598 - 429 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' B.2-0213 Attente '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 8 0.452 - 45 - 66
WINDOW 1 1 1.400 0.820 20 203 36
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' B.2-0236 Secretariat '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 29.2 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 299 - 1 m² - -
Wall Transmission 10 m² 55 - 10 m² 83 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 8 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 25 m² 100 - 25 m² 100 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 281 W 281 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 450 W 450 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 186 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 40 0
>> Total Zone Loads - 1408 180 - 445 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' B.2-0236 Secretariat '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 55 - 83
WINDOW 1 1 1.400 0.820 8 299 36
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' B.2-0237 Banque de Sang '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 29.2 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 299 - 1 m² - -
Wall Transmission 10 m² 55 - 10 m² 83 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 8 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 302 W 302 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 4 287 240 0 0 0
Infiltration - 0 0 - 200 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 32 0
>> Total Zone Loads - 2451 240 - 351 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' B.2-0237 Banque de Sang '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 55 - 83
WINDOW 1 1 1.400 0.820 8 299 36
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' B.2-0255 Centre de tri '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 29.2 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 4 m² 459 - 4 m² - -
Wall Transmission 39 m² 191 - 39 m² 332 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 4 m² 24 - 4 m² 109 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 880 W 880 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2000 W 2000 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 629 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 107 0
>> Total Zone Loads - 3913 301 - 1176 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' B.2-0255 Centre de tri '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 18 0.452 - 103 - 156
WINDOW 1 1 1.400 0.820 8 299 36
N EXPOSURE
WALL 20 0.452 - 88 - 176
WINDOW 1 3 1.400 0.820 16 160 72
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' B.2-0254 Laboratoire '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 20.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 1085 - 14 m² - -
Wall Transmission 61 m² 249 - 61 m² 528 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 187 - 14 m² 362 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4320 W 4320 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 9000 W 9000 - 0 0 -
People 25 1795 1503 0 0 0
Infiltration - 0 0 - 2859 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 375 0
>> Total Zone Loads - 16635 1503 - 4123 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' B.2-0254 Laboratoire '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 61 0.452 - 249 - 528
WINDOW 1 14 1.400 0.820 187 1085 362
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' B.2-0253 Bacteriologie '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 20.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 108 - 1 m² - -
Wall Transmission 22 m² 88 - 22 m² 187 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 19 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 10 m² 40 - 10 m² 40 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 950 W 950 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2000 W 2000 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 629 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 89 0
>> Total Zone Loads - 3564 301 - 981 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' B.2-0253 Bacteriologie '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 22 0.452 - 88 - 187
WINDOW 1 1 1.400 0.820 19 108 36
TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' B.2-0251Bureau '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 18.2 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 20 m² 80 - 20 m² 80 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 8 0
>> Total Zone Loads - 1040 120 - 88 0
TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' B.2-0251Bureau '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.8.A. COMPONENT LOADS FOR SPACE '' B.2-0185-Ch-8 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 20.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 108 - 1 m² - -
Wall Transmission 36 m² 159 - 36 m² 306 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 19 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 324 W 324 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 214 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 56 0
>> Total Zone Loads - 854 120 - 612 0
TABLE 1.8.B. ENVELOPE LOADS FOR SPACE '' B.2-0185-Ch-8 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 11 0.452 - 60 - 95
N EXPOSURE
WALL 25 0.452 - 100 - 212
WINDOW 1 1 1.400 0.820 19 108 36
TABLE 1.9.A. COMPONENT LOADS FOR SPACE '' B.2-0187 Ch-7 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 20.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 329 - 1 m² - -
Wall Transmission 9 m² 47 - 9 m² 74 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 19 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 10 m² 40 - 10 m² 40 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 259 W 259 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 172 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 32 0
>> Total Zone Loads - 937 120 - 354 0
TABLE 1.9.B. ENVELOPE LOADS FOR SPACE '' B.2-0187 Ch-7 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 9 0.452 - 47 - 74
WINDOW 1 1 1.400 0.820 19 329 36
TABLE 1.10.A. COMPONENT LOADS FOR SPACE '' B.2-0189 Sejour '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 20.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 658 - 3 m² - -
Wall Transmission 17 m² 93 - 17 m² 148 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 37 - 3 m² 72 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 144 - 36 m² 144 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 713 W 713 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 200 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 472 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 84 0
>> Total Zone Loads - 1989 120 - 920 0
TABLE 1.10.B. ENVELOPE LOADS FOR SPACE '' B.2-0189 Sejour '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 17 0.452 - 93 - 148
WINDOW 1 3 1.400 0.820 37 658 72
TABLE 1.11.A. COMPONENT LOADS FOR SPACE '' B.2-0168-Ch-1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 33.4 °C / 18.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 381 - 1 m² - -
Wall Transmission 36 m² 158 - 36 m² 306 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 12 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 324 W 324 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 214 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 56 0
>> Total Zone Loads - 1119 120 - 612 0
TABLE 1.11.B. ENVELOPE LOADS FOR SPACE '' B.2-0168-Ch-1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 11 0.452 - 35 - 95
S EXPOSURE
WALL 25 0.452 - 123 - 212
WINDOW 1 1 1.400 0.820 12 381 36
TABLE 1.12.A. COMPONENT LOADS FOR SPACE '' B.2-0170 Ch-2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 20.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 329 - 1 m² - -
Wall Transmission 9 m² 47 - 9 m² 74 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 19 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 10 m² 40 - 10 m² 40 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 259 W 259 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 172 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 32 0
>> Total Zone Loads - 937 120 - 354 0
TABLE 1.12.B. ENVELOPE LOADS FOR SPACE '' B.2-0170 Ch-2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 9 0.452 - 47 - 74
WINDOW 1 1 1.400 0.820 19 329 36
TABLE 1.13.A. COMPONENT LOADS FOR SPACE '' B.2-0172 Ch-1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 20.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 329 - 1 m² - -
Wall Transmission 9 m² 47 - 9 m² 74 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 19 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 10 m² 40 - 10 m² 40 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 259 W 259 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 172 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 32 0
>> Total Zone Loads - 937 120 - 354 0
TABLE 1.13.B. ENVELOPE LOADS FOR SPACE '' B.2-0172 Ch-1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 9 0.452 - 47 - 74
WINDOW 1 1 1.400 0.820 19 329 36
TABLE 1.14.A. COMPONENT LOADS FOR SPACE '' B.2-0174 Ch-2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 20.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 329 - 1 m² - -
Wall Transmission 9 m² 47 - 9 m² 74 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 19 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 10 m² 40 - 10 m² 40 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 259 W 259 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 172 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 32 0
>> Total Zone Loads - 937 120 - 354 0
TABLE 1.14.B. ENVELOPE LOADS FOR SPACE '' B.2-0174 Ch-2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 9 0.452 - 47 - 74
WINDOW 1 1 1.400 0.820 19 329 36
TABLE 1.15.A. COMPONENT LOADS FOR SPACE '' B.2-0176 Ch-3 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 20.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 329 - 1 m² - -
Wall Transmission 9 m² 47 - 9 m² 74 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 19 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 10 m² 40 - 10 m² 40 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 259 W 259 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 172 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 32 0
>> Total Zone Loads - 937 120 - 354 0
TABLE 1.15.B. ENVELOPE LOADS FOR SPACE '' B.2-0176 Ch-3 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 9 0.452 - 47 - 74
WINDOW 1 1 1.400 0.820 19 329 36
TABLE 1.16.A. COMPONENT LOADS FOR SPACE '' B.2-0178 Ch-4 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 20.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 329 - 1 m² - -
Wall Transmission 9 m² 47 - 9 m² 74 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 19 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 10 m² 40 - 10 m² 40 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 259 W 259 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 172 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 32 0
>> Total Zone Loads - 937 120 - 354 0
TABLE 1.16.B. ENVELOPE LOADS FOR SPACE '' B.2-0178 Ch-4 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 9 0.452 - 47 - 74
WINDOW 1 1 1.400 0.820 19 329 36
TABLE 1.17.A. COMPONENT LOADS FOR SPACE '' B.2-0194 Dialyse '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.7 °C / 19.3 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 1394 - 5 m² - -
Wall Transmission 29 m² 148 - 29 m² 251 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 5 m² 58 - 5 m² 145 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 40 m² 139 - 40 m² 160 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3110 W 2464 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 9000 W 8166 - 0 0 -
People 10 499 352 0 0 0
Infiltration - 0 0 - 2058 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 261 0
>> Total Zone Loads - 12869 352 - 2876 0
TABLE 1.17.B. ENVELOPE LOADS FOR SPACE '' B.2-0194 Dialyse '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 29 0.452 - 148 - 251
WINDOW 1 5 1.400 0.820 58 1394 145
TABLE 1.18.A. COMPONENT LOADS FOR SPACE '' B.2-0195 Box d'isolement '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.0 °C / 17.6 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 406 - 1 m² - -
Wall Transmission 12 m² 42 - 12 m² 102 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 7 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 346 W 269 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 901 - 0 0 -
People 2 97 70 0 0 0
Infiltration - 0 0 - 229 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 37 0
>> Total Zone Loads - 1723 70 - 403 0
TABLE 1.18.B. ENVELOPE LOADS FOR SPACE '' B.2-0195 Box d'isolement '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 12 0.452 - 42 - 102
WINDOW 1 1 1.400 0.820 7 406 36
TABLE 1.19.A. COMPONENT LOADS FOR SPACE '' B.2-0201 Bureau Medical '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 18.2 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 44 - 11 m² 44 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 238 W 238 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 4 0
>> Total Zone Loads - 725 120 - 48 0
TABLE 1.19.B. ENVELOPE LOADS FOR SPACE '' B.2-0201 Bureau Medical '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.20.A. COMPONENT LOADS FOR SPACE '' B.2-0205 Local Technique '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 18.2 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 9 m² 36 - 9 m² 36 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 626 W 626 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 750 W 750 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 4 0
>> Total Zone Loads - 1771 301 - 40 0
TABLE 1.20.B. ENVELOPE LOADS FOR SPACE '' B.2-0205 Local Technique '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.21.A. COMPONENT LOADS FOR SPACE '' B.2-0208 Surface Service '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 18.2 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 12 m² 48 - 12 m² 48 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 5 0
>> Total Zone Loads - 436 60 - 53 0
TABLE 1.21.B. ENVELOPE LOADS FOR SPACE '' B.2-0208 Surface Service '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.22.A. COMPONENT LOADS FOR SPACE '' B.2-0209 Surface Service '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 18.2 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 18 m² 72 - 18 m² 72 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 7 0
>> Total Zone Loads - 460 60 - 79 0
TABLE 1.22.B. ENVELOPE LOADS FOR SPACE '' B.2-0209 Surface Service '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.23.A. COMPONENT LOADS FOR SPACE '' B.2-0239 Bureau Medical '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 18.2 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 45 m² 180 - 45 m² 180 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 713 W 713 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 18 0
>> Total Zone Loads - 1708 180 - 198 0
TABLE 1.23.B. ENVELOPE LOADS FOR SPACE '' B.2-0239 Bureau Medical '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' B.2-0257 Sanitaries Pub '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 19.2 °C / 10.8 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 475 W 475 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 0 0
>> Total Zone Loads - 475 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' B.2-0257 Sanitaries Pub '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' B.2-Sanitaries Per '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 19.2 °C / 10.8 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1836 W 1836 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 0 0
>> Total Zone Loads - 2195 301 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' B.2-Sanitaries Per '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' B.1-0114 Scanner-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 46 m² 184 - 46 m² 184 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 648 W 513 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 8200 W 7440 - 0 0 -
People 3 160 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 18 0
>> Total Zone Loads - 8297 180 - 202 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' B.1-0114 Scanner-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' B.1-0119 Preperation-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 31 m² 124 - 31 m² 124 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 373 W 295 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 907 - 0 0 -
People 1 50 35 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 12 0
>> Total Zone Loads - 1376 35 - 136 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' B.1-0119 Preperation-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' B.1-0117 Local Technic-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 6 m² 24 - 6 m² 24 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 146 W 116 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3000 W 2722 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 2 0
>> Total Zone Loads - 2862 0 - 26 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' B.1-0117 Local Technic-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' B.1-0118 Local Technic-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 6 m² 24 - 6 m² 24 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 146 W 116 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3000 W 2722 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 2 0
>> Total Zone Loads - 2862 0 - 26 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' B.1-0118 Local Technic-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' B.1-0110 Radio-1-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 30 m² 120 - 30 m² 120 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 616 W 488 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 8400 W 7622 - 0 0 -
People 2 100 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 12 0
>> Total Zone Loads - 8329 70 - 132 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' B.1-0110 Radio-1-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' B.1-0109 Radio-2-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 45 m² 180 - 45 m² 180 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 648 W 513 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 8000 W 7259 - 0 0 -
People 2 100 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 18 0
>> Total Zone Loads - 8052 70 - 198 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' B.1-0109 Radio-2-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' B.1-0115 Bureau-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 18.2 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 173 W 173 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 5 0
>> Total Zone Loads - 668 120 - 57 0
TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' B.1-0115 Bureau-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.8.A. COMPONENT LOADS FOR SPACE '' B.1-0116 Bureau-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 18.2 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 173 W 173 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 5 0
>> Total Zone Loads - 668 120 - 57 0
TABLE 1.8.B. ENVELOPE LOADS FOR SPACE '' B.1-0116 Bureau-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.9.A. COMPONENT LOADS FOR SPACE '' B.1-0108 Radio-3-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 32 m² 128 - 32 m² 128 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 583 W 462 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 8500 W 7712 - 0 0 -
People 2 100 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 13 0
>> Total Zone Loads - 8402 70 - 141 0
TABLE 1.9.B. ENVELOPE LOADS FOR SPACE '' B.1-0108 Radio-3-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.10.A. COMPONENT LOADS FOR SPACE '' B.1-0104 Radio-4-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 32 m² 128 - 32 m² 128 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 632 W 501 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 8500 W 7712 - 0 0 -
People 2 100 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 13 0
>> Total Zone Loads - 8441 70 - 141 0
TABLE 1.10.B. ENVELOPE LOADS FOR SPACE '' B.1-0104 Radio-4-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.11.A. COMPONENT LOADS FOR SPACE '' B.1-0086-Echo-1-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.0 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 32 m² 164 - 32 m² 271 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 243 W 193 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1700 W 1542 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 32 0
>> Total Zone Loads - 2057 120 - 355 0
TABLE 1.11.B. ENVELOPE LOADS FOR SPACE '' B.1-0086-Echo-1-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 13 0.452 - 67 - 107
S EXPOSURE
WALL 19 0.452 - 97 - 163
TABLE 1.12.A. COMPONENT LOADS FOR SPACE '' B.1-0088 Echo-2-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 287 - 1 m² - -
Wall Transmission 11 m² 61 - 11 m² 96 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 20 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 243 W 193 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1300 W 1180 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 214 1
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 40 0
>> Total Zone Loads - 1898 120 - 438 1
TABLE 1.12.B. ENVELOPE LOADS FOR SPACE '' B.1-0088 Echo-2-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 11 0.452 - 61 - 96
WINDOW 1 1 1.400 0.820 20 287 36
TABLE 1.13.A. COMPONENT LOADS FOR SPACE '' B.1-0090 Echo-3-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 287 - 1 m² - -
Wall Transmission 11 m² 61 - 11 m² 96 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 20 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 243 W 193 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1300 W 1180 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 214 1
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 40 0
>> Total Zone Loads - 1898 120 - 438 1
TABLE 1.13.B. ENVELOPE LOADS FOR SPACE '' B.1-0090 Echo-3-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 11 0.452 - 61 - 96
WINDOW 1 1 1.400 0.820 20 287 36
TABLE 1.14.A. COMPONENT LOADS FOR SPACE '' B.1-0092 Echo-4-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 287 - 1 m² - -
Wall Transmission 11 m² 61 - 11 m² 96 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 20 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 243 W 193 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1300 W 1180 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 214 1
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 40 0
>> Total Zone Loads - 1898 120 - 438 1
TABLE 1.14.B. ENVELOPE LOADS FOR SPACE '' B.1-0092 Echo-4-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 11 0.452 - 61 - 96
WINDOW 1 1 1.400 0.820 20 287 36
TABLE 1.15.A. COMPONENT LOADS FOR SPACE '' B.1-0095 Bureau person-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 575 - 3 m² - -
Wall Transmission 21 m² 117 - 21 m² 184 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 39 - 3 m² 72 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 49 m² 196 - 49 m² 196 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 680 W 539 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 4 287 240 0 0 0
Infiltration - 0 0 - 600 2
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 105 0
>> Total Zone Loads - 2753 240 - 1158 2
TABLE 1.15.B. ENVELOPE LOADS FOR SPACE '' B.1-0095 Bureau person-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 21 0.452 - 117 - 184
WINDOW 1 3 1.400 0.820 39 575 72
TABLE 1.16.A. COMPONENT LOADS FOR SPACE '' B.1-0123 Attente-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 203 - 1 m² - -
Wall Transmission 11 m² 63 - 11 m² 91 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 20 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 50 m² 200 - 50 m² 200 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 324 W 257 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 23 1148 810 0 0 0
Infiltration - 0 0 - 286 1
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1891 810 - 675 1
TABLE 1.16.B. ENVELOPE LOADS FOR SPACE '' B.1-0123 Attente-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 11 0.452 - 63 - 91
WINDOW 1 1 1.400 0.820 20 203 36
TABLE 1.17.A. COMPONENT LOADS FOR SPACE '' B.1-0137 Lits Observat-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1000 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.4 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 1190 - 7 m² - -
Wall Transmission 73 m² 372 - 73 m² 624 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 7 m² 47 - 7 m² 181 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 24 m² 96 - 24 m² 96 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1922 W 1922 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2000 W 2000 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 1272 4
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 217 0
>> Total Zone Loads - 5963 176 - 2390 5
TABLE 1.17.B. ENVELOPE LOADS FOR SPACE '' B.1-0137 Lits Observat-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 29 0.452 - 166 - 246
WINDOW 1 3 1.400 0.820 19 486 72
E EXPOSURE
WALL 44 0.452 - 205 - 377
WINDOW 1 4 1.400 0.820 28 704 109
TABLE 1.18.A. COMPONENT LOADS FOR SPACE '' B.1-0142 Salle Exemens-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 95 - 1 m² - -
Wall Transmission 15 m² 60 - 15 m² 128 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 20 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 454 W 359 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 454 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 300 1
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 52 0
>> Total Zone Loads - 1146 120 - 568 1
TABLE 1.18.B. ENVELOPE LOADS FOR SPACE '' B.1-0142 Salle Exemens-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 15 0.452 - 60 - 128
WINDOW 1 1 1.400 0.820 20 95 36
TABLE 1.19.A. COMPONENT LOADS FOR SPACE '' B.1-0143 Salle Exemens-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.0 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 16 m² 66 - 16 m² 140 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 454 W 359 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 454 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 19 0
>> Total Zone Loads - 1037 120 - 211 0
TABLE 1.19.B. ENVELOPE LOADS FOR SPACE '' B.1-0143 Salle Exemens-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 16 0.452 - 66 - 140
TABLE 1.20.A. COMPONENT LOADS FOR SPACE '' B.1-0144 Salle Exemens '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 190 - 3 m² - -
Wall Transmission 14 m² 54 - 14 m² 117 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 39 - 3 m² 72 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 454 W 359 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 454 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 300 1
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 54 0
>> Total Zone Loads - 1255 120 - 595 1
TABLE 1.20.B. ENVELOPE LOADS FOR SPACE '' B.1-0144 Salle Exemens '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 14 0.452 - 54 - 117
WINDOW 1 3 1.400 0.820 39 190 72
TABLE 1.21.A. COMPONENT LOADS FOR SPACE '' B.1-0145 Antente PublicN '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 190 - 3 m² - -
Wall Transmission 10 m² 41 - 10 m² 88 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 39 - 3 m² 72 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 22 m² 88 - 22 m² 88 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 432 W 342 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 15 749 528 0 0 0
Infiltration - 0 0 - 286 1
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 53 0
>> Total Zone Loads - 1449 528 - 588 1
TABLE 1.21.B. ENVELOPE LOADS FOR SPACE '' B.1-0145 Antente PublicN '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 10 0.452 - 41 - 88
WINDOW 1 3 1.400 0.820 39 190 72
TABLE 1.22.A. COMPONENT LOADS FOR SPACE '' B.1-0148 Garde-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 40 m² 160 - 40 m² 160 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 367 W 291 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 272 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 16 0
>> Total Zone Loads - 829 120 - 176 0
TABLE 1.22.B. ENVELOPE LOADS FOR SPACE '' B.1-0148 Garde-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.23.A. COMPONENT LOADS FOR SPACE '' B.1-0149 Salle de Pet-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.0 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 5 m² 20 - 5 m² 43 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 35 m² 140 - 35 m² 140 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 411 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 4500 W 4083 - 0 0 -
People 4 213 240 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 18 0
>> Total Zone Loads - 4867 240 - 201 0
TABLE 1.23.B. ENVELOPE LOADS FOR SPACE '' B.1-0149 Salle de Pet-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 5 0.452 - 20 - 43
TABLE 1.24.A. COMPONENT LOADS FOR SPACE '' B.1-0150 Bureau-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 95 - 1 m² - -
Wall Transmission 10 m² 41 - 10 m² 88 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 20 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 44 - 11 m² 44 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 302 W 240 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 544 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 200 1
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 37 0
>> Total Zone Loads - 1090 120 - 405 1
TABLE 1.24.B. ENVELOPE LOADS FOR SPACE '' B.1-0150 Bureau-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 10 0.452 - 41 - 88
WINDOW 1 1 1.400 0.820 20 95 36
TABLE 1.25.A. COMPONENT LOADS FOR SPACE '' B.1-0151 Bureau-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 44 - 11 m² 44 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 302 W 240 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 544 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 4 0
>> Total Zone Loads - 934 120 - 48 0
TABLE 1.25.B. ENVELOPE LOADS FOR SPACE '' B.1-0151 Bureau-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.26.A. COMPONENT LOADS FOR SPACE '' B.1-0152 Deterte-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.0 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 283 - 1 m² - -
Wall Transmission 33 m² 161 - 33 m² 280 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 21 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 389 W 308 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 272 - 0 0 -
People 1 53 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 32 0
>> Total Zone Loads - 1099 60 - 348 0
TABLE 1.26.B. ENVELOPE LOADS FOR SPACE '' B.1-0152 Deterte-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 19 0.452 - 105 - 160
WINDOW 1 1 1.400 0.820 21 283 36
N EXPOSURE
WALL 14 0.452 - 57 - 120
TABLE 1.27.A. COMPONENT LOADS FOR SPACE '' B.1-0158 Salle de Decr-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 56 m² 224 - 56 m² 224 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 389 W 308 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 454 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 22 0
>> Total Zone Loads - 1092 120 - 246 0
TABLE 1.27.B. ENVELOPE LOADS FOR SPACE '' B.1-0158 Salle de Decr-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.28.A. COMPONENT LOADS FOR SPACE '' B.1-0160 Salle Exemens-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 42 m² 168 - 42 m² 168 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 432 W 342 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 454 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 17 0
>> Total Zone Loads - 1070 120 - 185 0
TABLE 1.28.B. ENVELOPE LOADS FOR SPACE '' B.1-0160 Salle Exemens-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.29.A. COMPONENT LOADS FOR SPACE '' B.1-0162 Salle de Platre '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 35 m² 140 - 35 m² 140 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 410 W 325 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 454 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 14 0
>> Total Zone Loads - 1025 120 - 154 0
TABLE 1.29.B. ENVELOPE LOADS FOR SPACE '' B.1-0162 Salle de Platre '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.30.A. COMPONENT LOADS FOR SPACE '' B.1-0131 En Reiten-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 18.2 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 16 m² 64 - 16 m² 64 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 173 W 173 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 6 0
>> Total Zone Loads - 380 120 - 70 0
TABLE 1.30.B. ENVELOPE LOADS FOR SPACE '' B.1-0131 En Reiten-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' B.1-0103 Corridor-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 33.4 °C / 18.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 15 m² 3241 - 15 m² - -
Wall Transmission 196 m² 692 - 196 m² 1505 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 15 m² 94 - 15 m² 356 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1296 W 988 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 10 474 352 0 0 0
Infiltration - 0 0 - 546 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 241 0
>> Total Zone Loads - 5488 352 - 2647 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' B.1-0103 Corridor-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 59 0.452 - 134 - 454
WINDOW 1 5 1.400 0.820 34 573 129
S EXPOSURE
WALL 137 0.452 - 558 - 1051
WINDOW 1 10 1.400 0.820 60 2668 227
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' B.1-0102 Radio Cor-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.1 °C / 14.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2430 W 1925 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 454 - 0 0 -
People 40 1997 1408 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 0 0
>> Total Zone Loads - 4376 1408 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' B.1-0102 Radio Cor-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' B.1-0094 Corridor '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.0 °C / 17.6 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 406 - 1 m² - -
Wall Transmission 6 m² 16 - 6 m² 46 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 4 - 1 m² 32 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 486 W 378 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 384 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 46 0
>> Total Zone Loads - 804 0 - 508 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' B.1-0094 Corridor '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 6 0.452 - 16 - 46
WINDOW 1 1 1.400 0.820 4 406 32
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' B.1-0136 Sanitares Pub-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.1 °C / 14.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 454 W 359 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 106 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 0 0
>> Total Zone Loads - 466 120 - 0 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' B.1-0136 Sanitares Pub-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' B.1-0135 Sanitares Pers '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.0 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 10 m² 53 - 10 m² 79 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1426 W 1130 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 907 - 0 0 -
People 5 266 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 8 0
>> Total Zone Loads - 2355 301 - 87 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' B.1-0135 Sanitares Pers '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 10 0.452 - 53 - 79
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' B.1-0141 Urgences-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 19.2 °C / 10.8 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1944 W 1944 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 0 0
>> Total Zone Loads - 2303 301 - 0 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' B.1-0141 Urgences-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' BR-0042 Vestaires Perso '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.6 °C / 20.1 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 4 m² 801 - 4 m² - -
Wall Transmission 54 m² 279 - 54 m² 468 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 4 m² 50 - 4 m² 109 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 29 m² 116 - 29 m² 116 -
Ceiling 31 m² 0 - 31 m² 716 -
Overhead Lighting 368 W 281 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 47 35 0 0 0
Infiltration - 0 0 - 443 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 185 0
>> Total Zone Loads - 1573 35 - 2036 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' BR-0042 Vestaires Perso '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 24 0.452 - 115 - 210
WINDOW 1 1 1.400 0.820 17 178 36
S EXPOSURE
WALL 30 0.452 - 164 - 258
WINDOW 1 3 1.400 0.820 33 623 72
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' BR-0047 Vestaires Pers '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.0 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 27 m² 162 - 27 m² 232 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 27 m² 108 - 27 m² 108 -
Ceiling 31 m² 0 - 31 m² 716 -
Overhead Lighting 502 W 398 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 150 106 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 106 0
>> Total Zone Loads - 818 106 - 1162 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' BR-0047 Vestaires Pers '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 27 0.452 - 162 - 232
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' BR-0048 Salle de detente '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.0 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 27 m² 162 - 27 m² 232 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 27 m² 108 - 27 m² 108 -
Ceiling 41 m² 0 - 41 m² 947 -
Overhead Lighting 664 W 526 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 150 106 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 129 0
>> Total Zone Loads - 947 106 - 1416 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' BR-0048 Salle de detente '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 27 0.452 - 162 - 232
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' BR-0056 Restaurant '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 29.2 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 17 m² 2929 - 17 m² - -
Wall Transmission 73 m² 381 - 73 m² 628 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 17 m² 103 - 17 m² 458 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 45 m² 180 - 45 m² 180 -
Ceiling 112 m² 0 - 112 m² 2587 -
Overhead Lighting 2419 W 1664 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 861 - 0 0 -
People 30 1503 2373 0 0 0
Infiltration - 0 0 - 1601 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 545 0
>> Total Zone Loads - 7620 2373 - 5999 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' BR-0056 Restaurant '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 25 0.452 - 107 - 213
WINDOW 1 5 1.400 0.820 32 311 140
E EXPOSURE
WALL 48 0.452 - 274 - 415
WINDOW 1 1 1.400 0.820 8 299 36
WINDOW 2 11 1.400 0.820 63 2319 281
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' BR-0066 Cusıne '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 22 m² 1566 - 22 m² - -
Wall Transmission 63 m² 251 - 63 m² 537 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 22 m² 326 - 22 m² 598 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 150 m² 0 - 150 m² 3465 -
Overhead Lighting 3240 W 2567 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2000 W 1815 - 0 0 -
People 30 1595 1803 0 0 0
Infiltration - 0 0 - 3216 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 782 0
>> Total Zone Loads - 8120 1803 - 8598 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' BR-0066 Cusıne '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 63 0.452 - 251 - 537
WINDOW 1 21 1.400 0.820 306 1472 562
WINDOW 2 1 1.400 0.820 20 95 36
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' BR-0000 Stockage Boundar '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.9 °C / 20.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 4 m² 839 - 4 m² - -
Wall Transmission 86 m² 425 - 86 m² 736 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 4 m² 56 - 4 m² 109 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 190 - 5 m² 368 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 120 m² 0 - 120 m² 2772 -
Overhead Lighting 1944 W 1540 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 907 - 0 0 -
People 20 998 704 0 0 0
Infiltration - 0 0 - 1715 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 570 0
>> Total Zone Loads - 4956 704 - 6269 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' BR-0000 Stockage Boundar '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 40 0.452 - 223 - 346
WINDOW 1 3 1.400 0.820 37 566 72
W EXPOSURE
WALL 45 0.452 - 202 - 390
WINDOW 1 1 1.400 0.820 19 274 36
DOOR 5 3.950 - 190 - 368
TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' BR-0017 Buandarie '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.9 °C / 20.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 20 m² 110 - 20 m² 172 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 41 m² 0 - 41 m² 947 -
Overhead Lighting 664 W 526 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 272 - 0 0 -
People 3 160 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 112 0
>> Total Zone Loads - 1068 180 - 1231 0
TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' BR-0017 Buandarie '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 20 0.452 - 110 - 172
TABLE 1.8.A. COMPONENT LOADS FOR SPACE '' BR-0080 Magasin '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.0 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 283 - 1 m² - -
Wall Transmission 74 m² 343 - 74 m² 633 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 21 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 60 m² 240 - 60 m² 240 -
Ceiling 60 m² 0 - 60 m² 1386 -
Overhead Lighting 972 W 770 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 750 W 681 - 0 0 -
People 10 499 352 0 0 0
Infiltration - 0 0 - 858 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 315 0
>> Total Zone Loads - 2837 352 - 3468 0
TABLE 1.8.B. ENVELOPE LOADS FOR SPACE '' BR-0080 Magasin '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 45 0.452 - 182 - 387
W EXPOSURE
WALL 29 0.452 - 161 - 246
WINDOW 1 1 1.400 0.820 21 283 36
TABLE 1.9.A. COMPONENT LOADS FOR SPACE '' BR-0081 Magasin '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.0 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 283 - 1 m² - -
Wall Transmission 21 m² 116 - 21 m² 177 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 21 - 1 m² 36 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 65 m² 260 - 65 m² 260 -
Ceiling 38 m² 0 - 38 m² 878 -
Overhead Lighting 567 W 449 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 454 - 0 0 -
People 5 250 176 0 0 0
Infiltration - 0 0 - 500 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 185 0
>> Total Zone Loads - 1832 176 - 2037 0
TABLE 1.9.B. ENVELOPE LOADS FOR SPACE '' BR-0081 Magasin '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 21 0.452 - 116 - 177
WINDOW 1 1 1.400 0.820 21 283 36
TABLE 1.10.A. COMPONENT LOADS FOR SPACE '' BR-0010 Bureau '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 18.2 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 26 m² 104 - 26 m² 104 -
Ceiling 13 m² 0 - 13 m² 300 -
Overhead Lighting 281 W 281 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 40 0
>> Total Zone Loads - 828 120 - 445 0
TABLE 1.10.B. ENVELOPE LOADS FOR SPACE '' BR-0010 Bureau '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' BR-0055 Corridor '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.4 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 108 m² -454 - 108 m² 2041 -
Overhead Lighting 2333 W 1848 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 250 176 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 204 0
>> Total Zone Loads - 1644 176 - 2245 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' BR-0055 Corridor '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' BR-0037 Corridor '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.3 °C / 19.2 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 375 - 1 m² - -
Wall Transmission 10 m² 39 - 10 m² 74 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 10 - 1 m² 32 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 47 m² -232 - 47 m² 888 -
Overhead Lighting 1015 W 790 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 243 176 0 0 0
Infiltration - 0 0 - 601 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 160 0
>> Total Zone Loads - 1226 176 - 1755 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' BR-0037 Corridor '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 10 0.452 - 39 - 74
WINDOW 1 1 1.400 0.820 10 375 32
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' C4-0211-Soins '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0700 HEATING DATA AT DES HTG
COOLING OA DB / WB 26.6 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 403 - 3 m² - -
Wall Transmission 33 m² 183 - 33 m² 287 -
Roof Transmission 24 m² 238 - 24 m² 333 -
Window Transmission 3 m² 10 - 3 m² 70 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 114 0
>> Total Zone Loads - 1847 120 - 1257 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' C4-0211-Soins '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 12 0.452 - 56 - 103
E EXPOSURE
WALL 21 0.452 - 127 - 184
WINDOW 1 3 1.400 0.820 10 403 70
H EXPOSURE
ROOF 24 0.731 - 238 - 333
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' C4-0212-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.7 °C / 20.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 493 - 3 m² - -
Wall Transmission 10 m² 53 - 10 m² 90 -
Roof Transmission 24 m² 120 - 24 m² 333 -
Window Transmission 3 m² 27 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 45 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 94 0
>> Total Zone Loads - 1592 70 - 1037 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' C4-0212-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 10 0.452 - 53 - 90
WINDOW 1 3 1.400 0.820 27 493 67
H EXPOSURE
ROOF 24 0.731 - 120 - 333
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' C4-0228-Bureau Medecin '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.3 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 510 - 3 m² - -
Wall Transmission 34 m² 127 - 34 m² 296 -
Roof Transmission 24 m² 106 - 24 m² 333 -
Window Transmission 3 m² 26 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 45 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 115 0
>> Total Zone Loads - 1776 120 - 1264 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' C4-0228-Bureau Medecin '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 10 0.452 - 52 - 90
WINDOW 1 3 1.400 0.820 26 510 67
W EXPOSURE
WALL 24 0.452 - 75 - 206
H EXPOSURE
ROOF 24 0.731 - 106 - 333
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' C4-0233-Secretariat '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.0 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 179 - 3 m² - -
Wall Transmission 34 m² 174 - 34 m² 296 -
Roof Transmission 24 m² 324 - 24 m² 333 -
Window Transmission 3 m² 32 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 115 0
>> Total Zone Loads - 1724 120 - 1264 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' C4-0233-Secretariat '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 10 0.452 - 43 - 90
WINDOW 1 3 1.400 0.820 32 179 67
W EXPOSURE
WALL 24 0.452 - 131 - 206
H EXPOSURE
ROOF 24 0.731 - 324 - 333
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' C4-0234-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.0 °C / 21.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 179 - 3 m² - -
Wall Transmission 10 m² 43 - 10 m² 90 -
Roof Transmission 24 m² 324 - 24 m² 333 -
Window Transmission 3 m² 32 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 94 0
>> Total Zone Loads - 1484 70 - 1037 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' C4-0234-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 10 0.452 - 43 - 90
WINDOW 1 3 1.400 0.820 32 179 67
H EXPOSURE
ROOF 24 0.731 - 324 - 333
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' C4-0250-Bureau Chef Med. '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0700 HEATING DATA AT DES HTG
COOLING OA DB / WB 26.6 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 403 - 3 m² - -
Wall Transmission 33 m² 180 - 33 m² 287 -
Roof Transmission 24 m² 238 - 24 m² 333 -
Window Transmission 3 m² 10 - 3 m² 70 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 114 0
>> Total Zone Loads - 1844 120 - 1257 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' C4-0250-Bureau Chef Med. '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 12 0.452 - 54 - 103
E EXPOSURE
WALL 21 0.452 - 127 - 184
WINDOW 1 3 1.400 0.820 10 403 70
H EXPOSURE
ROOF 24 0.731 - 238 - 333
TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' C4-0251-Menage '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 19.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 8 m² 114 - 8 m² 111 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 26 m² 104 - 26 m² 104 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 173 W 173 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 150 W 150 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 22 0
>> Total Zone Loads - 676 70 - 237 0
TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' C4-0251-Menage '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 8 0.731 - 114 - 111
TABLE 1.8.A. COMPONENT LOADS FOR SPACE '' C4-0259-Unite Probre '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 19.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 143 - 10 m² 139 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 44 - 11 m² 242 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 200 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 38 0
>> Total Zone Loads - 746 120 - 419 0
TABLE 1.8.B. ENVELOPE LOADS FOR SPACE '' C4-0259-Unite Probre '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 10 0.731 - 143 - 139
TABLE 1.9.A. COMPONENT LOADS FOR SPACE '' C4-0260-Infirmerie '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 19.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 143 - 10 m² 139 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 21 m² 84 - 21 m² 84 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 22 0
>> Total Zone Loads - 886 120 - 245 0
TABLE 1.9.B. ENVELOPE LOADS FOR SPACE '' C4-0260-Infirmerie '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 10 0.731 - 143 - 139
TABLE 1.10.A. COMPONENT LOADS FOR SPACE '' C4-0262-Preparation '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 19.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 143 - 10 m² 139 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 21 m² 84 - 21 m² 84 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 150 W 150 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 22 0
>> Total Zone Loads - 736 120 - 245 0
TABLE 1.10.B. ENVELOPE LOADS FOR SPACE '' C4-0262-Preparation '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 10 0.731 - 143 - 139
TABLE 1.11.A. COMPONENT LOADS FOR SPACE '' C4-0263-Unite Sale '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 19.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 143 - 10 m² 139 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 44 - 11 m² 44 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 18 0
>> Total Zone Loads - 846 120 - 201 0
TABLE 1.11.B. ENVELOPE LOADS FOR SPACE '' C4-0263-Unite Sale '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 10 0.731 - 143 - 139
TABLE 1.12.A. COMPONENT LOADS FOR SPACE '' C4-0264-Office '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 19.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 15 m² 214 - 15 m² 208 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 110 - 11 m² 242 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 324 W 324 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 45 0
>> Total Zone Loads - 1092 120 - 495 0
TABLE 1.12.B. ENVELOPE LOADS FOR SPACE '' C4-0264-Office '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 15 0.731 - 214 - 208
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' C4-0261-Corridor '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2000 HEATING DATA AT DES HTG
COOLING OA DB / WB 32.0 °C / 20.1 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 56 m² 290 - 56 m² 431 -
Roof Transmission 210 m² 2683 - 210 m² 2611 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 442 - 4 m² 95 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4536 W 4536 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 1671 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 481 0
>> Total Zone Loads - 8625 352 - 5288 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' C4-0261-Corridor '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 30 0.452 - 147 - 231
E EXPOSURE
WALL 26 0.452 - 143 - 200
DOOR GLASS 4 1.400 0.820 29 414 95
H EXPOSURE
ROOF 210 0.731 - 2683 - 2611
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' C4-0268 Stair Hall '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 29.2 °C / 19.2 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 31 m² 4044 - 31 m² - -
Wall Transmission 69 m² 284 - 69 m² 529 -
Roof Transmission 88 m² 677 - 88 m² 1094 -
Window Transmission 31 m² 100 - 31 m² 744 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 950 W 950 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 525 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 289 0
>> Total Zone Loads - 6055 0 - 3181 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' C4-0268 Stair Hall '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 19 0.452 - 66 - 142
WINDOW 1 8 1.400 0.820 24 435 179
N EXPOSURE
WALL 16 0.452 - 54 - 123
WINDOW 1 10 1.400 0.820 32 589 238
E EXPOSURE
WALL 34 0.452 - 164 - 263
WINDOW 1 6 1.400 0.820 20 1373 149
WINDOW 2 8 1.400 0.820 24 1647 179
H EXPOSURE
ROOF 88 0.731 - 677 - 1094
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' C3-0152-Soins '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0700 HEATING DATA AT DES HTG
COOLING OA DB / WB 26.6 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 403 - 3 m² - -
Wall Transmission 33 m² 183 - 33 m² 287 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 10 - 3 m² 70 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 81 0
>> Total Zone Loads - 1609 120 - 890 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' C3-0152-Soins '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 12 0.452 - 56 - 103
E EXPOSURE
WALL 21 0.452 - 127 - 184
WINDOW 1 3 1.400 0.820 10 403 70
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' C3-0153-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 16.1 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 655 - 3 m² - -
Wall Transmission 10 m² 23 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 4 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 10 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1546 70 - 671 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' C3-0153-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 10 0.452 - 23 - 90
WINDOW 1 3 1.400 0.820 4 655 67
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' C3-0155-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 16.1 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 655 - 3 m² - -
Wall Transmission 10 m² 23 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 4 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 10 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1546 70 - 671 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' C3-0155-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 10 0.452 - 23 - 90
WINDOW 1 3 1.400 0.820 4 655 67
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' C3-0157-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 16.1 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 655 - 3 m² - -
Wall Transmission 10 m² 23 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 4 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 10 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1546 70 - 671 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' C3-0157-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 10 0.452 - 23 - 90
WINDOW 1 3 1.400 0.820 4 655 67
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' C3-0159-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 16.1 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 655 - 3 m² - -
Wall Transmission 10 m² 23 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 4 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 10 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1546 70 - 671 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' C3-0159-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 10 0.452 - 23 - 90
WINDOW 1 3 1.400 0.820 4 655 67
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' C3-0161-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 16.1 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 655 - 3 m² - -
Wall Transmission 10 m² 23 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 4 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 10 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1546 70 - 671 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' C3-0161-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 10 0.452 - 23 - 90
WINDOW 1 3 1.400 0.820 4 655 67
TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' C3-0163-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 16.1 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 655 - 3 m² - -
Wall Transmission 10 m² 23 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 4 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 10 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1546 70 - 671 0
TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' C3-0163-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 10 0.452 - 23 - 90
WINDOW 1 3 1.400 0.820 4 655 67
TABLE 1.8.A. COMPONENT LOADS FOR SPACE '' C3-0165-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 16.1 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 655 - 3 m² - -
Wall Transmission 10 m² 23 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 4 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 10 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1546 70 - 671 0
TABLE 1.8.B. ENVELOPE LOADS FOR SPACE '' C3-0165-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 10 0.452 - 23 - 90
WINDOW 1 3 1.400 0.820 4 655 67
TABLE 1.9.A. COMPONENT LOADS FOR SPACE '' C3-0167-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.3 °C / 16.1 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 655 - 3 m² - -
Wall Transmission 10 m² 23 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 4 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 10 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1546 70 - 671 0
TABLE 1.9.B. ENVELOPE LOADS FOR SPACE '' C3-0167-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 10 0.452 - 23 - 90
WINDOW 1 3 1.400 0.820 4 655 67
TABLE 1.10.A. COMPONENT LOADS FOR SPACE '' C3-0169-Bureau Medecine '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.0 °C / 18.3 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 615 - 3 m² - -
Wall Transmission 34 m² 64 - 34 m² 296 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 14 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 22 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 82 0
>> Total Zone Loads - 1678 120 - 897 0
TABLE 1.10.B. ENVELOPE LOADS FOR SPACE '' C3-0169-Bureau Medecine '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 10 0.452 - 37 - 90
WINDOW 1 3 1.400 0.820 14 615 67
W EXPOSURE
WALL 24 0.452 - 27 - 206
TABLE 1.11.A. COMPONENT LOADS FOR SPACE '' C3-0175-Secretariat '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 187 - 3 m² - -
Wall Transmission 34 m² 172 - 34 m² 296 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 35 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 82 0
>> Total Zone Loads - 1408 120 - 897 0
TABLE 1.11.B. ENVELOPE LOADS FOR SPACE '' C3-0175-Secretariat '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 10 0.452 - 42 - 90
WINDOW 1 3 1.400 0.820 35 187 67
W EXPOSURE
WALL 24 0.452 - 130 - 206
TABLE 1.12.A. COMPONENT LOADS FOR SPACE '' C3-0176-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 187 - 3 m² - -
Wall Transmission 10 m² 42 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 35 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1170 70 - 671 0
TABLE 1.12.B. ENVELOPE LOADS FOR SPACE '' C3-0176-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 10 0.452 - 42 - 90
WINDOW 1 3 1.400 0.820 35 187 67
TABLE 1.13.A. COMPONENT LOADS FOR SPACE '' C3-0178-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 187 - 3 m² - -
Wall Transmission 10 m² 42 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 35 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1170 70 - 671 0
TABLE 1.13.B. ENVELOPE LOADS FOR SPACE '' C3-0178-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 10 0.452 - 42 - 90
WINDOW 1 3 1.400 0.820 35 187 67
TABLE 1.14.A. COMPONENT LOADS FOR SPACE '' C3-0180-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 187 - 3 m² - -
Wall Transmission 10 m² 42 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 35 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1170 70 - 671 0
TABLE 1.14.B. ENVELOPE LOADS FOR SPACE '' C3-0180-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 10 0.452 - 42 - 90
WINDOW 1 3 1.400 0.820 35 187 67
TABLE 1.15.A. COMPONENT LOADS FOR SPACE '' C3-0182-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 187 - 3 m² - -
Wall Transmission 10 m² 42 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 35 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1170 70 - 671 0
TABLE 1.15.B. ENVELOPE LOADS FOR SPACE '' C3-0182-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 10 0.452 - 42 - 90
WINDOW 1 3 1.400 0.820 35 187 67
TABLE 1.16.A. COMPONENT LOADS FOR SPACE '' C3-0184-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 187 - 3 m² - -
Wall Transmission 10 m² 42 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 35 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1170 70 - 671 0
TABLE 1.16.B. ENVELOPE LOADS FOR SPACE '' C3-0184-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 10 0.452 - 42 - 90
WINDOW 1 3 1.400 0.820 35 187 67
TABLE 1.17.A. COMPONENT LOADS FOR SPACE '' C3-0186-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 187 - 3 m² - -
Wall Transmission 10 m² 42 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 35 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1170 70 - 671 0
TABLE 1.17.B. ENVELOPE LOADS FOR SPACE '' C3-0186-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 10 0.452 - 42 - 90
WINDOW 1 3 1.400 0.820 35 187 67
TABLE 1.18.A. COMPONENT LOADS FOR SPACE '' C3-0188-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 187 - 3 m² - -
Wall Transmission 10 m² 42 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 35 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1170 70 - 671 0
TABLE 1.18.B. ENVELOPE LOADS FOR SPACE '' C3-0188-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 10 0.452 - 42 - 90
WINDOW 1 3 1.400 0.820 35 187 67
TABLE 1.19.A. COMPONENT LOADS FOR SPACE '' C3-0190-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 187 - 3 m² - -
Wall Transmission 10 m² 42 - 10 m² 90 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 35 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 100 W 100 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 61 0
>> Total Zone Loads - 1170 70 - 671 0
TABLE 1.19.B. ENVELOPE LOADS FOR SPACE '' C3-0190-Chambre 2 Lits '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 10 0.452 - 42 - 90
WINDOW 1 3 1.400 0.820 35 187 67
TABLE 1.20.A. COMPONENT LOADS FOR SPACE '' C3-0192-Bureau Chef Med. '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0700 HEATING DATA AT DES HTG
COOLING OA DB / WB 26.6 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 403 - 3 m² - -
Wall Transmission 33 m² 180 - 33 m² 287 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 10 - 3 m² 70 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 52 - 13 m² 52 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 400 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 81 0
>> Total Zone Loads - 1607 120 - 890 0
TABLE 1.20.B. ENVELOPE LOADS FOR SPACE '' C3-0192-Bureau Chef Med. '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 12 0.452 - 54 - 103
E EXPOSURE
WALL 21 0.452 - 127 - 184
WINDOW 1 3 1.400 0.820 10 403 70
TABLE 1.21.A. COMPONENT LOADS FOR SPACE '' C3-0193-Menage '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 26 m² 104 - 26 m² 104 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 173 W 173 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 150 W 150 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 10 0
>> Total Zone Loads - 562 70 - 114 0
TABLE 1.21.B. ENVELOPE LOADS FOR SPACE '' C3-0193-Menage '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.22.A. COMPONENT LOADS FOR SPACE '' C3-0201-Unite Probre '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 44 - 11 m² 242 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 200 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 24 0
>> Total Zone Loads - 604 120 - 266 0
TABLE 1.22.B. ENVELOPE LOADS FOR SPACE '' C3-0201-Unite Probre '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.23.A. COMPONENT LOADS FOR SPACE '' C3-0204-Preparation '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 21 m² 84 - 21 m² 84 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 150 W 150 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 8 0
>> Total Zone Loads - 594 120 - 92 0
TABLE 1.23.B. ENVELOPE LOADS FOR SPACE '' C3-0204-Preparation '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.24.A. COMPONENT LOADS FOR SPACE '' C3-0205-Unite Sale '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 44 - 11 m² 44 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 4 0
>> Total Zone Loads - 704 120 - 48 0
TABLE 1.24.B. ENVELOPE LOADS FOR SPACE '' C3-0205-Unite Sale '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.25.A. COMPONENT LOADS FOR SPACE '' C3-0206-Office '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 110 - 11 m² 242 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 324 W 324 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 24 0
>> Total Zone Loads - 878 120 - 266 0
TABLE 1.25.B. ENVELOPE LOADS FOR SPACE '' C3-0206-Office '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.26.A. COMPONENT LOADS FOR SPACE '' C3-0202-Infirmerie '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 21 m² 84 - 21 m² 84 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 8 0
>> Total Zone Loads - 744 120 - 92 0
TABLE 1.26.B. ENVELOPE LOADS FOR SPACE '' C3-0202-Infirmerie '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' C3-0203-Corridor '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 29.2 °C / 19.2 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 56 m² 284 - 56 m² 431 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 891 - 4 m² 95 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4536 W 4536 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 1671 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 220 0
>> Total Zone Loads - 6385 352 - 2416 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' C3-0203-Corridor '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 30 0.452 - 160 - 231
E EXPOSURE
WALL 26 0.452 - 124 - 200
DOOR GLASS 4 1.400 0.820 13 879 95
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' C3-0210 Stair Hall '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.6 °C / 20.8 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 31 m² 3934 - 31 m² - -
Wall Transmission 69 m² 246 - 69 m² 529 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 31 m² 292 - 31 m² 744 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 950 W 950 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 525 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 180 0
>> Total Zone Loads - 5422 0 - 1977 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' C3-0210 Stair Hall '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 19 0.452 - 85 - 142
WINDOW 1 8 1.400 0.820 70 1717 179
N EXPOSURE
WALL 16 0.452 - 32 - 123
WINDOW 1 10 1.400 0.820 93 418 238
E EXPOSURE
WALL 34 0.452 - 130 - 263
WINDOW 1 6 1.400 0.820 58 818 149
WINDOW 2 8 1.400 0.820 70 981 179
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' C1-0039-Bureau Medical '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.2 °C / 18.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 389 - 3 m² - -
Wall Transmission 47 m² 271 - 47 m² 407 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 14 - 3 m² 70 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 17 m² 68 - 17 m² 68 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 515 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 106 0
>> Total Zone Loads - 2076 180 - 1166 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' C1-0039-Bureau Medical '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 17 0.452 - 96 - 146
E EXPOSURE
WALL 30 0.452 - 175 - 261
WINDOW 1 3 1.400 0.820 14 389 70
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' C1-0040-Consultation-5 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.0 °C / 18.3 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 615 - 3 m² - -
Wall Transmission 14 m² 52 - 14 m² 124 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 14 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 17 m² 29 - 17 m² 68 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 515 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 77 0
>> Total Zone Loads - 2043 180 - 852 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' C1-0040-Consultation-5 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 14 0.452 - 52 - 124
WINDOW 1 3 1.400 0.820 14 615 67
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' C1-0056-Bureau Medical '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.3 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 510 - 3 m² - -
Wall Transmission 47 m² 175 - 47 m² 408 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 26 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 17 m² 59 - 17 m² 68 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 515 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 106 0
>> Total Zone Loads - 2103 180 - 1164 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' C1-0056-Bureau Medical '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 14 0.452 - 72 - 124
WINDOW 1 3 1.400 0.820 26 510 67
W EXPOSURE
WALL 33 0.452 - 103 - 284
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' C1-0083-Menage '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 58 m² 232 - 58 m² 232 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 150 W 150 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 23 0
>> Total Zone Loads - 733 70 - 255 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' C1-0083-Menage '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' C1-0090-Unite Sale '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 144 - 36 m² 144 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 173 W 173 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 14 0
>> Total Zone Loads - 760 120 - 158 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' C1-0090-Unite Sale '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' C1-0091-Infirmerie '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 144 - 36 m² 144 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 259 W 259 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 14 0
>> Total Zone Loads - 847 120 - 158 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' C1-0091-Infirmerie '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' C1-0092-Unite Probre '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 52 m² 208 - 52 m² 208 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 259 W 259 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 21 0
>> Total Zone Loads - 911 120 - 229 0
TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' C1-0092-Unite Probre '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.8.A. COMPONENT LOADS FOR SPACE '' C1-0058-Reserve '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 60 m² 240 - 60 m² 270 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 200 W 200 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 27 0
>> Total Zone Loads - 834 120 - 297 0
TABLE 1.8.B. ENVELOPE LOADS FOR SPACE '' C1-0058-Reserve '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.9.A. COMPONENT LOADS FOR SPACE '' C1-0081-Bureau Medical '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0700 HEATING DATA AT DES HTG
COOLING OA DB / WB 26.6 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 403 - 3 m² - -
Wall Transmission 47 m² 256 - 47 m² 407 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 10 - 3 m² 70 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 17 m² 68 - 17 m² 68 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 515 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 106 0
>> Total Zone Loads - 2070 180 - 1166 0
TABLE 1.9.B. ENVELOPE LOADS FOR SPACE '' C1-0081-Bureau Medical '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 17 0.452 - 76 - 146
E EXPOSURE
WALL 30 0.452 - 180 - 261
WINDOW 1 3 1.400 0.820 10 403 70
TABLE 1.10.A. COMPONENT LOADS FOR SPACE '' C1-0073-Consultation-1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 187 - 3 m² - -
Wall Transmission 14 m² 59 - 14 m² 124 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 35 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 17 m² 68 - 17 m² 68 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 515 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 77 0
>> Total Zone Loads - 1682 180 - 852 0
TABLE 1.10.B. ENVELOPE LOADS FOR SPACE '' C1-0073-Consultation-1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 14 0.452 - 59 - 124
WINDOW 1 3 1.400 0.820 35 187 67
TABLE 1.11.A. COMPONENT LOADS FOR SPACE '' C1-0068-A-Prelevement '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 187 - 3 m² - -
Wall Transmission 8 m² 34 - 8 m² 73 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 35 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 14 m² 78 - 14 m² 78 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 151 W 151 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 150 W 150 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 150 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 37 0
>> Total Zone Loads - 779 120 - 406 0
TABLE 1.11.B. ENVELOPE LOADS FOR SPACE '' C1-0068-A-Prelevement '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 8 0.452 - 34 - 73
WINDOW 1 3 1.400 0.820 35 187 67
TABLE 1.12.A. COMPONENT LOADS FOR SPACE '' C1-0069-B-Prelevement '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0300 HEATING DATA AT DES HTG
COOLING OA DB / WB 26.9 °C / 18.3 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 11 m² 52 - 11 m² 95 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 130 W 130 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 150 W 150 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 9 0
>> Total Zone Loads - 475 120 - 104 0
TABLE 1.12.B. ENVELOPE LOADS FOR SPACE '' C1-0069-B-Prelevement '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 11 0.452 - 52 - 95
TABLE 1.13.A. COMPONENT LOADS FOR SPACE '' C1-0070-C-Prelevement '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 187 - 3 m² - -
Wall Transmission 8 m² 34 - 8 m² 73 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 35 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 151 W 151 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 150 W 150 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 150 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 29 0
>> Total Zone Loads - 701 120 - 319 0
TABLE 1.13.B. ENVELOPE LOADS FOR SPACE '' C1-0070-C-Prelevement '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 8 0.452 - 34 - 73
WINDOW 1 3 1.400 0.820 35 187 67
TABLE 1.14.A. COMPONENT LOADS FOR SPACE '' C1-0067-Prelevements '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.6 °C / 19.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 48 m² 221 - 48 m² 221 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 475 W 475 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 22 0
>> Total Zone Loads - 1511 180 - 243 0
TABLE 1.14.B. ENVELOPE LOADS FOR SPACE '' C1-0067-Prelevements '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.15.A. COMPONENT LOADS FOR SPACE '' C1-0065 Accueil '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 187 - 3 m² - -
Wall Transmission 44 m² 219 - 44 m² 378 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 35 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 49 m² 247 - 49 m² 247 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 475 W 475 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 150 W 150 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 472 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 116 0
>> Total Zone Loads - 1650 176 - 1281 0
TABLE 1.15.B. ENVELOPE LOADS FOR SPACE '' C1-0065 Accueil '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 14 0.452 - 57 - 120
WINDOW 1 3 1.400 0.820 35 187 67
W EXPOSURE
WALL 30 0.452 - 162 - 258
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' C1-0057-Corridor '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0300 HEATING DATA AT DES HTG
COOLING OA DB / WB 26.9 °C / 18.3 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 39 m² 235 - 39 m² 300 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1037 W 1037 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 30 0
>> Total Zone Loads - 1609 176 - 330 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' C1-0057-Corridor '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 39 0.452 - 235 - 300
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' C1-0082-Corridor '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 29.2 °C / 19.2 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 16 m² 76 - 16 m² 123 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 891 - 4 m² 95 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3240 W 3240 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 1535 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 175 0
>> Total Zone Loads - 4882 352 - 1928 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' C1-0082-Corridor '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 16 0.452 - 76 - 123
DOOR GLASS 4 1.400 0.820 13 879 95
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' C1-0066 Entree '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 29.0 °C OCCUPIED T-STAT 17.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 187 - 3 m² - -
Wall Transmission 3 m² 6 - 3 m² 18 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 21 - 3 m² 53 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 6 m² 510 - 6 m² 122 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1447 W 1447 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 150 W 150 - 0 0 -
People 40 2696 1408 0 0 0
Infiltration - 0 0 - 1134 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 133 0
>> Total Zone Loads - 5017 1408 - 1460 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' C1-0066 Entree '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 3 0.452 - 6 - 18
WINDOW 1 3 1.400 0.820 21 187 53
DOOR GLASS 6 1.400 0.820 47 463 122
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' CR-0000-Bureau-1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.3 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 735 - 5 m² - -
Wall Transmission 45 m² 170 - 45 m² 385 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 5 m² 52 - 5 m² 138 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 17 m² 59 - 17 m² 68 -
Ceiling 24 m² -26 - 24 m² 554 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 515 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 166 0
>> Total Zone Loads - 2324 180 - 1826 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' CR-0000-Bureau-1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 14 0.452 - 72 - 124
WINDOW 1 3 1.400 0.820 26 510 67
E EXPOSURE
WALL 30 0.452 - 98 - 261
WINDOW 1 3 1.400 0.820 27 225 70
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' CR-0001-Bureau-2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.3 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 510 - 3 m² - -
Wall Transmission 14 m² 72 - 14 m² 124 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 26 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 17 m² 59 - 17 m² 68 -
Ceiling 24 m² -26 - 24 m² 554 -
Overhead Lighting 480 W 480 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 515 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 133 0
>> Total Zone Loads - 1936 180 - 1462 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' CR-0001-Bureau-2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 14 0.452 - 72 - 124
WINDOW 1 3 1.400 0.820 26 510 67
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' CR-0002-Bureau-3 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.3 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 510 - 3 m² - -
Wall Transmission 14 m² 72 - 14 m² 124 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 26 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 17 m² 59 - 17 m² 68 -
Ceiling 24 m² -26 - 24 m² 554 -
Overhead Lighting 480 W 480 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 515 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 133 0
>> Total Zone Loads - 1936 180 - 1462 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' CR-0002-Bureau-3 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 14 0.452 - 72 - 124
WINDOW 1 3 1.400 0.820 26 510 67
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' CR-0003-Bureau-4 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.3 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 510 - 3 m² - -
Wall Transmission 14 m² 72 - 14 m² 124 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 26 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 17 m² 59 - 17 m² 68 -
Ceiling 24 m² -26 - 24 m² 554 -
Overhead Lighting 480 W 480 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 515 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 133 0
>> Total Zone Loads - 1936 180 - 1462 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' CR-0003-Bureau-4 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 14 0.452 - 72 - 124
WINDOW 1 3 1.400 0.820 26 510 67
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' CR-0004-Bureau-5 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.3 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 510 - 3 m² - -
Wall Transmission 14 m² 72 - 14 m² 124 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 26 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 17 m² 59 - 17 m² 68 -
Ceiling 24 m² -26 - 24 m² 554 -
Overhead Lighting 480 W 480 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 515 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 133 0
>> Total Zone Loads - 1936 180 - 1462 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' CR-0004-Bureau-5 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 14 0.452 - 72 - 124
WINDOW 1 3 1.400 0.820 26 510 67
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' CR-0005-Accueil '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.3 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 1020 - 5 m² - -
Wall Transmission 27 m² 134 - 27 m² 231 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 5 m² 51 - 5 m² 135 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 43 m² 216 - 43 m² 241 -
Ceiling 66 m² -72 - 66 m² 1525 -
Overhead Lighting 1426 W 1426 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 150 W 150 - 0 0 -
People 20 1348 704 0 0 0
Infiltration - 0 0 - 1415 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 355 0
>> Total Zone Loads - 4273 704 - 3901 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' CR-0005-Accueil '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 27 0.452 - 134 - 231
WINDOW 1 5 1.400 0.820 51 1020 135
TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' CR-0008-Commerce '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.3 °C / 19.9 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 510 - 3 m² - -
Wall Transmission 40 m² 155 - 40 m² 348 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 26 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 258 - 36 m² 288 -
Ceiling 18 m² -20 - 18 m² 416 -
Overhead Lighting 389 W 389 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 386 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 150 0
>> Total Zone Loads - 2134 180 - 1655 0
TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' CR-0008-Commerce '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 15 0.452 - 77 - 133
WINDOW 1 3 1.400 0.820 26 510 67
W EXPOSURE
WALL 25 0.452 - 78 - 215
TABLE 1.8.A. COMPONENT LOADS FOR SPACE '' CR-0020-Reserve Cafe '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 40 m² 194 - 40 m² 339 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 327 - 4 m² 93 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 0 - 15 m² 90 -
Ceiling 18 m² 0 - 18 m² 416 -
Overhead Lighting 389 W 389 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 150 W 150 - 0 0 -
People 8 657 633 0 0 0
Infiltration - 0 0 - 386 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 132 0
>> Total Zone Loads - 1717 633 - 1457 0
TABLE 1.8.B. ENVELOPE LOADS FOR SPACE '' CR-0020-Reserve Cafe '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 15 0.452 - 59 - 125
DOOR GLASS 4 1.400 0.820 48 279 93
W EXPOSURE
WALL 25 0.452 - 135 - 215
TABLE 1.9.A. COMPONENT LOADS FOR SPACE '' CR-0021-Cafeteria '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 374 - 5 m² - -
Wall Transmission 28 m² 113 - 28 m² 240 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 5 m² 70 - 5 m² 135 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 288 - 36 m² 288 -
Ceiling 52 m² 0 - 52 m² 1201 -
Overhead Lighting 1123 W 1123 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 20 1642 1582 0 0 0
Infiltration - 0 0 - 1115 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 298 0
>> Total Zone Loads - 3860 1582 - 3277 0
TABLE 1.9.B. ENVELOPE LOADS FOR SPACE '' CR-0021-Cafeteria '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 28 0.452 - 113 - 240
WINDOW 1 5 1.400 0.820 70 374 135
TABLE 1.10.A. COMPONENT LOADS FOR SPACE '' CR-0022-Salle de Confere '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 374 - 5 m² - -
Wall Transmission 28 m² 113 - 28 m² 240 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 5 m² 70 - 5 m² 135 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 30 m² 240 - 30 m² 240 -
Ceiling 82 m² 0 - 82 m² 1894 -
Overhead Lighting 1771 W 1771 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 50 3370 1760 0 0 0
Infiltration - 0 0 - 1758 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 427 0
>> Total Zone Loads - 6438 1760 - 4694 0
TABLE 1.10.B. ENVELOPE LOADS FOR SPACE '' CR-0022-Salle de Confere '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 28 0.452 - 113 - 240
WINDOW 1 5 1.400 0.820 70 374 135
TABLE 1.11.A. COMPONENT LOADS FOR SPACE '' CR-0023-Bureau-6 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 187 - 3 m² - -
Wall Transmission 14 m² 59 - 14 m² 124 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 35 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 17 m² 68 - 17 m² 68 -
Ceiling 24 m² 0 - 24 m² 554 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 515 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 133 0
>> Total Zone Loads - 1682 180 - 1462 0
TABLE 1.11.B. ENVELOPE LOADS FOR SPACE '' CR-0023-Bureau-6 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 14 0.452 - 59 - 124
WINDOW 1 3 1.400 0.820 35 187 67
TABLE 1.12.A. COMPONENT LOADS FOR SPACE '' CR-0024-Bureau-7 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 187 - 3 m² - -
Wall Transmission 14 m² 59 - 14 m² 124 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 35 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 17 m² 68 - 17 m² 68 -
Ceiling 24 m² 0 - 24 m² 554 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 515 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 133 0
>> Total Zone Loads - 1682 180 - 1462 0
TABLE 1.12.B. ENVELOPE LOADS FOR SPACE '' CR-0024-Bureau-7 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 14 0.452 - 59 - 124
WINDOW 1 3 1.400 0.820 35 187 67
TABLE 1.13.A. COMPONENT LOADS FOR SPACE '' CR-0025-Bureau-8 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 187 - 3 m² - -
Wall Transmission 14 m² 59 - 14 m² 124 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 35 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 17 m² 68 - 17 m² 68 -
Ceiling 24 m² 0 - 24 m² 554 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 515 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 133 0
>> Total Zone Loads - 1682 180 - 1462 0
TABLE 1.13.B. ENVELOPE LOADS FOR SPACE '' CR-0025-Bureau-8 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 14 0.452 - 59 - 124
WINDOW 1 3 1.400 0.820 35 187 67
TABLE 1.14.A. COMPONENT LOADS FOR SPACE '' CR-0026-Bureau-9 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 187 - 3 m² - -
Wall Transmission 14 m² 59 - 14 m² 124 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 35 - 3 m² 67 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 17 m² 68 - 17 m² 68 -
Ceiling 24 m² 0 - 24 m² 554 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 515 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 133 0
>> Total Zone Loads - 1682 180 - 1462 0
TABLE 1.14.B. ENVELOPE LOADS FOR SPACE '' CR-0026-Bureau-9 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 14 0.452 - 59 - 124
WINDOW 1 3 1.400 0.820 35 187 67
TABLE 1.15.A. COMPONENT LOADS FOR SPACE '' CR-0027-Bureau-10 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.7 °C / 18.7 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 25.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 518 - 5 m² - -
Wall Transmission 45 m² 239 - 45 m² 385 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 5 m² 24 - 5 m² 138 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 17 m² 68 - 17 m² 68 -
Ceiling 24 m² 0 - 24 m² 554 -
Overhead Lighting 518 W 518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 515 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 166 0
>> Total Zone Loads - 2183 180 - 1826 0
TABLE 1.15.B. ENVELOPE LOADS FOR SPACE '' CR-0027-Bureau-10 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 14 0.452 - 63 - 124
WINDOW 1 3 1.400 0.820 12 117 67
E EXPOSURE
WALL 30 0.452 - 176 - 261
WINDOW 1 3 1.400 0.820 12 401 70
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' CR-0006/16 Hall Attente '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 33.4 °C / 19.6 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 34 m² 112 - 34 m² 261 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 10 m² 2866 - 10 m² 238 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 116 m² 164 - 116 m² 2192 -
Overhead Lighting 2506 W 2505 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 25 1685 880 0 0 0
Infiltration - 0 0 - 1187 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 388 0
>> Total Zone Loads - 7332 880 - 4266 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' CR-0006/16 Hall Attente '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 19 0.452 - 78 - 146
DOOR GLASS 10 1.400 0.820 63 2803 238
W EXPOSURE
WALL 15 0.452 - 35 - 115
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' CR-0028 Admin Corridor '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0200 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.3 °C / 18.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 110 m² -7 - 110 m² 2079 -
Overhead Lighting 2376 W 2376 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 15 1011 528 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 208 0
>> Total Zone Loads - 3380 528 - 2287 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' CR-0028 Admin Corridor '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' CR-0038 Hall de Recep '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 29.2 °C / 19.2 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 24 m² 3609 - 24 m² - -
Wall Transmission 168 m² 688 - 168 m² 1293 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 24 m² 76 - 24 m² 565 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 245 - 4 m² 95 -
Floor Transmission 88 m² 0 - 88 m² 367 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1426 W 1426 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 15 1011 528 0 0 0
Infiltration - 0 0 - 675 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 300 0
>> Total Zone Loads - 7354 528 - 3296 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' CR-0038 Hall de Recep '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 48 0.452 - 172 - 369
DOOR GLASS 4 1.400 0.820 13 232 95
N EXPOSURE
WALL 42 0.452 - 142 - 323
WINDOW 1 10 1.400 0.820 32 589 238
E EXPOSURE
WALL 78 0.452 - 374 - 602
WINDOW 1 6 1.400 0.820 20 1373 149
WINDOW 2 8 1.400 0.820 24 1647 179
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' CR-0038 Hall de Recep '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 29.2 °C / 19.2 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 29.0 °C OCCUPIED T-STAT 17.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 24 m² 3609 - 24 m² - -
Wall Transmission 168 m² 536 - 168 m² 1141 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 24 m² 9 - 24 m² 499 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 234 - 4 m² 84 -
Floor Transmission 88 m² 0 - 88 m² 324 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1426 W 1426 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 15 1011 528 0 0 0
Infiltration - 0 0 - 596 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 264 0
>> Total Zone Loads - 7124 528 - 2908 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' CR-0038 Hall de Recep '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 48 0.452 - 129 - 326
DOOR GLASS 4 1.400 0.820 2 232 84
N EXPOSURE
WALL 42 0.452 - 104 - 285
WINDOW 1 10 1.400 0.820 4 589 210
E EXPOSURE
WALL 78 0.452 - 303 - 531
WINDOW 1 6 1.400 0.820 2 1373 131
WINDOW 2 8 1.400 0.820 3 1647 158
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 0.0 Corridor '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1162 - 8 m² - -
Wall Transmission 133 m² 1109 - 133 m² 1639 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 84 - 8 m² 183 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 158 m² -664 - 158 m² 3650 -
Overhead Lighting 3413 W 3413 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 1616 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 709 0
>> Total Zone Loads - 5442 176 - 7797 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 0.0 Corridor '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 13 0.723 - 146 - 165
WINDOW 1 3 1.400 0.820 28 339 61
N EXPOSURE
WALL 32 0.723 - 202 - 399
WINDOW 1 3 1.400 0.820 28 204 61
NW EXPOSURE
WALL 20 0.723 - 149 - 246
SW EXPOSURE
WALL 25 0.723 - 222 - 307
W EXPOSURE
WALL 13 0.723 - 121 - 165
WINDOW 1 3 1.400 0.820 28 619 61
E EXPOSURE
WALL 5 0.723 - 54 - 61
NE EXPOSURE
WALL 24 0.723 - 216 - 295
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 0.0 Corridor-2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.1 °C / 18.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 39 m² 11815 - 39 m² - -
Wall Transmission 47 m² 92 - 47 m² 578 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 39 m² 63 - 39 m² 928 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 60 m² -338 - 60 m² 1386 -
Overhead Lighting 1296 W 1296 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 921 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 381 0
>> Total Zone Loads - 13266 176 - 4194 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 0.0 Corridor-2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 18 0.723 - -40 - 221
S EXPOSURE
WALL 29 0.723 - 132 - 357
WINDOW 1 39 1.400 0.820 63 11815 928
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' 12.6 Corridor '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1162 - 8 m² - -
Wall Transmission 133 m² 1109 - 133 m² 1639 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 84 - 8 m² 183 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3413 W 3413 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 1616 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 344 0
>> Total Zone Loads - 6105 176 - 3782 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' 12.6 Corridor '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 13 0.723 - 146 - 165
WINDOW 1 3 1.400 0.820 28 339 61
N EXPOSURE
WALL 32 0.723 - 202 - 399
WINDOW 1 3 1.400 0.820 28 204 61
NW EXPOSURE
WALL 20 0.723 - 149 - 246
SW EXPOSURE
WALL 25 0.723 - 222 - 307
W EXPOSURE
WALL 13 0.723 - 121 - 165
WINDOW 1 3 1.400 0.820 28 619 61
E EXPOSURE
WALL 5 0.723 - 54 - 61
NE EXPOSURE
WALL 24 0.723 - 216 - 295
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' 12.6 Corridor-2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.1 °C / 18.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 43 m² 11916 - 43 m² - -
Wall Transmission 93 m² -9 - 93 m² 1145 -
Roof Transmission 60 m² 576 - 60 m² 735 -
Window Transmission 43 m² 70 - 43 m² 1020 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1296 W 1296 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 921 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 382 0
>> Total Zone Loads - 14185 176 - 4203 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' 12.6 Corridor-2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 64 0.723 - -141 - 789
WINDOW 1 4 1.400 0.820 6 100 91
S EXPOSURE
WALL 29 0.723 - 132 - 357
WINDOW 1 39 1.400 0.820 63 11815 928
H EXPOSURE
ROOF 60 0.721 - 576 - 735
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' 16.10 Corridor-N '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.7 °C / 21.6 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 993 - 8 m² - -
Wall Transmission 149 m² 956 - 149 m² 1836 -
Roof Transmission 158 m² 3749 - 158 m² 1936 -
Window Transmission 8 m² 92 - 8 m² 183 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3413 W 3413 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 1616 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 557 0
>> Total Zone Loads - 9540 176 - 6128 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' 16.10 Corridor-N '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 13 0.723 - 146 - 165
WINDOW 1 3 1.400 0.820 31 391 61
N EXPOSURE
WALL 32 0.723 - 154 - 399
WINDOW 1 3 1.400 0.820 31 165 61
NW EXPOSURE
WALL 20 0.723 - 100 - 246
SW EXPOSURE
WALL 25 0.723 - 139 - 307
W EXPOSURE
WALL 29 0.723 - 164 - 362
WINDOW 1 3 1.400 0.820 31 437 61
E EXPOSURE
WALL 5 0.723 - 54 - 61
NE EXPOSURE
WALL 24 0.723 - 200 - 295
H EXPOSURE
ROOF 158 0.721 - 3749 - 1936
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' 4.55 Corridor '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1162 - 8 m² - -
Wall Transmission 133 m² 1109 - 133 m² 1639 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 84 - 8 m² 183 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3413 W 3413 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 1616 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 344 0
>> Total Zone Loads - 6105 176 - 3782 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' 4.55 Corridor '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 13 0.723 - 146 - 165
WINDOW 1 3 1.400 0.820 28 339 61
N EXPOSURE
WALL 32 0.723 - 202 - 399
WINDOW 1 3 1.400 0.820 28 204 61
NW EXPOSURE
WALL 20 0.723 - 149 - 246
SW EXPOSURE
WALL 25 0.723 - 222 - 307
W EXPOSURE
WALL 13 0.723 - 121 - 165
WINDOW 1 3 1.400 0.820 28 619 61
E EXPOSURE
WALL 5 0.723 - 54 - 61
NE EXPOSURE
WALL 24 0.723 - 216 - 295
TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' 4.55 Corridor-2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.1 °C / 18.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 43 m² 11916 - 43 m² - -
Wall Transmission 93 m² -9 - 93 m² 1145 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 43 m² 70 - 43 m² 1020 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1296 W 1296 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 921 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 309 0
>> Total Zone Loads - 13609 176 - 3394 0
TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' 4.55 Corridor-2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 64 0.723 - -141 - 789
WINDOW 1 4 1.400 0.820 6 100 91
S EXPOSURE
WALL 29 0.723 - 132 - 357
WINDOW 1 39 1.400 0.820 63 11815 928
TABLE 1.8.A. COMPONENT LOADS FOR SPACE '' 9.1 Corridor-2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.1 °C / 18.0 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 43 m² 11916 - 43 m² - -
Wall Transmission 93 m² -9 - 93 m² 1145 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 43 m² 70 - 43 m² 1020 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1296 W 1296 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 921 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 309 0
>> Total Zone Loads - 13609 176 - 3394 0
TABLE 1.8.B. ENVELOPE LOADS FOR SPACE '' 9.1 Corridor-2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 64 0.723 - -141 - 789
WINDOW 1 4 1.400 0.820 6 100 91
S EXPOSURE
WALL 29 0.723 - 132 - 357
WINDOW 1 39 1.400 0.820 63 11815 928
TABLE 1.9.A. COMPONENT LOADS FOR SPACE '' 9.10 Corridor '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.3 °C / 21.4 °C HEATING OA DB / WB 2.0 °C / 2.0 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 19.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1162 - 8 m² - -
Wall Transmission 133 m² 1109 - 133 m² 1639 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 84 - 8 m² 183 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3413 W 3413 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 1616 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 10% 344 0
>> Total Zone Loads - 6105 176 - 3782 0
TABLE 1.9.B. ENVELOPE LOADS FOR SPACE '' 9.10 Corridor '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 13 0.723 - 146 - 165
WINDOW 1 3 1.400 0.820 28 339 61
N EXPOSURE
WALL 32 0.723 - 202 - 399
WINDOW 1 3 1.400 0.820 28 204 61
NW EXPOSURE
WALL 20 0.723 - 149 - 246
SW EXPOSURE
WALL 25 0.723 - 222 - 307
W EXPOSURE
WALL 13 0.723 - 121 - 165
WINDOW 1 3 1.400 0.820 28 619 61
E EXPOSURE
WALL 5 0.723 - 54 - 61
NE EXPOSURE
WALL 24 0.723 - 216 - 295
Soğutma, ΔT:8C, Tmahal: 25C, Tuf: 17C
Isıtma, ΔT:5.5C, Tmahal: 21C, Tuf: 26.5C
GP‐B2 AIR HANDLING UNIT BALANCE TABLE
Selected
Exhaust Air
Area Heat Loss Supply Air
Room No Room Name Flow Air Change
(m2) (Watt) Flow
(m3/h)
(m3/h)
BR‐0000 Stockage Buanderie 116.0 289 750.0 750.0 2.4
BR‐0001 Local Dechets 41.0 289 250.0 250.0 2.3
BR‐0002
BR‐0003 WC 6.0 0 ‐ 100.0 6.2
BR‐0004
BR‐0005
BR‐0006 WC 6.0 0 ‐ 100.0 6.2
BR‐0007
BR‐0009 Reserve 5.0 289 ‐ 50.0 3.7
BR‐0010 Bureau 12.5 445 100.0 100.0 3.0
BR‐0011
Vest‐Sanit 12.0 509 150.0 200.0 6.2
BR‐0012
BR‐0013 WC 1.5 ‐ 50.0 12.3
BR‐0014
Vest‐Sanit 12.0 509 150.0 200.0 6.2
BR‐0015
BR‐0016 WC 1.5 ‐ 50.0 12.3
BR‐0017 Buanderie 40.5 1231 1,300.0 1,450.0 13.3
BR‐0018 Zone Sale 40.5 2243 1,300.0 1,400.0 12.8
BR‐0022 Buanderie 15.0 333 150.0 ‐ 3.7
GP‐B2 AIR FLOW 6,137.0 4,150 4,700
4.39
Isıtma, Tmahal: 18C, Tuf: 22.5C
GP‐B3 AIR HANDLING UNIT BALANCE TABLE
Selected
Exhaust Air
Area Supply Air
Room No Room Name Flow Air Change
(m2) Flow
(m3/h)
(m3/h)
BR‐0079 Burea 11.5 150.0 150.0 4.8
BR‐0080 Magasin 35.0 650.0 650.0 6.9
BR‐0081 Magasin 60.0 1,000.0 1,000.0 6.2
BR‐0055 Corridor 54.0 200 0 1.37
GP‐B3 AIR FLOW 2,000.0 1,800.0
Soğutma, Tmahal: 25C, Tuf: 25C
Isıtma, Tmahal: 21C, Tuf: 21C
GP‐B4 AIR HANDLING UNIT BALANCE TABLE
Area Supply Air Exhaust Air
Room No Room Name Air Change
(m2) (m3/h) (m3/h)
BR‐0038
BR‐0039 Vestiaires Sanitaires Personnel 39.0 500.0 400.0 4.7
BR‐0042
BR‐0040 Dusche 2.0 ‐ 75.0 13.9
BR‐0041 WC 1.5 ‐ 50.0 12.3
BR‐0046 WC 1.5 ‐ 50.0 12.3
BR‐0045 Dusche 2.0 ‐ 75.0 13.9
BR‐0043
BR‐0044 Vestiaires Sanitaires Personnel 39.0 500.0 400.0 4.7
BR‐0047
BR‐0048 Salle de Detente Personnel 41.0 400.0 400.0 3.6
BR‐0049
BR‐0050 WC 6.0 ‐ 100.0 6.2
BR‐0051
BR‐0052
BR‐0053 WC 6.0 ‐ 100.0 6.2
BR‐0054
BR‐0055 Corridor 54.0 200.0 ‐ 1.4
BR‐0056 Restaurant 95.5 3,000.0 2,000.0 11.6
BR‐0057 Distribution Restaurant 20.0 ‐ 1,000.0 18.5
BR‐0069 WC 1.5 ‐ 50.0 12.3
BR‐0072 WC 1.5 ‐ 50.0 12.3
GP‐B4 AIR FLOW 4,600 4,750
Soğutma, Tmahal: 25C, Tuf: 25C
Isıtma, Tmahal: 21C, Tuf: 21C
GP‐B5 AIR HANDLING UNIT BALANCE TABLE
Area Supply Air Exhaust Air
Room No Room Name Air Change
(m2) (m3/h) (m3/h)
BR‐0074 Stock Denrees 37.5 400.0 500.0 4.9
BR‐0064 Plonge Chariots
42.5 900.0 500.0 7.8
BR‐0065 Lavage
BR‐0063 Preparation Poisson 6.0 200.0 ‐ 12.3
BR‐0062 Preparation Viandes 7.5 200.0 500.0 24.7
BR‐0061 Preparation Legumes 18.0 450.0 500.0 10.3
BR‐0060 Pain‐Patisserie 12.0 450.0 500.0 15.4
BR‐0059 Chaud & Cuisine 70.5 4,500.0 6,000.0 31.5
BR‐0058 Froid & Portionnement 43.5 900.0 500.0 7.7
BR‐0067 Bureau 5.5 100.0 ‐ 6.7
GP‐B5 AIR FLOW 8,100 9,000
Soğutma, Tmahal: 25C, Tuf: 25C
Isıtma, Tmahal: 18C, Tuf: 18C
GP‐B6 AIR HANDLING UNIT BALANCE TABLE
Area Supply Air Exhaust Air
Room No Room Name Air Change
(m2) (m3/h) (m3/h)
B1‐0086 Echo‐1 16.0 200.0 200.0 4.6
B1‐0087 Echo‐1 Room 2.0 ‐ 50.0 9.3
B1‐0088 Echo‐2 16.0 200.0 200.0 4.6
B1‐0089 Echo‐2 Room 2.0 ‐ 50.0 9.3
B1‐0090 Echo‐3 16.0 200.0 200.0 4.6
B1‐0091 Echo‐3 Room 2.0 ‐ 50.0 9.3
B1‐0092 Echo‐4 16.0 200.0 200.0 4.6
B1‐0093 Echo‐4 Room 2.0 ‐ 50.0 9.3
B1‐0094 Echo Corridor 29.0 200.0 ‐ 2.6
B1‐0095 Bureau du Personel Medical 41.0 300.0 300.0 2.7
B1‐0096
B1‐0097 WC 6.0 ‐ 150.0 9.3
B1‐0098
B1‐0099
B1‐0100 WC 6.0 ‐ 150.0 9.3
B1‐0101
B1‐0102 Radiologie 146.0 800.0 1,100.0 1.8
B1‐0103 Corridor 79.0 400.0 300.0 2.1
B1‐0104 Radio‐4 37.5 500.0 375.0 4.9
B1‐0105
WC 13.0 ‐ 250.0 7.1
B1‐0106
B1‐0107 Lavage 1.5 ‐ 50.0 12.3
B1‐0108 Radio‐3 36.5 500.0 375.0 5.1
B1‐0109 Radio‐2 36.5 500.0 375.0 5.1
B1‐0110 Radio‐1 37.5 500.0 375.0 4.9
B1‐0111
WC 13.0 ‐ 250.0 7.1
B1‐0112
B1‐0113 Lavage 1.5 ‐ 50.0 12.3
B1‐0114 Scanner 38.0 500.0 500.0 4.9
B1‐0115 Bureau‐1 7.0 100.0 ‐ 5.3
B1‐0116 Bureau‐2 7.0 100.0 ‐ 5.3
B1‐0117 Local Technique‐1 6.5 150.0 ‐ 8.5
B1‐0118 Local Technique‐2 9.0 ‐ 150.0 6.2
B1‐0119 Preperation 22.5 200.0 ‐ 3.3
B1‐0120 Preperation WC 2.0 ‐ 100.0 18.5
B1‐0121 Preperation Room‐1 2.0 ‐ 50.0 9.3
B1‐0122 Preperation Room‐2 2.0 ‐ 50.0 9.3
B1‐0123 Attente 20.0 400.0 400.0 8.3
B1‐0124
B1‐0125 WC 6.0 ‐ 150.0 9.3
B1‐0126
B1‐0127
B1‐0128 WC 6.0 ‐ 150.0 9.3
B1‐0129
B1‐0130 Accueil Secreteriat 22.5 100.0 ‐ 1.6
B1‐0132 Depot Sterile 22.0 100.0 100.0 1.5
B1‐0133 Depot Propre 22.0 100.0 100.0 1.5
GP‐B6 AIR FLOW 6,250 6,850
Soğutma, Tmahal: 25C, Tuf: 25C
Isıtma, Tmahal: 21C, Tuf: 21C
GP‐B7 AIR HANDLING UNIT BALANCE TABLE
Area Supply Air Exhaust Air
Room No Room Name Air Change
(m2) (m3/h) (m3/h)
B1‐0136 Sanitarias Public 24.5 200.0 ‐ 3.4
B1‐0137 Lits Observation 87.0 800.0 600.0 3.4
B1‐0138 Sanitaria 3.0 ‐ 50.0 6.2
B1‐0139 US 1.2 ‐ 50.0 15.4
B1‐0140 Douche 3.0 ‐ 100.0 12.3
B1‐0141 Urgences 113.0 300.0 700.0 2.6
B1‐0142 Salle Examens 21.0 250.0 250.0 4.4
B1‐0143 Salle Examens 21.0 250.0 250.0 4.4
B1‐0144 Salle Examens 21.0 250.0 250.0 4.4
B1‐0145 Attente Public 19.5 450.0 350.0 8.5
B1‐0163
WC 2.5 ‐ 50.0 7.4
B1‐0164
B1‐0146 Corridor 10.5 ‐ 150.0 6.0
B1‐0147 Corridor 11.5 ‐ 150.0 5.4
B1‐0148 Garde 17.5 300.0 ‐ 7.1
B1‐0149 Salle de Petite Chirurgie 25.5 400.0 400.0 5.8
B1‐0150 Bureau 16.5 100.0 100.0 2.2
B1‐0151 Bureau 14.0 200.0 200.0 5.3
B1‐0152 Detente 18.0 300.0 300.0 6.2
B1‐0158 Salle de Decrassage 19.0 250.0 250.0 4.9
B1‐0159 Unite Propre 7.5 100.0 ‐ 4.9
B1‐0160 Salle Examens 20.0 250.0 250.0 4.6
B1‐0161 Unite Sale 10.5 ‐ 100.0 3.5
B1‐0162 Salle de Platre 19.0 250.0 250.0 4.9
GP‐B7 AIR FLOW 4,650 4,800
Soğutma, Tmahal: 25C, Tuf: 25C
Isıtma, Tmahal: 21C, Tuf: 21C
GP‐B8 AIR HANDLING UNIT BALANCE TABLE
Area Supply Air Exhaust Air
Room No Room Name Air Change
(m2) (m3/h) (m3/h)
B2‐0214
B2‐0215 Sanitaires Public 6.5 ‐ 100 5.7
B2‐0216
B2‐0217 Proprete 2.0 ‐ 50 9.3
B2‐0232
B2‐0233 Sanitaires Public 6.5 ‐ 100 5.7
B2‐0234
B2‐0235 Proprete 2.0 ‐ 50 9.3
B2‐0236 Secretariat 13.0 100 100 2.8
B2‐0237 Banque de Sang 14.0 100 100 2.6
B2‐0239 Bureau Medical 33.0 180 200 2.2
B2‐0241 Laverie 18.0 130 150 3.1
B2‐0242 Reserve 17.5 90 100 2.1
B2‐0245
B2‐0246 Vest. Sanitare 10.0 100 100 3.7
B2‐0247
B2‐0248
B2‐0249 Vest. Sanitare 9.0 100 100 4.1
B2‐0250
B2‐0251 Bureau 9.0 150 100 6.2
B2‐0253 Bacteriologie 40.5 800 1,000 9.1
B2‐0254 Laboratoire 199.0 2,400 2,700 5.0
B2‐0255 Centre de Tri 41.0 200 200 1.8
GP‐B8 AIR FLOW 4,350 5,150
Soğutma, Tmahal: 25C, Tuf: 25C
Isıtma, Tmahal: 21C, Tuf: 21C
GP‐B9 AIR HANDLING UNIT BALANCE TABLE
Area Supply Air Exhaust Air
Room No Room Name Air Change
(m2) (m3/h) (m3/h)
B2‐0168 CH‐1 15.5 100 ‐ 2.0
B2‐0169 WC 3.0 ‐ 100 10.1
B2‐0170 CH‐2 11.5 100 ‐ 2.6
B2‐0171 WC 3.0 ‐ 100 10.1
B2‐0172 CH‐1 12.0 100 ‐ 2.5
B2‐0173 WC 3.0 ‐ 100 10.1
B2‐0174 CH‐2 12.0 100 ‐ 2.5
B2‐0175 WC 3.0 ‐ 100 10.1
B2‐0176 CH‐3 12.0 100 ‐ 2.5
B2‐0177 WC 3.0 ‐ 100 10.1
B2‐0178 CH‐4 12.0 100 ‐ 2.5
B2‐0179 WC 3.0 ‐ 100 10.1
B2‐0180 Logements De Garde 20.5 100 50 2.0
B2‐0181 Reserve 3.0 ‐ 50 6.2
B2‐0256 Sanitaires Personnel 89.5 300 ‐ 1.4
B2‐0182
B2‐0183 WC 6.0 ‐ 100 6.2
B2‐0184
B2‐0185 CH‐8 12.0 100 ‐ 2.5
B2‐0186 WC 3.0 ‐ 100 10.1
B2‐0187 CH‐7 12.0 100 ‐ 2.5
B2‐0188 WC 3.0 ‐ 100 10.1
B2‐0189 Sejour 32.0 200 100 1.2
B2‐0190 Logements De Garde 5.0 100 150 1.2
B2‐0191 Reserve 3.0 ‐ 50 6.2
B2‐0192
WC 6.0 ‐ 100 6.2
B2‐0193
GP‐B9 AIR FLOW 1,500 1,400
Soğutma, Tmahal: 25C, Tuf: 25C
Isıtma, Tmahal: 21C, Tuf: 21C
GP‐B10 AIR HANDLING UNIT BALANCE TABLE
Area Supply Air Exhaust Air
Room No Room Name Air Change
(m2) (m3/h) (m3/h)
B2‐0194 Dialyse 140.0 900 350 0.9
B2‐0195 Box d'isolement 15.0 200 250 6.2
B2‐0197 Sejour Patients 10.0 150 150 5.6
B2‐0198
Vest. Patients 7.0 ‐ 150 7.9
B2‐0199
B2‐0200 Unite Sale 5.5 ‐ 50 3.4
B2‐0201 Bureau Medical 10.5 150 100 5.3
B2‐0202
Vest. Patients 7.0 ‐ 150 7.9
B2‐0203
B2‐0204 Dechets 2.5 ‐ 50 7.4
B2‐0205 Local Technique 28.0 150 150 2.0
GP‐B10 AIR FLOW 1,550 1,400
Soğutma, Tmahal: 25C, Tuf: 25C
Isıtma, Tmahal: 21C, Tuf: 21C
GP‐B12 AIR HANDLING UNIT BALANCE TABLE
Selected
Sensible Latent Cooling Total Cooling Calculated Air Exhaust Air
Area Heat Loss Supply Air
Room No Room Name Cooling Load Load Load Flow Flow Air Change
(m2) (Watt) Flow
(Watt) (Watt) (Watt) (m3/h) (m3/h)
(m3/h)
B4.Q.10.2 Transfert et Sas 30.5 1281 120 1401 605 475 475 275 5.2
B4.P.10.2 Bureau 9.5 1104 120 1224 206 409 400 400 14.0
B4.P.10.1 Stock Propre 13.5 457 0 457 237 169 150 ‐ 3.7
B4.O.10 Stock Sterile 13.5 457 0 457 237 169 150 ‐ 3.7
B4.N.10.5 Materiel 20.0 649 0 649 315 241 250 250 4.2
B4.N.10.1
B4.N.10.2
Dressing 15.0 ‐ ‐ ‐ ‐ ‐ 350 350 9.7
B4.N.11.1
B4.N.11.2
B4.M.10.2
B4.M.10.3
Dressing 15.0 ‐ ‐ ‐ ‐ ‐ 350 350 9.7
B4.M.11.3
B4.M.11.4
B4.M.10.1 Service 11.5 1554 120 1674 695 576 575 575 16.7
B4.O.10 Block Operatoire
103.0 3400 301 3701 2430 1,260 1,300 2,200 4.2
B4.O.10.1 Brancards
B4.O.6.1 Couloir 60.0 2682 120 2802 2654 994 ‐ 1,000 6.9
GP‐B‐12 AIR FLOW 11,584 781 12,365 7,379 4,294 4,000 5,400
Soğutma, ΔT:8C, Tmahal: 25C, Tuf: 17C 5.47
Isıtma, ΔT:5.5C, Tmahal: 21C, Tuf: 26.5C
GP‐B13 AIR HANDLING UNIT BALANCE TABLE
Selected
Sensible Latent Total Cooling Calculated Exhaust Air
Area Heat Loss Supply Air
Room No Room Name Cooling Load Cooling Load Load Air Flow Flow Air Change
(m2) (Watt) Flow
(Watt) (Watt) (Watt) (m3/h) (m3/h)
(m3/h)
B4‐R.13 Chambre 4 lift 84.0 4868 176 5044 4067 2,062 2,075 2,075 8.2
B4‐R.11.5 En Reiten 5.5 391 120 511 180 166 ‐ 50 3.0
B4‐R.11.4 Unite Salle 6.5 236 0 236 136 100 ‐ 100 5.1
B4‐Q 11 Reserve 5.0 ‐ ‐ 100 6.7
B4‐Q.15.1 Chambre 21.5 734 35 769 483 311 400 400 6.2
B4‐Q.15.2 Chambre 21.5 826 35 861 1025 350 400 400 6.2
B4‐P 15.1 Chambre 21.5 854 35 889 1072 362 400 400 6.2
B4‐P.15.2 Chambre 21.5 847 35 882 1055 359 400 400 6.2
B4‐P.13.6 Service 8.5 436 70 506 70 185 200 ‐ 7.8
B4‐P.13.7
Soins Intensif
B4‐Q.13 122.0 3661 301 3962 1143 1,551 1,550 700 4.2
Poste Infirmier Monitoring
B4‐N.13
B4‐O 13.1 Service 8.5 540 174 714 184 229 200 ‐ 7.8
B4‐N 11.4 Reserve 5.0 290 0 290 114 123 ‐ 100 6.7
B4‐O.15.1 Chambre 21.5 847 35 882 1055 359 400 400 6.2
B4‐O.15.2 Chambre 21.5 847 35 882 1055 359 400 400 6.2
B4‐N.15.1 Chambre 21.5 826 35 861 1025 350 400 400 6.2
B4‐N.15.2 Chambre 21.5 734 35 769 483 311 400 400 6.2
B4‐M.15 Chambre 4 lift 88.5 5086 176 5262 4488 2,155 2,175 2,175 8.2
B4‐M.11.4 En Reiten 5.5 433 120 553 195 183 ‐ 50 3.0
B4‐M.11.5 Unite Salle 6.5 305 0 305 179 129 ‐ 100 5.1
B4.P.11.3
B4.P.13.1
Dressing 15.0 ‐ ‐ 225 6.3
B4.P.13.2
B4.P.13.5
B4.O.11.1
B4.O.13.2
Dressing 15.0 ‐ ‐ 225 6.3
B4.O.13.3
B4.O.13.4
GP‐B‐13 AIR FLOW 22,761 1,417 24,178 18,009 9,643 9,400 9,100
Soğutma, ΔT:7C, Tmahal: 25C, Tuf: 18C 5.68
Isıtma, ΔT:6C, Tmahal: 21C, Tuf: 27C
GP‐B14 AIR HANDLING UNIT BALANCE TABLE
Selected
Sensible Latent Cooling Total Cooling Calculated Air Exhaust Air
Area Heat Loss Supply Air
Room No Room Name Cooling Load Load Load Flow Flow Air Change
(m2) (Watt) Flow
(Watt) (Watt) (Watt) (m3/h) (m3/h)
(m3/h)
B4.R.8 Salle de Reveil 119.5 7088 493 7581 4886 2,803 3,000 3,000 8.4
B4.R.11.2 Unite Propre 5.0 273 0 273 222 108 150 ‐ 10.0
B4.R.11.1 Unite Sale 5.0 101 0 101 35 40 ‐ 150 10.0
GP‐B‐14 AIR FLOW 7,462 493 7,955 5,143 2,950 3,150 3,150
Soğutma, ΔT:7.5C, Tmahal: 25C, Tuf: 17.5C 4.84
Isıtma, ΔT:5C, Tmahal: 21C, Tuf: 26C
GP‐OP‐1 AIR HANDLING UNIT BALANCE TABLE
Selected
Sensible Latent Cooling Total Cooling Calculated Air Exhaust Air
Area Heat Loss Supply Air
Room Name Cooling Load Load Load Flow Flow Air Change
(m2) (Watt) Flow
(Watt) (Watt) (Watt) (m3/h) (m3/h)
(m3/h)
OP‐1 / Chirurgie Majeure 41.5 6148 800 6948 423 3,315 3,800 3,400 30.5
OP‐1 / Unite Propre 7.5 439 120 559 51 237 200 100 8.9
OP‐1 / Scrub 14.0 605 120 725 89 326 ‐ 100 2.4
GP‐OP‐1 AIR FLOW 7,192 1,040 8,232 563 3,878 4,000 3,600
Soğutma, ΔT:5.5C, Tmahal: 24C, Tuf: 18.5C
Isıtma, ΔT:1C, Tmahal: 18C, Tuf: 19C
GP‐OP‐2 AIR HANDLING UNIT BALANCE TABLE
Selected
Sensible Latent Cooling Total Cooling Calculated Air Exhaust Air
Area Heat Loss Supply Air
Room Name Cooling Load Load Load Flow Flow Air Change
(m2) (Watt) Flow
(Watt) (Watt) (Watt) (m3/h) (m3/h)
(m3/h)
OP‐2 / Chirurgie Gyneco. 41.5 6148 800 6948 423 3,315 3,800 3,400 30.5
OP‐2 / Unite Propre 6.5 439 120 559 51 237 200 100 10.3
OP‐2 / Scrub 14.0 605 120 725 89 326 ‐ 100 2.4
GP‐OP‐2 AIR FLOW 7,192 1,040 8,232 563 3,878 4,000 3,600
Soğutma, ΔT:5.5C, Tmahal: 24C, Tuf: 18.5C
Isıtma, ΔT:1C, Tmahal: 18C, Tuf: 19C
GP‐OP‐3 AIR HANDLING UNIT BALANCE TABLE
Selected
Sensible Latent Cooling Total Cooling Calculated Air Exhaust Air
Area Heat Loss Supply Air
Room Name Cooling Load Load Load Flow Flow Air Change
(m2) (Watt) Flow
(Watt) (Watt) (Watt) (m3/h) (m3/h)
(m3/h)
Salle OP‐3 41.5 5966 800 6766 266 5,055 6,250 5,850 50.2
Unite Propre 6.5 439 120 559 51 372 400 300 20.5
Scrub 14.0 605 120 725 89 513 ‐ 100 2.4
GP‐OP‐3 AIR FLOW 7,010 1,040 8,050 406 5,940 6,650 6,250
Soğutma, ΔT:3.5C, Tmahal: 24C, Tuf: 20.5C
Isıtma, ΔT:1C, Tmahal: 18C, Tuf: 19C
GP‐OP‐4 AIR HANDLING UNIT BALANCE TABLE
Selected
Sensible Latent Cooling Total Cooling Calculated Air Exhaust Air
Area Heat Loss Supply Air
Room Name Cooling Load Load Load Flow Flow Air Change
(m2) (Watt) Flow
(Watt) (Watt) (Watt) (m3/h) (m3/h)
(m3/h)
OP‐4 / Chirurgie Majeure 41.5 6148 800 6948 423 5,209 6,250 5,850 50.2
OP‐4 / Unite Propre 6.5 439 120 559 51 372 400 300 20.5
OP‐4 / Scrub 14.0 605 120 725 89 513 ‐ 100 2.4
GP‐OP‐4 AIR FLOW 7,192 1,040 8,232 563 6,094 6,650 6,250
Soğutma, ΔT:3.5C, Tmahal: 24C, Tuf: 20.5C
Isıtma, ΔT:1C, Tmahal: 18C, Tuf: 19C
GP‐OP‐5 AIR HANDLING UNIT BALANCE TABLE
Selected
Sensible Latent Cooling Total Cooling Calculated Air Exhaust Air
Area Heat Loss Supply Air
Room Name Cooling Load Load Load Flow Flow Air Change
(m2) (Watt) Flow
(Watt) (Watt) (Watt) (m3/h) (m3/h)
(m3/h)
OP‐5 / Chirurgie Majeure 56.5 7088 800 7888 1307 7,007 8,500 8,100 50.1
OP‐5 / Unite Propre 6.5 483 120 603 123 477 500 400 25.6
OP‐5 / Scrub 14.0 807 120 927 296 798 ‐ 100 2.4
GP‐OP‐5 AIR FLOW 8,378 1,040 9,418 1,726 8,282 9,000 8,600
Soğutma, ΔT:3C, Tmahal: 24C, Tuf: 21C
Isıtma, ΔT:1C, Tmahal: 18C, Tuf: 19C
GP‐OP‐6 AIR HANDLING UNIT BALANCE TABLE
Selected
Sensible Latent Cooling Total Cooling Calculated Air Exhaust Air
Area Heat Loss Supply Air
Room Name Cooling Load Load Load Flow Flow Air Change
(m2) (Watt) Flow
(Watt) (Watt) (Watt) (m3/h) (m3/h)
(m3/h)
B1.0155 / Salle Op.‐1 31.0 5,543.0 800.0 6,343.0 156.0 3,287.6 3,000.0 2,400.0 32.3
B1.0156 / Unite Sale 8.5 184.0 ‐ 184.0 ‐ 109.1 150.0 150.0 5.9
B1.0157 / Scrub 8.7 320.0 120.0 440.0 ‐ 189.8 150.0 150.0 5.7
GP‐OP‐6 AIR FLOW 6,047.0 920.0 6,967.0 156.0 3,586.5 3,300.0 2,700.0
Soğutma, ΔT:5C, Tmahal: 24C, Tuf: 19C
Isıtma, ΔT:1C, Tmahal: 18C, Tuf: 19C
GP‐OP‐7 AIR HANDLING UNIT BALANCE TABLE
Selected
Sensible Latent Cooling Total Cooling Calculated Air Exhaust Air
Area Heat Loss Supply Air
Room Name Cooling Load Load Load Flow Flow Air Change
(m2) (Watt) Flow
(Watt) (Watt) (Watt) (m3/h) (m3/h)
(m3/h)
B2‐0208 Surface Service 10.0 460 60 520 53 171 175 175 6.5
B2‐0209 Surface Service 9.5 496 60 556 79 184 200 200 7.8
B2‐0210 Explorations Fonctuoinnelles 98.0 2621 267 2888 1189 972 975 1,475 6.3
B2‐0211 Acueil Controle 6.5 513 35 548 119 190 200 300 12.8
B2‐0213 Antente 13.0 1494 598 2092 429 554 450 550 17.6
B2‐0219 Salle‐1 33.0 4568 800 5368 ‐ 1,693 2,000 1,500 20.2
B2‐0220 Scrub 6.0 290 120 410 ‐ 108 ‐ 100 5.6
B2‐0221 Scrub 6.0 290 120 410 ‐ 108 ‐ 100 5.6
B2‐0222 Circulation Sale 6.7 205 0 205 134 76 ‐ 100 6.2
B2‐0224 Salle‐2 29.0 4473 800 5273 ‐ 1,658 2,000 1,500 23.0
B2‐0226 Salle‐3 29.5 4489 800 5289 ‐ 1,664 2,000 1,500 22.6
B2‐0227 Entretien Material 51.0 1702 267 1969 1087 631 550 1,050 8.6
B2‐0228 Scrub 9.0 336 120 456 ‐ 125 ‐ 200 9.3
B2‐0229 Salle‐4 28.0 5352 800 6152 839 1,984 2,000 1,500 23.8
GP‐OP‐7 AIR FLOW 27,289 4,847 32,136 3,929 10,116 10,550 10,250
Soğutma, ΔT:8C, Tmahal: 24C, Tuf: 16C
Isıtma, ΔT:1.5C, Tmahal: 21C, Tuf: 22.5C
GP‐C1 AIR HANDLING UNIT BALANCE TABLE
Area Supply Air Exhaust Air
Room No Room Name Air Change
(m2) (m3/h) (m3/h)
CR‐0000 Bureau‐1 22.5 100 100 1.6
CR‐0001 Bureau‐2 23.5 100 100 1.6
CR‐0002 Bureau‐3 23.5 100 100 1.6
CR‐0003 Bureau‐4 23.5 100 100 1.6
CR‐0004 Bureau‐5 23.5 100 100 1.6
CR‐0005 Accueil 64.5 200 200 1.1
CR‐0022 Sale de Conferences 78.5 2,000 1,900 9.4
CR‐0023 Bureau‐6 23.5 100 100 1.6
CR‐0024 Bureau‐7 23.5 100 100 1.6
CR‐0025 Bureau‐8 23.5 100 100 1.6
CR‐0026 Bureau‐9 23.5 100 100 1.6
CR‐0027 Bureau‐10 23.5 100 100 1.6
CR‐0028 Attente 107.0 400 200 1.4
CR‐0029 Archieves 22.0 100 100 1.7
CR‐0030
CR‐0031 WC 5.5 ‐ 100 6.7
CR‐0032
CR‐0033
CR‐0034 Sanit Public 5.5 ‐ 100 6.7
CR‐0035
CR‐0036 Reserve 4.5 ‐ 50 4.1
CR‐0037 Vestiaire 4.5 ‐ 50 4.1
GP‐C1 AIR FLOW 3,700 3,700
GP‐C2 AIR HANDLING UNIT BALANCE TABLE
Area Supply Air Exhaust Air
Room No Room Name Air Change
(m2) (m3/h) (m3/h)
CR‐0006 Hall Entree 41.0 ‐ 800 8.1
CR‐0008 Commerce 17.0 200 200 4.4
CR‐0011
CR‐0012
Sanit Public 12.0 ‐ 150 4.6
CR‐0013
CR‐0014
CR‐0015 Hall Attente 73.5 1,100 ‐ 6.2
CR‐0016
CR‐0017
Sanit Public 12.0 ‐ 150 4.6
CR‐0018
CR‐0019
CR‐0020 Reserve Cafeteria 17.0 200 200 4.4
CR‐0021 Cafeteria 47.5 2,500 2,500 19.5
GP‐C2 AIR FLOW 4,000 4,000
GP‐C3 AIR HANDLING UNIT BALANCE TABLE
Area Supply Air Exhaust Air
Room No Room Name Air Change
(m2) (m3/h) (m3/h)
C1‐0039 Bureau Medical 22.0 100 100 1.7
C1‐0040 Consultation 5 21.5 200 ‐ 3.4
C1‐0041 WC 1.5 ‐ 100 24.7
C1‐0042 Consultation 6 21.5 200 ‐ 3.4
C1‐0043 WC 1.5 ‐ 100 24.7
C1‐0044 Consultation 7 21.5 200 ‐ 3.4
C1‐0045 WC 1.5 ‐ 100 24.7
C1‐0046 Consultation 8 21.5 200 ‐ 3.4
C1‐0047 WC 1.5 ‐ 100 24.7
C1‐0048 Consultation 9 21.5 200 ‐ 3.4
C1‐0049 WC 1.5 ‐ 100 24.7
C1‐0050 Consultation 10 21.5 200 ‐ 3.4
C1‐0051 WC 1.5 ‐ 100 24.7
C1‐0052 Consultation 11 21.5 200 ‐ 3.4
C1‐0053 WC 1.5 ‐ 100 24.7
C1‐0054 Consultation 12 21.5 200 ‐ 3.4
C1‐0055 WC 1.5 ‐ 100 24.7
C1‐0056 Bureau Medecin 22.0 100 100 1.7
C1‐0058 Reserve 9.5 ‐ 50 1.9
C1‐0059
C1‐0060 WC 6.0 ‐ 100 6.2
C1‐0061
C1‐0062
C1‐0063 WC 6.0 ‐ 100 6.2
C1‐0064
C1‐0065 Accueil 22.0 150 150 2.5
C1‐0066 Entree 65.5 900 700 5.7
C1‐0067 Prelevements 20.5 300 ‐ 6.1
C1‐0068 Prelevements‐1 7.0 ‐ 75 4.5
C1‐0069 Prelevements‐2 5.5 ‐ 50 3.8
C1‐0070 Prelevements‐3 7.0 ‐ 75 4.5
C1‐0071 WC 2.0 ‐ 50 10.4
C1‐0072 WC 2.0 ‐ 50 10.4
C1‐0073 Consultation‐1 21.5 200 ‐ 3.9
C1‐0074 WC 1.5 ‐ 100 27.8
C1‐0075 Consultation‐2 21.5 200 ‐ 3.9
C1‐0076 WC 1.5 ‐ 100 27.8
C1‐0077 Consultation‐3 21.5 200 ‐ 3.9
C1‐0078 WC 1.5 ‐ 100 27.8
C1‐0079 Consultation‐4 21.5 200 ‐ 3.9
C1‐0080 WC 1.5 ‐ 100 27.8
C1‐0081 Bureau Medical 22.5 100 100 1.6
C1‐0082 Couloir 140.5 300 900 0.9
C1‐0083 Menage 9.5 ‐ 50 1.9
C1‐0084
C1‐0085 WC 6.0 ‐ 100 6.2
C1‐0096
C1‐0087
C1‐0088 WC 6.0 ‐ 100 6.2
C1‐0089
C1‐0090 Unite Sale 5.5 ‐ 100 6.7
C1‐0091 Infirmerie 12.0 100 100 3.1
C1‐0092 Unite Propre 11.0 50 100 3.4
GP‐C3 AIR FLOW 4,500 4,350
GP‐C4 AIR HANDLING UNIT BALANCE TABLE
Area Supply Air Exhaust Air
Room No Room Name Air Change
(m2) (m3/h) (m3/h)
BATIMENT‐C‐ NIVEAU +16.10
C4‐0211 Soins 22.0 100 100 1.7
C4‐0212 Chambre 2 lits 1 19.0 100 ‐ 1.6
C4‐0213 WC 3.0 ‐ 100 12.3
C4‐0214 Chambre 2 lits 2 19.0 100 ‐ 1.6
C4‐0215 WC 3.0 ‐ 100 12.3
C4‐0216 Chambre 2 lits 3 19.0 100 ‐ 1.6
C4‐0217 WC 3.0 ‐ 100 12.3
C4‐0218 Chambre 2 lits 4 19.0 100 ‐ 1.6
C4‐0219 WC 3.0 ‐ 100 12.3
C4‐0220 Chambre 2 lits 5 19.0 100 ‐ 1.6
C4‐0221 WC 3.0 ‐ 100 12.3
C4‐0222 Chambre 2 lits 6 19.0 100 ‐ 1.6
C4‐0223 WC 3.0 ‐ 100 12.3
C4‐0224 Chambre 2 lits 7 19.0 100 ‐ 1.6
C4‐0225 WC 3.0 ‐ 100 12.3
C4‐0226 Chambre 2 lits 8 19.0 100 ‐ 1.6
C4‐0227 WC 3.0 ‐ 100 12.3
C4‐0228 Bureau Medecin 18.0 100 150 3.1
C4‐0229
WC 3.5 ‐ 50 5.3
C4‐0230
C4‐0231
WC 3.5 ‐ 50 5.3
C4‐0232
C4‐0233 Bureau Secretariat 18.0 100 150 3.1
C4‐0234 Chambre 2 lits 9 19.0 100 ‐ 1.6
C4‐0235 WC 3.0 ‐ 100 12.3
C4‐0236 Chambre 2 lits 10 19.0 100 ‐ 1.6
C4‐0237 WC 3.0 ‐ 100 12.3
C4‐0238 Chambre 2 lits 11 19.0 100 ‐ 1.6
C4‐0239 WC 3.0 ‐ 100 12.3
C4‐0240 Chambre 2 lits 12 19.0 100 ‐ 1.6
C4‐0241 WC 3.0 ‐ 100 12.3
C4‐0242 Chambre 2 lits 13 19.0 100 ‐ 1.6
C4‐0243 WC 3.0 ‐ 100 12.3
C4‐0244 Chambre 2 lits 14 19.0 100 ‐ 1.6
C4‐0245 WC 3.0 ‐ 100 12.3
C4‐0246 Chambre 2 lits 15 19.0 100 ‐ 1.6
C4‐0247 WC 3.0 ‐ 100 12.3
C4‐0248 Chambre 2 lits 16 19.0 100 ‐ 1.6
C4‐0249 WC 3.0 ‐ 100 12.3
C4‐0250 Bureau Chef Medecin 22.0 100 100 1.7
C4‐0251 Menage 6.5 ‐ 50 2.8
C4‐0252 Douche 3.3 ‐ 150 16.8
C4‐0253 Douche 3.3 ‐ 150 16.8
C4‐0254
WC 3.0 ‐ 50 6.2
C4‐0257
C4‐0255
WC 3.0 ‐ 50 6.2
C4‐0256
C4‐0259 Unite Propre 9.8 100 100 3.8
C4‐0260 Infirmerie 9.8 100 100 3.8
C4‐0261
Couloir 203.0 800 ‐ 1.6
C4‐0267
C4‐0262 Preparation 9.0 100 100 4.1
C4‐0263 Unite Sale 9.8 ‐ 100 3.8
C4‐0264 Office 15.0 200 200 4.9
C4‐0265 Armoires Electriques 2.5 ‐ 50 5.4
C4‐0266 Armoires Electriques 2.5 ‐ 50 5.4
BATIMENT‐C‐ NIVEAU +16.10 TOTAL 3,300 3,350
BATIMENT‐C‐ NIVEAU +12.60
C3‐0152 Soins 22.0 100 100 1.7
C3‐0153 Chambre 2 lits 1 19.0 100 ‐ 1.6
C3‐0154 WC 3.0 ‐ 100 12.3
C3‐0155 Chambre 2 lits 2 19.0 100 ‐ 1.6
C3‐0156 WC 3.0 ‐ 100 12.3
C3‐0157 Chambre 2 lits 3 19.0 100 ‐ 1.6
C3‐0158 WC 3.0 ‐ 100 12.3
C3‐0159 Chambre 2 lits 4 19.0 100 ‐ 1.6
C3‐0160 WC 3.0 ‐ 100 12.3
C3‐0161 Chambre 2 lits 5 19.0 100 ‐ 1.6
C3‐0162 WC 3.0 ‐ 100 12.3
C3‐0163 Chambre 2 lits 6 19.0 100 ‐ 1.6
C3‐0164 WC 3.0 ‐ 100 12.3
C3‐0165 Chambre 2 lits 7 19.0 100 ‐ 1.6
C3‐0166 WC 3.0 ‐ 100 12.3
C3‐0167 Chambre 2 lits 8 19.0 100 ‐ 1.6
C3‐0168 WC 3.0 ‐ 100 12.3
C3‐0169 Bureau Medecin 18.0 100 150 3.1
C3‐0170
WC 3.5 ‐ 50 5.3
C3‐0171
C3‐0173
WC 3.5 ‐ 50 5.3
C3‐0174
C3‐0175 Bureau Secretariat 18.0 100 150 3.1
C3‐0176 Chambre 2 lits 9 19.0 100 ‐ 1.6
C3‐0177 WC 3.0 ‐ 100 12.3
C3‐0178 Chambre 2 lits 10 19.0 100 ‐ 1.6
C3‐0179 WC 3.0 ‐ 100 12.3
C3‐0180 Chambre 2 lits 11 19.0 100 ‐ 1.6
C3‐0181 WC 3.0 ‐ 100 12.3
C3‐0182 Chambre 2 lits 12 19.0 100 ‐ 1.6
C3‐0183 WC 3.0 ‐ 100 12.3
C3‐0184 Chambre 2 lits 13 19.0 100 ‐ 1.6
C3‐0185 WC 3.0 ‐ 100 12.3
C3‐0186 Chambre 2 lits 14 19.0 100 ‐ 1.6
C3‐0187 WC 3.0 ‐ 100 12.3
C3‐0188 Chambre 2 lits 15 19.0 100 ‐ 1.6
C3‐0189 WC 3.0 ‐ 100 12.3
C3‐0190 Chambre 2 lits 16 19.0 100 ‐ 1.6
C3‐0191 WC 3.0 ‐ 100 12.3
C3‐0192 Bureau Chef Medecin 22.0 100 100 1.4
C3‐0193 Menage 6.5 ‐ 50 2.8
C3‐0194 Douche 3.3 ‐ 150 16.8
C3‐0195 Douche 3.3 ‐ 150 16.8
C3‐0196
WC 3.0 ‐ 50 6.2
C3‐0198
C3‐0197
WC 3.0 ‐ 50 6.2
C3‐0199
C3‐0201 Unite Propre 9.8 100 100 3.8
C3‐0202 Infirmerie 9.8 100 100 3.8
C3‐0203
Couloir 203.0 800 ‐ 1.6
C3‐0209
C3‐0204 Preparation 9.0 100 100 4.1
C3‐0205 Unite Sale 9.8 ‐ 100 3.8
C3‐0206 Office 15.0 200 200 4.9
C3‐0207 Armoires Electriques 2.5 ‐ 50 5.4
C3‐0208 Armoires Electriques 2.5 ‐ 50 5.4
BATIMENT‐C‐ NIVEAU +12.60 TOTAL 3,300 3,350
BATIMENT‐C‐ NIVEAU +9.10
C2‐0094 Soins 22.0 100 100 1.7
C2‐0095 Chambre 2 lits 1 19.0 100 ‐ 1.6
C2‐0096 WC 3.0 ‐ 100 12.3
C2‐0097 Chambre 2 lits 2 19.0 100 ‐ 1.6
C2‐0098 WC 3.0 ‐ 100 12.3
C2‐0099 Chambre 2 lits 3 19.0 100 ‐ 1.6
C2‐0100 WC 3.0 ‐ 100 12.3
C2‐0101 Chambre 2 lits 4 19.0 100 ‐ 1.6
C2‐0102 WC 3.0 ‐ 100 12.3
C2‐0103 Chambre 2 lits 5 19.0 100 ‐ 1.6
C2‐0104 WC 3.0 ‐ 100 12.3
C2‐0105 Chambre 2 lits 6 19.0 100 ‐ 1.6
C2‐0106 WC 3.0 ‐ 100 12.3
C2‐0107 Chambre 2 lits 7 19.0 100 ‐ 1.6
C2‐0108 WC 3.0 ‐ 100 12.3
C2‐0109 Chambre 2 lits 8 19.0 100 ‐ 1.6
C2‐0110 WC 3.0 ‐ 100 12.3
C2‐0111 Bureau Medecin 18.0 100 150 3.1
C2‐0112
WC 3.5 ‐ 50 5.3
C2‐0113
C2‐0114
WC 3.5 ‐ 50 5.3
C2‐0115
C2‐0116 Bureau Secretariat 18.0 100 150 3.1
C2‐0117 Chambre 2 lits 9 19.0 100 ‐ 1.6
C2‐0118 WC 3.0 ‐ 100 12.3
C2‐0119 Chambre 2 lits 10 19.0 100 ‐ 1.6
C2‐0120 WC 3.0 ‐ 100 12.3
C2‐0121 Chambre 2 lits 11 19.0 100 ‐ 1.6
C2‐0122 WC 3.0 ‐ 100 12.3
C2‐0123 Chambre 2 lits 12 19.0 100 ‐ 1.6
C2‐0124 WC 3.0 ‐ 100 12.3
C2‐0125 Chambre 2 lits 13 19.0 100 ‐ 1.6
C2‐0126 WC 3.0 ‐ 100 12.3
C2‐0127 Chambre 2 lits 14 19.0 100 ‐ 1.6
C2‐0128 WC 3.0 ‐ 100 12.3
C2‐0129 Chambre 2 lits 15 19.0 100 ‐ 1.6
C2‐0130 WC 3.0 ‐ 100 12.3
C2‐0131 Chambre 2 lits 16 19.0 100 ‐ 1.6
C2‐0132 WC 3.0 ‐ 100 12.3
C2‐0133 Bureau Chef Medecin 22.0 100 100 1.7
C2‐0134 Menage 6.5 ‐ 50 2.8
C2‐0135 Douche 3.3 ‐ 150 16.8
C2‐0136 Douche 3.3 ‐ 150 16.8
C2‐0137
WC 3.0 ‐ 50 6.2
C2‐0139
C2‐0138
WC 3.0 ‐ 50 6.2
C2‐0140
C2‐0142 Unite Propre 9.8 100 100 3.8
C2‐0143 Infirmerie 9.8 100 100 3.8
C2‐0144
Couloir 203.0 800 ‐ 1.6
C2‐0150
C2‐0145 Preparation 9.0 100 100 4.1
C2‐0146 Unite Sale 9.8 ‐ 100 3.8
C2‐0147 Office 15.0 200 200 4.9
C2‐0148 Armoires Electriques 2.5 ‐ 50 5.4
C2‐0149 Armoires Electriques 2.5 ‐ 50 5.4
BATIMENT‐C‐ NIVEAU +9.10 TOTAL 3,300 3,350
GP‐C4 AIR FLOW 9,900 10,050
Rel. humidity
Water
100%
70%
50%
40%
BLOCK B GP-B1 AIR
HANDLING UNIT lp
y
a
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 1 14 g/kg
³
15%
20 12 g/kg
kJ
/kg
10 g/kg
3
10%
1 .2 4
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 39.470
Capacity kW 29.070
Moistening flow kg/h 39.128
Moistening temperature ºC 100.000
Moistening enthalpy kJ/kg 2674.645
Water
100%
70%
50%
40%
BLOCK B GP-B2 AIR
HANDLING UNIT y
a lp
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 14 g/kg
³
15%
20 12 g/kg
kJ
/kg
10 g/kg
10%
1 .2
5k 8 g/kg
g /m
³
6 g/kg
1 .3
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
Heating of air
Capacity kW 30.455
Water
100%
70%
50%
40%
BLOCK B GP-B3 AIR
HANDLING UNIT y
a lp
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 14 g/kg
³ 1
15%
20 12 g/kg
kJ
/kg
10 g/kg
10%
1 .2
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 13.603
Water
100%
70%
50%
40%
BLOCK B GP-B4 AIR
y
HANDLING UNIT a lp
th
PSYCHOMETRIC DIAGRAM En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 14 g/kg
³ 1
15%
20 12 g/kg
kJ
/kg
10 g/kg
10%
1 .2
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 31.286
Water
100%
70%
50%
40%
BLOCK B GP-B5 AIR
HANDLING UNIT lp
y
a
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 14 g/kg
³
1
15%
20 12 g/kg
kJ
/kg
10 g/kg
10%
1 .2
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 46.390
Water
100%
70%
50%
40%
BLOCK B GP-B6 AIR
HANDLING UNIT y
PSYCHOMETRIC DIAGRAM a lp
th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 14 g/kg
³
15%
20 12 g/kg
kJ
/kg
1
10 g/kg
10%
1 .2
5k 8 g/kg
g /m
³
6 g/kg
1 .3
0k
2
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 42.508
Water
100%
70%
50%
40%
BLOCK B GP-B7 AIR
HANDLING UNIT y
a lp
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 14 g/kg
³ 1
15%
20 12 g/kg
kJ
/kg
10 g/kg
10%
1 .2
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 31.626
Water
100%
70%
50%
40%
BLOCK B GP-B8 AIR
HANDLING UNIT y
a lp
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 1 14 g/kg
³
15%
20 12 g/kg
kJ
/kg
10 g/kg
10%
1 .2
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 29.586
Water
100%
70%
50%
40%
BLOCK B GP-B9 AIR
HANDLING UNIT y
a lp
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 1 14 g/kg
³
15%
20 12 g/kg
kJ
/kg
10 g/kg
10%
1 .2
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 10.202
Water
100%
70%
50%
40%
BLOCK B GP-B10 AIR
HANDLING UNIT lp
y
a
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 1 14 g/kg
³
15%
20 12 g/kg
kJ
/kg
10 g/kg
10%
1 .2
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 10.542
Water
100%
70%
50%
40%
BLOCK B GP-B12 AIR
HANDLING UNIT y
a lp
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 14 g/kg
³
15%
20 1 12 g/kg
kJ
/kg
10 g/kg
3
10%
1 .2
5k 8 g/kg
g /m 4
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 35.084
Capacity kW 25.851
Moistening flow kg/h 34.795
Moistening temperature ºC 100.000
Moistening enthalpy kJ/kg 2674.645
Water
100%
70%
50%
40%
BLOCK B GP-B13 AIR
HANDLING UNIT lp
y
a
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 14 g/kg
³
15%
20 1 12 g/kg
kJ
/kg
10 g/kg
3
10%
1 .2
5k 8 g/kg
g /m 4
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 84.131
Capacity kW 63.653
Moistening flow kg/h 85.675
Moistening temperature ºC 100.000
Moistening enthalpy kJ/kg 2674.645
Water
100%
70%
50%
40%
BLOCK B GP-B14 AIR
HANDLING UNIT y
a lp
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 14 g/kg
³ 1
15%
20 12 g/kg
kJ
/kg
4 10 g/kg
3
10%
1 .2
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 27.065
Capacity kW 19.404
Moistening flow kg/h 26.117
Moistening temperature ºC 100.000
Moistening enthalpy kJ/kg 2674.645
Water
100%
70%
50%
40%
BLOCK B GP-OP 1 AIR
HANDLING UNIT y
a lp
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 1 14 g/kg
³
15%
20 12 g/kg
kJ
/kg
10 g/kg
3
10%
1 .2 5
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
4 2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 24.341
4) Heating of air
Capacity kW 8.122
Capacity kW 20.066
Moistening flow kg/h 27.008
Moistening temperature ºC 100.000
Moistening enthalpy kJ/kg 2674.645
Water
100%
70%
50%
40%
BLOCK B GP-OP 2 AIR
HANDLING UNIT y
a lp
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 1 14 g/kg
³
15%
20 12 g/kg
kJ
/kg
10 g/kg
3
10%
1 .2 5
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
4 2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 24.341
4) Heating of air
Capacity kW 8.122
Capacity kW 20.052
Moistening flow kg/h 26.989
Moistening temperature ºC 100.000
Moistening enthalpy kJ/kg 2674.645
Water
100%
70%
50%
40%
BLOCK B GP-OP 3 AIR
HANDLING UNIT y
a lp
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 14 g/kg
³ 1
15%
20 12 g/kg
kJ
/kg
10 g/kg
3
10%
1 .2 5
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
4
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 40.466
4) Heating of air
Capacity kW 13.502
Capacity kW 33.366
Moistening flow kg/h 44.910
Moistening temperature ºC 100.000
Moistening enthalpy kJ/kg 2674.645
Water
100%
70%
50%
40%
BLOCK B GP-OP 4 AIR
HANDLING UNIT y
a lp
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 14 g/kg
³ 1
15%
20 12 g/kg
kJ
/kg
10 g/kg
3
10%
1 .2 5
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
4 2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 40.466
4) Heating of air
Capacity kW 13.502
Capacity kW 33.358
Moistening flow kg/h 44.899
Moistening temperature ºC 100.000
Moistening enthalpy kJ/kg 2674.645
Water
100%
70%
50%
40%
BLOCK B GP-OP 5 AIR
HANDLING UNIT y
a lp
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 1 14 g/kg
³
15%
20 12 g/kg
kJ
/kg
3 10 g/kg
10%
1 .2 5
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
4 2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 54.766
4) Heating of air
Capacity kW 18.274
Capacity kW 45.219
Moistening flow kg/h 60.863
Moistening temperature ºC 100.000
Moistening enthalpy kJ/kg 2674.645
Water
100%
70%
50%
40%
BLOCK B GP-OP 6 AIR HANDLING
UNIT PSYCHOMETRIC DIAGRAM y
a lp
th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 14 g/kg
³ 1
15%
20 12 g/kg
kJ
/kg
10 g/kg
3
10%
1 .2 5
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
4 2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 20.081
4) Heating of air
Capacity kW 6.700
Capacity kW 16.577
Moistening flow kg/h 22.313
Moistening temperature ºC 100.000
Moistening enthalpy kJ/kg 2674.645
Water
100%
70%
50%
40%
BLOCK B GP-OP 7 (GP-B11)
AIR HANDLING UNIT y
a lp
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 14 g/kg
³ 1
15%
20 12 g/kg
kJ
/kg
10 g/kg
10%
1 .2
5k
3 4 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 77.054
Capacity kW 44.797
Moistening flow kg/h 60.296
Moistening temperature ºC 100.000
Moistening enthalpy kJ/kg 2674.645
Water
100%
70%
50%
40%
BLOCK A GP-A1 AIR HANDLING
UNIT PSYCHOMETRIC DIAGRAM y
a lp
th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 14 g/kg
³
15%
20 12 g/kg
kJ
/kg
1
10 g/kg
10%
1 .2
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 20.404
Water
100%
70%
50%
40%
BLOCK A GP-A2 AIR HANDLING
UNIT PSYCHOMETRIC DIAGRAM y
a lp
th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 14 g/kg
³
15%
20 12 g/kg
kJ
/kg
1
10 g/kg
10%
1 .2
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 13.603
Water
100%
70%
50%
40%
BLOCK A GP-A3 AIR HANDLING
UNIT PSYCHOMETRIC DIAGRAM y
a lp
th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 14 g/kg
³
15%
20 12 g/kg
kJ
/kg
1
10 g/kg
10%
1 .2
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 12.582
Water
100%
70%
50%
40%
BLOCK A GP-A4 AIR HANDLING
UNIT PSYCHOMETRIC y
a lp
DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 14 g/kg
³
15%
20 12 g/kg
kJ
/kg
1
10 g/kg
10%
1.2
5k 8 g/kg
g/m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.15 kg/m³
1.10 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 39.000 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 89.768
Water
100%
70%
50%
40%
BLOCK C GP-C1 AIR
HANDLING UNIT lp
y
a
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k 1 14 g/kg
g/m
³
15%
20 12 g/kg
kJ
/kg
10 g/kg
10%
1 .2
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 25.165
Water
100%
70%
50%
40%
BLOCK C GP-C2 AIR
HANDLING UNIT lp
y
a
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k 1 14 g/kg
g/m
³
15%
20 12 g/kg
kJ
/kg
10 g/kg
10%
1 .2
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 27.205
Water
100%
70%
50%
40%
BLOCK C GP-C3 AIR
HANDLING UNIT y
a lp
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k
g/m 14 g/kg
³
15%
20 12 g/kg
kJ
/kg
1
10 g/kg
10%
1 .2
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 30.606
Water
100%
70%
50%
40%
BLOCK C GP-C4 AIR
HANDLING UNIT y
a lp
PSYCHOMETRIC DIAGRAM th
En 24 g/kg
30%
22 g/kg
60
kJ
/kg 20 g/kg
18 g/kg
40
20%
kJ 16 g/kg
/kg
1 .2
0k 1 14 g/kg
g/m
³
15%
20 12 g/kg
kJ
/kg
10 g/kg
10%
1 .2
5k 8 g/kg
g /m
³
6 g/kg
1 .3 2
0k
5%
g/m 4 g/kg
³
1.10 kg/m³
1.15 kg/m³
2 g/kg
0 g/kg
-5 º
-15 º
-10 º
0º
5º
10 º
15 º
20 º
25 º
30 º
35 º
40 º
45 º
50 º
Temperature
Carrier psychrometric chart for air humid - Pressure 1.011 bar (25.000 m / 41.500 °C / 17.000 % rH)
1) Cooling of air - Partition of fins (2.5 - 3.5 mm)
2) Heating of air
Capacity kW 67.333
COOLING LOAD COOLING TOTAL COOLING FCU SENSIBLE FCU SENSIBLE FCU UNIT FCU TOTAL
ROOM HEAT LOSS
NO ROOM NAME SENSIBLE LOAD LATENT LOAD QUANTITY TYPE FCU TYPE COOLING COOLING TOTAL COOLING COOLING TOTAL
(W)
(W) (w) (W) CAPACITY (w) (w) CAPACITY (w) (w)
4th FLOOR
A4-0242 SOINS 1,803 120 1,923 1,257 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0241 CHAMBRE 2 LITS 1,777 70 1,847 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0240 CHAMBRE 2 LITS 1,777 70 1,847 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0239 CHAMBRE 2 LITS 1,777 70 1,847 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0238 CHAMBRE 2 LITS 1,777 70 1,847 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0237 CHAMBRE 2 LITS 1,777 70 1,847 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0236 CHAMBRE 2 LITS 1,777 70 1,847 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0235 CHAMBRE 2 LITS 1,777 70 1,847 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0234 CHAMBRE 2 LITS 1,777 70 1,847 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0233 BUREAU MEDECIN 1,984 120 2,104 1,264 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0232 BUREAU SECRETARIA 1,826 120 1,946 1,264 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0231 CHAMBRE 2 LITS 1,609 70 1,679 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0230 CHAMBRE 2 LITS 1,609 70 1,679 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0229 CHAMBRE 2 LITS 1,609 70 1,679 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0228 CHAMBRE 2 LITS 1,609 70 1,679 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0227 CHAMBRE 2 LITS 1,609 70 1,679 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0226 CHAMBRE 2 LITS 1,609 70 1,679 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0225 CHAMBRE 2 LITS 1,609 70 1,679 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0224 CHAMBRE 2 LITS 1,609 70 1,679 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0223 BUREAU CHEF MEDECIN 1,806 120 1,926 1,257 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0279 CORRIDOR 8,188 352 8,540 5,483 4 Ceiling Type FCU-3 2,080 8,320 3,000 12,000
A4-0263 MENAGE 676 70 746 237 1 Ceiling Type FCU-1 790 790 1,180 1,180
A4-0271 UNITE PROPRE 846 120 966 416 1 Ceiling Type FCU-1 790 790 1,180 1,180
A4-0272 INFIRMERIE 886 120 1,006 245 1 Ceiling Type FCU-1 790 790 1,180 1,180
A4-0273 PREPARATION 736 120 856 245 1 Ceiling Type FCU-1 790 790 1,180 1,180
A4-0274 UNITE SALE 769 120 889 357 1 Ceiling Type FCU-1 790 790 1,180 1,180
427 OFFICE 1,091 120 1,211 493 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
428 STAIR HALL 8,085 - 8,085 3,368 1 Ceiling Type FCU-9 7,640 7,640 10,580 10,580
4th FLOOR TOTAL 58,406 32,478 31 59,530 81,180
3rd FLOOR
A3-0184 SOINS 1,718 120 1,838 890 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A3-0183 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0182 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0181 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0180 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0179 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0178 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0177 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0176 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0175 BUREAU MEDECIN 1,676 120 1,796 897 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A3-0174 BUREAU SECRETARIA 1,593 120 1,713 897 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A3-0173 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0172 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0171 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
COOLING LOAD COOLING TOTAL COOLING FCU SENSIBLE FCU SENSIBLE FCU UNIT FCU TOTAL
ROOM HEAT LOSS
NO ROOM NAME SENSIBLE LOAD LATENT LOAD QUANTITY TYPE FCU TYPE COOLING COOLING TOTAL COOLING COOLING TOTAL
(W)
(W) (w) (W) CAPACITY (w) (w) CAPACITY (w) (w)
A3-0170 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0169 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0168 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0167 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0166 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0165 BUREAU CHEF MEDECIN 1,720 120 1,840 890 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A3-0221 CORRIDOR 5,544 352 5,896 2,611 4 Ceiling Type FCU-2 1,560 6,240 2,250 9,000
A3-0205 MENAGE 562 70 632 114 1 Ceiling Type FCU-1 790 790 1,180 1,180
A3-0213 UNITE PROPRE 703 120 823 264 1 Ceiling Type FCU-1 790 790 1,180 1,180
A3-0214 INFIRMERIE 744 120 864 92 1 Ceiling Type FCU-1 790 790 1,180 1,180
A3-0215 PREPARATION 594 120 714 92 1 Ceiling Type FCU-1 790 790 1,180 1,180
A3-0216 UNITE SALE 634 120 754 204 1 Ceiling Type FCU-1 790 790 1,180 1,180
A3-0217 OFFICE 876 120 996 264 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0164 STAIR HALL 7,633 - 7,633 2,164 1 Ceiling Type FCU-9 7,640 7,640 10,580 10,580
3rd FLOOR TOTAL 49,387 20,099 31 49,610 67,940
2nd FLOOR
A2-0126 SOINS 1,718 120 1,838 890 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A2-0125 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0124 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0123 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0122 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0121 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0120 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0119 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0118 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0117 BUREAU MEDECIN 1,676 120 1,796 897 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A2-0116 BUREAU SECRETARIA 1,593 120 1,713 897 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A2-0115 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0114 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0113 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0112 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0111 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0110 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0109 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0108 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0107 BUREAU CHEF MEDECIN 1,720 120 1,840 890 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A2-0147 CORRIDOR 5,544 352 5,896 2,611 4 Ceiling Type FCU-2 1,560 6,240 2,250 9,000
A2-0148 MENAGE 562 70 632 114 1 Ceiling Type FCU-1 790 790 1,180 1,180
A2-0156 UNITE PROPRE 703 120 823 264 1 Ceiling Type FCU-1 790 790 1,180 1,180
A2-0157 INFIRMERIE 744 120 864 92 1 Ceiling Type FCU-1 790 790 1,180 1,180
A2-0158 PREPARATION 594 120 714 92 1 Ceiling Type FCU-1 790 790 1,180 1,180
A2-0159 UNITE SALE 634 120 754 204 1 Ceiling Type FCU-1 790 790 1,180 1,180
A2-0160 OFFICE 876 120 996 264 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0107 STAIR HALL 7,633 - 7,633 2,164 1 Ceiling Type FCU-9 7,640 7,640 10,580 10,580
8th FLOOR TOTAL 49,387 20,099 31 49,610 67,940
COOLING LOAD COOLING TOTAL COOLING FCU SENSIBLE FCU SENSIBLE FCU UNIT FCU TOTAL
ROOM HEAT LOSS
NO ROOM NAME SENSIBLE LOAD LATENT LOAD QUANTITY TYPE FCU TYPE COOLING COOLING TOTAL COOLING COOLING TOTAL
(W)
(W) (w) (W) CAPACITY (w) (w) CAPACITY (w) (w)
1 st FLOOR
A1-0068 SOINS 1,718 120 1,838 890 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A1-0067 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A1-0066 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A1-0065 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A1-0064 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A1-0063 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A1-0062 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A1-0061 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A1-0060 CHAMBRE 2 LITS 1,469 70 1,539 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A1-0059 BUREAU MEDECIN 1,676 120 1,796 897 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A1-0058 BUREAU SECRETARIA 1,593 120 1,713 897 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A1-0057 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A1-0056 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A1-0055 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A1-0054 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A1-0053 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A1-0052 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A1-0051 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A1-0050 CHAMBRE 2 LITS 1,377 70 1,447 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A1-0049 BUREAU CHEF MEDECIN 1,720 120 1,840 890 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A1-0089 CORRIDOR 5,544 352 5,896 2,611 4 Ceiling Type FCU-2 1,560 6,240 2,250 9,000
A2-0090 MENAGE 562 70 632 114 1 Ceiling Type FCU-1 790 790 1,180 1,180
A2-0098 UNITE PROPRE 703 120 823 264 1 Ceiling Type FCU-1 790 790 1,180 1,180
A2-0099 INFIRMERIE 744 120 864 92 1 Ceiling Type FCU-1 790 790 1,180 1,180
A2-0100 PREPARATION 594 120 714 92 1 Ceiling Type FCU-1 790 790 1,180 1,180
A2-0101 UNITE SALE 634 120 754 204 1 Ceiling Type FCU-1 790 790 1,180 1,180
A2-0102 OFFICE 876 120 996 264 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A1-0049 STAIR HALL 7,633 - 7,633 2,164 1 Ceiling Type FCU-9 7,640 7,640 10,580 10,580
1 st FLOOR TOTAL 49,387 20,099 31 49,610 67,940
GROUND FLOOR
AR-0000 BUREAU 2,354 180 2,534 1,674 1 Ceiling Type FCU-4 2,420 2,420 3,130 3,130
AR-0001 PREPARATION 2,441 120 2,561 2,754 1 Ceiling Type FCU-4 2,420 2,420 3,130 3,130
AR-0002 PREPARATION 3,485 240 3,725 2,814 2 Ceiling Type FCU-3 1,910 3,820 2,540 5,080
AR-0003 BUREAU DE EXPEDITIONS 3,651 180 3,831 2,607 2 Ceiling Type FCU-3 1,910 3,820 2,540 5,080
AR-0004 PHARMACIE 1,287 106 1,393 2,048 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
AR-0010 BUREAU MEDECIN 746 120 866 454 1 Ceiling Type FCU-1 790 790 1,180 1,180
AR-0005 MEDECIN LEGALE 1,603 186 1,789 1,148 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
AR-0014 SAS DE DISTRIBUTION 1,340 120 1,460 1,617 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
AR-0026 ACCUEIL 2,987 528 3,515 2,617 2 Ceiling Type FCU-3 1,910 3,820 2,540 5,080
AR-0028 CORRIDOR 1,953 176 2,129 1,559 1 Ceiling Type FCU-3 2,080 2,080 3,000 3,000
AR-0030 BUREAU 1,857 180 2,037 1,701 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
AR-0031 SALLE DE TRAITEMENT HOMMES 3,436 240 3,676 2,899 2 Ceiling Type FCU-3 1,910 3,820 2,540 5,080
AR-0032 SALLE DE TRAITEMENT HOMMES 3,436 240 3,676 2,899 2 Ceiling Type FCU-3 1,910 3,820 2,540 5,080
AR-0033 KINESITHERAPI 785 60 845 247 1 Ceiling Type FCU-1 790 790 1,180 1,180
COOLING LOAD COOLING TOTAL COOLING FCU SENSIBLE FCU SENSIBLE FCU UNIT FCU TOTAL
ROOM HEAT LOSS
NO ROOM NAME SENSIBLE LOAD LATENT LOAD QUANTITY TYPE FCU TYPE COOLING COOLING TOTAL COOLING COOLING TOTAL
(W)
(W) (w) (W) CAPACITY (w) (w) CAPACITY (w) (w)
AR-0034 KINESITHERAPI 1,350 120 1,470 691 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
AR-0035 KINESITHERAPI 1,350 120 1,470 691 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
AR-0036 KINESITHERAPI 785 60 845 247 1 Ceiling Type FCU-1 790 790 1,180 1,180
AR-0037 KINESITHERAPI 785 60 845 247 1 Ceiling Type FCU-1 790 790 1,180 1,180
AR-0038 KINESITHERAPI 1,350 120 1,470 691 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
AR-0039 KINESITHERAPI 1,350 120 1,470 691 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
AR-0040 KINESITHERAPI 773 60 833 234 1 Ceiling Type FCU-1 790 790 1,180 1,180
AR-0041 KINESITHERAPI 745 60 805 203 1 Ceiling Type FCU-1 790 790 1,180 1,180
AR-0042 KINESITHERAPI 745 60 805 203 1 Ceiling Type FCU-1 790 790 1,180 1,180
AR-0047 HALL DE RECEPTION 8,026 352 8,378 2,423 1 Ceiling Type FCU-9 7,640 7,640 10,580 10,580
GROUND FLOOR TOTAL 52,428 33,359 49,110 69,980
COOLING LOAD COOLING TOTAL COOLING FCU SENSIBLE FCU SENSIBLE FCU UNIT FCU TOTAL
ROOM HEAT LOSS
NO ROOM NAME SENSIBLE LOAD LATENT LOAD QUANTITY TYPE FCU TYPE COOLING COOLING TOTAL COOLING COOLING TOTAL
(W)
(W) (w) (W) CAPACITY (w) (w) CAPACITY (w) (w)
2nd FLOOR
B2-0168 CH-1 864 120 984 612 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B2-0170 CH-2 1,119 120 1,239 612 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B2-0172 CH-1 937 120 1,057 354 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B2-0174 CH-2 937 120 1,057 354 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B2-0176 CH-3 937 120 1,057 354 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B2-0178 CH-4 937 120 1,057 354 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B2-0185 CH-8 864 120 984 612 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B2-0187 CH-7 937 120 1,057 354 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B2-0189 SEJOUR 1,989 120 2,109 920 2 Ceiling Type FCU-2 1,420 2,840 1,900 3,800
2 Ceiling Type FCU-5 2,940 5,880 3,850 7,700
B2-0194 DIALYSE 12,869 352 13,221 2,876
2 Ceiling Type FCU-6 4,140 8,280 5,460 10,920
B2-0195 BOX DISOLEMENT 1,723 70 1,793 403 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
B2-0201 BUREAU MEDICAL 725 120 845 48 1 Ceiling Type FCU-1 790 790 1,180 1,180
B2-0205 LOCAL TECHNIQUE 1,771 301 2,072 40 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
B2-0208 SURFACE SERVICE 436 60 496 53 1 Ceiling Type FCU-1 790 790 1,180 1,180
B2-0209 SURFACE SERVICE 460 60 520 79 1 Ceiling Type FCU-1 790 790 1,180 1,180
B2-0213 ATTENTE 1,444 598 2,042 429 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
B2-0236 SECRETARIAT 1,408 180 1,588 445 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B2-0239 BUREAU MEDICAL 1,708 180 1,888 198 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
B2-0237 BANQUE DE SONG 2,451 240 2,691 351 1 Ceiling Type FCU-4 2,420 2,420 3,130 3,130
B2-0251 BUREAU 1,040 120 1,160 88 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B2-0253 BACTEROLOGIE 3,564 301 3,865 981 1 Ceiling Type FCU-6 4,140 4,140 5,460 5,460
B2-0254 LABORATORIE 16,635 1,503 18,138 4,123 3 Ceiling Type FCU-8 6,110 18,330 7,860 23,580
B2-0255 CENTRE DE TRI 3,913 301 4,214 1,176 2 Ceiling Type FCU-3 1,910 3,820 2,540 5,080
B2-0256 SANITARIES PERSONEL 2,195 301 2,496 - 2 Ceiling Type FCU-2 1,560 3,120 2,250 4,500
B2-0257 SANITARIES PUBLIC 475 - 475 - 1 Ceiling Type FCU-1 790 790 1,180 1,180
2nd FLOOR TOTAL 38,557 15,816 14 73,830 98,050
1st FLOOR
B1-086 ECHO-1 2,057 120 2,177 355 1 Ceiling Type FCU-4 2,420 2,420 3,130 3,130
B1-088 ECHO-2 1,898 120 2,018 438 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
B1-090 ECHO-3 1,898 120 2,018 438 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
B1-092 ECHO-4 1,898 120 2,018 438 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
B1-094 CORRIDOR 804 - 804 508 1 Ceiling Type FCU-1 870 870 1,039 1,039
B1-095 BUREAU DE PERSONEL MEDICAL 2,753 240 2,993 1,158 2 Ceiling Type FCU-2 1,420 2,840 1,900 3,800
B1-102 RADIOLOGIE CORRIDOR 4,376 1,408 5,784 2,647 3 Ceiling Type FCU-2 1,560 4,680 2,250 6,750
1 Ceiling Type FCU-3 2,080 2,080 3,000 3,000
B1-103 CORRIDOR 5,488 352 5,840 2,647
2 Ceiling Type FCU-2 1,560 3,120 2,250 4,500
B1-104 RADIO-4 8,441 70 8,511 141 2 Ceiling Type FCU-6 4,140 8,280 5,460 10,920
B1-108 RADIO-3 8,402 70 8,472 141 2 Ceiling Type FCU-6 4,140 8,280 5,460 10,920
B1-109 RADIO-2 8,052 70 8,122 132 2 Ceiling Type FCU-6 4,140 8,280 5,460 10,920
B1-110 RADIO-1 8,319 70 8,389 132 2 Ceiling Type FCU-6 4,140 8,280 5,460 10,920
B1-114 SCANNER 8,297 180 8,477 202 2 Ceiling Type FCU-6 4,140 8,280 5,460 10,920
B1-115 BUREAU 668 120 788 57 1 Ceiling Type FCU-1 790 790 1,180 1,180
B1-116 BUREAU 668 120 788 57 1 Ceiling Type FCU-1 790 790 1,180 1,180
COOLING LOAD COOLING TOTAL COOLING FCU SENSIBLE FCU SENSIBLE FCU UNIT FCU TOTAL
ROOM HEAT LOSS
NO ROOM NAME SENSIBLE LOAD LATENT LOAD QUANTITY TYPE FCU TYPE COOLING COOLING TOTAL COOLING COOLING TOTAL
(W)
(W) (w) (W) CAPACITY (w) (w) CAPACITY (w) (w)
B1-117 LOCAL TECHNIQUE 2,862 - 2,862 26 1 Ceiling Type FCU-5 2,940 2,940 3,850 3,850
B1-118 LOCAL TECHNIQUE 2,862 - 2,862 26 1 Ceiling Type FCU-5 2,940 2,940 3,850 3,850
B1-119 PREPARATION 1,376 35 1,411 136 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B1-0123 ATTENTE 1,891 810 2,701 675 1 Ceiling Type FCU-4 2,420 2,420 3,130 3,130
B1-0131 ENTREITEN 380 120 500 70 1 Ceiling Type FCU-1 790 790 1,180 1,180
B1-0135 SANITARIES PERSONEL 2,355 301 2,656 76 3 Ceiling Type FCU-1 870 2,610 1,039 3,117
B1-0136 SANITARIES PUBLIC 466 120 586 - 1 Ceiling Type FCU-1 790 790 1,180 1,180
B1-0137 LITS OBSERVATION 5,963 176 6,139 2,390 4 Ceiling Type FCU-3 1,910 7,640 2,540 10,160
B1-0141 URGENCES CORIDOR 2,303 201 2,504 - 2 Ceiling Type FCU-2 1,560 3,120 2,250 4,500
B1-0142 SALLE EXAMENS 1,146 120 1,266 568 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B1-0143 SALLE EXAMENS 1,037 120 1,157 211 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B1-0144 SALLE EXAMENS 1,255 120 1,375 595 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B1-0145 ATTENTE PUBLIC 1,449 528 1,977 588 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
B1-0146 GARDE 829 120 949 176 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B1-0149 SALLE DE PETITE CHIRURGIE 4,867 240 5,107 201 1 Ceiling Type FCU-7 5,110 5,110 6,530 6,530
B1-0150 BUREAU 1,090 120 1,210 405 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B1-0151 BUREAU 934 120 1,054 48 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B1-0152 DETENTE 1,090 60 1,150 348 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B1-0158 SALLE DE DECRASSAGE 1,092 120 1,212 246 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B1-0160 SALLE EXAMENS 1,070 120 1,190 185 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
B1-0162 SALLE DE PLATRE 1,025 120 1,145 154 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
1st FLOOR TOTAL 59,455 16,615 33 110,610 147,736
GROUND FLOOR
BR-0000 Stockage Buanderie 4,956 704 5,660 6,269 3 Ceiling Type FCU-3 1,910 5,730 2,540 7,620
BR-0010 Bureau 828 120 948 445 1 Ceiling Type FCU-1 790 790 1,180 1,180
BR-0017 Buanderie 1,068 180 1,248 1,231 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
BR-0037 Corridor 1,226 176 1,402 1,755 1 Ceiling Type FCU-2 1,560 1,560 2,250 2,250
BR-0042 Vestiaires-Sanitaries Personel 1,573 120 1,693 2,036 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
BR-0047 Vestiaires-Sanitaries Personel 1,898 120 2,018 438 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
BR-0048 Salle de Datente Personel 947 106 1,053 1,416 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
BR-0055 Corridor 1,644 176 1,820 2,245 3 Ceiling Type FCU-1 870 2,610 1,039 3,117
BR-0056 Resturant 7,620 2,373 9,993 5,999 4 Ceiling Type FCU-3 1,910 7,640 2,540 10,160
4 Ceiling Type FCU-1 790 3,160 1,180 4,720
BR-0066 Cuisine 8,120 1,802 9,922 8,493
4 Ceiling Type FCU-2 1,420 5,680 1,900 7,600
BR-0080 Magasin 2,837 352 3,189 3,468 1 Ceiling Type FCU-5 2,940 2,940 3,850 3,850
BR-0081 Magasin 1,837 176 2,013 2,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
GROUND FLOOR 40,959 35,832 38,680 51,917
COOLING LOAD COOLING TOTAL COOLING FCU SENSIBLE FCU SENSIBLE FCU UNIT FCU TOTAL
ROOM HEAT LOSS
NO ROOM NAME SENSIBLE LOAD LATENT LOAD QUANTITY TYPE FCU TYPE COOLING COOLING TOTAL COOLING COOLING TOTAL
(W)
(W) (w) (W) CAPACITY (w) (w) CAPACITY (w) (w)
4th FLOOR
A4-0211 SOINS 1,847 120 1,967 1,257 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0212 CHAMBRE 2 LITS 1,592 70 1,662 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0214 CHAMBRE 2 LITS 1,592 70 1,662 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0216 CHAMBRE 2 LITS 1,592 70 1,662 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0218 CHAMBRE 2 LITS 1,592 70 1,662 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0220 CHAMBRE 2 LITS 1,592 70 1,662 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0222 CHAMBRE 2 LITS 1,592 70 1,662 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0224 CHAMBRE 2 LITS 1,592 70 1,662 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0226 CHAMBRE 2 LITS 1,592 70 1,662 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0228 BUREAU MEDECIN 1,776 120 1,896 1,264 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0233 BUREAU SECRETARIA 1,724 120 1,844 1,264 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0234 CHAMBRE 2 LITS 1,484 70 1,554 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0236 CHAMBRE 2 LITS 1,484 70 1,554 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0238 CHAMBRE 2 LITS 1,484 70 1,554 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0240 CHAMBRE 2 LITS 1,484 70 1,554 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0242 CHAMBRE 2 LITS 1,484 70 1,554 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0244 CHAMBRE 2 LITS 1,484 70 1,554 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0246 CHAMBRE 2 LITS 1,484 70 1,554 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0248 CHAMBRE 2 LITS 1,484 70 1,554 1,037 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0250 BUREAU CHEF MEDECIN 1,844 120 1,964 1,257 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A4-0261 CORRIDOR 8,625 352 8,977 5,288 4 Ceiling Type FCU-3 2,080 8,320 3,000 12,000
A4-0251 MENAGE 676 70 746 237 1 Ceiling Type FCU-1 790 790 1,180 1,180
A4-0259 UNITE PROPRE 846 120 966 416 1 Ceiling Type FCU-1 790 790 1,180 1,180
A4-0260 INFIRMERIE 886 120 1,006 245 1 Ceiling Type FCU-1 790 790 1,180 1,180
A4-0262 PREPARATION 736 120 856 245 1 Ceiling Type FCU-1 790 790 1,180 1,180
A4-0263 UNITE SALE 846 120 966 357 1 Ceiling Type FCU-1 790 790 1,180 1,180
A4-0264 OFFICE 1,091 120 1,211 493 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A4-0268 STAIR HALL 6,055 - 6,055 3,181 1 Ceiling Type FCU-7 5,570 5,570 7,710 7,710
4th FLOOR TOTAL 54,182 32,096 31 57,460 78,310
3rd FLOOR
A3-0152 SOINS 1,609 120 1,729 890 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A3-0153 CHAMBRE 2 LITS 1,546 70 1,616 671 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A3-0155 CHAMBRE 2 LITS 1,546 70 1,616 671 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A3-0157 CHAMBRE 2 LITS 1,546 70 1,616 671 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A3-0159 CHAMBRE 2 LITS 1,546 70 1,616 671 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A3-0161 CHAMBRE 2 LITS 1,546 70 1,616 671 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A3-0163 CHAMBRE 2 LITS 1,546 70 1,616 671 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A3-0165 CHAMBRE 2 LITS 1,546 70 1,616 671 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A3-0167 CHAMBRE 2 LITS 1,546 70 1,616 671 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A3-0169 BUREAU MEDECIN 1,678 120 1,798 897 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A3-0175 BUREAU SECRETARIA 1,408 120 1,528 897 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0176 CHAMBRE 2 LITS 1,170 70 1,240 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0178 CHAMBRE 2 LITS 1,170 70 1,240 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
COOLING LOAD COOLING TOTAL COOLING FCU SENSIBLE FCU SENSIBLE FCU UNIT FCU TOTAL
ROOM HEAT LOSS
NO ROOM NAME SENSIBLE LOAD LATENT LOAD QUANTITY TYPE FCU TYPE COOLING COOLING TOTAL COOLING COOLING TOTAL
(W)
(W) (w) (W) CAPACITY (w) (w) CAPACITY (w) (w)
A3-0180 CHAMBRE 2 LITS 1,170 70 1,240 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0182 CHAMBRE 2 LITS 1,170 70 1,240 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0184 CHAMBRE 2 LITS 1,170 70 1,240 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0186 CHAMBRE 2 LITS 1,170 70 1,240 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0188 CHAMBRE 2 LITS 1,170 70 1,240 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0190 CHAMBRE 2 LITS 1,170 70 1,240 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0192 BUREAU CHEF MEDECIN 1,607 120 1,727 890 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A3-0203 CORRIDOR 6,385 352 6,737 2,416 4 Ceiling Type FCU-2 1,560 6,240 2,250 9,000
A3-0193 MENAGE 562 70 632 114 1 Ceiling Type FCU-1 790 790 1,180 1,180
A3-0201 UNITE PROPRE 604 120 724 266 1 Ceiling Type FCU-1 790 790 1,180 1,180
A3-0202 INFIRMERIE 744 120 864 92 1 Ceiling Type FCU-1 790 790 1,180 1,180
A3-0204 PREPARATION 594 120 714 92 1 Ceiling Type FCU-1 790 790 1,180 1,180
A3-0205 UNITE SALE 704 120 824 204 1 Ceiling Type FCU-1 790 790 1,180 1,180
A3-0206 OFFICE 878 120 998 266 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A3-0210 STAIR HALL 5,422 - 5,422 1,977 1 Ceiling Type FCU-7 5,570 5,570 7,710 7,710
3rd FLOOR TOTAL 46,545 19,729 31 50,970 69,550
2nd FLOOR
A2-0094 SOINS 1,609 120 1,729 890 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A2-0095 CHAMBRE 2 LITS 1,546 70 1,616 671 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A2-0097 CHAMBRE 2 LITS 1,546 70 1,616 671 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A2-0099 CHAMBRE 2 LITS 1,546 70 1,616 671 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A2-0101 CHAMBRE 2 LITS 1,546 70 1,616 671 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A2-0103 CHAMBRE 2 LITS 1,546 70 1,616 671 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A2-0105 CHAMBRE 2 LITS 1,546 70 1,616 671 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A2-0107 CHAMBRE 2 LITS 1,546 70 1,616 671 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A2-0109 CHAMBRE 2 LITS 1,546 70 1,616 671 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A2-0111 BUREAU MEDECIN 1,678 120 1,798 897 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A2-0116 BUREAU SECRETARIA 1,408 120 1,528 897 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0117 CHAMBRE 2 LITS 1,170 70 1,240 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0119 CHAMBRE 2 LITS 1,170 70 1,240 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0121 CHAMBRE 2 LITS 1,170 70 1,240 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0123 CHAMBRE 2 LITS 1,170 70 1,240 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0125 CHAMBRE 2 LITS 1,170 70 1,240 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0127 CHAMBRE 2 LITS 1,170 70 1,240 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0129 CHAMBRE 2 LITS 1,170 70 1,240 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0131 CHAMBRE 2 LITS 1,170 70 1,240 670 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0133 BUREAU CHEF MEDECIN 1,607 120 1,727 890 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
A2-0144 CORRIDOR 6,385 352 6,737 2,416 4 Ceiling Type FCU-2 1,560 6,240 2,250 9,000
A2-0134 MENAGE 562 70 632 114 1 Ceiling Type FCU-1 790 790 1,180 1,180
A2-0142 UNITE PROPRE 604 120 724 266 1 Ceiling Type FCU-1 790 790 1,180 1,180
A2-0143 INFIRMERIE 744 120 864 92 1 Ceiling Type FCU-1 790 790 1,180 1,180
A2-0145 PREPARATION 594 120 714 92 1 Ceiling Type FCU-1 790 790 1,180 1,180
A2-0146 UNITE SALE 704 120 824 204 1 Ceiling Type FCU-1 790 790 1,180 1,180
A2-0147 OFFICE 878 120 998 266 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
A2-0151 STAIR HALL 5,422 - 5,422 1,977 1 Ceiling Type FCU-7 5,570 5,570 7,710 7,710
COOLING LOAD COOLING TOTAL COOLING FCU SENSIBLE FCU SENSIBLE FCU UNIT FCU TOTAL
ROOM HEAT LOSS
NO ROOM NAME SENSIBLE LOAD LATENT LOAD QUANTITY TYPE FCU TYPE COOLING COOLING TOTAL COOLING COOLING TOTAL
(W)
(W) (w) (W) CAPACITY (w) (w) CAPACITY (w) (w)
1 st FLOOR
C1-0039 BUREAU MEDICAL 2,076 180 2,256 1,166 1 Ceiling Type FCU-4 2,420 2,420 3,130 3,130
C1-0040 CONSULTATION-5 2,043 180 2,223 852 1 Ceiling Type FCU-4 2,420 2,420 3,130 3,130
C1-0042 CONSULTATION-6 2,043 180 2,223 852 1 Ceiling Type FCU-4 2,420 2,420 3,130 3,130
C1-0044 CONSULTATION-7 2,043 180 2,223 852 1 Ceiling Type FCU-4 2,420 2,420 3,130 3,130
C1-0046 CONSULTATION-8 2,043 180 2,223 852 1 Ceiling Type FCU-4 2,420 2,420 3,130 3,130
C1-0048 CONSULTATION-9 2,043 180 2,223 852 1 Ceiling Type FCU-4 2,420 2,420 3,130 3,130
C1-0050 CONSULTATION-10 2,043 180 2,223 852 1 Ceiling Type FCU-4 2,420 2,420 3,130 3,130
C1-0052 CONSULTATION-11 2,043 180 2,223 852 1 Ceiling Type FCU-4 2,420 2,420 3,130 3,130
C1-0054 CONSULTATION-12 2,043 180 2,223 852 1 Ceiling Type FCU-4 2,420 2,420 3,130 3,130
C1-0056 BUREAU MEDICAL 2,103 180 2,283 1,164 1 Ceiling Type FCU-4 2,420 2,420 3,130 3,130
C1-0057 CORRIDOR 1,609 176 1,785 330 1 Ceiling Type FCU-3 2,080 2,080 3,000 3,000
C1-0058 RESERVE 834 120 954 297 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
C1-0065 ACCUEIL 1,650 176 1,826 1,281 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
C1-0066 ENTREE 5,017 1,408 6,425 1,460 3 Ceiling Type FCU-2 1,650 4,950 2,530 7,590
C1-0067 PRELEVEMENTS 1,511 180 1,691 243 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
C1-0068 PRELEVEMENTS-A 779 120 899 406 1 Ceiling Type FCU-1 790 790 1,180 1,180
C1-0069 PRELEVEMENTS-B 475 120 595 104 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
C1-0070 PRELEVEMENTS-C 701 120 821 319 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
C1-0073 CONSULTATION-1 1,682 180 1,862 852 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
C1-0075 CONSULTATION-2 1,682 180 1,862 852 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
C1-0077 CONSULTATION-3 1,682 180 1,862 852 1 Ceiling Type FCU-3 1,560 1,560 2,540 2,540
C1-0079 CONSULTATION-4 1,682 180 1,862 852 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
C1-0081 BUREAU MEDICAL 2,070 180 2,250 1,166 1 Ceiling Type FCU-4 2,420 2,420 3,130 3,130
C1-0082 CORRIDOR 4,882 352 5,234 1,928 3 Ceiling Type FCU-2 1,560 4,680 2,250 6,750
C1-0083 MENAGE 773 70 843 255 1 Ceiling Type FCU-1 790 790 1,180 1,180
C1-0090 UNITE SALE 760 120 880 158 1 Ceiling Type FCU-1 790 790 1,180 1,180
C1-0091 INFIRMERIE 847 120 967 158 1 Ceiling Type FCU-1 790 790 1,180 1,180
C1-0092 UNITE PROPRE 911 120 1,031 229 1 Ceiling Type FCU-2 1,420 1,420 1,900 1,900
C1-0093 STAIR HALL 5,422 - 5,422 1,977 1 Ceiling Type FCU-7 5,570 5,570 7,710 7,710
1 st FLOOR TOTAL 61,394 22,865 32 63,850 87,040
GROUND FLOOR
C-0000 BUREAU-1 2,324 180 2,504 1,826 1 Ceiling Type FCU-4 2,420 2,420 3,130 3,130
C-0001 BUREAU-2 1,936 180 2,116 1,462 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
C-0002 BUREAU-3 1,936 180 2,116 1,462 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
C-0003 BUREAU-4 1,936 180 2,116 1,462 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
C-0004 BUREAU-5 1,936 180 2,116 1,462 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
C-0005 ACCUEIL 4,273 704 4,977 3,901 2 Ceiling Type FCU-4 2,420 4,840 3,130 6,260
C-0006/16 HALL/ATTENTE 7,332 880 8,212 4,266 4 Ceiling Type FCU-3 2,080 8,320 3,000 12,000
C-0008 COMMERCCE 2,134 180 2,314 1,655 1 Ceiling Type FCU-4 2,420 2,420 3,130 3,130
C-0020 RESERVE CAFE 1,717 633 2,350 1,457 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
C-0021 CAFETERIA 3,860 1,562 5,422 3,277 2 Ceiling Type FCU-4 2,420 4,840 3,130 6,260
C-0022 SALLE DE CONFERENCE 6,438 1,760 8,198 4,694 4 Ceiling Type FCU-3 1,910 7,640 2,540 10,160
C-0023 BUREAU-6 1,682 180 1,862 1,462 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
C-0024 BUREAU-7 1,682 180 1,862 1,462 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
COOLING LOAD COOLING TOTAL COOLING FCU SENSIBLE FCU SENSIBLE FCU UNIT FCU TOTAL
ROOM HEAT LOSS
NO ROOM NAME SENSIBLE LOAD LATENT LOAD QUANTITY TYPE FCU TYPE COOLING COOLING TOTAL COOLING COOLING TOTAL
(W)
(W) (w) (W) CAPACITY (w) (w) CAPACITY (w) (w)
C-0025 BUREAU-8 1,682 180 1,862 1,462 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
C-0026 BUREAU-9 1,682 180 1,862 1,462 1 Ceiling Type FCU-3 1,910 1,910 2,540 2,540
C-0027 BUREAU-10 2,183 120 2,303 1,826 1 Ceiling Type FCU-4 2,420 2,420 3,130 3,130
C-0028 CORRIDOR 3,380 528 3,908 2,287 2 Ceiling Type FCU-3 2,080 4,160 3,000 6,000
C-0038 HALL DE RECEPTION 7,124 528 7,652 2,908 1 Ceiling Type FCU-9 8,010 8,010 10,580 10,580
GROUND FLOOR TOTAL 61,248 37,967 26 59,840 83,510
COOLING LOAD COOLING TOTAL COOLING FCU SENSIBLE FCU SENSIBLE FCU UNIT FCU TOTAL
ROOM HEAT LOSS
NO ROOM NAME SENSIBLE LOAD LATENT LOAD QUANTITY TYPE FCU TYPE COOLING COOLING TOTAL COOLING COOLING TOTAL
(W)
(W) (w) (W) CAPACITY (w) (w) CAPACITY (w) (w)
4th FLOOR
16,10, CORRIDOR 9,540 176 9,716 5,772 4 Ceiling Type FCU-4 2,640 10,560 3,700 14,800
3rd FLOOR
12,6, CORRIDOR 6,105 176 6,281 3,782 4 Ceiling Type FCU-2 1,560 6,240 2,250 9,000
12,6, CORRIDOR-2 14,185 176 14,361 4,203 2 Ceiling Type FCU-9 7,640 15,280 10,580 21,160
2nd FLOOR
9,10, CORRIDOR 6,105 176 6,281 3,782 4 Ceiling Type FCU-2 1,560 6,240 2,250 9,000
9,10, CORRIDOR-2 13,609 176 13,785 3,394 2 Ceiling Type FCU-8 6,660 13,320 9,290 18,580
1st FLOOR
4,55, CORRIDOR 6,105 176 6,281 3,782 4 Ceiling Type FCU-2 1,560 6,240 2,250 9,000
4,55, CORRIDOR-2 13,609 176 13,785 3,394 2 Ceiling Type FCU-8 6,660 13,320 9,290 18,580
GROUND FLOOR
0,00, CORRIDOR 5,442 176 5,618 7,797 4 Ceiling Type FCU-2 1,560 6,240 2,250 9,000
0,00, CORRIDOR-2 13,266 176 13,442 4,194 2 Ceiling Type FCU-8 6,660 13,320 9,290 18,580
BLOCK D TOTAL 89,550 40,100
AHU-GP-A1S
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 3,000 550 300 27 439 5.1 0.019 0.648 17.49 0.90 93.82
2 1,900 400 250 2 343.3 5.3 0.020 0.956 1.91 1.80 30.18
3 1,500 400 250 5.5 343 4.2 0.020 0.617 3.39 0.45 4.70
4 1,000 350 200 6.5 286.4 4.0 0.021 0.707 4.60 0.60 5.69
5 700 350 200 1.3 286 2.8 0.023 0.368 0.48 0.45 2.09
6 400 300 150 6 228.5 2.5 0.025 0.394 2.36 0.60 2.20
7 100 150 150 7 164 1.2 0.031 0.171 1.20 0.45 30.41
8 3,000 550 300 1.5 439.1 5.1 0.019 0.648 0.97 40.00
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 32.40 209.10
GUVENLIK FAKTORU (%5) 1.62 10.45
GENEL TOPLAM 34 220
CIHAZ DISI TOPLAM STATIK BASINC 254 Pa
AHU-GP-A2S
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 2,000 400 300 30 378 4.6 0.019 0.665 19.96 0.75 39.68
2 950 250 300 1.5 299.1 3.5 0.022 0.537 0.81 1.80 13.41
3 700 200 300 1.5 266 3.2 0.022 0.534 0.80 0.45 2.85
4 550 150 300 2.5 228.5 3.4 0.023 0.704 1.76 0.60 4.16
5 450 150 300 3 229 2.8 0.024 0.488 1.46 0.45 2.09
6 350 150 300 3.5 228.5 2.2 0.025 0.309 1.08 0.45 1.26
7 100 150 150 8.5 164 1.2 0.031 0.171 1.45 0.90 30.83
8 2,000 400 300 1 377.7 4.6 0.019 0.665 0.67 0.15 91.94
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 27.99 186.22
GUVENLIK FAKTORU (%5) 1.40 9.31
GENEL TOPLAM 29 196
CIHAZ DISI TOPLAM STATIK BASINC 225 Pa
AHU-GP-A3S
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 1,850 400 300 30 378 4.3 0.020 0.576 17.28 0.75 38.28
2 1,350 400 300 2 377.7 3.1 0.021 0.323 0.65 0.60 3.53
3 1,100 300 300 5.5 328 3.4 0.021 0.448 2.47 0.45 3.12
4 800 300 200 1.5 266.4 3.7 0.022 0.682 1.02 0.50 4.13
5 400 300 150 2 229 2.5 0.025 0.394 0.79 0.75 32.75
6 1,850 400 300 1.5 377.7 4.3 0.020 0.576 0.86 0.30 93.31
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 23.07 175.12
GUVENLIK FAKTORU (%5) 1.15 8.76
GENEL TOPLAM 24 184
CIHAZ DISI TOPLAM STATIK BASINC 208 Pa
AHU-GP-A4S
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 13,200 1000 500 4 762 7.3 0.016 0.674 2.70 0.30 9.71
2 6,400 550 500 11 573.1 6.5 0.017 0.748 8.23 0.65 31.35
3 4,800 550 400 4 511 6.1 0.018 0.760 3.04 0.60 13.27
4 3,200 550 300 4 439.1 5.4 0.018 0.730 2.92 0.60 10.48
5 1,600 400 300 4 378 3.7 0.020 0.441 1.76 0.60 4.95
6 1,100 350 200 1.5 286.4 4.4 0.021 0.843 1.26 2.30 41.38
7 1,000 350 200 1 286 4.0 0.021 0.707 0.71 0.45 4.27
8 800 300 150 2 228.5 4.9 0.022 1.405 2.81 0.60 8.81
9 700 300 150 3 229 4.3 0.022 1.098 3.29 0.45 5.06
10 400 200 150 3 188.9 3.7 0.024 1.049 3.15 1.15 9.50
11 200 200 150 1 189 1.9 0.027 0.297 0.30 0.45 0.93
12 100 150 150 11 164.0 1.2 0.031 0.171 1.88 0.65 30.60
13 13,200 1200 500 1 827 6.1 0.016 0.432 0.43 0.30 93.64
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 32.48 263.95
GUVENLIK FAKTORU (%5) 1.62 13.20
GENEL TOPLAM 34 277
CIHAZ DISI TOPLAM STATIK BASINC 311 Pa
GO-OP1 SUPPLY
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 4,000 700 300 7.5 490 5.3 0.018 0.619 4.65 0.75 62.64
2 2,100 400 300 1.2 377.7 4.9 0.019 0.728 0.87 0.50 7.11
3 1,900 400 300 2.5 378 4.4 0.020 0.605 1.51 0.45 5.24
4 950 400 300 3 377.7 2.2 0.022 0.170 0.51 0.45 401.31
5 4,000 550 400 8 511 5.1 0.018 0.539 4.32 90.00
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 11.86 566.30
GUVENLIK FAKTORU (%5) 0.59 28.32
GENEL TOPLAM 12 595
CIHAZ DISI TOPLAM STATIK BASINC 607 Pa
GP-OP2 SUPPLY
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 4,000 700 300 7.5 490 5.3 0.018 0.619 4.65 0.75 62.64
2 2,100 400 300 1.2 377.7 4.9 0.019 0.728 0.87 0.50 7.11
3 1,900 400 300 2.5 378 4.4 0.020 0.605 1.51 0.45 5.24
4 950 400 300 3 377.7 2.2 0.022 0.170 0.51 0.45 401.31
5 4,000 550 400 8 511 5.1 0.018 0.539 4.32 90.00
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 11.86 566.30
GUVENLIK FAKTORU (%5) 0.59 28.32
GENEL TOPLAM 12 595
CIHAZ DISI TOPLAM STATIK BASINC 607 Pa
KS-OB03-1S
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 6,500 700 300 7.5 490 8.6 0.017 1.554 11.65 0.75 83.38
2 3,525 550 300 4.5 439.1 5.9 0.018 0.874 3.94 0.50 10.60
3 1,625 500 300 2.5 420 3.0 0.020 0.264 0.66 0.45 402.45
4 6,500 920 480 2 717.1 4.1 0.017 0.241 0.48 0.15 91.51
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 16.73 587.94
GUVENLIK FAKTORU (%5) 0.84 29.40
GENEL TOPLAM 18 617
CIHAZ DISI TOPLAM STATIK BASINC 635 Pa
KS-OB04-1S
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 6,500 700 300 7.5 490 8.6 0.017 1.554 11.65 0.75 83.38
2 3,525 550 300 4.5 439.1 5.9 0.018 0.874 3.94 0.50 10.60
3 1,625 500 300 2.5 420 3.0 0.020 0.264 0.66 0.45 402.45
4 6,500 920 480 2 717.1 4.1 0.017 0.241 0.48 0.15 91.51
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 16.73 587.94
GUVENLIK FAKTORU (%5) 0.84 29.40
GENEL TOPLAM 18 617
CIHAZ DISI TOPLAM STATIK BASINC 635 Pa
KS-OB05-1S
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 9,000 800 350 18 567 8.9 0.017 1.402 25.23 0.90 108.19
2 8,500 800 350 3 566.6 8.4 0.017 1.257 3.77 0.45 19.26
3 4,250 700 300 3 490 5.6 0.018 0.694 2.08 0.50 9.51
4 2,125 650 300 3 474.0 3.0 0.020 0.229 0.69 0.50 402.76
5 9,000 850 400 1 626 7.4 0.017 0.858 0.86 90.00
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 32.63 629.73
GUVENLIK FAKTORU (%5) 1.63 31.49
GENEL TOPLAM 34 661
CIHAZ DISI TOPLAM STATIK BASINC 695 Pa
GP-OP6 SUPPLY
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 3,300 550 300 40 439 5.6 0.018 0.773 30.93 1.50 107.87
2 300 200 200 2.5 218.6 2.1 0.026 0.306 0.76 1.00 2.61
3 150 200 150 7 189 1.4 0.029 0.177 1.24 1.45 501.68
4 3,300 600 300 15 457.0 5.1 0.018 0.626 9.38 0.60 99.37
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 42.32 711.53
GUVENLIK FAKTORU (%5) 2.12 35.58
GENEL TOPLAM 44 747
CIHAZ DISI TOPLAM STATIK BASINC 792 Pa
GP-OP7 SUPPLY
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 10,550 1000 450 35 719 6.5 0.016 0.577 20.18 0.75 49.15
2 7,700 1000 300 6.5 573.7 7.1 0.017 0.900 5.85 1.80 55.08
3 5,700 950 300 2.5 561 5.6 0.017 0.577 1.44 0.50 9.29
4 5,500 950 250 2.8 505.8 6.4 0.018 0.862 2.41 0.45 11.21
5 5,000 950 250 5 506 5.8 0.018 0.720 3.60 0.45 9.26
6 4,550 900 250 2 494.2 5.6 0.018 0.686 1.37 0.60 11.40
7 2,550 600 250 3.5 414 4.7 0.019 0.616 2.16 0.45 6.04
8 2,000 600 200 7 365.3 4.6 0.020 0.694 4.86 0.99 662.77
9 10,550 1000 450 9 719 6.5 0.016 0.577 5.19 0.15 93.83
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 47.06 908.04
GUVENLIK FAKTORU (%5) 2.35 45.40
GENEL TOPLAM 49 953
CIHAZ DISI TOPLAM STATIK BASINC 1003 Pa
GP-B1 SUPPLY
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 4,500 650 350 29 515 5.5 0.018 0.626 18.15 0.90 46.36
2 4,350 650 350 1.5 515.3 5.3 0.018 0.587 0.88 0.45 7.64
3 4,050 650 350 1.5 515 4.9 0.018 0.513 0.77 0.60 8.83
4 3,900 550 350 1 476.6 5.6 0.018 0.720 0.72 0.60 11.44
5 3,100 550 350 3.5 477 4.5 0.018 0.467 1.63 0.60 7.23
6 2,950 550 300 1.1 439.1 5.0 0.019 0.628 0.69 0.60 8.91
7 2,800 550 300 1.4 439 4.7 0.019 0.570 0.80 1.00 13.38
8 2,000 400 300 3.8 377.7 4.6 0.019 0.665 2.53 0.60 7.74
9 1,650 400 250 3.2 343 4.6 0.020 0.736 2.35 1.00 12.65
10 650 250 250 7 273.3 2.9 0.023 0.419 2.93 0.84 204.22
11 325 250 200 4.5 244 1.8 0.026 0.206 0.93 1.60 303.14
12 4,500 950 280 1 539.5 4.7 0.018 0.441 0.44 0.15 91.99
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 32.83 723.53
GUVENLIK FAKTORU (%5) 1.64 36.18
GENEL TOPLAM 34 760
CIHAZ DISI TOPLAM STATIK BASINC 794 Pa
GP-B2 SUPPLY
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 2,000 350 350 43 383 4.5 0.019 0.630 27.10 0.90 41.14
2 1,850 350 350 5 382.6 4.2 0.020 0.546 2.73 0.45 4.77
3 1,650 350 300 6 354 4.4 0.020 0.647 3.88 0.60 6.88
4 1,150 300 300 2.5 327.9 3.5 0.021 0.486 1.22 0.60 4.55
5 650 250 200 5.5 244 3.6 0.023 0.726 4.00 0.60 4.71
6 325 250 150 3.5 210.0 2.4 0.025 0.418 1.46 1.90 36.63
7 2,000 400 250 2 343 5.6 0.019 1.052 2.10 0.15 92.79
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 42.49 191.47
GUVENLIK FAKTORU (%5) 2.12 9.57
GENEL TOPLAM 45 201
CIHAZ DISI TOPLAM STATIK BASINC 246 Pa
GP-B3 SUPPLY
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 2,000 350 350 43 383 4.5 0.019 0.630 27.10 0.90 41.14
2 1,850 350 350 5 382.6 4.2 0.020 0.546 2.73 0.45 4.77
3 1,650 350 300 6 354 4.4 0.020 0.647 3.88 0.60 6.88
4 1,150 300 300 2.5 327.9 3.5 0.021 0.486 1.22 0.60 4.55
5 650 250 200 5.5 244 3.6 0.023 0.726 4.00 0.60 4.71
6 325 250 150 3.5 210.0 2.4 0.025 0.418 1.46 1.90 36.63
7 2,000 400 250 2 343 5.6 0.019 1.052 2.10 0.15 92.79
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 42.49 191.47
GUVENLIK FAKTORU (%5) 2.12 9.57
GENEL TOPLAM 45 201
CIHAZ DISI TOPLAM STATIK BASINC 246 Pa
GP-B4 SUPPLY
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 4,600 550 400 49 511 5.8 0.018 0.702 34.39 1.35 57.42
2 1,600 350 300 1.8 354.0 4.2 0.020 0.611 1.10 0.50 5.39
3 1,400 350 300 6 354 3.7 0.020 0.478 2.87 0.45 18.72
4 1,000 250 300 5 299.1 3.7 0.021 0.590 2.95 0.60 4.95
5 750 200 300 2 266 3.5 0.022 0.606 1.21 0.60 4.35
6 500 150 300 4.2 228.5 3.1 0.024 0.592 2.48 0.60 3.44
7 250 150 300 2.2 229 1.5 0.027 0.169 0.37 1.45 32.08
8 4,600 600 400 3 532.8 5.3 0.018 0.566 1.70 0.30 95.12
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 47.07 221.47
GUVENLIK FAKTORU (%5) 2.35 11.07
GENEL TOPLAM 49 233
CIHAZ DISI TOPLAM STATIK BASINC 282 Pa
GP-B5 SUPPLY
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 8,100 700 500 31 644 6.4 0.017 0.642 19.91 1.05 56.12
2 6,200 650 450 4 588.7 5.9 0.017 0.607 2.43 1.00 20.87
3 1,700 350 300 3.5 354 4.5 0.020 0.684 2.39 0.50 6.09
4 800 250 250 2 273.3 3.6 0.022 0.613 1.23 0.60 4.57
5 400 200 200 2.6 219 2.8 0.024 0.516 1.34 1.15 5.34
6 200 150 200 4.5 188.9 1.9 0.027 0.297 1.34 1.95 34.03
7 8,100 800 600 2.5 755 4.7 0.017 0.292 0.73 0.30 93.97
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 29.37 220.98
GUVENLIK FAKTORU (%5) 1.47 11.05
GENEL TOPLAM 31 232
CIHAZ DISI TOPLAM STATIK BASINC 263 Pa
GP-B6 SUPPLY
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 6,250 800 350 30 567 6.2 0.017 0.701 21.03 0.75 47.36
2 6,050 800 350 4.5 566.6 6.0 0.017 0.659 2.97 0.45 9.76
3 3,750 650 300 2.5 474 5.3 0.018 0.653 1.63 1.00 17.18
4 2,800 550 300 4.7 439.1 4.7 0.019 0.570 2.68 0.60 8.03
5 2,050 400 300 5.6 378 4.7 0.019 0.696 3.90 0.60 8.13
6 1,800 400 300 6.4 377.7 4.2 0.020 0.548 3.50 0.45 4.70
7 1,300 350 250 2 322 4.1 0.021 0.656 1.31 0.60 6.15
8 1,000 300 250 3.5 299.1 3.7 0.021 0.590 2.07 1.00 8.26
9 800 250 250 1.5 273 3.6 0.022 0.613 0.92 0.60 4.57
10 600 200 250 1.5 244.1 3.3 0.023 0.627 0.94 0.60 4.01
11 400 250 200 7 244 2.2 0.025 0.300 2.10 0.60 1.78
12 200 100 200 5 152.3 2.8 0.027 0.810 4.05 0.75 28.48
13 6,250 750 550 1.5 700 4.2 0.017 0.262 0.39 0.15 90.86
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 47.49 239.28
GUVENLIK FAKTORU (%5) 2.37 11.96
GENEL TOPLAM 50 251
CIHAZ DISI TOPLAM STATIK BASINC 301 Pa
GP-B7 SUPPLY
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 4,650 750 300 13.5 506 5.7 0.018 0.696 9.39 0.60 41.90
2 3,000 600 300 3 457.0 4.6 0.019 0.524 1.57 1.15 14.84
3 2,700 650 250 4.5 429 4.6 0.019 0.565 2.54 0.45 5.77
4 2,000 500 250 3.8 380.8 4.4 0.020 0.611 2.32 1.15 13.68
5 1,750 450 250 4 363 4.3 0.020 0.616 2.46 0.75 8.43
6 1,500 400 250 3.8 343.3 4.2 0.020 0.617 2.34 1.15 12.02
7 1,000 350 250 2.8 322 3.2 0.022 0.405 1.13 1.15 6.98
8 800 350 200 15 286.4 3.2 0.022 0.470 7.04 0.90 5.46
9 600 250 200 3.2 244 3.3 0.023 0.627 2.01 0.60 4.01
10 400 250 150 3.2 210.0 3.0 0.024 0.610 1.95 0.60 3.17
11 200 200 150 3.2 189 1.9 0.027 0.297 0.95 2.05 34.23
12 4,650 600 400 4 532.8 5.4 0.018 0.578 2.31 0.30 5.23
13 9,050 900 500 14 726 5.6 0.016 0.427 5.98 0.50 95.07
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 42.01 250.79
GUVENLIK FAKTORU (%5) 2.10 12.54
GENEL TOPLAM 44 263
CIHAZ DISI TOPLAM STATIK BASINC 307 Pa
GP-B8 SUPPLY
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 4,350 700 300 8 490 5.8 0.018 0.725 5.80 0.60 41.96
2 2,900 550 300 3.5 439.1 4.9 0.019 0.608 2.13 0.50 7.17
3 2,000 400 300 3.5 378 4.6 0.019 0.665 2.33 1.00 12.90
4 1,600 350 300 4 354.0 4.2 0.020 0.611 2.45 0.60 6.47
5 1,200 300 300 4.7 328 3.7 0.021 0.526 2.47 0.60 4.95
6 800 200 300 3.5 266.4 3.7 0.022 0.682 2.39 0.60 4.95
7 400 200 150 3 189 3.7 0.024 1.049 3.15 0.60 4.95
8 200 200 150 1.5 188.9 1.9 0.027 0.297 0.45 1.00 2.06
9 100 150 150 5 164 1.2 0.031 0.171 0.86 2.05 26.88
10 4,350 600 400 3 532.8 5.0 0.018 0.510 1.53 0.15 2.29
11 9,050 900 500 13 726 5.6 0.016 0.427 5.55 0.65 102.21
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 29.09 216.82
GUVENLIK FAKTORU (%5) 1.45 10.84
GENEL TOPLAM 31 228
CIHAZ DISI TOPLAM STATIK BASINC 258 Pa
GP-B9 SUPPLY
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 1,500 400 250 36 343 4.2 0.020 0.617 22.21 0.90 39.41
2 800 250 200 2.5 244.1 4.4 0.022 1.065 2.66 1.80 36.40
3 500 200 150 4.5 189 4.6 0.023 1.582 7.12 0.50 6.45
4 400 200 150 3 188.9 3.7 0.024 1.049 3.15 0.45 3.72
5 300 200 150 1 189 2.8 0.025 0.619 0.62 0.45 2.09
6 200 150 150 1 164.0 2.5 0.027 0.596 0.60 0.45 1.65
7 100 150 100 7.5 133 1.9 0.030 0.460 3.45 1.90 28.92
8 1,500 400 200 2 304.7 5.2 0.020 1.083 2.17 0.15 92.45
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 41.97 211.09
GUVENLIK FAKTORU (%5) 2.10 10.55
GENEL TOPLAM 44 222
CIHAZ DISI TOPLAM STATIK BASINC 266 Pa
GP-B10 SUPPLY
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 1,550 450 200 21 321 4.8 0.020 0.865 18.16 0.75 40.33
2 1,400 450 200 1.5 321.5 4.3 0.020 0.716 1.07 0.45 5.06
3 1,100 400 200 7 305 3.8 0.021 0.610 4.27 0.60 5.27
4 650 250 200 5 244.1 3.6 0.023 0.726 3.63 1.15 9.03
5 200 150 150 2.2 164 2.5 0.027 0.596 1.31 0.15 25.55
6 1,550 400 300 2 377.7 3.6 0.020 0.416 0.83 0.15 91.16
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 29.29 176.40
GUVENLIK FAKTORU (%5) 1.46 8.82
GENEL TOPLAM 31 185
CIHAZ DISI TOPLAM STATIK BASINC 216 Pa
GP-B12 SUPPLY
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 4,000 550 350 5.5 477 5.8 0.018 0.755 4.15 0.75 15.04
2 2,650 450 350 1.5 433.0 4.7 0.019 0.571 0.86 1.15 30.12
3 2,300 450 300 1.5 400 4.7 0.019 0.646 0.97 1.00 13.48
4 2,050 400 300 9 377.7 4.7 0.019 0.696 6.27 0.45 6.10
5 1,900 400 300 3.2 378 4.4 0.020 0.605 1.94 0.45 5.24
6 1,475 400 250 1 343.3 4.1 0.020 0.598 0.60 0.45 4.55
7 1,325 350 250 2 322 4.2 0.021 0.680 1.36 0.60 6.39
8 925 350 200 4.5 286.4 3.7 0.022 0.613 2.76 0.45 3.65
9 475 300 200 6 266 2.2 0.024 0.264 1.58 1.90 505.53
10 4,050 550 400 7 511.1 5.1 0.018 0.552 3.87 0.15 92.36
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 24.34 682.47
GUVENLIK FAKTORU (%5) 1.22 34.12
GENEL TOPLAM 26 717
CIHAZ DISI TOPLAM STATIK BASINC 742 Pa
GP-B13 SUPPLY
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 9,400 1000 450 3 719 5.8 0.016 0.464 1.39 0.30 6.08
2 4,650 600 400 21 532.8 5.4 0.018 0.578 12.14 0.80 13.95
3 4,450 600 400 4 533 5.2 0.018 0.532 2.13 0.60 24.58
4 3,400 550 350 4 476.6 4.9 0.018 0.554 2.22 0.50 7.25
5 2,875 550 300 2 439 4.8 0.019 0.599 1.20 0.45 6.35
6 2,475 550 300 1 439.1 4.2 0.019 0.454 0.45 0.45 4.70
7 2,075 400 300 5 378 4.8 0.019 0.712 3.56 0.84 211.67
8 1,575 350 250 1 322.2 5.0 0.020 0.936 0.94 0.50 7.53
9 1,050 300 250 3 299 3.9 0.021 0.646 1.94 0.60 5.46
10 525 300 250 3.2 299.1 1.9 0.024 0.183 0.58 1.90 304.32
11 9,400 1000 450 3 719 5.8 0.016 0.464 1.39 0.30 96.08
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 27.93 687.97
GUVENLIK FAKTORU (%5) 1.40 34.40
GENEL TOPLAM 29 722
CIHAZ DISI TOPLAM STATIK BASINC 752 Pa
AHU-GP-C1S
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 3,700 600 300 1.5 457 5.7 0.018 0.774 1.16 0.30 5.89
2 1,700 450 250 29 362.8 4.2 0.020 0.584 16.93 1.10 41.67
3 900 350 200 4.5 286 3.6 0.022 0.583 2.62 1.80 13.82
4 600 250 200 2.5 244.1 3.3 0.023 0.627 1.57 1.80 12.04
5 500 200 200 1 219 3.5 0.023 0.776 0.78 0.60 4.35
6 400 200 200 3.5 218.6 2.8 0.024 0.516 1.81 0.60 2.79
7 200 150 150 3 164 2.5 0.027 0.596 1.79 0.60 2.20
8 100 150 150 7 164.0 1.2 0.031 0.171 1.20 2.20 32.02
9 3,700 600 300 1 457 5.7 0.018 0.774 0.77 0.30 95.89
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 28.62 210.67
GUVENLIK FAKTORU (%5) 1.43 10.53
GENEL TOPLAM 30 221
CIHAZ DISI TOPLAM STATIK BASINC 251 Pa
AHU-GP-C2S
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 4,000 550 350 29 477 5.8 0.018 0.755 21.89 0.60 42.03
2 1,500 400 250 2.5 343.3 4.2 0.020 0.617 1.54 2.30 24.04
3 1,100 400 200 4.5 305 3.8 0.021 0.610 2.75 0.45 3.95
4 900 350 200 3 286.4 3.6 0.022 0.583 1.75 1.30 9.98
5 600 250 200 3.5 244 3.3 0.023 0.627 2.20 0.60 4.01
6 200 150 150 3 164.0 2.5 0.027 0.596 1.79 2.05 37.52
7 4,000 600 300 1.5 457 6.2 0.018 0.901 1.35 0.30 96.88
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 33.26 218.42
GUVENLIK FAKTORU (%5) 1.66 10.92
GENEL TOPLAM 35 229
CIHAZ DISI TOPLAM STATIK BASINC 264 Pa
AHU-GP-C3S
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 4,500 700 300 2.5 490 6.0 0.018 0.773 1.93 0.30 6.40
2 2,300 550 250 31 397.7 4.6 0.019 0.628 19.46 1.25 46.25
3 1,350 450 200 4 321 4.2 0.021 0.670 2.68 1.80 18.81
4 1,050 400 200 3 304.7 3.6 0.021 0.560 1.68 1.80 14.40
5 150 150 150 10 164 1.9 0.028 0.354 3.54 2.35 34.85
6 4,500 700 300 1 490.2 6.0 0.018 0.773 0.77 0.30 96.40
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 30.08 217.11
GUVENLIK FAKTORU (%5) 1.50 10.86
GENEL TOPLAM 32 228
CIHAZ DISI TOPLAM STATIK BASINC 260 Pa
AHU-GP-C4S
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 9,900 800 300 3 520 11.5 0.016 2.506 7.52 0.30 23.71
2 4,800 550 450 16 543.2 5.4 0.018 0.566 9.05 0.80 28.98
3 3,200 550 300 4 439 5.4 0.018 0.730 2.92 0.60 10.48
4 1,600 350 250 6 322.2 5.1 0.020 0.964 5.78 1.60 39.85
5 1,000 350 200 1 286 4.0 0.021 0.707 0.71 1.75 16.59
6 800 300 150 2 228.5 4.9 0.022 1.405 2.81 0.60 8.81
7 700 300 150 3 229 4.3 0.022 1.098 3.29 0.45 5.06
8 400 200 150 3.5 188.9 3.7 0.024 1.049 3.67 1.15 9.50
9 100 150 150 11 164 1.2 0.031 0.171 1.88 0.65 30.60
10 9,900 1000 500 1.5 761.7 5.5 0.016 0.391 0.59 0.15 92.73
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 38.22 266.30
GUVENLIK FAKTORU (%5) 1.91 13.32
GENEL TOPLAM 40 280
CIHAZ DISI TOPLAM STATIK BASINC 320 Pa
EF-GE-A1R
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 100 150 150 3 164 1.2 0.031 0.171 0.51 1.15 31.06
2 200 150 150 3.5 164.0 2.5 0.027 0.596 2.09 1.75 6.42
3 650 250 200 2 244 3.6 0.023 0.726 1.45 1.00 7.85
4 800 250 250 1 273.3 3.6 0.022 0.613 0.61 0.60 4.57
5 950 300 250 2.5 299 3.5 0.022 0.537 1.34 0.60 4.47
6 1,150 350 250 2 322.2 3.7 0.021 0.524 1.05 0.60 4.81
7 1,200 350 250 1 322 3.8 0.021 0.566 0.57 0.60 5.24
8 1,400 350 300 2.5 354.0 3.7 0.020 0.478 1.20 0.60 4.95
9 1,450 350 300 2.5 354 3.8 0.020 0.510 1.28 0.45 3.99
10 1,650 350 300 2.5 354.0 4.4 0.020 0.647 1.62 0.45 5.16
11 1,700 350 300 1 354 4.5 0.020 0.684 0.68 0.45 5.48
12 2,300 450 300 3 399.6 4.7 0.019 0.646 1.94 1.90 25.62
13 3,000 550 300 26 439 5.1 0.019 0.648 16.84 1.40 41.61
14 3,000 600 300 5 457 4.6 0.019 0.524 2.62 0.15 41.04
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 33.80 192.27
GUVENLIK FAKTORU (%5) 1.69 9.61
GENEL TOPLAM 35 202
CIHAZ DISI TOPLAM STATIK BASINC 237 Pa
EF-GE-A2R
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 200 150 200 7 189 1.9 0.027 0.297 2.08 2.60 35.37
2 300 200 200 1 218.6 2.1 0.026 0.306 0.31 1.15 3.00
3 700 300 200 5 266 3.2 0.022 0.534 2.67 0.60 3.79
4 950 350 200 1 286.4 3.8 0.022 0.644 0.64 0.60 5.13
5 1,050 350 200 1 286 4.2 0.021 0.774 0.77 0.60 6.27
6 1,300 350 250 3.5 322.2 4.1 0.021 0.656 2.30 1.75 17.94
7 1,900 400 300 1 378 4.4 0.020 0.605 0.61 0.50 5.82
8 2,000 400 300 26 377.7 4.6 0.019 0.665 17.30 1.35 47.42
9 2,000 400 300 1 378 4.6 0.019 0.665 0.67 0.30 43.87
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 27.34 168.63
GUVENLIK FAKTORU (%5) 1.37 8.43
GENEL TOPLAM 29 177
CIHAZ DISI TOPLAM STATIK BASINC 206 Pa
EF-GE-A3R
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 200 200 150 1 189 1.9 0.027 0.297 0.30 2.45 35.06
2 250 200 150 3.5 188.9 2.3 0.026 0.445 1.56 0.60 1.94
3 400 200 200 2.7 219 2.8 0.024 0.516 1.39 0.60 2.79
4 700 300 200 3 266.4 3.2 0.022 0.534 1.60 0.60 3.79
5 900 350 200 31 286 3.6 0.022 0.583 18.06 3.50 56.88
6 900 350 200 2 286.4 3.6 0.022 0.583 1.17 0.30 42.30
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 24.08 142.75
GUVENLIK FAKTORU (%5) 1.20 7.14
GENEL TOPLAM 25 150
CIHAZ DISI TOPLAM STATIK BASINC 175 Pa
EF-GE-A3.1R
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 550 150 300 2.5 229 3.4 0.023 0.704 1.76 3.45 53.94
2 950 250 300 29 299.1 3.5 0.022 0.537 15.58 1.35 40.06
3 950 250 300 2 299 3.5 0.022 0.537 1.07 0.30 42.24
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 18.41 136.24
GUVENLIK FAKTORU (%5) 0.92 6.81
GENEL TOPLAM 19 143
CIHAZ DISI TOPLAM STATIK BASINC 162 Pa
EF-GE-A4R
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 100 150 150 6.5 164 1.2 0.031 0.171 1.11 2.60 32.39
2 150 250 150 1 210.0 1.1 0.029 0.104 0.10 0.60 0.45
3 225 250 150 1 210 1.7 0.027 0.215 0.22 0.45 0.75
4 300 250 150 1 210.0 2.2 0.026 0.362 0.36 0.45 1.34
5 550 250 150 4.5 210 4.1 0.023 1.094 4.92 1.15 11.49
6 1,050 300 250 2 299.1 3.9 0.021 0.646 1.29 3.30 45.04
7 1,650 400 300 4 378 3.8 0.020 0.467 1.87 1.00 8.78
8 3,300 550 300 4 439.1 5.6 0.018 0.773 3.09 0.60 11.15
9 4,950 600 400 4 533 5.7 0.018 0.650 2.60 0.60 11.86
10 6,600 600 500 16 598.1 6.1 0.017 0.639 10.22 0.90 35.23
11 13,400 1000 500 2.5 762 7.4 0.016 0.694 1.73 0.60 20.02
12 13,400 1200 500 5 827.3 6.2 0.016 0.444 2.22 0.30 46.95
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 29.74 225.45
GUVENLIK FAKTORU (%5) 1.49 11.27
GENEL TOPLAM 31 237
CIHAZ DISI TOPLAM STATIK BASINC 268 Pa
OP-GE1 RETURN
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 150 150 150 2 164 1.9 0.028 0.354 0.71 1.15 232.37
2 1,800 350 300 1.5 354.0 4.8 0.020 0.760 1.14 1.00 13.65
3 3,600 450 400 4 464 5.6 0.018 0.722 2.89 1.60 29.73
4 3,600 600 300 4 457.0 5.6 0.018 0.735 2.94 0.45 48.36
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 7.68 324.11
GUVENLIK FAKTORU (%5) 0.38 16.21
GENEL TOPLAM 8 340
CIHAZ DISI TOPLAM STATIK BASINC 348 Pa
OP-GE2 RETURN
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 150 150 150 2 164 1.9 0.028 0.354 0.71 1.15 232.37
2 1,800 350 300 1.5 354.0 4.8 0.020 0.760 1.14 1.00 13.65
3 3,600 450 400 4 464 5.6 0.018 0.722 2.89 1.60 29.73
4 3,600 600 300 4 457.0 5.6 0.018 0.735 2.94 0.45 48.36
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 7.68 324.11
GUVENLIK FAKTORU (%5) 0.38 16.21
GENEL TOPLAM 8 340
CIHAZ DISI TOPLAM STATIK BASINC 348 Pa
KS-OPGE3-1R
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 100 150 150 2 164 1.2 0.031 0.171 0.34 1.15 231.06
2 3,025 450 400 1.5 463.6 4.7 0.018 0.523 0.78 1.00 13.12
3 6,250 450 400 4 464 9.6 0.017 2.070 8.28 1.60 89.60
4 6,250 600 300 4 457.0 9.6 0.017 2.106 8.42 0.45 65.20
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 17.83 398.98
GUVENLIK FAKTORU (%5) 0.89 19.95
GENEL TOPLAM 19 419
CIHAZ DISI TOPLAM STATIK BASINC 438 Pa
KS-OPGE4-1R
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 100 150 150 2 164 1.2 0.031 0.171 0.34 1.15 231.06
2 3,025 450 400 1.5 463.6 4.7 0.018 0.523 0.78 1.00 13.12
3 6,250 450 400 4 464 9.6 0.017 2.070 8.28 1.60 89.60
4 6,250 600 300 4 457.0 9.6 0.017 2.106 8.42 0.45 65.20
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 17.83 398.98
GUVENLIK FAKTORU (%5) 0.89 19.95
GENEL TOPLAM 19 419
CIHAZ DISI TOPLAM STATIK BASINC 438 Pa
KS-OPGE5-1R
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 400 200 150 2 189 3.7 0.024 1.049 2.10 1.15 239.50
2 1,725 350 250 2 322.2 5.5 0.020 1.108 2.22 1.00 18.05
3 8,500 500 500 2.5 547 9.4 0.017 1.630 4.07 1.00 53.70
4 8,600 500 500 22 546.6 9.6 0.017 1.666 36.66 1.80 113.94
5 8,600 750 400 3 592 8.0 0.017 1.070 3.21 0.15 45.73
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 48.26 470.91
GUVENLIK FAKTORU (%5) 2.41 23.55
GENEL TOPLAM 51 494
CIHAZ DISI TOPLAM STATIK BASINC 545 Pa
OP-GE6 RETURN
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1
2 150 150 200 2 188.9 1.4 0.029 0.177 0.35 1.15 231.34
3 1,350 350 300 2 354 3.6 0.021 0.447 0.89 1.15 8.83
4 1,500 350 300 2 354.0 4.0 0.020 0.543 1.09 0.60 5.69
5 2,700 500 300 34 420 5.0 0.019 0.672 22.85 3.35 80.42
6 2,700 500 300 1.5 420.0 5.0 0.019 0.672 1.01 0.45 46.77
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 26.19 373.04
GUVENLIK FAKTORU (%5) 1.31 18.65
GENEL TOPLAM 28 392
CIHAZ DISI TOPLAM STATIK BASINC 419 Pa
OP-GE7 RETURN
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 375 250 150 9 210 2.8 0.025 0.542 4.88 0.30 26.39
2 750 300 200 5 266.4 3.5 0.022 0.606 3.03 0.50 3.63
3 1,125 450 200 3 321 3.5 0.021 0.479 1.44 0.50 3.63
4 2,850 550 300 4.5 439.1 4.8 0.019 0.589 2.65 0.69 209.56
5 4,350 750 300 11 506 5.4 0.018 0.614 6.75 0.65 11.29
6 4,900 800 300 5 520.3 5.7 0.018 0.657 3.28 0.60 11.62
7 5,200 800 300 1.6 520 6.0 0.018 0.735 1.18 0.45 9.81
8 5,950 800 350 3 566.6 5.9 0.017 0.639 1.92 0.60 12.59
9 6,675 850 350 1.5 582 6.2 0.017 0.685 1.03 0.45 10.52
10 6,875 850 350 1.5 582.2 6.4 0.017 0.724 1.09 0.45 11.16
11 10,250 850 500 14 706 6.7 0.016 0.622 8.70 1.25 63.77
12 10,250 850 500 22 706.5 6.7 0.016 0.622 13.68 0.75 60.26
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 49.61 434.24
GUVENLIK FAKTORU (%5) 2.48 21.71
GENEL TOPLAM 52 456
CIHAZ DISI TOPLAM STATIK BASINC 508 Pa
GE-B1 RETURN
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 375 200 250 4 244 2.1 0.025 0.267 1.07 1.15 33.00
2 750 250 250 5 273.3 3.3 0.022 0.544 2.72 0.84 205.62
3 1,150 300 300 4 328 3.5 0.021 0.486 1.95 1.00 7.58
4 2,000 400 300 1.1 377.7 4.6 0.019 0.665 0.73 0.45 5.81
5 2,550 500 300 1.5 420 4.7 0.019 0.604 0.91 0.60 8.05
6 2,700 500 300 1 420.0 5.0 0.019 0.672 0.67 0.45 6.77
7 3,000 550 300 1.6 439 5.1 0.019 0.648 1.04 0.60 9.21
8 3,400 550 300 1 439.1 5.7 0.018 0.818 0.82 0.45 8.88
9 3,850 550 300 26.5 439 6.5 0.018 1.038 27.50 0.75 48.97
10 3,850 550 300 1.5 439.1 6.5 0.018 1.038 1.56 0.15 43.79
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 38.96 377.69
GUVENLIK FAKTORU (%5) 1.95 18.88
GENEL TOPLAM 41 397
CIHAZ DISI TOPLAM STATIK BASINC 437 Pa
GE-B2 RETURN
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 475 200 300 3 266 2.2 0.024 0.264 0.79 2.45 37.13
2 925 250 300 4 299.1 3.4 0.022 0.512 2.05 0.75 5.30
3 1,400 350 300 4 354 3.7 0.020 0.478 1.91 0.60 4.95
4 2,850 600 300 1.1 457.0 4.4 0.019 0.477 0.52 0.60 6.99
5 3,150 650 300 6 474 4.5 0.018 0.473 2.84 0.60 7.27
6 3,500 650 300 2 474.0 5.0 0.018 0.575 1.15 0.45 6.73
7 4,700 650 300 37 474 6.7 0.018 1.006 37.21 1.35 66.43
8 4,700 650 300 4.5 474.0 6.7 0.018 1.006 4.53 0.30 48.10
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 51.00 182.90
GUVENLIK FAKTORU (%5) 2.55 9.15
GENEL TOPLAM 54 192
CIHAZ DISI TOPLAM STATIK BASINC 246 Pa
GE-B3 RETURN
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 325 150 250 3.5 210 2.4 0.025 0.418 1.46 2.45 38.55
2 650 200 250 6 244.1 3.6 0.023 0.726 4.36 0.90 7.07
3 1,650 350 300 5.5 354 4.4 0.020 0.647 3.56 1.15 13.19
4 1,800 400 300 29 377.7 4.2 0.020 0.548 15.88 1.50 45.68
5 1,800 400 250 3.5 343 5.0 0.020 0.865 3.03 0.45 46.77
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 28.29 151.25
GUVENLIK FAKTORU (%5) 1.41 7.56
GENEL TOPLAM 30 159
CIHAZ DISI TOPLAM STATIK BASINC 189 Pa
GE-B4 RETURN
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 75 150 150 1.2 164 0.9 0.033 0.102 0.12 2.45 26.26
2 125 150 150 2 164.0 1.5 0.029 0.255 0.51 0.45 0.65
3 325 200 200 2 219 2.3 0.025 0.354 0.71 1.00 3.07
4 525 250 200 4.5 244.1 2.9 0.023 0.491 2.21 0.60 3.07
5 725 300 200 1.6 266 3.4 0.022 0.569 0.91 0.45 3.05
6 850 350 200 1 286.4 3.4 0.022 0.525 0.52 0.60 4.11
7 1,050 400 200 8.5 305 3.6 0.021 0.560 4.76 0.75 6.00
8 1,450 400 250 1 343.3 4.0 0.020 0.580 0.58 0.60 5.86
9 1,650 450 250 3 363 4.1 0.020 0.553 1.66 0.45 19.50
10 4,650 650 350 7 515.3 5.7 0.018 0.666 4.66 0.50 9.70
11 4,750 650 350 30 515 5.8 0.018 0.693 20.79 1.80 66.45
12 4,750 600 400 4 532.8 5.5 0.018 0.602 2.41 0.45 48.19
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 39.84 195.91
GUVENLIK FAKTORU (%5) 1.99 9.80
GENEL TOPLAM 42 206
CIHAZ DISI TOPLAM STATIK BASINC 248 Pa
GE-B5 RETURN
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 500 200 300 3.5 266 2.3 0.024 0.289 1.01 2.45 37.90
2 1,500 400 300 2.2 377.7 3.5 0.020 0.392 0.86 2.15 15.60
3 2,000 400 300 2.5 378 4.6 0.019 0.665 1.66 1.15 14.84
4 2,500 550 300 5.5 439.1 4.2 0.019 0.462 2.54 0.60 6.40
5 9,000 750 500 29 666 6.7 0.016 0.661 19.18 3.20 115.62
6 9,000 900 500 1.5 725.6 5.6 0.016 0.423 0.63 0.15 42.79
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 25.89 233.15
GUVENLIK FAKTORU (%5) 1.29 11.66
GENEL TOPLAM 27 245
CIHAZ DISI TOPLAM STATIK BASINC 272 Pa
GE-B6 RETURN
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 200 200 100 6 152 2.8 0.027 0.810 4.86 2.45 41.38
2 400 150 250 4 210.0 3.0 0.024 0.610 2.44 0.60 3.17
3 600 200 250 1 244 3.3 0.023 0.627 0.63 0.45 3.01
4 975 250 300 2 299.1 3.6 0.021 0.563 1.13 0.60 4.71
5 1,175 300 300 4 328 3.6 0.021 0.506 2.02 0.60 4.75
6 1,475 350 300 7.5 354.0 3.9 0.020 0.526 3.95 1.00 9.17
7 2,125 450 300 1 400 4.4 0.019 0.558 0.56 2.00 23.02
8 2,500 500 300 8 420.0 4.6 0.019 0.583 4.66 0.45 5.81
9 3,075 550 300 2.2 439 5.2 0.018 0.678 1.49 0.45 7.26
10 5,000 600 400 2.3 532.8 5.8 0.018 0.663 1.52 2.00 40.32
11 5,100 600 400 27 533 5.9 0.017 0.688 18.58 1.50 61.46
12 5,100 750 400 7.5 591.5 4.7 0.018 0.398 2.99 0.45 46.04
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 44.83 250.10
GUVENLIK FAKTORU (%5) 2.24 12.50
GENEL TOPLAM 47 263
CIHAZ DISI TOPLAM STATIK BASINC 310 Pa
GE-B7 RETURN
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 200 150 200 3.2 189 1.9 0.027 0.297 0.95 2.45 35.06
2 400 200 200 3 218.6 2.8 0.024 0.516 1.55 0.60 2.79
3 600 250 200 2 244 3.3 0.023 0.627 1.25 0.60 4.01
4 800 250 250 3.5 273.3 3.6 0.022 0.613 2.15 0.45 3.42
5 1,050 250 300 3.5 299 3.9 0.021 0.646 2.26 0.60 5.46
6 1,550 400 300 4 377.7 3.6 0.020 0.416 1.66 2.15 16.66
7 1,900 450 300 4 400 3.9 0.020 0.454 1.82 2.15 19.78
8 2,750 550 300 4.5 439.1 4.6 0.019 0.551 2.48 2.15 27.74
9 2,900 600 300 3 457 4.5 0.019 0.492 1.48 1.75 21.10
10 4,800 700 350 30 533.2 5.4 0.018 0.590 17.69 1.70 60.31
11 4,800 600 400 1 533 5.6 0.018 0.614 0.61 0.30 45.57
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 33.90 241.92
GUVENLIK FAKTORU (%5) 1.70 12.10
GENEL TOPLAM 36 254
CIHAZ DISI TOPLAM STATIK BASINC 290 Pa
GE-B8 RETURN
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 100 150 150 1.5 164 1.2 0.031 0.171 0.26 2.45 27.25
2 150 150 150 7 164.0 1.9 0.028 0.354 2.48 0.60 1.24
3 300 200 150 1.5 189 2.8 0.025 0.619 0.93 0.60 2.79
4 400 250 150 4 210.0 3.0 0.024 0.610 2.44 0.60 3.17
5 700 300 200 2 266 3.2 0.022 0.534 1.07 2.15 13.59
6 1,150 350 250 8 322.2 3.7 0.021 0.524 4.19 2.15 17.25
7 1,800 550 250 1.5 398 3.6 0.020 0.400 0.60 2.00 15.92
8 2,250 550 250 4 397.7 4.5 0.019 0.603 2.41 0.60 7.46
9 2,400 600 250 3.5 414 4.4 0.019 0.551 1.93 0.45 5.35
10 2,850 700 250 2 443.0 4.5 0.019 0.522 1.04 0.45 5.54
11 3,300 700 250 5.5 443 5.2 0.018 0.685 3.77 0.60 9.91
12 4,850 700 250 2 443.0 7.7 0.018 1.423 2.85 0.45 16.06
13 5,150 800 350 15 567 5.1 0.018 0.487 7.30 2.60 52.06
14 5,150 600 400 10 533 6.0 0.017 0.701 7.01 0.45 45.20
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 38.27 222.79
GUVENLIK FAKTORU (%5) 1.91 11.14
GENEL TOPLAM 40 234
CIHAZ DISI TOPLAM STATIK BASINC 274 Pa
GE-B9 RETURN
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 100 150 150 2 164 1.2 0.031 0.171 0.34 2.45 27.25
2 200 200 150 5.5 188.9 1.9 0.027 0.297 1.63 0.60 1.24
3 300 200 150 1.5 189 2.8 0.025 0.619 0.93 0.45 2.09
4 400 200 150 1 188.9 3.7 0.024 1.049 1.05 0.45 3.72
5 450 200 200 4 219 3.1 0.024 0.639 2.56 0.60 3.53
6 550 250 200 2 244.1 3.1 0.023 0.535 1.07 0.60 3.37
7 650 300 200 3.5 266 3.0 0.023 0.466 1.63 0.60 3.27
8 800 350 200 1 286.4 3.2 0.022 0.470 0.47 1.75 25.62
9 1,400 400 250 29 343 3.9 0.020 0.543 15.76 1.40 42.75
10 1,400 400 250 8 343.3 3.9 0.020 0.543 4.35 0.15 41.37
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 29.79 154.19
GUVENLIK FAKTORU (%5) 1.49 7.71
GENEL TOPLAM 31 162
CIHAZ DISI TOPLAM STATIK BASINC 193 Pa
GE-B10 RETURN
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 250 150 150 7.5 164 3.1 0.026 0.896 6.72 2.45 39.05
2 600 350 200 4.5 286.4 2.4 0.023 0.278 1.25 0.60 2.05
3 850 400 200 3 305 3.0 0.022 0.380 1.14 0.75 3.93
4 1,400 450 250 24.5 362.8 3.5 0.021 0.408 10.01 1.75 27.59
5 1,400 450 250 8 363 3.5 0.021 0.408 3.27 0.30 42.16
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 22.39 114.78
GUVENLIK FAKTORU (%5) 1.12 5.74
GENEL TOPLAM 24 121
CIHAZ DISI TOPLAM STATIK BASINC 144 Pa
GE-B12 RETURN
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 250 200 150 7.5 189 2.3 0.026 0.445 3.33 2.45 32.90
2 500 250 200 7.5 244.1 2.8 0.024 0.450 3.37 0.60 2.79
3 750 300 200 7.5 266 3.5 0.022 0.606 4.54 0.60 4.35
4 1,000 350 200 18.5 286.4 4.0 0.021 0.707 13.08 0.90 208.53
5 1,275 350 250 5 322 4.0 0.021 0.633 3.17 0.45 4.44
6 1,715 350 250 2.5 322.2 5.4 0.020 1.096 2.74 0.45 8.03
7 2,115 400 350 5 409 4.2 0.019 0.503 2.51 0.60 6.36
8 2,555 450 400 4 463.6 3.9 0.019 0.383 1.53 0.60 5.62
9 2,995 450 450 3.5 492 4.1 0.019 0.384 1.34 0.45 4.57
10 3,425 450 450 4 491.9 4.7 0.018 0.491 1.97 0.45 5.98
11 3,685 500 450 4 518 4.5 0.018 0.434 1.73 0.45 20.61
12 4,700 650 400 16 553.4 5.0 0.018 0.485 7.75 1.90 28.84
13 4,700 650 400 5.5 553 5.0 0.018 0.485 2.67 0.15 41.23
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 49.75 374.25
GUVENLIK FAKTORU (%5) 2.49 18.71
GENEL TOPLAM 52 393
CIHAZ DISI TOPLAM STATIK BASINC 445 Pa
GE-B13 RETURN
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 500 300 200 3.2 266 2.3 0.024 0.289 0.93 2.45 32.90
2 1,025 300 250 3 299.1 3.8 0.021 0.618 1.85 0.60 5.21
3 1,550 350 350 2.2 383 3.5 0.020 0.394 0.87 0.60 4.46
4 2,075 400 300 7 377.7 4.8 0.019 0.712 4.99 1.19 216.53
5 2,825 450 350 2.5 433 5.0 0.019 0.643 1.61 1.00 14.94
6 3,225 500 350 4 455.5 5.1 0.018 0.634 2.54 0.45 7.10
7 4,025 550 400 21 511 5.1 0.018 0.546 11.46 1.10 32.10
8 8,150 900 450 1.5 685.5 5.6 0.017 0.458 0.69 0.65 12.23
9 8,150 900 550 1.5 763 4.6 0.017 0.276 0.41 0.30 43.78
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 25.34 369.25
GUVENLIK FAKTORU (%5) 1.27 18.46
GENEL TOPLAM 27 388
CIHAZ DISI TOPLAM STATIK BASINC 414 Pa
GE-B14 RETURN
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 500 200 300 2.2 266 2.3 0.024 0.289 0.64 2.45 37.90
2 1,000 250 300 2.2 299.1 3.7 0.021 0.590 1.30 0.60 4.95
3 1,500 300 350 4.7 354 4.0 0.020 0.543 2.55 0.60 5.69
4 2,500 300 500 3.2 420.0 4.6 0.019 0.583 1.86 0.55 7.10
5 2,650 300 500 2 420 4.9 0.019 0.649 1.30 1.15 16.67
6 3,150 300 600 16 457.0 4.9 0.018 0.574 9.18 1.20 32.07
7 2,650 300 600 1 457 4.1 0.019 0.417 0.42 0.15 41.51
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 17.25 145.90
GUVENLIK FAKTORU (%5) 0.86 7.29
GENEL TOPLAM 18 153
CIHAZ DISI TOPLAM STATIK BASINC 171 Pa
EF-GE-C1R
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 100 150 150 7.5 164 1.2 0.031 0.171 1.28 2.75 32.52
2 200 150 150 5 164.0 2.5 0.027 0.596 2.98 0.45 1.65
3 300 200 150 1 189 2.8 0.025 0.619 0.62 0.60 2.79
4 900 300 250 3 299.1 3.3 0.022 0.486 1.46 1.80 12.04
5 1,700 450 250 24 363 4.2 0.020 0.584 14.01 1.25 43.26
6 3,700 600 300 2 457.0 5.7 0.018 0.774 1.55 0.30 45.89
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 21.90 138.15
GUVENLIK FAKTORU (%5) 1.10 6.91
GENEL TOPLAM 23 145
CIHAZ DISI TOPLAM STATIK BASINC 168 Pa
EF-GE-C2R
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 625 200 350 2 286 2.5 0.023 0.299 0.60 2.45 39.07
2 1,250 300 350 1 354.0 3.3 0.021 0.388 0.39 0.60 3.95
3 2,075 400 350 3 409 4.1 0.019 0.485 1.46 0.75 7.65
4 2,500 400 350 2 408.8 5.0 0.019 0.685 1.37 0.60 8.89
5 2,850 450 350 4 433 5.0 0.019 0.653 2.61 1.90 28.90
6 4,000 600 350 28 496.5 5.3 0.018 0.610 17.07 1.35 52.75
7 4,000 600 350 2 496 5.3 0.018 0.610 1.22 0.30 45.06
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 24.72 186.27
GUVENLIK FAKTORU (%5) 1.24 9.31
GENEL TOPLAM 26 196
CIHAZ DISI TOPLAM STATIK BASINC 222 Pa
EF-GE-C3R
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 75 150 150 2.5 164 0.9 0.033 0.102 0.26 2.45 31.26
2 125 150 150 2.5 164.0 1.5 0.029 0.255 0.64 0.45 0.65
3 200 150 150 6 164 2.5 0.027 0.596 3.58 0.60 2.20
4 300 300 150 8 228.5 1.9 0.026 0.234 1.87 0.75 1.55
5 1,400 500 200 1.5 337 3.9 0.021 0.556 0.83 0.50 4.55
6 1,500 500 200 1 337.0 4.2 0.020 0.631 0.63 1.75 18.29
7 2,300 550 300 30 439 3.9 0.019 0.396 11.89 1.10 39.93
8 4,500 700 300 1.5 490.2 6.0 0.018 0.773 1.16 0.80 17.06
9 4,500 700 300 1.5 490 6.0 0.018 0.773 1.16 0.30 46.40
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 22.02 161.89
GUVENLIK FAKTORU (%5) 1.10 8.09
GENEL TOPLAM 23 170
CIHAZ DISI TOPLAM STATIK BASINC 193 Pa
EF-GE-C4R
KANAL BASINC KAYBI
KANAL UZUNLU ESDEGE
NO DEBI HIZ f R LxR C Z
EBT K R CAP
m3/h mm mm m mm m/s Pa/m Pa Pa
1 100 150 150 6 164 1.2 0.031 0.171 1.03 2.60 32.39
2 150 250 150 1 210.0 1.1 0.029 0.104 0.10 0.45 0.33
3 225 250 150 1 210 1.7 0.027 0.215 0.22 0.45 0.75
4 425 250 150 1 210.0 3.1 0.024 0.682 0.68 0.45 2.68
5 500 250 150 1 210 3.7 0.023 0.918 0.92 0.45 3.72
6 550 250 150 4.5 210.0 4.1 0.023 1.094 4.92 1.90 18.98
7 1,050 300 250 2 299 3.9 0.021 0.646 1.29 1.00 24.10
8 1,650 400 300 5 377.7 3.8 0.020 0.467 2.33 1.00 8.78
9 3,300 500 300 4 420 6.1 0.018 0.976 3.91 0.60 13.49
10 4,950 500 400 17 488.1 6.9 0.018 1.021 17.35 1.05 44.88
11 10,050 900 450 3 686 6.9 0.016 0.680 2.04 0.80 22.88
12 10,050 1000 500 2 761.7 5.6 0.016 0.402 0.80 0.30 45.63
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
STATIK DINAMIK
KAYIP KAYIP
TOPLAM 35.60 218.62
GUVENLIK FAKTORU (%5) 1.78 10.93
GENEL TOPLAM 37 230
CIHAZ DISI TOPLAM STATIK BASINC 267 Pa
GDYEL HOSPITAL
BLOCK B BOILER CIRCULATION PUMPS PRESSURE LOSS CALCULATION
ATTACHMENT-6
TOTAL LENGTH
PIPE LENGTH
SECTION NO
FLOW RATE
AHU CRITICAL CURCUIT ELBOW TEE VALVE NON RETURN VALVE STRAINER OTHER
lt/s inch (m) (m) (m) (m) (m) (m) (m) m kPa kPa
CP-1 Boiler Outlet - CP-2 Branch 1 6.93 5 5.0 1.0 x 4.0 = 4.0 1.0 x 9.4 = 9.4 3.0 x 0.9 = 2.6 1.0 x 9.8 = 9.8 1.0 x 13.7 = 13.7 1.0 x 4.0 = 4.0 48.4 4.0 1.9
CP-2 Branch - CP-3 Branch 2 13.86 6 2.5 - x - = - 1.0 x 9.8 = 9.8 - x - = - - x - = - - x - = - - x - = - 12.3 6.8 0.8
CP-3 Branch - Supply Header Inlet 3 20.78 8 21.0 6.0 x 6.4 = 38.4 1.0 x 13.1 = 13.1 3.0 x 1.4 = 4.1 - x - = - - x - = - 1.0 x 14.0 = 14.0 90.6 2.8 2.5
Return Header Inlet - CP-3 Branch 4 20.78 8 37.0 11.0 x 6.4 = 70.4 1.0 x 13.1 = 13.1 3.0 x 1.4 = 4.1 - x - = - - x - = - 1.0 x 14.0 = 14.0 138.7 2.8 3.9
CP-1 Branch - CP-2 Branch 5 13.86 6 2.5 - x - = - 1.0 x 9.8 = 9.8 - x - = - - x - = - - x - = - - x - = - 12.3 6.8 0.8
CP-2 Branch - CP-3 Boiler Inlet 6 6.93 5 5.0 2.0 x 4.0 = 7.9 1.0 x 9.4 = 9.4 2.0 x 0.9 = 1.7 - x - = - 1.0 x 13.7 = 13.7 1.0 x 4.0 = 4.0 41.8 4.0 1.7
TOTAL LENGTH
PIPE LENGTH
SECTION NO
FLOW RATE
AHU CRITICAL CURCUIT ELBOW TEE VALVE NON RETURN VALVE STRAINER OTHER
lt/s inch (m) (m) (m) (m) (m) (m) (m) m kPa kPa
TOTAL LENGTH
PIPE LENGTH
SECTION NO
FLOW RATE
AHU CRITICAL CURCUIT ELBOW TEE VALVE NON RETURN VALVE STRAINER OTHER
lt/s inch (m) (m) (m) (m) (m) (m) (m) m kPa kPa
TOTAL LENGTH
PIPE LENGTH
SECTION NO
FLOW RATE
AHU CRITICAL CURCUIT ELBOW TEE VALVE NON RETURN VALVE STRAINER OTHER
lt/s inch (m) (m) (m) (m) (m) (m) (m) m kPa kPa
Heating Supply Header - GP/B11 Branch 1 5.67 5 16.0 3.0 x 4.0 = 11.9 1.0 x 9.8 = 9.8 3.0 x 0.9 = 2.6 1.0 x 10.1 = 10.1 1.0 x 15.2 = 15.2 1.0 x 20.7 = 20.7 86.2 3.0 2.6
GP/B11 Branch - GP/OP1 Branch 2 4.74 4 9.0 1.0 x 3.4 = 3.4 1.0 x 8.5 = 8.5 - x - = - - x - = - - x - = - - x - = - 20.9 5.0 1.0
GP/OP1 Branch - GP/B14 Branch 3 4.44 4 5.5 - x - = - 1.0 x 8.5 = 8.5 - x - = - - x - = - - x - = - - x - = - 14.0 4.7 0.7
GP/B14 Branch - GP/OP2 Branch 4 4.11 4 2.5 - x - = - 1.0 x 8.5 = 8.5 3.0 x 0.6 = 1.8 - x - = - - x - = - - x - = - 12.9 4.1 0.5
GP/OP2 Branch - GP/B1 Branch 5 3.81 4 4.0 2.0 x 3.4 = 6.7 1.0 x 6.7 = 6.7 - x - = - - x - = - - x - = - - x - = - 17.4 4.0 0.7
GP/B1 Branch - GP/OP3 Branch 6 3.33 4 4.0 - x - = - 1.0 x 6.7 = 6.7 - x - = - - x - = - - x - = - - x - = - 10.7 2.8 0.3
GP/OP3 Branch - GP/OP5 Branch 7 2.84 3 7.0 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 11.9 6.8 0.8
GP/OP5 Branch - GP/OP4 Branch 8 2.19 3 6.0 1.0 x 2.4 = 2.4 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 13.3 3.5 0.5
GP/OP4 Branch - GP/B12 Branch 9 1.70 3 6.0 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 10.9 2.5 0.3
GP/B12 Branch - GP/B13 Branch 10 1.27 21/2 6.0 2.0 x 2.1 = 4.3 1.0 x 4.0 = 4.0 - x - = - - x - = - - x - = - - x - = - 14.2 3.2 0.5
GP/B13 Branch - GP/OP6 Coil Inlet 11 0.25 11/2 14.0 5.0 x 1.2 = 6.1 1.0 x 2.7 = 2.7 2.0 x 0.3 = 0.5 - x - = - 1.0 x 6.1 = 6.1 1.0 x 0.8 = 0.8 30.3 2.0 0.6
GP/OP6 Coil Outlet - GP/B13 Branch 12 0.25 11/2 14.0 5.0 x 1.2 = 6.1 1.0 x 2.7 = 2.7 3.0 x 0.3 = 0.8 - x - = - 1.0 x 6.1 = 6.1 1.0 x 1.4 = 1.4 31.2 2.0 0.6
GP/B13 Branch - GP/B12 Branch 13 1.27 21/2 6.0 2.0 x 2.1 = 4.3 1.0 x 4.0 = 4.0 - x - = - - x - = - - x - = - - x - = - 14.2 3.2 0.5
GP/B12 Branch - GP/OP4 Branch 14 1.70 3 6.0 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 10.9 2.5 0.3
GP/OP4 Branch - GP/OP5 Branch 15 2.19 3 6.0 1.0 x 2.4 = 2.4 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 13.3 3.5 0.5
GP/OP5 Branch - GP/OP3 Branch 16 2.84 3 7.0 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 11.9 6.8 0.8
GP/OP3 Branch - GP/B1 Branch 17 3.33 4 4.0 - x - = - 1.0 x 6.7 = 6.7 - x - = - - x - = - - x - = - - x - = - 10.7 2.8 0.3
GP/B1 Branch - GP/OP2 Branch 18 3.81 4 4.0 2.0 x 3.4 = 6.7 1.0 x 6.7 = 6.7 - x - = - - x - = - - x - = - - x - = - 17.4 4.0 0.7
GP/OP2 Branch - GP/B14 Branch 19 4.11 4 2.5 - x - = - 1.0 x 8.5 = 8.5 3.0 x 0.6 = 1.8 - x - = - - x - = - - x - = - 12.9 4.1 0.5
GP/B14 Branch - GP/OP1 Branch 20 4.44 4 5.5 - x - = - 1.0 x 8.5 = 8.5 - x - = - - x - = - - x - = - - x - = - 14.0 4.7 0.7
GP/OP1 Branch - GP/B11 Branch 21 4.74 4 9.0 1.0 x 3.4 = 3.4 1.0 x 8.5 = 8.5 - x - = - - x - = - - x - = - - x - = - 20.9 5.0 1.0
GP/B11 Branch - Heating Return Header 22 5.67 5 13.0 5.0 x 4.0 = 19.8 1.0 x 9.8 = 9.8 1.0 x 0.9 = 0.9 - x - = - - x - = - 1.0 x 2.4 = 2.4 45.9 3.0 1.4
TOTAL LENGTH
PIPE LENGTH
SECTION NO
FLOW RATE
AHU CRITICAL CURCUIT ELBOW TEE VALVE NON RETURN VALVE STRAINER OTHER
lt/s inch (m) (m) (m) (m) (m) (m) (m) m kPa kPa
Heating Supply Header - GP/B7/8 Branch 1 3.00 3 5.0 - x - = - 1.0 x 4.9 = 4.9 3.0 x 0.5 = 1.6 1.0 x 6.1 = 6.1 1.0 x 9.1 = 9.1 1.0 x 12.2 = 12.2 38.9 6.7 2.6
GP/B7/8 Branch - GP/B9 Branch 2 2.26 3 13.0 1.0 x 2.4 = 2.4 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 20.3 3.7 0.8
GP/B9 Branch - GP/B3 Branch 3 2.13 3 1.5 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 6.4 3.5 0.2
GP/B3 Branch - GP/B2 Branch 4 1.96 3 1.0 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 5.9 3.0 0.2
GP/B2 Branch - GP/B10 Branch 5 1.59 3 3.0 1.0 x 2.4 = 2.4 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 10.3 2.3 0.2
GP/B10 Branch - GP/B6 Branch 6 1.46 3 5.0 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 9.9 2.0 0.2
GP/B6 Branch - GP/B4 Branch 7 0.94 2 29.0 1.0 x 1.7 = 1.7 1.0 x 3.7 = 3.7 - x - = - - x - = - - x - = - - x - = - 34.3 8.3 2.8
GP/B4 Branch - GP/B5 Coil Inlet 8 0.56 2 9.0 4.0 x 1.7 = 6.7 1.0 x 3.7 = 3.7 2.0 x 0.4 = 0.7 - x - = - 1.0 x 7.6 = 7.6 1.0 x 0.9 = 0.9 28.6 4.5 1.3
GP/B5 Coil Outlet - GP/B4 Branch 9 0.56 2 9.0 4.0 x 1.7 = 6.7 1.0 x 3.7 = 3.7 3.0 x 0.4 = 1.1 - x - = - 1.0 x 7.6 = 7.6 1.0 x 1.5 = 1.5 29.6 4.5 1.3
GP/B4 Branch - GP/B6 Branch 10 0.94 2 29.0 1.0 x 1.7 = 1.7 1.0 x 3.7 = 3.7 - x - = - - x - = - - x - = - - x - = - 34.3 8.3 2.8
GP/B6 Branch - GP/B10 Branch 11 1.46 3 5.0 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 9.9 2.0 0.2
GP/B10 Branch - GP/B2 Branch 12 1.59 3 3.0 1.0 x 2.4 = 2.4 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 10.3 2.3 0.2
GP/B2 Branch - GP/B3 Branch 13 1.96 3 1.0 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 5.9 3.0 0.2
GP/B3 Branch - GP/B9 Branch 14 2.13 3 1.5 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 6.4 3.5 0.2
GP/B9 Branch - GP/B7/8 Branch 15 2.26 3 10.0 2.0 x 2.4 = 4.9 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 19.8 3.7 0.7
GP/B7/8 Branch - Heating Return Header 16 3.00 3 5.0 - x - = - 1.0 x 4.9 = 4.9 1.0 x 0.5 = 0.5 - x - = - - x - = - 1.0 x 1.8 = 1.8 12.2 6.7 0.8
TOTAL LENGTH
PIPE LENGTH
SECTION NO
FLOW RATE
AHU CRITICAL CURCUIT ELBOW TEE VALVE NON RETURN VALVE STRAINER OTHER
lt/s inch (m) (m) (m) (m) (m) (m) (m) m kPa kPa
Heating Supply Header - Exchanger 1 Branch 1 3.58 4 17.0 4.0 x 3.4 = 13.4 1.0 x 8.5 = 8.5 3.0 x 0.6 = 1.8 1.0 x 8.5 = 8.5 1.0 x 12.2 = 12.2 1.0 x 17.7 = 17.7 79.2 3.2 2.5
Exchanger 1 Branch - Exchanger 2 Inlet 2 1.79 21/2 8.0 2.0 x 2.1 = 4.3 1.0 x 4.0 = 4.0 2.0 x 0.4 = 0.8 - x - = - 1.0 x 7.6 = 7.6 1.0 x 1.2 = 1.2 25.9 7.0 1.8
Exchanger 2 Outlet - Exchanger 1 Branch 3 1.79 21/2 8.0 2.0 x 2.1 = 4.3 1.0 x 4.0 = 4.0 3.0 x 0.4 = 1.2 - x - = - 1.0 x 7.6 = 7.6 1.0 x 0.9 = 0.9 26.0 7.0 1.8
Exchanger 1 Branch - Heating Return Header 4 3.58 4 22.0 4.0 x 3.4 = 13.4 1.0 x 8.5 = 8.5 1.0 x 0.6 = 0.6 - x - = - - x - = - 1.0 x 2.4 = 2.4 47.0 3.2 1.5
TOTAL LENGTH
PIPE LENGTH
SECTION NO
FLOW RATE
AHU CRITICAL CURCUIT ELBOW TEE VALVE NON RETURN VALVE STRAINER OTHER
lt/s inch (m) (m) (m) (m) (m) (m) (m) m kPa kPa
Heating Supply Header - GP/A3 Branch 1 1.65 3 9.0 2.0 x 2.4 = 4.9 - x - = - 4.0 x 0.5 = 2.1 1.0 x 5.8 = 5.8 1.0 x 8.5 = 8.5 1.0 x 16.0 = 16.0 46.2 3.0 1.4
GP/A3 Branch - GP/A4 Branch 2 1.49 3 3.0 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 7.9 2.0 0.2
GP/A4 Branch - GP/A2 Branch 3 0.42 2 3.0 - x - = - 1.0 x 3.7 = 3.7 - x - = - - x - = - - x - = - - x - = - 6.7 3.5 0.2
GP/A2 Branch - GP/A1 Coil Inlet 4 0.25 11/2 10.0 4.0 x 1.2 = 4.9 1.0 x 2.7 = 2.7 3.0 x 0.6 = 1.7 - x - = - 1.0 x 6.1 = 6.1 1.0 x 0.3 = 0.3 25.8 2.0 0.5
GP/A1 Coil Outlet - GP/A2 Branch 5 0.25 11/2 10.0 4.0 x 1.2 = 4.9 1.0 x 2.7 = 2.7 2.0 x 0.6 = 1.2 - x - = - 1.0 x 6.1 = 6.1 1.0 x 1.2 = 1.2 26.1 2.0 0.5
GP/A2 Branch - GP/A4 Branch 6 0.42 2 3.0 - x - = - 1.0 x 3.7 = 3.7 - x - = - - x - = - - x - = - - x - = - 6.7 3.5 0.2
GP/A4 Branch - GP/A3 Branch 7 1.49 3 3.0 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 7.9 2.0 0.2
GP/A3 Branch - Heating Return Header 8 1.65 3 10.0 3.0 x 2.4 = 7.3 - x - = - 1.0 x 0.5 = 0.5 - x - = - - x - = - 1.0 x 1.5 = 1.5 19.4 3.0 0.6
TOTAL LENGTH
PIPE LENGTH
SECTION NO
FLOW RATE
AHU CRITICAL CURCUIT ELBOW TEE VALVE NON RETURN VALVE STRAINER OTHER
lt/s inch (m) (m) (m) (m) (m) (m) (m) m kPa kPa
Heating Supply Header - GP/C2 Branch 1 1.83 3 11.0 2.0 x 2.4 = 4.9 - x - = - 4.0 x 0.5 = 2.1 1.0 x 5.8 = 5.8 1.0 x 8.5 = 8.5 1.0 x 16.0 = 16.0 48.2 3.0 1.4
GP/C2 Branch - GP/C1 Branch 2 1.49 3 2.0 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 6.9 2.0 0.1
GP/C1 Branch - GP/C4 Branch 3 1.18 21/2 3.0 - x - = - 1.0 x 4.3 = 4.3 - x - = - - x - = - - x - = - - x - = - 7.3 3.0 0.2
GP/C4 Branch - GP/C3 Coil Inlet 4 0.37 2 10.0 4.0 x 1.7 = 6.7 1.0 x 3.7 = 3.7 3.0 x 0.6 = 1.8 - x - = - 1.0 x 7.6 = 7.6 1.0 x 0.9 = 0.9 30.7 2.2 0.7
GP/C3 Coil Outlet - GP/C4 Branch 5 0.37 2 10.0 4.0 x 1.7 = 6.7 1.0 x 3.7 = 3.7 2.0 x 0.6 = 1.2 - x - = - 1.0 x 7.6 = 7.6 1.0 x 1.8 = 1.8 31.0 2.2 0.7
GP/C4 Branch - GP/C1 Branch 6 1.18 21/2 3.0 - x - = - 1.0 x 4.3 = 4.3 - x - = - - x - = - - x - = - - x - = - 7.3 3.0 0.2
GP/C1 Branch - GP/C2 Branch 7 1.49 3 2.0 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 6.9 2.0 0.1
GP/C2 Branch - Heating Return Header 8 1.83 3 12.0 3.0 x 2.4 = 7.3 - x - = - 1.0 x 0.5 = 0.5 - x - = - - x - = - 1.0 x 1.5 = 1.5 21.4 3.0 0.6
TOTAL LENGTH
PIPE LENGTH
SECTION NO
FLOW RATE
AHU CRITICAL CURCUIT ELBOW TEE VALVE NON RETURN VALVE STRAINER OTHER
lt/s inch (m) (m) (m) (m) (m) (m) (m) m kPa kPa
Cooling Supply Header - GP/B6/10 Branch 1 8.60 5 11.0 2.0 x 4.0 = 7.9 1.0 x 8.5 = 8.5 3.0 x 0.9 = 2.6 1.0 x 10.4 = 10.4 1.0 x 15.2 = 15.2 1.0 x 25.6 = 25.6 81.3 5.8 4.7
GP/B6/10 Branch - GP/B4 Branch 2 5.64 4 22.5 1.0 x 3.4 = 3.4 1.0 x 6.7 = 6.7 - x - = - - x - = - - x - = - - x - = - 32.6 7.0 2.3
GP/B4 Branch - GP/B5 Branch 3 4.44 4 4.0 - x - = - 1.0 x 6.7 = 6.7 - x - = - - x - = - - x - = - - x - = - 10.7 4.5 0.5
GP/B5 Branch - GP/B8 Branch 4 2.34 21/2 29.0 3.0 x 2.1 = 6.4 1.0 x 4.0 = 4.0 - x - = - - x - = - - x - = - - x - = - 39.4 14.0 5.5
GP/B8 Branch - GP/B7 Coil Inlet 5 1.19 21/2 10.0 3.0 x 2.1 = 6.4 1.0 x 4.0 = 4.0 2.0 x 0.4 = 0.8 - x - = - 1.0 x 12.2 = 12.2 1.0 x 0.7 = 0.7 34.0 3.0 1.0
GP/B7 Coil Outlet - GP/B8 Branch 6 1.19 21/2 10.0 - x - = - 1.0 x 4.0 = 4.0 3.0 x 0.4 = 1.2 - x - = - 1.0 x 12.2 = 12.2 1.0 x 2.1 = 2.1 29.5 3.0 0.9
GP/B8 Branch - GP/B5 Branch 7 2.34 21/2 29.0 3.0 x 2.1 = 6.4 1.0 x 4.0 = 4.0 - x - = - - x - = - - x - = - - x - = - 39.4 14.0 5.5
GP/B5 Branch - GP/B4 Branch 8 4.44 4 4.0 - x - = - 1.0 x 6.7 = 6.7 - x - = - - x - = - - x - = - - x - = - 10.7 4.5 0.5
GP/B4 Branch - GP/B6/10 Branch 9 5.64 4 22.5 1.0 x 3.4 = 3.4 1.0 x 6.7 = 6.7 - x - = - - x - = - - x - = - - x - = - 32.6 7.0 2.3
GP/B6/10 Branch - Cooling Return Header 1 8.60 5 18.0 3.0 x 4.0 = 11.9 1.0 x 8.5 = 8.5 1.0 x 0.9 = 0.9 - x - = - 1.0 x 15.2 = 15.2 1.0 x 2.1 = 2.1 56.7 5.8 3.3
TOTAL LENGTH
PIPE LENGTH
SECTION NO
FLOW RATE
AHU CRITICAL CURCUIT ELBOW TEE VALVE NON RETURN VALVE STRAINER OTHER
lt/s inch (m) (m) (m) (m) (m) (m) (m) m kPa kPa
Cooling Supply Header - GP/B1 Branch 1 26.80 8 15.0 3.0 x 6.4 = 19.2 1.0 x 13.1 = 13.1 3.0 x 1.4 = 4.1 1.0 x 16.2 = 16.2 1.0 x 22.9 = 22.9 1.0 x 37.8 = 37.8 128.2 4.5 5.8
GP/B1 Branch - GP/OP1/OP2 Branch 2 24.80 8 2.0 - x - = - 1.0 x 13.1 = 13.1 - x - = - - x - = - - x - = - - x - = - 15.1 4.0 0.6
GP/OP1/OP2 Branch - GP/OP3 Branch 3 15.05 5 5.0 - x - = - 1.0 x 9.4 = 9.4 - x - = - - x - = - - x - = - - x - = - 14.4 17.0 2.5
GP/OP3 Branch - GP/OP5 Branch 4 12.66 5 13.0 1.0 x 4.0 = 4.0 1.0 x 9.4 = 9.4 - x - = - - x - = - - x - = - - x - = - 26.4 9.5 2.5
GP/OP5 Branch - GP/OP4 Branch 5 9.51 5 2.5 - x - = - 1.0 x 9.4 = 9.4 - x - = - - x - = - - x - = - - x - = - 11.9 7.0 0.8
GP/OP4 Branch - GP/OP12 Branch 6 7.12 4 6.5 - x - = - 1.0 x 6.7 = 6.7 - x - = - - x - = - - x - = - - x - = - 13.2 12.0 1.6
GP/OP12 Branch - GP/OP13 Branch 7 5.30 4 10.5 - x - = - 1.0 x 6.7 = 6.7 - x - = - - x - = - - x - = - - x - = - 17.2 7.0 1.2
GP/OP13 Branch - GP/OP6 Coil Inlet 8 1.34 21/2 18.0 4.0 x 2.1 = 8.5 1.0 x 4.0 = 4.0 2.0 x 0.4 = 0.8 - x - = - 1.0 x 12.2 = 12.2 1.0 x 0.7 = 0.7 44.2 4.4 1.9
GP/OP6 Coil Outlet - GP/OP13 Branch 9 1.34 21/2 18.0 4.0 x 2.1 = 8.5 1.0 x 4.0 = 4.0 3.0 x 0.4 = 1.2 - x - = - 1.0 x 12.2 = 12.2 1.0 x 2.1 = 2.1 46.0 4.4 2.0
GP/OP13 Branch - GP/OP12 Branch 10 5.30 4 10.5 - x - = - 1.0 x 6.7 = 6.7 - x - = - - x - = - - x - = - - x - = - 17.2 7.0 1.2
GP/OP12 Branch - GP/OP4 Branch 11 7.12 4 6.5 - x - = - 1.0 x 6.7 = 6.7 - x - = - - x - = - - x - = - - x - = - 13.2 12.0 1.6
GP/OP4 Branch - GP/OP5 Branch 12 9.51 5 2.5 - x - = - 1.0 x 9.4 = 9.4 - x - = - - x - = - - x - = - - x - = - 11.9 7.0 0.8
GP/OP5 Branch - GP/OP3 Branch 13 12.66 5 13.0 1.0 x 4.0 = 4.0 1.0 x 9.4 = 9.4 - x - = - - x - = - - x - = - - x - = - 26.4 9.5 2.5
GP/OP3 Branch - GP/OP1/OP2 Branch 14 15.05 5 5.0 - x - = - 1.0 x 9.4 = 9.4 - x - = - - x - = - - x - = - - x - = - 14.4 17.0 2.5
GP/OP1/OP2 Branch - GP/B1 Branch 15 24.80 8 2.0 - x - = - 1.0 x 13.1 = 13.1 - x - = - - x - = - - x - = - - x - = - 15.1 4.0 0.6
GP/B1 Branch - Cooling Return Header 16 26.80 8 15.0 3.0 x 6.4 = 19.2 1.0 x 13.1 = 13.1 1.0 x 1.4 = 1.4 x = - x = - 1.0 x 2.4 = 2.4 51.1 4.5 2.3
TOTAL LENGTH
PIPE LENGTH
SECTION NO
FLOW RATE
AHU CRITICAL CURCUIT ELBOW TEE VALVE NON RETURN VALVE STRAINER OTHER
lt/s inch (m) (m) (m) (m) (m) (m) (m) m kPa kPa
Cooling Supply Header - GP/A3 Branch 1 5.16 4 10.0 3.0 x 3.7 = 11.0 - x - = - 4.0 x 0.7 = 2.8 1.0 x 7.6 = 7.6 1.0 x 13.7 = 13.7 1.0 x 24.4 = 24.4 69.5 6.5 4.5
GP/A3 Branch - GP/A4 Branch 2 4.68 4 4.0 - x - = - 1.0 x 6.7 = 6.7 - x - = - - x - = - - x - = - - x - = - 10.7 6.0 0.6
GP/A4 Branch - GP/A2 Branch 3 1.29 3 3.0 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 7.9 1.3 0.1
GP/A2 Branch - GP/A1 Coil Inlet 4 0.19 2 11.0 6.0 x 1.7 = 10.1 1.0 x 3.7 = 3.7 3.0 x 0.4 = 1.2 - x - = - 1.0 x 6.7 = 6.7 1.0 x 1.1 = 1.1 33.7 1.0 0.3
GP/A1 Coil Outlet - GP/A2 Branch 5 0.19 2 11.0 6.0 x 1.7 = 10.1 1.0 x 3.7 = 3.7 2.0 x 0.4 = 0.8 - x - = - 1.0 x 6.7 = 6.7 1.0 x 0.4 = 0.4 32.6 1.0 0.3
GP/A2 Branch - GP/A4 Branch 6 1.29 3 3.0 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 7.9 1.3 0.1
GP/A4 Branch - GP/A3 Branch 7 4.68 4 4.0 - x - = - 1.0 x 6.7 = 6.7 - x - = - - x - = - - x - = - - x - = - 10.7 6.0 0.6
GP/A3 Branch - Cooling Return Header 8 5.16 4 8.0 2.0 x 3.7 = 7.3 - x - = - 1.0 x 0.7 = 0.7 - x - = - - x - = - 1.0 x 1.8 = 1.8 17.8 6.5 1.2
TOTAL LENGTH
PIPE LENGTH
SECTION NO
FLOW RATE
AHU CRITICAL CURCUIT ELBOW TEE VALVE NON RETURN VALVE STRAINER OTHER
lt/s inch (m) (m) (m) (m) (m) (m) (m) m kPa kPa
Cooling Supply Header - GP/C2 Branch 1 5.69 4 11.0 3.0 x 3.7 = 11.0 - x - = - 4.0 x 0.7 = 2.8 1.0 x 7.6 = 7.6 1.0 x 13.7 = 13.7 1.0 x 24.4 = 24.4 70.5 7.5 5.3
GP/C2 Branch - GP/C1 Branch 2 4.63 3 1.5 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 6.4 15.0 1.0
GP/C1 Branch - GP/C4 Branch 3 3.68 3 3.0 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 7.9 10.0 0.8
GP/C4 Branch - GP/C3 Coil Inlet 4 1.15 2 10.0 4.0 x 1.7 = 6.7 1.0 x 3.7 = 3.7 3.0 x 0.6 = 1.8 - x - = - 1.0 x 7.6 = 7.6 1.0 x 0.9 = 0.9 30.7 11.0 3.4
GP/C3 Coil Outlet - GP/C4 Branch 5 1.15 2 10.0 4.0 x 1.7 = 6.7 1.0 x 3.7 = 3.7 2.0 x 0.6 = 1.2 - x - = - 1.0 x 7.6 = 7.6 1.0 x 1.8 = 1.8 31.0 11.0 3.4
GP/C4 Branch - GP/C1 Branch 6 3.68 3 3.0 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 7.9 10.0 0.8
GP/C1 Branch - GP/C2 Branch 7 4.63 3 1.5 - x - = - 1.0 x 4.9 = 4.9 - x - = - - x - = - - x - = - - x - = - 6.4 15.0 1.0
GP/C2 Branch - Cooling Return Header 8 5.69 4 9.0 3.0 x 3.7 = 11.0 - x - = - 1.0 x 0.7 = 0.7 - x - = - - x - = - 1.0 x 1.8 = 1.8 22.5 7.5 1.7