Air Circuit Breakers


Configuration Manual · 2012

SENTRON
Answers for infrastructure.
© Siemens AG 2011
© Siemens AG 2011

3WL Air Circuit Breakers

2 Introduction

3WL air circuit breakers


3WL air circuit breakers/non-automatic
air circuit breakers up to 6300 A (AC)
General data
6 - Design
12 - Function
19 - Configuration
24 - Technical specifications
Project planning aids
34 - Characteristic curves
36 - Dimensional drawings
49 - Circuit diagrams
51 - More information
3WL non-automatic air circuit breakers
up to 4000 A (DC)
General data
52 - Technical specifications
Project planning aids
53 - Characteristic curves
53 - Dimensional drawings
57 - Circuit diagrams
58 - More information

© Siemens AG 2011
All dimensions in mm.

Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers

Introduction

■ Overview

Size I Size II Size III


3WL air circuit breakers
3WL air circuit breakers/non-automatic air circuit breakers 3WL non-automatic air circuit breakers
for AC, up to 6300 A, IEC up to 4000 A (DC)
Sizes I, II, III II
Rated current In A 630, 800, 1000, 1250, 1000, 2000, 4000
1600, 2000, 2500, 3200, 4000,
5000, 6300
Number of poles 3-pole, 4-pole 3-pole, 4-pole
Rated operational V AC ... 690/1000/1150 --
voltage Ue V DC -- ... 1000
Rated ultimate Size I Size II Size III
short-circuit breaking kA 55/66/85 66/80/100 100/150 (3-pole), 30/25/20
capacity at 500 V AC 130 (4-pole) (at 300/600/1000 V DC)
Endurance Operating Up to 20000 15000 10000 15000
cycles
Mounting position 30° 30° 30° 30° 30° 30° 30° 30°

NSE0_00061a NSE0_00062a NSE0_00061a NSE0_00062a

Degree of protection
With cover IP55 IP55
Without cover IP41 IP41
(with door sealing frame)
Dimensions 3-/4-pole W mm 320/410 460/590 704/914 460/590
W D Fixed H mm 434 434 434 434
mounting D mm 291 291 291 291
H

Withdraw- H mm 465,5 465,5 465,5 465,5


NSS0_00535 able D mm 471 471 471 471
NSE0_01109a
NSE0_01108a
NSE0_01107a
NSE0_01106a

NSE0_01111a

Rating Plug

Type ETU15B1) ETU25B ETU27B ETU45B ETU76B


Electronic releases for 3WL circuit breakers
Overload protection ✓ ✓ ✓ ✓ ✓
Short-time delayed -- ✓ ✓ ✓ ✓
short-circuit protection
Instantaneous ✓ ✓ ✓ ✓ ✓
short-circuit protection
Neutral conductor protection -- -- ✓ ✓ ✓
Ground-fault protection -- -- ✓ ❑ ❑
Zone Selective Interlocking -- -- -- ❑ ❑
LCD, 4-line -- -- -- ❑ --
LCD, graphic -- -- -- -- ✓
Communication -- -- -- ❑ ❑
Measurement function Plus -- -- -- ❑ ❑
Selectable parameter sets -- -- -- -- ✓
Parameters freely programmable -- -- -- -- ✓
CubicleBUS -- -- -- ✓ ✓
✓ Standard
-- Not available
❑ Optional
1)
ETU15B cannot be used with 3WL circuit breakers, size III.
3WL air circuit breakers/non-automatic air circuit breakers
according to UL 489 up to 5000 A, see Catalog LV 16.

2 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers

Introduction

Switching capacity
Sizes I II III
Type 3WL11 3WL12 3WL13
Switching capacity class N S H N S H H C C
N S H N S H H 3-pole C 4-pole C

Short-circuit breaking capacity


Rated operational voltage Ue up to 415 V AC
Icu kA 55 66 85 66 80 100 100 150 130
Ics kA 55 66 85 66 80 100 100 150 130
Icm kA 121 145 187 145 176 220 220 330 286
Rated operational voltage Ue up to 500 V AC
Icu kA 55 66 85 66 80 100 100 150 130
Ics kA 55 66 85 66 80 100 100 150 130
Icm kA 121 145 187 145 176 220 220 330 286
Rated operational voltage Ue up to 690 V AC
Icu kA 42 50 66 50 75 85 85 150 130
Ics kA 42 50 66 50 75 85 85 150 130
Icm kA 88 105 145 105 165 187 187 330 286
Rated operational voltage Ue
up to 1000 V/1150 V AC
Icu kA -- -- 509) -- -- 50 50 704) 704)
Ics kA -- -- 509) -- -- 50 50 704) 704)
Icm kA -- -- 1059) -- -- 105 105 1544) 1544)
Rated short-time withstand current Icw
of the circuit breakers3)
0.5 s kA 55 66 75 66 80 100 100 100 100
1s kA 42 50 66 55 66 80 100 100 100
2s kA 29,5 35 46 39 46 651)/702) 80 80 80
3s kA 24 29 37 32 44 501)/652) 65 65 65
Short-circuit breaking capacity Icc
of the non-automatic air circuit breakers
Up to 500 V AC kA 55 66 75 66 80 100 100 100 100
Up to 690 V AC kA 42 50 66 50 75 85 85 100 100
Up to 1000 V /1150 V AC kA -- -- 509) -- -- 504) 504) 704) 704)

Sizes II
DC

Type 3WL12
Switching capacity class DC
Short-circuit breaking capacity
Up to 220 V DC Icc kA 35
Up to 300 V DC Icc kA 30
Up to 600 V DC Icc kA 25
Up to 1000 V DC Icc kA 20
Rated short-time withstand current Icw
0.5 s kA --
1s kA 355)/306)/257)/208)
2s kA --
3s kA --

Circuit breaker with ECO switching capacity N Abbreviations


N (functions)

S
Circuit breaker with standard switching capacity S L = Long Time Delay = Overload protection
S = Short Time Delay = Short-circuit protection
H
Circuit breaker with high switching capacity H (short-time delayed)
I = Instantaneous = Short-circuit protection
C
Circuit breakers with very high switching capacity C (instantaneous)
N = Neutral Protection Neutral conductor protec-
DC
Non-automatic air circuit breakers with DC switching tion
capacity G = Ground Fault Ground-fault protection
These switching capacities are indicated in the corre-
sponding tables by the symbols shown on orange back-
grounds. L, S, I, N, G: Designation according to IEC 60947-2, Appendix K.
6)
1) Size II with In max ≤ 2500 A. At Ue = 300 V DC.
2) 7) At Ue = 600 V DC.
Size II with In max = 3200 A and In max = 4000 A.
8)
3) At a rated voltage of ≥ 690 V the Icw value of the circuit breaker cannot be At Ue = 1000 V DC.
greater than the Icu or Ics value at 690 V. 9)
Values also apply to version 690 V + 20 % with Z option "A16".
4) Rated operational voltage Ue = 1150 V.
5) At Ue = 220 V DC.

Siemens · 2012 3
© Siemens AG 2011

3WL Air Circuit Breakers

Introduction
3WL air circuit breakers:
Superior individual products integrated into uniform power dis-
tribution systems - up to and including industry-specific indus-
trial and infrastructure solutions

7
2

3 8

5
4

9
1
25

21
10
19

22 11

23
12

24 18 13

17

14
NSE0_01887c

20
16
15

$ Guide frame 4 Operating cycles counter


% Main circuit connection, front, flange, horizontal, vertical 5 Breaker Status Sensor (BSS)
& Position signaling switch 6 Protective devices with device holder, electronic releases (ETU)
( Grounding connection, leading 7 Remote reset solenoid
) Shutter 8 Breaker Data Adapter (BDA Plus)
* COM15 PROFIBUS modules or COM16 MODBUS modules 9 Four-line display
+ External CubicleBUS modules : Ground-fault protection module
, Closing solenoid, auxiliary release ; Rated current module
- Auxiliary conductor plug-in system < Measuring function module
. Auxiliary switch block = Circuit breaker
/ Door sealing frame
0 Interlocking set for mechanical ON/OFF
1 Transparent panel, function insert
2 EMERGENCY-STOP pushbutton, key operated
3 Motorized operating mechanism

4 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers

Introduction
Communication-capable circuit breakers (with ETU45B or ETU76B electronic release)

18

Ethernet

16

17

PROFIBUS

4 4 19 11 12 13 14 15 5

ab Release 2

CubicleBUS
7
8 6
1 1
9
10

NSE0_01105k
2 3

1 3VL molded case circuit breakers 11 Zone Selective Interlocking modules


2 Electronic release LCD ETU 12 Digital output module with relay contacts
3 Electronic release ETU 13 Digital output module with relay contacts, configurable
4 COM20 Release 2 PROFIBUS module 1) Including ZSS 14 Analog output modules
5 BDA Plus with Ethernet interface 15 Digital input module
6 3WL air circuit breakers 16 Switch ES Power On PC / powerconfig as of V2.3
7 COM15 PROFIBUS module 2) 17 PLC, e. g. SIMATIC S7
8 Breaker status sensor (BSS) 18 e. g. Powermanager or SIMATIC powerrate
9 Electronic release ETU 19 7KM PAC measuring devices
10 Measurement function Plus
1) For a MODBUS-RTU connection the COM21 module is required.
2) For a MODBUS-RTU connection the COM16 module is required.

Features
• Coordinated communication concept using the Communication:
PROFIBUS DP or MODBUS, ranging from 16 A to 6300 A with • For air circuit breakers with optional communication function
3VL compact circuit breakers and 3WL air circuit breakers (ETU45B or ETU76B electronic release)
• The high level of modularity of circuit breakers and accesso- see Catalog LV 10.1.
ries allows easy retrofitting of all communication components • For accessories see Catalog LV 10.1.
• Significant additional benefits for the switchboard due to the • For more information see also Catalog LV 10.1, chapter "Mea-
possibility of linking up external input and output modules to suring Devices and energy management" and "Software".
the circuit breaker-internal CubicleBUS of the 3WL air circuit
breaker
• Innovative software products for parameterization, operation,
monitoring, and diagnostics of circuit breakers, both locally or
via PROFIBUS DP, MODBUS or Ethernet/Intranet/Internet
• Complete integration of the circuit breakers into the Totally
Integrated Power and Totally Integrated Automation solutions

Siemens · 2012 5
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data

■ Design
Circuit breaker Breaking capacity Dimensions
rated current n max (A) With-
cu at 500 V AC (kA) or Fixed-mounted, drawable
cc at 300 V DC (kA) 3- /4-pole 3- /4-pole

704 / 914 704 / 914 Width


6300
Size III

5000 434 / 434 460 / 460 Height


H C
100 150 (3p)
4000 130 (4p) 291 / 291 385 / 385 Depth

4000

3200 460 / 590 460 / 590 Width

2500

2000
Size II

434 / 434 460 / 460 Height


1600 DC N S H

1250 30 66 80 100

1000 291 / 291 385 / 385 Depth

800

2000 320 / 410 320 / 410 Width


1600

1250
Size I

H 434 / 434 460 / 460 Height


N S
1000

800
55 66 85

630
291 / 291 385 / 385 Depth

The dimension for the depth of the circuit breaker is from the circuit breaker rear to the inner surface of the closed switchgear door. NSE0_00887p

Overview of 3WL circuit breakers/non-automatic air circuit breakers Coordinated dimensions


Versions The dimensions of 3WL circuit breakers only differ in terms of the
width of the device which depends on the number of poles and
• Rated currents: 630 A to 6300 A the size.
• 3 sizes for different rated current ranges (see above illustra- Due to the nature of the design, the dimensions of devices with
tion) a withdrawable version are determined by the dimensions of the
• 3 and 4-pole versions guide frames, which are slightly larger.
• Rated operational voltage up to 690 V AC and 1000 V DC. Non-automatic air circuit breakers
Special versions up to 1000 V AC and 1150 V AC available
• 4 different switching capacity classes in the range from 55 kA One special version of circuit breaker is utilized as a non-auto-
to 150 kA for AC applications and one switching capacity matic air circuit breaker. The non-automatic air circuit breakers
class for DC applications. are designed without an electronic release system and do not
perform any protection function for the system.
The 3WL circuit breakers are supplied complete with operating
mechanism (manual operating mechanism with mechanical One potential application is the use as a bus coupler in systems
closing), electronic release and auxiliary switches (2 NO con- with parallel feed-ins.
tacts + 2 NC contacts in the standard version), and can be The versions and features can be selected according to those of
equipped with auxiliary releases. the circuit breakers.
Installation types Operating mechanisms
Fixed-mounted or withdrawable version The circuit breakers are available with various optional
operating mechanisms:
Ambient temperatures
• Manual operating mechanism with mechanical closing (stan-
The 3WL circuit breakers are climate-proof according to dard design)
IEC 60068-2-30. They are intended for use in enclosed areas
where no severe operating conditions (e. g. dust, corrosive va- • Manual operating mechanism with mechanical and electrical
pors, damaging gases) are present. closing
• Motorized operating mechanism with mechanical and electri-
When installed in dusty and damp areas, suitable enclosures cal closing
must be provided.
The operating mechanisms with electrical closing can be used
for synchronization tasks.

6 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Safety and reliability
Fixed-mounted circuit breakers
The system contains many blocking devices to protect the cir-
cuit breakers and plant against unauthorized switching and to
protect maintenance and operator personnel from danger.
Others can be retrofitted.
N S E 0 _ 0 0 9 6 8 b

N S E 0 _ 0 0 9 6 9 b

N S E 0 _ 0 0 9 7 9 a
N S E 0 _ 0 0 9 6 7 b

Other safety features include:


• Infeed from above or below, as required
Horizontal Front connection with single Vertical
• Locking of the guide frame with the circuit breaker removed,
connection hole or double hole connection as standard
• Locking of the withdrawable circuit breaker against move-
Withdrawable circuit breaker, withdrawable guide frame ment, as standard
• High degree of protection with cover IP55
• Mechanical reclosing lockout after overload or short-circuit
release as standard
N S E 0 _ 0 0 9 7 1 b

• The circuit breaker is always equipped with the required


N S E 0 _ 0 0 9 7 0 b

N S E 0 _ 0 0 9 7 3 b
N S E 0 _ 0 0 9 7 2 b

number of auxiliary supply connectors


N S E 0 _ 0 0 9 6 7 b

Standard versions

Horizontal Front connection with single Vertical Flange 3WL circuit breakers are equipped with the following features as
connection hole or double hole connection connection standard:
• Mechanical ON pushbutton and mechanical OFF pushbutton
Main circuit connections – connection types
• Manual operating mechanism with mechanical closing
Main circuit connections
• Switch position indication
All circuit breakers are equipped with horizontal main circuit • Ready-to-close indicator
connections on the rear for up to 5000 A as standard (horizontal
connection to busbars). Exception: Circuit breakers of size II • Memory status indicator
with max. rated current 4000 A. • Auxiliary switch 2 NO + 2 NC
Circuit breaker with a maximum rated current of 6300 A and • Rear horizontal main connectors for fixed mounting and for
circuit breaker of the size II with a maximum rated current of withdrawable version up to 5000 A, and rear vertical main con-
4000 A are equipped with vertical main connections (for upright nections at 6300 A and size II with 4000 A
busbars).
• For 4-pole circuit breakers, the fourth pole (N) is installed on
The following options are available, with all combinations of the left and is 100 % loadable with the rated current
top and bottom connections possible: • Contact erosion indicator for the main contacts
• Accessible from the front, single hole (for vertically installed
busbars) • Auxiliary circuit plug-in system with SIGUT screw terminals
• Accessible from the front, double hole (holes according to Delivery inclusive of all auxiliary circuit connectors to internal
DIN 43673) (for vertically installed busbars) features including coding device for the prevention of incor-
• At the rear, vertical (for vertically installed busbars) rect installation of auxiliary supply connectors for fixed-
• Connecting flange (for direct connection to guide frame up to mounted circuit breakers
4000 A). • Mechanical "tripped" indicator for electronic release system
• Mechanical reclosing lockout after tripping operation
Connection using Screwless
N S E 0 _ 0 0 9 7 6 b

• Operator panel cannot be taken off with the circuit breaker in


N S E 0 _ 0 0 9 7 5 b

screw connection connection method


system (SIGUT) (tension springs) the ON position
(standard) (optional) Additional features of the withdrawable version:
• Main contacts:
Connection options for auxiliary circuit connections Laminated receptacles in the guide frame,
Auxiliary circuit connections penetration blades on the withdrawable circuit breaker
• Position indicator in the operator panel of the withdrawable cir-
The type of connection for the auxiliary switches depends on the cuit breaker
installation type:
• Captive manual crank handle for moving the withdrawable cir-
• Withdrawable version: The internal auxiliary switches are con- cuit breaker
nected to the male connector on the switch side. When fully in-
serted, the connector makes a connection with the sliding • Guide frame with guide rails for easy moving of the withdraw-
contact module (see the graphic "Guide Frame" in "Design") in able circuit breaker
the guide frame. Various adapters can then be used to com- • The withdrawable circuit breaker can be locked to prevent it
plete the wiring (see the graphic "Connection Options for Aux- being pushed out of position
iliary Circuit Connections"). • The withdrawable circuit breaker cannot be moved when it is
• Fixed mounting: In this case the auxiliary supply connectors in the ON position
are engaged directly onto the circuit breaker. The connectors • Coding of the rated current between the guide frame and the
are equipped with withdrawable circuit breaker
coding pins that prevent them being mistakenly interchanged.
Standards
Operator panel
3WL circuit breakers comply with:
The operator panel is designed to protrude from a cutout in the • IEC 60947-2
door providing access to all control elements and displays with • Climate-proof according to IEC 60068-2-30.
the control cabinet door closed.
The operator panels for all circuit breakers (fixed-mounted/with- Versions according to UL 489 also available, see Catalog LV 16.
drawable versions, 3-/4-pole) are identical. The operator panel Additional standards: www.siemens.com/lowvoltage/support or
ensures degree of protection IP41. www.siemens.com/lowvoltage/configurators.

Siemens · 2012 7
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Withdrawable short-circuit, grounding, and bridging units An energy storage device for shunt releases allows the circuit
breaker to be opened even if the control voltage is no longer
Portable positively-driven grounding and short-circuit devices available.
are used for the disconnected system sections to verify isolation
from the supply at the workplace. Undervoltage release
Withdrawable grounding units allow simple and comfortable The undervoltage release causes the circuit breaker to be
grounding. They are simply inserted into the guide frames in opened if the operational voltage falls below a certain value or is
place of the corresponding withdrawable circuit breakers. This not applied. The circuit breaker cannot be closed manually or by
ensures that these devices are always first connected with the means of an electrical ON command if the undervoltage release
grounding electrode and then with the components to be is not connected to the operational voltage. The undervoltage re-
grounded. lease has no delay as standard. A delay can be set by the cus-
The grounding contacts are fitted to the side of the switch enclo- tomer in the range between td < 80 ms and td < 200 ms.
sure and establish the connection when inserted into the guide In addition, an undervoltage release with a delay in the range
frame. from 0.2 to 3.2 s is available.
Closing solenoid
Short-time current of the ground- kA 15 (500 ms)
ing contact The closing solenoid is used to close the circuit breaker electri-
Rated operational voltage V 1000 (690 for size I)
cally by means of a local electrical "ON" command or by a re-
mote unit.
Standards DIN VDE 0683
Motorized operating mechanism
All withdrawable terminals are short-circuited and grounded on The operating mechanism is used to load the storage spring au-
delivery. tomatically.
They are easily converted into withdrawable bridging units by The operating mechanism is activated if the storage spring has
qualified electricians according to the enclosed instructions. been unloaded and the control voltage is available.
In addition, the withdrawable unit can be adapted to various It is switched off automatically after loading. This does not affect
rated currents of a size. manual operation of the storage spring.
Withdrawable short-circuit and grounding unit Indicators, signals, and control elements
The withdrawable short-circuit and grounding unit consists of a Motor shutdown switch
breaker enclosure with penetration blades which are connected
with the short-circuiting link. Control switch for switching off the motorized operating mecha-
nism (automatic loading).
Depending on the version, the short-circuiting links are arranged
at the top and/or bottom. The grounding and short-circuit con- Operating cycles counter
nections are established when the device is inserted. The motorized operating mechanism can be supplied with a
It must be ensured that the side to be short-circuited and 5-digit operating cycles counter. The display is incremented by
grounded is not live. For this reason it is recommended that the "1" as soon as the storage spring is fully loaded.
withdrawable unit is only wound in when the door is closed. Resetting the manual tripped signal
Withdrawable bridging unit When the circuit breaker has tripped, this is indicated by the pro-
The withdrawable bridging unit consists of a breaker enclosure truding red mechanical tripped indicator on the ETU. When the
in which all disconnection components and the operating mech- mechanical tripped indicator is activated, the tripping solenoid
anism have been replaced with simple connections between the and tripped signal are reset. If this display is to be reset remotely,
upper and lower contacts. the reset button can be equipped with a reset solenoid.
This option allows the circuit breaker to be reset both manually
Auxiliary releases and electrically.
Up to two auxiliary releases can be installed at the same time. Automatic resetting of reclosing lockout
The following are available:
When the ETU is activated, reclosing of the circuit breaker is pre-
1 shunt release vented until the release is either electrically or manually reset. If
or 1 undervoltage release the "Automatic resetting of reclosing lockout" option is used, the
or 2 shunt releases pre-tensioned circuit breaker is ready to close immediately after
or 1 shunt release tripping. Resetting the manual tripped indicator is not included
+ 1 undervoltage release. in this option.
Signaling switch for auxiliary releases Tripped signaling switch
One signaling contact is used for each auxiliary release to deter- If the circuit breaker has tripped due to an overload, short-cir-
mine the switch positions of the auxiliary releases. cuit, ground fault or extended protection function, the tripped
Shunt release signaling switch can indicate this. This signaling switch is avail-
able as an option. If the circuit breaker is used for communica-
When the operational voltage is connected to the shunt release, tion, this option is supplied as standard.
the circuit breaker is opened immediately. The shunt release is
available in the versions 5 % OP for over-excitation Ready-to-close signaling switches
and 100 % OP for permanent excitation. This means that it is also The 3WL circuit breakers are equipped with an optical ready-to-
possible to block the circuit breaker against being jogged into close indicator as standard. In addition, the ready-to-close sta-
closing. tus can be transmitted by means of a signaling switch as an op-
tion. If the switch is used for communication, the signaling switch
is supplied as standard.

8 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Circuit breakers

(2 8 ) (1 ) (1) Arc chute


(2) Carrying handle
(2 ) (3) Labeling plates
(2 7 ) (4) Motor shutdown switch (option) or
"Electrical ON" (option)
(5) Name plate for circuit breaker
(2 6 ) (3 )
(6) Memory status indicator
(4 ) (7) "Mechanical ON" button
(2 5 ) (8) Rated current indication
(5 )
(9) Positioning pictogram
(2 4 ) (10) Operating cycles counter (option)
(6 )
(11) Hand-operated lever
(2 3 )
(12) Crank handle
(2 2 ) (7 ) (13) Withdrawable unit drive shaft
(14) Equipment plate
(2 1 )
(15) Ground terminal
(8 ) (16) Position indicator
(17) Table for ground-fault protection
(2 0 ) (9 )
(18) Safety lock for crank handle (option)
(19) Mechanical unlocking of
(1 9 ) (1 0 ) crank handle (option)
(1 1 ) (20) Electronic releases
(1 8 ) (21) Rated current modules
(22) "Mechanical OFF" button or
(1 7 ) "EMERGENCY-STOP" mushroom push-
(1 2 )
button (option)
(1 3 ) (23) Ready-to-close indicator
(1 6 )
(1 4 ) (24) Switch position indicator
(1 5 ) (25) "Tripped" indicator (reset button)
N S E 0 _ 0 0 9 6 5 b
(26) "Secure OFF" locking device (option)
(27) Operator panel
(28) Male connector for auxiliary circuit
connections

Guide frames

(1) Arc chute cover (option)


(2) Blow-out openings
(1 ) (3) Opening for crane hook
(4) Shutter (option)
(2 )
(5) Locking device (shutter) (option)
(6) Type plate for guide frame
(1 8 ) (3 ) (7) Isolating contacts
(8) Ground terminal Ø 14 mm
(9) Locking device for racking rail
(10) Locking device against movement when
control cabinet door is open (option)
(1 7 ) (4 ) (11) Door interlocking for guide frame
(option)
(5 ) (12) Racking rail
(13) Factory-set rated current coding
(6 )
(14) Sliding contact for breaker grounding
(1 6 ) (option)
(7 ) (15) Equipment-dependent coding (option)
(1 5 ) (16) Shutter actuator (optional)
(17) Position signaling switch (optional)
(1 4 )
(18) Sliding contact module for auxiliary
(8 ) conductors (number depends on
(1 3 ) equipment)

(1 2 )

(9 )
(1 1 )
(1 0 ) N S E 0 _ 0 0 9 6 6 b

Siemens · 2012 9
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Locking devices Sealing devices
Locking device in OFF position Sealing cap for "Electrical ON" button
This function prevents closing of the circuit breaker and com- The "Electrical ON button" is equipped with a sealing cap as
plies to the specifications for main switches according to standard.
EN 60204 (VDE 0113) - disconnector unit. This lockout only af-
fects this circuit breaker. Sealing cap for "Mechanical ON button" and "OFF"

If the circuit breaker is replaced, closing is no longer prevented The interlocking set contains covering caps which can be
unless the new circuit breaker is also protected against unau- sealed.
thorized closing. Sealing device for electronic releases
To activate the locking device, the circuit breaker must be The transparent cover can be sealed. The parameter setting
opened. The locking device is disabled when the circuit breaker ranges are covered to prevent unauthorized access. Openings
is closed. The lock is only activated when the key is removed. allow access to the query and test button.
The safety key can be removed only in the "OFF" position.
Locking mechanisms
Locking device for "Electrical ON"
(see graphic "Circuit breakers") Locking device against movement for withdrawable circuit
breakers when the control cabinet door is open
This prevents unauthorized electrical closing from the operator
panel. Mechanical closing and remote closing remain possible. The crank handle is blocked when the control cabinet door is
The lock is only activated when the key is removed. open and cannot be removed. The withdrawable circuit breaker
cannot be moved. The lock only affects the inserted crank han-
Locking device for "Mechanical ON" dle.
(see graphic "Circuit breakers")
Interlocking of the control cabinet door
This prevents unauthorized mechanical closing. The mechanical
ON button can only be activated if the key is inserted (key oper- The control cabinet door cannot be opened if
ation). Closing with the "Electrical ON" button and remote closing • The fixed-mounted circuit breaker is closed (the blocking sig-
remain possible. The lock is only activated when the key is re- nal is transmitted via the Bowden wire) or
moved. • The withdrawable circuit breaker is in the connected position.
"Secure OFF" circuit breaker-independent locking device Blocking mechanism using "Mechanical ON" and "OFF" buttons
against unauthorized closing
The "Mechanical ON" and "OFF" buttons are covered with a cap
This special switch-independent function for withdrawable cir- which only allows actuation with a tool. These covering caps are
cuit breakers prevents closing and fulfills the specifications for part of the interlocking set.
main switches to EN 60204 (VDE 0113) – disconnector unit. Un-
authorized closing remains impossible even after the circuit Accessories for guide frames
breaker has been exchanged.
Shutters
To activate the lock, the circuit breaker must be opened. The
locking device is disabled when the circuit breaker is closed. The sealing strips of the shutter seal the laminated contacts of
The lock is only activated when the key is removed. The safety the guide frame when the withdrawable circuit breaker is re-
key can be removed only in the "OFF" position. moved and therefore implement touch protection.

Locking device for crank handle The sealing strips can be manually opened using the strip le-
vers.
Prevents removal of the crank. The circuit breaker is protected
against movement. The lock is only activated when the key is re- The position of the sealing strips can be locked in various posi-
moved. tions using padlocks for securing against tampering.

Locking device for "Mechanical OFF"


Prevents unauthorized mechanical opening from the operator
panel. The "Mechanical OFF pushbutton" can only be activated
if the key is inserted (key operation). Remote opening remains
possible. The lock is only activated when the key is removed.
Locking device for hand-operated lever
The hand-operated lever can be locked with a padlock. The stor-
age spring cannot be loaded manually.
Locking device against resetting the "tripped" indicator
A lockable cover prevents manual resetting of the "tripped" indi-
cator after overcurrent tripping. This locking device is supplied
together with the transparent cover for electronic releases.

10 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Rated current coding unit between circuit breaker and guide Equipment-dependent coding
frame
Withdrawable circuit breakers and guide frames can be retrofit-
Withdrawable circuit breakers and guide frames are equipped ted with an equipment-dependent coding unit.
with a rated current coding unit as standard.
This allows different designs of circuit breakers and guide
This ensures that only circuit breakers whose penetration blades frames to be uniquely assigned. If the circuit breaker and guide
are suited to the laminated contacts of the guide frame can be frame have been assigned different codes, the circuit breaker
inserted into a guide frame (see diagram below). cannot be inserted.
36 different coding options can be selected.
Position signaling switches for guide frames
N S E 0 _ 0 1 0 3 1 a

The guide frame can be equipped with position signaling

N S E 0 _ 0 1 0 3 2 a
switches. These can be used to determine the position of the cir-
cuit breaker in the guide frame.
(1 )
Two versions are available:
(4 ) • Option 1
Connected position 1 CO contact,
(2 )
Test position 1 CO contact,
Disconnected position 1 CO contact;
(3 ) (5 )
• Option 2
(1) Guide frame, interior of l/h side; interior of r/h side similar Connected position 3 CO contacts,
(2) Coding pin on racking rail in guide frame Test position 2 CO contacts,
(3) Racking rail
Disconnected position 1 CO contact.
(4) Withdrawable circuit breaker, r/h side; l/h side similar
(5) Coding pin on guide frame

Rated current coding unit between circuit breaker and guide frame

Positions of the withdrawable circuit breaker in the guide frame


presenting Position indicator Main circuit Auxiliary circuit Control cabinet Shutters
door
Maintenance position (2 ) CONNECT
Disconnected Disconnected Open Closed
(1 )
TEST

(4 )
DISCON
N S E 0 _ 0 1 0 3 3 a
NSE01037

Disconnected position CONNECT


Disconnected Disconnected Closed Closed
(3 )
TEST

DISCON
N S E 0 _ 0 1 0 3 4 a
NSE01038

Test position CONNECT


Disconnected Connected Closed Closed

TEST

DISCON

N S E 0 _ 0 1 0 3 5 a
NSE01039

Connected position CONNECT


Connected Connected Closed Open

TEST

DISCON

N S E 0 0 1 0 3 6 a NSE01040

(1) Auxiliary circuit (2) Main circuit (3) Control cabinet door (4) Shutter

Phase barriers Door sealing frame and cover


The plant engineering company can manufacture phase barriers 3WL circuit breakers have degree of protection IP20 as stan-
made of insulating material for the arcing fault barriers. The rear dard. However, if the switchgear is to be equipped with a higher
panel of the fixed-mounted circuit breakers or guide frames are degree of protection, a door sealing frame with IP41 and a cover
equipped with guide grooves. with IP55 are available.
Arc chute covers
The arc chute cover is available as accessory for the guide
frame. It protects switchgear components which are located di-
rectly above the circuit breaker.

Siemens · 2012 11
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data

■ Function

NSE0_00882b
NSE0_00881b
NSE0_00880b
R
R R

s d
s d
t
i t s d
s d
g
t g

N S E 0 _ 0 0 9 5 0 c N S E 0 _ 0 0 9 5 1 b N S E 0 _ 0 0 9 5 2 b

ETU15B ETU25B ETU27B


Functions of the electronic releases
Basic protection functions
Overload protection L ✔ ✔ ✔
Short-time delayed short-circuit protection S -- ✔ ✔
Instantaneous short-circuit protection I ✔ ✔ ✔
Neutral conductor protection N -- -- ✔
Ground-fault protection G -- -- ✔

Additional functions
N-conductor protection can be switched on/off -- -- ✔
N-conductor protection adjustable -- -- --
Short-time delayed short-circuit protection can be switched on/off -- -- --
Instantaneous short-circuit protection can be switched on/off -- -- --
Thermal image can be switched on/off -- -- --
Load monitoring -- -- --
Short-time delayed short-circuit protection switchable to I2t -- -- --
Instantaneous short-circuit protection adjustable ✔ -- --
Overload protection switchable to I4t -- -- --
Overload protection can be switched on/off -- -- --
Selectable parameter sets -- -- --

Parameterization and display


Parameterization through rotary coding switches (10 steps) ✔ ✔ ✔
Parameterization through communication (absolute values) -- -- --
Parameterization through user interface of ETU (absolute values) -- -- --
Parameterization of the extended protection functions -- -- --
LCD alphanumerical -- -- --
Graphic LCD -- -- --

Measurement function
Measurement function Plus -- -- --

Communication
CubicleBUS -- -- --
Communication through PROFIBUS DP -- -- --
Communication through MODBUS -- -- --
Communication through Ethernet -- -- --
✔ Standard -- Not available ❑ Optional
Detailed information about the functions of the electronic releases is given in the following.

12 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data

ETU76B

Rating Plug
=
12

NSE0_00886c
NSE0_00883b

IR IR
tR tR

Isd Isd
t sd t sd
Ig Ig
Ii Ii
tg tg

NSE0 00953a NSE0 00953a

ETU45B ETU76B

✔ ✔
✔ ✔
✔ ✔
✔ ✔
❑ ❑

✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
-- ✔
-- ✔

✔ --
-- ✔
-- ✔
❑ ❑
❑ --
-- ✔

❑ ❑

✔ ✔
❑ ❑
❑ ❑
❑ ❑

Siemens · 2012 13
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Electronic releases (ETU) Tripped indicator/
The electronic release is controlled by a microprocessor and op- Reset button
erates independently of an auxiliary voltage. It enables systems
to be adapted to the different protection requirements of distri-
bution systems, motors, transformers and generators.
Communication capability
LCD alpha-
The international standard PROFIBUS DP or MODBUS can be numeric
used to transmit data such as current values, switching states, with 15°
reasons for tripping etc. to central computers. inclination
and rotatable
Data acquisition and energy management are possible in con- through 180°
junction with the Plus measurement function.
Slide switch
A new internal circuit breaker data bus allows switchboard panel Rated current for switchable
communication between the circuit breaker and secondary de- module/ overload
vices in the circuit breaker section: rating plug characteristic
curve
• Actuation of analog displays
• Facility to test the communication build-up with circuit break-
ers
• Display of tripping state and tripping reasons
• Input module for reading in further switchgear panel signals Ground-fault
protection
and for transmission of these signals to the PROFIBUS DP or module (retro-
MODBUS fittable)
• Various output modules for displaying measured values.
This means that it is not only possible to monitor the device re-
motely, but also to transmit current values from the entire system
and perform switching operations remotely.
I2t and I4t characteristic curve for overload protection
Example of configuration for ETU45B
The best protection for the whole switchgear is achieved by set-
ting the tripping characteristic curve to an optimum value. In or-
der to achieve optimal discrimination for upstream fuses or me-
dium voltage protection systems, the inclination of the
characteristic curve can be selected for the overload range.
The overload protection L (long time protection) for the elec-
tronic releases ETU45B and ETU76B allows the characteristic
curve to be switched between I2t and I4t.
The I4t characteristic improves discrimination for downstream
circuit breakers and fuses.
Electronic releases ETU
Modularity has also been strictly emphasized during the devel-
opment of the electronic releases. These are some of the mod-
ules which can be easily retrofitted at any time:
• Ground-fault protection module
• Communication
• Measurement function
• Display
• Rated current module (Rating Plug)
This allows quick adaptation to new local mains specifications.
In addition, innovative functions have been included in the ETUs.
Rated current module/Rating Plug
The rated current module is an exchangeable module which al- Measurement function Plus
lows the user to reduce the rated device current so as to adapt
it optimally to the plant; e.g.if a new plant section is taken into op-
eration. The rated current module must be selected to fit the Selectable parameters
rated current of the plant.
In the case of quick changes of power supply conditions,
e. g. for switchovers from transformer to generator operation or
if a section of the supply is disconnected when the shift
changes, the 3WL circuit breaker allows the relevant protection
parameters to be quickly adapted to the new conditions.
The ETU76B contains two independent tripping characteristic
curves (parameter sets). The switchover is completed within
200 ms and is performed with the help of an external signal.

14 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
ETU15B electronic release
Application:
Option: safety lock
prevents pressing of Simple building and system
Mechanical RESET reset button after protection without time-selective
for reclosing lockout overcurrent release
coordination up to 4000 A. Not to
and mechanical
tripped indicator be used for size III.
Features:
• Adjustable overload protection
with I2t characteristic curve
Indicator: overcurrent
release activated with preset delay time
Indicator: overload alarm Indicator: fault in
tR = 10 seconds at 6 × IR
overcurrent release • Instantaneous short-circuit pro-
Rotary switch for setting
tection adjustable in the range
value, overload release 2 ... 8 × In
• Overload display
Rotary switch for setting
• Protection function is set by
value, instantaneous means of the rotary coding
Sealing ring
short-circuit release switch
For technical details see the table
"Functional Overview of the
Electronic Release System"
NSE0_00954b

under "Technical Specifications".


Test socket

ETU25B electronic release


Application:
Option: safety lock
prevents pressing of Classical building, motor and sys-
Mechanical RESET reset button after
overcurrent release tem protection with time-selective
for reclosing lockout
and mechanical coordination for up to 6300 A
tripped indicator
Features:
• Adjustable overload protection
with I2t- characteristic curve
Indicator: overcurrent ETU25B
Delay time
release activated tR = 10 seconds at 6 × IR
Indicator: overload alarm
Rating Plug Indicator: fault in • Short-time delayed short-circuit
overcurrent release
Rated current module protection adjustable in the
Rotary switch for setting
range 1.25 ... 12 × In and
Indicator: cause of release
value, overload release • Instantaneous short-circuit pro-
Rotary switch for setting Rotary switch for delay, tection preset
value, instantaneous short-circuit release to 20 × In, max. 50 kA
short-circuit release
Short-circuit protection • Can be adapted at any time to
Sealing ring
fixed setting the required plant currents
NSE0_00955b

through retrofittable rated cur-


rent module,
Query pushbutton thus ensuring overload protec-
Test pushbutton Clear pushbutton tion in the range from 100 A to
Test socket 6300 A.
• Overload display
• Indicates the reason for tripping
by means of an LED
• Test facility for the release
• Protection functions are
set by means of the
rotary coding switch
For technical details see the table
"Functional Overview
of the Electronic Release System"
under "Technical Specifications".

Siemens · 2012 15
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
ETU27B electronic release
Application:
Option: safety lock
prevents pressing of Classical building, motor and sys-
reset button after
Mechanical RESET
overcurrent release tem protection with time-selective
for reclosing lockout
and mechanical coordination for up to 6300 A
tripped indicator

NSE0_00956c
Features:
The same as ETU25B but also
Indicator: overcurrent • Reversible neutral conductor
ETU27B N-conductor protection
release activated
on/off
protection
Indicator: overload alarm OFF ON

Rating Plug Indicator: fault in • Permanently integrated ground-


Rated current module overcurrent release fault protection. Calculation of
the ground-fault current through
Rotary switch for setting N

value, overload release


Indicator: cause of release vectorial summation current for-
mation
Rotary switch for setting Rotary switch for delay,
value, instantaneous short-circuit release For technical details see the table
short-circuit release
"Functional Overview
Short-circuit protection Sealing ring of the Electronic Release System"
fixed setting
Rotary switch for setting
OFF
Rotary switch for delay, under "Technical Specifications".
earth-fault protection
value, earth-fault protection

Query pushbutton
Test pushbutton Clear pushbutton
Test socket

ETU45B electronic release

Mechanical RESET Option: safety lock


Application:
for reclosing lockout prevents pressing of
and mechanical reset button after Low-cost all-round system for
tripped indicator overcurrent release intelligent buildings and all types of industrial
Scroll up applications – "CubicleBUS integrated"
Option: alphanumeric display
Indicators:
Overcurrent release Scroll down Features:
activated Indicator: fault in
Overload alarm overcurrent release The same as ETU25B but also
COMMUNICATION
ETU45B
Thermal memory on/off • Adjustable time-lag class
EXPANDED N-conductor protection on/off
OFF ON
for overload protection
Setting value
Rated current module
Rating Plug
N-conductor overload • Selectable characteristic for overload and
Rotary switch for setting =
Transfer of overload short-delayed short-circuit range (current
value, overload release characteristic 2 t / 4t
1
1
discrimination) for more accurate discrimi-
Rotary switch for setting 1
1 Rotary switch for delay, nation adaptation to upstream fuses and
value, instantaneous 1
overload release
short-circuit release protective devices
Rotary switch for delay,
12

Rotary switch for setting short-circuit release • Thermal image as restart protection for
value, short-circuit
protection
Indicator: cause of release tripped motor outgoing feeders
Sealing ring
Selector for
Option: earth-fault module
• Reversible and adjustable neutral conduc-
earth-fault protection SI tor protection
Indicator: earth-fault alarm
Rotary switch for setting g

value, earth-fault • Modular ground-fault protection module


protection Indicator: earth-fault tripped with alarm and tripping functions which can
Rotary switch for setting Rotary switch for delay, be adjusted separately
value, earth-fault alarm earth-fault protection t g / 2
tg
Test pushbutton Clear pushbutton • Communication interface,
Query pushbutton Test socket measurement function Plus, optional
NSE0_00957b
connection of external modules or for retro-
fitting
• Storage of events and causes for tripping
for detailed fault analysis
• Extended protection function possible with
measurement function
• Optional high-contrast display with viewing
angle adjustment option
• The protection functions can be set by
means of a rotary coding switch or slide
switch
For technical details see the table
"Functional Overview of the Electronic
Release System" under "Technical
Specifications".

16 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
ETU76B electronic release
Application:
Mechanical RESET Option: safety lock
for reclosing lockout prevents pressing of The multi-talent with graphical
and mechanical reset button after display for system analysis –
tripped indicator ETU76B overcurrent release
"CubicleBUS integrated"
Features:
The same as ETU45B but also in-
Indicators:
Overcurrent release
cluding
activated Graphical display • Two protection parameter sets
Overload alarm
which can be stored separately
COMMUNICATION
EXPANDED in the release (switchover is per-
Indicator: fault in
overcurrent release formed by means of external sig-
nal)
Indicator: cause of release Rating Plug
Control keys for setting
• With overload protection which
he release parameters can be deactivated for operation
Rated current module in modern drive technology
Option: earth-fault module Indicators: • Adjustable delay of
Ground-fault alarm
Ground-fault tripped
delayed short-circuit protection
Fields for noting up to 4000 ms
setting values Fields for noting
setting values
• Neutral conductor protection ad-
Test pushbutton justable up to IN = 200 % In
Clear pushbutton
Query pushbutton Test socket
• Setting of protection functions by
means of Breaker Data Adapter
NSE0_00960b (BDA) or via communications in-
terface
• Graphical display of all
parameters and events/
curve trends
• Graphics display with high con-
trast, backlit display, and sleep
mode.
For technical details see the table
"Functional Overview of the
Electronic Release System"
under "Technical Specifications".

Ground-fault protection
Selector for Ground-fault releases "G" sense fault currents that flow to ground
Indicators: Ground-fault
ground-fault
alarm
and that can cause fire in the plant. Multiple circuit breakers con-
detection nected in series can have their delay times adjusted so as to pro-
GFM AT 45B Ground-fault
Rotary switch I vide graduated discrimination.
tripped
for setting g TRIP ALARM t
ALARM (s) I 2t g
value,
G A
g
.5 .1
When setting the parameters for the electronic release it is pos-
ground-fault sible to choose between "alarm" and "trip" in the event that the
B .4 .2
protection
C TRIP .3 .3 set current value is exceeded. The reason for tripping is indi-
D .2 .4
OFF E .1 .5
Rotary switch cated by means of an LED when the query button is activated.
for setting
NSE0_00962a
Rotary switch value, ground- The ETU45B and ETU76B electronic release versions can be ret-
for setting value fault protection delay
ground-fault alarm 2
rofitted with a ground-fault protection module. This ground fault
t g/I t g protection function is integrated in ETU27B electronic releases.
GFM AT 45B ground-fault module

Field for Indicators: Ground-fault


noting alarm
transfer GFM AT 55B-76B
g I Ground-fault
ground-fault tripped
detection ALARM ALARM
I g= A

TRIP TRIP I 2t
I g= A t g= ms
Fields for Fields for
noting setting NSE0_00964a
noting setting
values values

GFM AT 55B-76B ground-fault module

Siemens · 2012 17
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Measurement method Setting
Vectorial summation current formation (measurement method 1) How the module is set depends on the measurement method
used (see above):
The three phase currents and the N conductor current are mea-
sured directly. Measurement method 1: in position .
The electronic release determines the ground-fault current by Measurement method 2: in position .
means of vectorial summation current formation for the three
phase currents and the N conductor current. This setting can be implemented for the electronic release ver-
sion ETU76B with Menu/Comm.
Direct measurement of the ground-fault current (measurement
method 2) Ground-fault protection with I2t characteristic curve

A standard current transformer with the following data is used for With the exception of the ETU27B electronic release, all
measurement of the ground-fault current: versions of the ground-fault modules are supplied with an I2t
1200 A/1 A, Class 1 (the internal load of the 3WL circuit breaker characteristic curve which can be activated.
is 0.11 Ω). The current transformer can be installed directly in the Selection criteria for 3WL circuit breakers
grounded neutral point of a transformer.
Basic criteria for selecting circuit breakers are:
• Max. short-circuit current at place of installation of circuit
L1 breaker I ″k max .
L2 This value determines the short-circuit breaking capacity or
SENTRON WL
L3 short-circuit current carrying capacity of the circuit breaker.
N • It is compared with the value Icu, Ics, Icw of the circuit breaker
T5 PE and essentially determines the size of the circuit breaker.
NSE 00946 See illustration "Overview of 3WL Circuit Breakers/Non-Auto-
matic Air Circuit Breakers".
• Rated current In which is to flow through the branch circuit.
3-pole circuit breakers, current transformers in the N conductor This value must not be greater than the maximum rated circuit
breaker current of the circuit breaker.
L1 The rated current for the 3WL circuit breaker is specified using
L2 the rated current module. See illustration "Overview of 3WL
SENTRON WL
L3 Circuit Breakers/Non-Automatic Air Circuit Breakers" in "De-
N sign".
• Ambient temperature
T6 for the circuit breaker.
PE This is usually the control cabinet internal temperature.
T6: 1200 A/1 A NSE 00947
• Design of the circuit breaker
3-pole circuit breakers, current transformers in the grounded neutral • Minimum short-circuit current
point of the transformer. which flows through the switching device. The release must
still detect this value as a short-circuit and must respond by
L1 tripping.
L2
Protection functions of the circuit breaker.
SENTRON WL L3
These are determined by the selection of the
N
corresponding electronic release, see the table
"Functions of the Electronic Releases" under "Functions".
T6
PE

NSE 00948
T6: 1200 A/1 A

4-pole circuit breakers, current transformers in the grounded neutral


point of the transformer.

18 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
3WL circuit breakers for DC applications
This version of the 3WL non-automatic air circuit breaker is suit-
able for direct current applications. The external protective de-
vice DIGmat S100 provides adjustable overload and short-cir-
cuit protection for 3WL non-automatic air circuit breakers.
This is based on the measuring chain of a shunt resistor and the
DIGmat S100 tripping unit. Shunt resistors are available for
1000 A, 2000 A and 4000 A (special ranges on request).
They are in accordance with DIN 43703 and have a class
accuracy of 0.5.
A measuring-circuit voltage of 60 mV DC is picked off for rated
current In.
The measuring-circuit voltage is a linear image of the primary
current. DIGmat S100

The DIGmat S100 tripping unit monitors the image of the primary
current thus supplied and compares it with the tripping charac- • Short-circuit protection:
teristic curve set on the device. The parameter settings on the Setting range Ii = 1.25 × IR up to max. 4 × In
DIGmat S100 apply also for DC feedbacks. If the set value is exceeded, tripping occurs in less than
Reversing duty is possible therefore. 50 ms.
The tripping characteristic curve is determined and described In = Rated current of the circuit breaker
by the following IR = Set current value of the adjustable overload release
variables: tR = Assigned tripping time of the overload trip
• Overload protection: Ii = Instantaneous tripping current of the adjustable short-cir-
Setting range IR = 0.4 ... 1.0 In cuit releases
The characteristic curve has an I2t characteristic.
The components are available only from the company
The tripping time tR can be selected between 2 and 10 s,
mat – Maschinen- und Anlagentechnik:
although tR for 6 × IR is defined.
mat – Maschinen- und Anlagentechnik
Dr. Becker GmbH
Rudolf-Diesel-Straße 22
D-22941 Bargteheide
Tel.: +49 (4532) 20 21-01
Fax: +49 (4532) 20 21-21
E-mail: info@m-a-t.de
Internet: www.m-a-t.de

■ Configuration
Mutual mechanical circuit breaker interlocking • The bending radii of the Bowden wire must be > 500 mm.
The module for mutual mechanical interlocking can be used for • The sum of all bending angles along the Bowden cable must
one or two 3WL circuit breakers and can be adapted easily to not exceed 640°.
the corresponding versions. The fixed-mounted and withdraw- • In a vertical arrangement of circuit breakers to be interlocked,
able circuit breaker versions are fully compatible and can there- the interlocking mechanisms must be in line.
fore be used in a mixed configuration in an installation. This also • Circuit breakers to be interlocked must be arranged so that
applies to 3WN6 circuit breakers. Bowden cables can be optimally installed in compliance with
The circuit breakers can be mounted alongside each other or the conditions mentioned in the above points.
one above the other, whereby the distance of the circuit breakers • The installed Bowden cable must be fixed (with cable ties or
is determined solely by the length of the Bowden wire (lengths: the like) before the interlock is adjusted.
2 m/3 m/4.5 m). Interlock signals are looped through using the
Bowden cables. Interlocking is only effective in the connected • Select the width of switchgear cubicle to allow enough free-
position in the case of withdrawable circuit breakers. The me- dom of movement for adjusting the interlock!
chanical endurance of the Bowden cables is 10000 operating • Openings and cut-outs in system elements must be designed
cycles. so that Bowden cables are not changed in direction or ob-
structed when they are passed through.
Minimum requirements must be fulfilled in the switchgear for the
interlocking to function:
• Bowden cables must be installed as far as possible in a
straight line with minimum bending.
Mutual mechanical interlocking of circuit breakers – examples
Mutual interlocking of two Interlocking between three Mutual interlocking of three Interlocking of three circuit
circuit breakers circuit breakers circuit breakers breakers, two of them mutual

G G G
S1 S2 S1 S3 S1 S3
S1 S2 S3

S2 S1 S2 S3 S2

NSE01041 NSE01042 NSE01043 NSE01044 NSE01045

Siemens · 2012 19
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Communication-capable circuit breakers

PLC e.g. SIMATIC S7 PC with Switch ES Power


data acquisition and SENTRON 3WL/3VL parameterization
processing and visualization tool through
PROFIBUS DP

Output device
Ethernet/ e.g. notebook
Intranet/ with browser

Zone Selective
Interlocking module
Digital output module
Relay
Digital output module
Relay, configurable

Analog output module

Digital input module


Internet
COM15
BSS
ETU
Measurement-
BDA Plus function Plus

NSE0_01820b
Communication with PROFIBUS DP

MODBUS Master Configuration and


PLC or monitoring software display software

MODBUS

Output device
Ethernet/ e.g. notebook
Intranet/ with browser
Zone Selective
Interlocking module
Digital output module
Relay
Digital output module
Relay, configurable

Analog output module

Digital input module


Internet
COM16
BSS
ETU
Measurement
function Plus
NSE0_01894a

BDAPlus

Communication with MODBUS


The requirements for power distribution in terms of communica- The high level of modularity of the system allows communication
tion capability, data transparency, flexibility and integration are functions to be retrofitted at any time (e. g. the measurement
constantly increasing. An integrated and modular communica- function). Similarly, the upgrade of a non-communication-capa-
tion architecture was designed for the 3WL circuit breaker to en- ble 3WL circuit breaker (e. g. changeover from ETU25B to
sure that it can satisfy these requirements. ETU45B with CubicleBUS) can be carried out easily on site in
the plant. All modules connected to the CubicleBUS can directly
The core component of this architecture is the CubicleBUS, access the existing source data of the circuit breaker, which
which links together all of the intelligent components within the guarantees the quickest possible access to information and
3WL circuit breaker and enables the easy and safe connection response to events.
of other additional external components to the circuit breaker.
The CubicleBUS is already incorporated and pre-connected in Furthermore, additional external modules (including digital
all complete circuit breakers with ETU45B and ETU76B releases. inputs/outputs, analog outputs) can be connected to the
CubicleBUS to provide cost-effective solutions for the automa-
tion of further devices in the switchgear.

20 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Communication-capable 3WL circuit breakers
Function Electronic Breaker PROFI- Mea- Analog Digital Digital ZSI Breaker
release version Status BUS sure- output output input module Data
ETU45B ETU76B Sensor com- ment modules module module Adapter
munica- func- Plus
tion tion
port Plus
Functions of the communication-capable 3WL circuit breakers
Indication of measured values in release (current only) ✓ ✓ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏
Indication of measured values in release
✓ ✓ ❏ ❏ ✓ ❏ ❏ ❏ ❏ ❏
(U, I, P, S, Q, p.f., etc.)
Indication of measured values (current only), parameter,
-- ✓ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏
diagnostic values etc. on display
Indication of measured values (U, I, P, S, Q, p.f., etc.),
-- ✓ ❏ ❏ ✓ ❏ ❏ ❏ ❏ ❏
parameters, diagnostic values etc. in release
Output of measured values (current only)
✓ ✓ ❏ ❏ ❏ ✓ ❏ ❏ ❏ ❏
to rotary coil instruments in control cabinet door
Output of measured values (U, I, P, S, Q, p.f., etc.) to
✓ ✓ ❏ ❏ ✓ ✓ ❏ ❏ ❏ ❏
rotary coil instruments in control cabinet door
Output of digital signals
(e. g. reason for tripping, alarm signals, status) ✓ ✓ ❏ ❏ ❏ ❏ ✓ ❏ ❏ ❏
through contacts
Automatic changeover between
-- ✓ ❏ ❏ ❏ ❏ ❏ ✓ ❏ ❏
parameter sets A and B
Read in digital signals and forward to
✓ ✓ ❏ ✓ ❏ ❏ ❏ ✓ ❏ ❏
PROFIBUS/MODBUS
Transmission of switch information
✓ ✓ ✓ ❏ ❏ ❏ ❏ ❏ ❏ ✓
on HTML basis locally to a PC
Transmission of switch information
✓ ✓ ✓ ❏ ❏ ❏ ❏ ❏ ❏ ✓
on HTML basis through Ethernet
Short-time grading control for
✓ ✓ ❏ ❏ ❏ ❏ ❏ ❏ ✓ ❏
S tripping and G protection
Local display of harmonic analysis and waveform
-- ✓ ❏ ❏ ✓ ❏ ❏ ❏ ❏ ❏
memory
Local storage of harmonic analysis and waveform
✓ ✓ ✓ ✓ ✓ ❏ ❏ ❏ ❏ ❏
memory and transmission through PROFIBUS
Read out protection parameters through PROFIBUS ✓ ✓ ✓ ✓ ❏ ❏ ❏ ❏ ❏ ❏
Read out and adjust protection parameters through
-- ✓ ✓ ✓ ❏ ❏ ❏ ❏ ❏ ❏
PROFIBUS
✓Required ❏ Not necessary for this function, optionally combinable
Function can optionally be taken over by more than one release. -- Function not available

Function can optionally be taken over by one of these modules.

Siemens · 2012 21
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Data that can be transmitted over the PROFIBUS DP/MODBUS or the Breaker Data Adapter
All 3WL circuit breakers with ETU45B, ETU76B (CubicleBUS integrated)

Transmittable circuit breaker data


BSS BDAPLUS BSS COM15/COM16
Order code (Order No. of circuit breaker + "–Z") F01 F02/F12
Order No. +"BDAPLUS"-
Order No.
Potential applications
Transmission of circuit breaker data to PROFIBUS DP or MODBUS and integration into
higher-level visualization systems are possible -- ✔
e. g. in PCS7, Power Management Systems, WinCC (including add-ons like the text message radio server)
Transmission of circuit breaker data and software (i. e. HTML pages with data) to a local output
device, or remotely through Ethernet/Intranet/Internet (without the possibility of integration into
higher-level visualization systems) ✔ --
e. g. for monitoring, diagnostics, maintenance and parameterization of individual circuit breakers
Utilization of the functionality of all CubicleBUS modules
e.g. configuration of the configurable digital output module, status check of the digital input modules, ✔ ✔
diagnostics
Transmittable circuit breaker data without integrated measurement function
Device identification
Communication address, Order No., switch in as-delivered state, circuit breaker parameters ✔ ✔
(size, number of poles, rated current module etc.), identification numbers, release type,
1)
free text for plant code and comments -- ✔
Operating states
On/off status message, storage spring, tripped, readiness ✔ ✔
Switching position (connected, test and disconnected position, not present) for withdrawable circuit --1) ✔
breakers,
PROFIBUS/MODBUS write protection on/off, free user input --1) ✔
Control commands
Switch circuit breakers ON/OFF, switch free user output ON/OFF --1) ✔
Reset tripped signal ✔ ✔
Delete event and history memory --1) ✔
Rest min./max. measured values, reset maintenance information ✔ ✔
History
Read out the event protocol, read out the release protocol --1) ✔
Information on maintenance
Number of tripping operations - L, S/I and total, contact erosion ✔ ✔
Number of switching operations - under load and total, operating hours --1) ✔
Event signals
Tripped signals with data on tripping currents ✔ ✔
Alarmsignals (e. g. overload) with incoming/outgoing information --1) ✔
All named event signals with time stamp --1) ✔
Parameterization of protection functions
Readout of protection function parameters ✔ ✔
Modification of settings for protection function parameters via communication ✔ 2) ✔ 2)
Parameter set switchover supported (set A to set B and vice versa) ✔ 2) ✔ 2)
Measured values
Phase currents, each with min./max. value ✔ ✔
Temperature in the circuit breaker with min./max. value --1) ✔
Temperature in the control cabinet with min./max. value --1) ✔
All named measured values with time stamp --1) ✔

Measurement function Plus


Order code F01+ ... or F02+ ... F05
Additional transmittable circuit breaker data with integrated measurement function
Additional event signals
Threshold value alarms (e. g. over/underfrequency, over/undervoltage) ✔
Parameterization of expanded protection functions and setpoints (threshold values)
Readout of parameters of expanded protection functions ✔
Modification of settings for protection function parameters ✔
Readout and setting of threshold values ✔
Additional measured values
Voltages, powers, energy, p.f., Frequency with min./max. value ✔
Harmonic analysis ✔
Recording of currents and voltages for configurable events in waveform memory ✔
1) Data only available in conjunction with the COM15 module (BUS connec- ✔ Available
tion not required). -- Not available
2) Only possible with ETU76B.

22 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
CubicleBUS modules
Digital output modules with rotary coding switch
6 items of binary information concerning the state of the circuit
breaker (reasons for tripping and warnings) can be output via
this module to external signaling devices (e. g. light, horn) or be
used for the selective shut-down of other system components
(e. g. frequency converters).
Digital output modules are available in versions with and without
a rotary coding switch. On modules with a rotary coding switch
it is possible to choose between two signaling blocks each with
6 defined assignments and to set an additional response delay. Analog output modules

All the digital output modules are available as a version with re- Digital input module
lay outputs (CO contacts, up to 12 A). Up to two modules of this With the digital input module, up to 6 additional binary signals
type can be connected to one 3WL circuit breaker. (24 V DC) in the circuit breaker environment can be connected
to the system. It is thus possible for example to send messages
concerning the state of a switch disconnector or a control cabi-
net door to the PROFIBUS DP/MODBUS.
With the digital input module on the CubicleBUS it is also possi-
ble for the two different protection parameter sets held in the
ETU76B electronic releases to be switched over automatically in
a few milliseconds. It is thus possible, for example, to automati-
cally change the parameters of a coupling switch should the
transformer infeed fail.
One module each of this type can be used for holding the six
items of digital information and for automatically switching over
Digital output modules with rotary coding switch the parameters.
Digital output modules, configurable
The configurable output module is available for higher-perfor-
mance solutions. With this module, random events on the
CubicleBUS can be switched directly to one of six available out-
puts or three of these outputs can be assigned with up to six
events. In other words, up to six events can be placed on one
physical output with "OR" operation. Either BDA/BDA Plus or
Switch ES Power is used for configuring.
A relay variant is also available here the same as for the output
modules with rotary coding switch. Only one module of this type
is possible per 3WL circuit breaker.
Digital input module
ZSI modules (short-time grading control)
The use of ZSI modules is recommended when Siemens circuit
breakers are arranged in several staggered levels but full grad-
ing with the smallest possible delay is to be assured neverthe-
less.
The circuit breakers are interconnected by these modules. In
case of a short-circuit, each affected circuit breaker asks the cir-
cuit breakers directly downstream whether the short-circuit has
also occurred in the next, lower level. The short-circuit is exactly
localized as the result, and only the next upstream circuit
Digital output modules, configurable breaker in the energy flow direction is switched off.
Analog output modules
The analog output module can be used to output the following
measured values to analog indicators in the control cabinet
door:
• IL1, IL2, IL3, IN or
• UL12, UL23, UL31, UL1N or
• PL1, PL2, PL3, Stot or
• p.f. 1, p.f. 2, p.f. 3, ΔI % or
• favg, ULLavg, Ptot, p.f.avg
Four 4-20-mA/0-10-V interfaces are available for this. The mea-
sured values to be output are selected with a rotary coding
switch. By using the analog output module it is possible to do ZSI modules (short-time grading control)
without additional converters and their conventional installa-
tion/wiring in the main current path. Up to two modules of this
type can be connected to one 3WL circuit breaker.

Siemens · 2012 23
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data

■ Technical specifications
Switching capacity
Sizes I II III
Type 3WL11 3WL12 3WL13
Switching capacity class N S H N S H H C C
N S H N S H H C C
3-pole 4-pole
Short-circuit breaking capacity
Rated operational voltage Ue up to 415 V AC
Icu kA 55 66 85 66 80 100 100 150 130
Ics kA 55 66 85 66 80 100 100 150 130
Icm kA 121 145 187 145 176 220 220 330 286
Rated operational voltage Ue up to 500 V AC
Icu kA 55 66 85 66 80 100 100 150 130
Ics kA 55 66 85 66 80 100 100 150 130
Icm kA 121 145 187 145 176 220 220 330 286
Rated operational voltage Ue up to 690 V AC
Icu kA 42 50 66 50 75 85 85 150 130
Ics kA 42 50 66 50 75 85 85 150 130
Icm kA 88 105 145 105 165 187 187 330 286
Rated operational voltage Ue
up to 1000 V/1150 V AC
Icu kA -- -- 509) -- -- 50 50 704) 704)
Ics kA -- -- 509) -- -- 50 50 704) 704)
Icm kA -- -- 1059) -- -- 105 105 1544) 1544)
Rated short-time withstand current Icw
of the circuit breakers3)
0.5 s kA 55 66 75 66 80 100 100 100 100
1s kA 42 50 66 55 66 80 100 100 100
2s kA 29.5 35 46 39 46 651)/702) 80 80 80
3s kA 24 29 37 32 44 501)/652) 65 65 65
Short-circuit breaking capacity Icc
of the non-automatic air circuit breakers
Up to 500 V AC kA 55 66 75 66 80 100 100 100 100
Up to 690 V AC kA 42 50 66 50 75 85 85 100 100
Up to 1000 V /1150 V AC kA -- -- 509) -- -- 504) 504) 704) 704)

Sizes II
DC

Type 3WL12
Switching capacity class DC
Short-circuit breaking capacity
Up to 220 V DC Icc kA 35
Up to 300 V DC Icc kA 30
Up to 600 V DC Icc kA 25
Up to 1000 V DC Icc kA 20
Rated short-time withstand current Icw
0.5 s kA --
1s kA 355)/306)/257)/208)
2s kA --
3s kA --

Circuit breaker with ECO switching capacity N Abbreviations


N (functions)

S
Circuit breaker with standard switching capacity S L = Long Time Delay = Overload protection
S = Short Time Delay = Short-circuit protection
H
Circuit breaker with high switching capacity H (short-time delayed)
I = Instantaneous = Short-circuit protection
C
Circuit breakers with very high switching capacity C (instantaneous)
N = Neutral Protection Neutral conductor protec-
DC
Non-automatic air circuit breakers with DC switching ca- tion
pacity G = Ground Fault Ground-fault protection
These switching capacities are indicated in the corre-
sponding tables by the symbols shown on orange back-
grounds. L, S, I, N, G: Designation according to IEC 60947-2, Appendix K.
6)
1)
Size II with In max ≤ 2500 A. At Ue = 300 V DC.
2) 7)
Size II with In max = 3200 A and In max = 4000 A. At Ue = 600 V DC.
8)
3)
At a rated voltage of ≥ 690 V the Icw value of the circuit breaker cannot be At Ue = 1000 V DC.
greater than the Icu or Ics value at 690 V. 9) Values also apply to version 690 V + 20 % with Z option "A16".
4)
Rated operational voltage Ue = 1150 V.
5)
At Ue = 220 V DC.

24 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data

Sizes I II
Type ... 3WL11 10 3WL11 12 3WL11 16 3WL11 20 3WL12 08 3WL12 10 3WL12 12 3WL12 16
Rated current In at 40 °C, at 50/60 Hz
Main conductors A ... 1000 1250 1600 2000 800 1000 1250 1600
N conductor (only on 4-pole versions) A ... 1000 1250 1600 2000 800 1000 1250 1600
Rated operational voltage Ue at 50/60 Hz V AC ... ... ... ... ... ... ... ...
(1000 V version, see Catalog LV 10.1, "Options") 690/1000 690/1000 690/1000 690/1000 690/1000 690/1000 690/1000 690/1000
Rated insulation voltage Ui V AC 1000 1000 1000 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp
• Main current paths kV 12 12 12 12 12 12 12 12
• Auxiliary circuits kV 4 4 4 4 4 4 4 4
• Control circuits kV 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
Isolating function to EN 60 947-2 Yes Yes Yes Yes Yes Yes Yes Yes
Utilization category B
Permissible ambient temperature
• During operation (in operation with LCD max. 55 °C)4) °C –25/+70 –25/+70 –25/+70 –25/+70 –25/+70 –25/+70 –25/+70 –25/+70
• During storage (special conditions for LCDs must be °C –40/+70 –40/+70 –40/+70 –40/+70 –40/+70 –40/+70 –40/+70 –40/+70
observed)
Permissible load • Up to 55 °C (Cu bare) A 1000 1250 1600 2000 800 1000 1250 1600
At rear horizontal main con- • Up to 60 °C (Cu bare)5) A 1000 1250 1600 1930 800 1000 1250 1600
nections • Up to 70 °C (Cu black A 1000 1210 14908) 1780 800 1000 1250 1600
painted)5)
Rated rotor operational voltage Uer V 2000 2000 2000 2000 2000 2000 2000 2000
Power loss at In
with 3-phase symmetrical load
• Fixed-mounted circuit breakers W 100 105 150 240 40 45 80 85
• Withdrawable circuit breakers W 195 205 350 440 85 95 165 175
Switching times
• Make-time ms 35 35 35 35 35 35 35 35
• Opening time ms 38 38 38 38 34 34 34 34
• Electrical make-time (through closing solenoid)2) ms 80 80 80 80 100 100 100 100
• Electrical opening time (through shunt release) ms 73 73 73 73 73 73 73 73
• Electrical opening time (instantaneous undervoltage ms 73 73 73 73 73 73 73 73
release)
1) 1) 1) 1) 1) 1) 1)
• Opening time due to ETU, instantaneous short-circuit ms 50 50 50 50 50 50 50 501)
release
Endurance: Switching capacity N and S. 3/4-pole
• Mechanical (without maintenance) Operating cycles 10 000 10 000 10 000 10 000 10 000 10 000 10 000 10 000
• Mechanical (with maintenance)3) Operating cycles 20 000 20 000 20 000 15 000 15 000 15 000 15 000 15 000
• Electrical (without maintenance) Operating cycles 10 000 10 000 10 000 7500 7500 7500 7500 7500
• 1000 V version, electrical Operating cycles -- -- -- 1000 1000 1000 1000 1000
(without maintenance)
• 1150 V version, electrical Operating cycles -- -- -- -- 500 500 500 500
(without maintenance)
• Electrical (with maintenance)3) Operating cycles 20 000 20 000 20 000 15 000 15 000 15 000 15 000 15 000
Endurance: Switching capacity H, 3-pole
• Mechanical (without maintenance) Operating cycles 10 000 10 000 10 000 10 000 10 000 10 000 10 000 10 000
• Mechanical (with maintenance)3) Operating cycles 15 000 15 000 15 000 15 000 15 000 15 000 15 000 15 000
• Electrical (without maintenance) Operating cycles 7 500 7 500 7 500 7500 7500 7500 7500 7500
• 1000 V version, electrical Operating cycles 1000 1000 1000 1000 1000 1000 1000 1000
(without maintenance)
• 1150 V version, electrical Operating cycles -- -- -- -- 500 500 500 500
(without maintenance)
• Electrical (with maintenance) 3)9) Operating cycles 15 000 15 000 15 000 15 000 15 000 15 000 15 000 15 000
Endurance: Switching capacity H, 4-pole
• Mechanical (without maintenance) Operating cycles 10 000 10 000 10 000 10 000 10 000 10 000 10 000 10 000
• Mechanical (with maintenance)3) Operating cycles 15 000 15 000 15 000 15 000 15 000 15 000 15 000 15 000
• Electrical (without maintenance) Operating cycles 7 500 7 500 7 500 7500 7500 7500 7500 7500
• 1000 V version, electrical Operating cycles 1000 1000 1000 1000 1000 1000 1000 1000
(without maintenance)
• 1150 V version, electrical Operating cycles -- -- -- -- 500 500 500 500
(without maintenance)
3)9)
• Electrical (with maintenance) Operating cycles 10 000 10 000 10 000 10 000 15 000 15 000 15 000 15 000
Switching frequency6)
• 690 V version 1/h 607) 607) 607) 60 607) 607) 607) 607)
• 1000 V version 1/h -- -- -- 20 20 20 20 20
• 1150 V version 1/h -- -- -- -- 20 20 20 20
Minimum interval between tripping operation by elec- ms 80 80 80 80 80 80 80 80
tronic release and next making operation of the circuit
breaker (only with autom. mechanical resetting of the
lockout device).
Minimum interval between ON/OFF or OFF/ON switching
operations.
1) 5)
Opening time on instantaneous short-circuit release with ETU76B with graphics display can be used up to max. 55 °C.
ETU15B = 85 ms. 6)
Minimum interval between 2 switching operations.
2)
Make-time through closing solenoid for synchronization purposes 7)
3-pole switching with switching capacity N and S: 45/h.
(short-time excited) 50 ms. 8)
3) For switching capacity H: 1600 A to 70 °C.
Maintenance means: replace main contact elements and arc chutes (see 9)
Operating Manual). The main contacts of size I circuit breakers with switching capacity H can
4) only be replaced at the factory.
Use of releases from –20 °C

Siemens · 2012 25
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data

Sizes I II
Type ... 3WL11 10 3WL11 12 3WL11 16 3WL11 20 3WL12 08 3WL12 10 3WL12 12 3WL12 16
Mounting position 3 0 ° 3 0 ° 3 0 ° 3 0 °

h m a x .
= 1 m m
and/or

N S E 0 _ 0 0 0 6 1 a N S E 0 _ 0 0 0 6 2 a N S E 0 _ 0 0 9 2 7 a

Degree of protection IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover
Main conductor • Copper bars, Unit(s) 1× 2× 2× 3× 1× 1× 2× 2×
minimum bare mm2 60 × 10 40 × 10 50 × 10 50 × 10 50 × 10 60 × 10 40 × 10 50 × 10
cross-sections • Copper bars, Unit(s) 1× 2× 2× 3× 1× 1× 2× 2×
painted black mm2 60 × 10 40 × 10 50 × 10 50 × 10 50 × 10 60 × 10 40 × 10 50 × 10
Auxiliary conductors (Cu) Standard connection = strain-
Max. number of relief clamp
auxiliary conductors × cross- • Without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14)
section • With end sleeve according to 1 × 0.5 mm2 (AWG 20) ... 1 × 1.5 mm2 (AWG 16)
(solid/stranded) DIN 46228 Part 2
• With twin end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
Optional connection = tension
spring
• Without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 2.5 mm2 (AWG 14)
• With end sleeve according to 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
DIN 46228 Part 2
Position signaling switches Tension spring terminals 1 × 0.5 mm2 (AWG 20) ... 1 × 2.5 mm2 (AWG 14)
Weights 3-pole • Fixed-mounted CBs kg 43 43 43 43 56 56 56 56
• Withdrawable CBs kg 45 45 45 45 60 60 60 60
• Guide frames kg 25 25 25 25 31 31 31 31
4-pole • Fixed-mounted CBs kg 50 50 50 50 67 67 67 67
• Withdrawable CBs kg 54 54 54 54 72 72 72 72
• Guide frames kg 30 30 30 30 37 37 37 37

26 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data

Sizes II III
Type 3WL12 20 3WL12 25 3WL12 32 3WL12 40 3WL13 40 3WL13 50 3WL13 63
Rated current In at 40 °C, at 50/60 Hz
Main conductors A 2000 2500 3200 4000 4000 5000 6300
N conductor (only on 4-pole versions) A 2000 2500 3200 4000 4000 5000 6300
Rated operational voltage Ue at 50/60 Hz V AC ... ... ... ... 690 ... ... ...
(1000 V version, see Catalog LV 10.1, "Options") 690/1000 690/1000 690/1000 690/1000 690/1000 690/1000
Rated insulation voltage Ui V AC 1000 1000 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp
• Main current paths kV 12 12 12 12 12 12 12
• Auxiliary circuits kV 4 4 4 4 4 4 4
• Control circuits kV 2.5 2.5 2.5 2.5 2.5 2.5 2.5
Isolating function to EN 60947-2 Yes Yes Yes Yes Yes Yes Yes
Utilization category B (except switching capacity class DC)
Permissible ambient temperature
• During operation (in operation with LCD max. 55 °C)4) °C –25/+70 –25/+70 –25/+70 –25/+70 –25/+70 –25/+70 –25/+70
• During storage (special conditions for LCDs must be observed) °C –40/+70 –40/+70 –40/+70 –40/+70 –40/+70 –40/+70 –40/+70
Permissible load6) • Up to 55 °C (Cu bare) A 2000 2500 3200 3950 4000 5000 5920
• Up to 60 °C (Cu bare)5) A 2000 2500 3020 3810 4000 5000 5810
• Up to 70 °C (Cu black painted)5) A 2000 2280 2870 3600 4000 5000 5500
Rated rotor operational voltage Uer V 2000 2000 2000 2000 2000 2000 2000
Power loss at In
with 3-phase symmetrical load
• Fixed-mounted circuit breakers W 180 270 410 750 520 630 900
• Withdrawable circuit breakers W 320 520 710 925 810 1050 1600
Switching times
• Make-time ms 35 35 35 35 35 35 35
• Opening time ms 34 34 34 34 34 34 34
• Electrical make-time (through closing solenoid)2) ms 100 100 100 100 100 100 100
• Electrical opening time (through shunt release) ms 73 73 73 73 73 73 73
• Electrical opening time (instantaneous undervoltage release) ms 73 73 73 73 73 73 73
• Opening time due to ETU, instantaneous short-circuit release ms 501) 501) 501) 501) 50 50 50
Endurance
• Mechanical (without maintenance) Operating cycles 10000 10000 10000 10000 5000 5000 5000
• Mechanical (with maintenance)3) Operating cycles 15000 15000 15000 15000 10000 10000 10000
• Electrical (without maintenance) up to 690 V Operating cycles 7500 7500 4000 2000 2000 2000 2000
• 1000 V version, electrical (without maintenance) Operating cycles 1000 1000 1000 1000 1000 1000 1000
• 1150 V version, electrical7) (without maintenance) Operating cycles 500 500 500 500 500 500 500
• Switching capacity C: Electrical Operating cycles -- -- -- -- 1000 1000 1000
(without maintenance) up to 690 V
• Switching capacity C: Electrical Operating cycles -- -- -- -- 500 500 500
(without maintenance) up to 1150 V
• Electrical (with maintenance)3) Operating cycles 15000 15000 15000 15000 10000 10000 10000
Switching frequency8)
• 690 V version 1/h 609) 609) 609) 609) 60 60 60
• 1000 V version 1/h 20 20 20 20 20 20 20
• 1150 V version7) 1/h 20 20 20 20 20 20 20
Minimum interval between tripping operation by electronic ms 80 80 80 80 80 80 80
release and next making operation of the
circuit breaker (only with automatic
mechanical resetting of the lockout device)
Minimum interval between ON/OFF or OFF/ON switching opera-
tions.
1) 5)
Opening time on instantaneous short-circuit release with ETU76B with graphics display can be used up to max. 55 °C.
ETU15B = 85 ms. 6)
4000 A, size II in fixed-mounted version, 3-pole.
2)
Make-time through closing solenoid for synchronization purposes 7)
Size II with order code "A15" and size III:
(short-time excited) 50 ms. Data for very high switching capacity.
3)
Maintenance means: replace main contact elements and arc chutes 8)
Minimum interval between 2 switching operations.
(see Operating Manual). 9)
4) 3-pole switching with switching capacity N and S: 45/h.
Use of releases from –20 °C

Siemens · 2012 27
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data

Sizes II III
Type 3WL12 20 3WL12 25 3WL12 32 3WL12 40 3WL13 40 3WL13 50 3WL13 63
3 0 ° 3 0 °

h m a x .
Mounting position 3 0 ° 3 0 °

= 1 m m
and/
or
N S E 0 _ 0 0 0 6 1 a N S E 0 _ 0 0 0 6 2 a N S E 0 _ 0 0 9 2 7 a

Degree of protection IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover
Main conductor • Copper bars, Unit(s) 3 × 2× 3× 4× 4x 6x 6x
minimum bare mm2 50 × 10 100 × 10 100 × 10 120 × 10 100 x 10 100 x 10 120 x 10
cross-sections • Copper bars, Unit(s) 3 × 2× 3× 4× 4× 6× 6×
painted black mm2 50 × 10 100 × 10 100 × 10 100 × 101) 100 × 10 100 × 10 120 × 10
Auxiliary conductors Standard connection = strain-relief clamp
(Cu) • Without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14)
Max. no. of • With end sleeve according to 1 × 0.5 mm2 (AWG 20) ... 1 × 1.5 mm2 (AWG 16)
auxiliary conductors × DIN 46228 Part 2
cross-section • With twin end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
(solid/stranded)
Optional connection = tension spring
• Without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 2.5 mm2 (AWG 14)
• With end sleeve according to 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
DIN 46228 Part 2
Position signaling Tension spring terminals 1 × 0.5 mm2 (AWG 20) ... 1 × 2.5 mm2 (AWG 14)
switches
Weights 3-pole • Fixed-mounted circuit breakers kg 56 59 64 85 82 82 90
• Withdrawable circuit breakers kg 60 63 68 121 88 88 96
• Guide frames kg 31 39 45 52 60 60 70
4-pole • Fixed-mounted circuit breakers kg 67 71 77 103 99 99 108
• Withdrawable circuit breakers kg 72 76 82 146 106 106 108
• Guide frames kg 37 47 54 62 84 84 119
1) Minimum main conductor cross-sections for 4-pole withdrawable circuit
breakers: 4 x 120 x 10 mm

28 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data

Sizes I to III
Type 3WL1
Manual operating mechanism with mechanical closing
Closing/ Max. force required to operate the hand lever N ≤ 230
Charging stored- Required number of strokes on the hand lever 9
energy feature
Manual operating mechanism with mechanical and electrical closing
Charging stored-
energy feature
Closing solenoid • Primary operating range 0.85 ... 1.1 × Us
(CC)
• Extended operating range for battery operation At 24 V DC, 48 V DC 0.7 ... 1.26 × Us
60 V DC, 110 V DC
220 V DC
• Rated control supply voltage Us 50/60 Hz AC V 110 ... 127; 208 ... 240
DC V 24; 30; 48; 60; 110 ... 125; 220 ... 250
• Power consumption AC/DC VA/W 15/15
• Minimum command duration at Us for the closing solenoid ms 60
• Short-circuit protection 1 A TDz (slow)/1 A
Smallest permissible DIAZED fuse (gL operational class)/
miniature circuit breaker with C characteristic
Manual/motorized operating mechanism with mechanical and electrical closing
Manual operating For data see above.
mechanism
Motor • Primary operating range 0.85 ... 1.1 × Us
• Extended operating range for battery operation At 24 V DC, 48 V DC 0.7 ... 1.26 × Us
60 V DC, 110 V DC
220 V DC
• Power consumption of motor AC/DC VA/W 135/135
• Time required to charge the stored-energy mechanism at 1 × Us s ≤ 10
Closing solenoid For data see above.
For motor and • Short-circuit protection 6 A TDz (slow)/2 A
closing solenoid Smallest permissible DIAZED fuse (gL operational class)/miniature circuit breaker with
C characteristic; Motor and closing solenoid for identical rated control supply voltages
• Smallest permissible DIAZED fuse (gL operational class)/ At Us = 24 ... 30 V 6A
miniature circuit breaker with C characteristic (for different At Us = 48 ... 60 V 6A
rated control supply voltages) At Us = 110 ... 125 V DC/ 2A
110 ... 127 V AC
At Us = 220 ... 250 V DC/ 2A
208 ... 240 V AC
Electronic release signals
Measuring accuracy of the electronic release Protection functions acc. to
EN 60947; current indication ≤ 10 %;
Measurement function
Base electrical quantities ≤ 1 %;
Measurement function
derived variables ≤ 4 %
Auxiliary releases
Undervoltage • Response values Pick-up ≥ 0.85 × Us (circuit breaker can
releases be closed)
UVR (F3) and Dropout 0.35 ... 0.7× Us
UVR-td (F4) (circuit breaker is tripped)
• Primary operating range 0.85 ... 1.1
• Extended operating range for battery operation At 24 V DC, 30 V DC, 0.85 ... 1.26
48 V DC, 110 V DC, 220 V DC
• Rated control supply voltage Us Instantaneous
50/60 Hz AC V 110 ... 127/208 ... 240/380 ... 415
DC V 24/30/48/60/110 ... 125/220 ... 2501)
Delayed
50/60 Hz AC V 110 ... 127; 208 ... 240; 380 ... 415
DC V 48; 110 ... 125; 220 ... 250
• Power consumption (pickup/uninterrupted duty) AC VA 20/5
DC W 20/5
• Opening time of circuit breaker at Us = 0 ms 200
- Version UVR (F3)
Instantaneous ms 80
With delay ms 200
- Version UVR-td (F8)
with delay, td = 0.2 to 3.2 s s 0.2 ... 3.2
Reset via additional NC contact – direct switching off ms ≤ 100
• Short-circuit protection 1 A TDz (slow)/1 A
Smallest permissible DIAZED fuse (gL operational class)/
miniature circuit breaker with C characteristic
1)
24 V and 30 V only with undervoltage release UVR (F3).

Siemens · 2012 29
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data

Sizes I to III
Type 3WL1
Auxiliary releases
Shunt release (ST) • For continuous command - Response value Pick-up > 0.7 × Us
(F1, F2) (100 % ON period), locks (circuit breaker is tripped)
out on momentary-con- - Primary operating range 0.85 ... 1.1 × Us
tact commands
- Extended operating range At 24 V DC, 48 V DC 0.7 ... 1.26 × Us
for battery operation 60 V DC, 110 V DC
220 V DC
- Rated control supply voltage Us 50/60 Hz AC V 110 ... 127; 208 ... 240
DC V 24; 30; 48; 60; 110 ... 125;
220 ... 250
- Power consumption AC/DC VA/W 15/15
- Minimum command duration at Us ms 60
- Opening time of circuit breaker at AC/DC ms 80
Us = 100 %
- Short-circuit protection 1 A TDz (slow)/1 A
Smallest permissible DIAZED fuse (gL operational
class)/miniature circuit breaker with C characteristic
5 % OP - Response value Pick-up > 0.7 × Us
(circuit breaker is tripped)
- Primary operating range 0.85 ... 1.1 × Us
- Extended operating range At 24 V DC, 48 V DC 0.7 ... 1.26 × Us
for battery operation 60 V DC, 110 V DC
220 V DC
- Rated control supply voltage Us 50/60 Hz AC V 110 ... 127; 208 ... 240
DC V 24; 48; 110 ... 125; 220 ... 250
- Power consumption AC/DC VA/W 15/15
- Minimum command duration at Us ms 25
- Opening time of circuit breaker at AC/DC ms 50
Us = 100 %
- Short-circuit protection 1 A TDz (slow)/1 A
Smallest permissible DIAZED fuse (gL operational
class)/miniature circuit breaker with C characteristic
• With stored energy fea- - Rated control supply voltage Us 50/60 Hz AC V 110; 230
ture DC V 110; 220
consisting of shunt re- - Primary operating range 0.85 ... 1.1 × Us
lease and capacitor stor-
age device - Power consumption AC/DC VA/W 1/1
- Storage time at Us/ max. 5 min/min. 5 s
recharging time at Us
- Opening time of circuit breaker, short-circuit protec- As with "for continuous com-
tion mand"
Remote reset solenoid for mechanical tripped indicator (F7)
Remote reset solenoid for - Primary operating range 0.85 ... 1.1 × Us
mechanical tripped indica- - Extended operating range At 24 V DC, 48 V DC 0.7 ... 1.26 × Us
tor (F7) for battery operation 110 V DC
220 V DC
- Power consumption AC/DC VA/W 50/50
- Minimum command duration at Us for the remote re- ms 60
set solenoid
- Short-circuit protection
Smallest permissible DIAZED fuse (gL operational class)/ 2 A TDz (slow)/1 A at 24 V DC
miniature circuit breaker with C characteristic and 48 V DC,
1 A TDz (slow)/1 A at 110 V and
208 ... 250 V
Contact position-driven auxiliary switches (S1, S2, S3, S4, S7, S8)
Rated insulation voltage Ui V AC/DC 500
Rated operational voltage Ue V AC/DC 500
Rated impulse withstand voltage Uimp kV 4
Switching capacity • Alternating current - Rated operational voltage Ue V 24 ... 230 380/400 500
50/60 Hz - rated operational current
Ie /AC-12 A 10 10 10
Ie/AC-15 A 4 3 2
• Direct current - Rated operational voltage Ue V 24 48 110 220
- rated operational current
Ie/DC-12 A 10 8 3.5 1
Ie/DC-13 A 8 4 1.2 0.4
Short-circuit protection • Largest permissible DIAZED fuse (gL operational class) 10 A TDz, 10 A Dz
• Largest permissible miniature circuit breaker with C characteristic 10 A

30 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data

Sizes I to III
Type 3WL1
Ready-to-close signaling switch (S20) (according to DIN VDE 0630)
Switching capacity • Alternating current - Rated operational voltage Ue V 250
- Rated operational current Ie A 8
• Direct current - Rated operational voltage Ue V 125 250
- Rated operational current Ie A 0.4 0.2
Short-circuit protection Largest permissible DIAZED fuse (gL operational class) 2 A Dz (quick)
Tripped signaling switch (S24) and signaling switch for auxiliary releases (S22, S23)
(according to DIN VDE 0630)
Switching capacity • Alternating current - Rated operational voltage Ue V 250
- Rated operational current Ie/AC-12 A 8
• Direct current - Rated operational voltage Ue V 24 125 250
- Rated operational current Ie/DC-12 A 6 0.4 0.2
Short-circuit protection Largest permissible DIAZED fuse (gL operational class) 6 A Dz (quick)
Tripped signaling switch Signal duration after tripping Until manual or electrical
remote reset (option)
Position signaling switch on guide frame
Type of contact • Signal: - "Circuit breaker in connected posi- 3 CO 1 CO
tion" 2 CO or 1 CO
- "Circuit breaker in test position" 1 CO 1 CO
- "Circuit breaker in disconnected
position"
Rated insulation voltage Ui 50/60 Hz AC V 440
DC V 250
Rated operational voltage Ue V 250
Rated impulse withstand voltage Uimp kV 4
Switching capacity • Rated operational - Ie/AC-12 24 V 10 A, 110/127 V 10 A,
current Ie 220/240 V 10 A, 320/440 V 10 A
- Ie/AC-15 220/240 V 4 A,
320/440 V 3 A,
- Ie/DC-12 24 V 10 A, 48 V 2.5 A,
220/240 V 0.2 A,
- Ie/DC-13 24 V 3.0 A, 220/240 V 0.1 A

- A 300 (AC) 120 V 6 A, 240 V 3 A

- R 300 (DC) 125 V 0.22 A, 250 V 0.11 A


Short-circuit protection • Largest permissible DIAZED fuse (gL operational class) 8 A TDz (slow)
• Largest permissible miniature circuit breaker with C characteristic 8 A TDz (slow)

Siemens · 2012 31
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data

Protection functions ETU15B ETU25B ETU27B


Parameterization by D D D&S
Functional overview of the electronic release system
Overload protection ✓ ✓ ✓
Function can be switched on/off -- -- --
Setting range IR = In × ... 0.5-0.55-0.6-0.65-0.7- 0.4-0.45-0.5-0.55-0.6- 0.4-0.45-0.5-0.55-0.6-
0.75-0.8-0.85-0.9-1 0.65-0.7-0.8-0.9-1 0.65-0.7-0.8-0.9-1
R
L Switchable overload protection
(I2t- or I4t-dependent function)
-- -- --

Setting range for time-lag class tR at I2t 10 s fixed 10 s fixed 10 s fixed


R
Setting range for time-lag class tR at I4t -- -- --
Thermal image can be switched on/off -- -- --
Phase failure sensitivity -- At tsd = 20 ms (M) At tsd = 20 ms (M)
Neutral conductor protection -- -- ✓
N Function can be switched on/off
N conductor setting range IN = In × ...
--
--
--
--

1
Short-time delayed short-circuit protection -- ✓ ✓
Function can be switched on/off -- -- --
s d Setting range Isd = In × ... -- 1.25-1.5-2-2.5-3-4-6-8-10-12 1.25-1.5-2-2.5-3-4-6-8-10-12
S s d
Setting range for delay time tsd
Switchable short-time delayed short-circuit
--
--
0-M-100-200-300-400 ms
--
0-M-100-200-300-400 ms
--
protection (I2t-dependent function)
Setting range for delay time tsd at I2t -- -- --
Zone Selective Interlocking function -- -- --
i Instantaneous short-circuit protection ✓ ✓ ✓
I
N S E 0 _ 0 0 8 8 8 b Function can be switched on/off
Setting range Ii = In × ...
--
2-3-4-5-6-7-8
--
Fixed for Ii ≥ 20 × In, max. 50 kA
--
Fixed for Ii ≥ 20 × In, max. 50 kA
Ground-fault protection -- -- ✓ Fixed mounted
Tripping and alarm function -- -- --
Tripping function can be switched on/off -- -- ✓
Alarm function can be switched on/off -- -- --
Detection of the ground-fault current through summa- -- -- ✓
g tion current formation with internal or external N con-
ductor transformer
Detection of ground-fault current through external -- -- --

g
G current transformer
Setting range of the operating current Ig for tripping -- -- A-B-C-D-E
N S E 0 _ 0 0 8 8 9 a Setting range of the operating current Ig for alarm -- -- --
Setting range of the delay time tg -- -- 100-200-300-400-500 ms
Switchable ground-fault protection characteristic -- -- --
2
curve (I t-dependent function)
Setting range for delay time tg at I2t -- -- --
Zone Selective Interlocking ground-fault protect. -- -- --
function
Parameter set switchover
Switchable between parameter set A and B -- -- --
LCD
Alphanumeric LCD (4-line) -- -- --
Graphical LCD (24 V, external power supply required) -- -- --
Communication
CubicleBUS integrated -- -- --
Communication-capable through PROFIBUS DP -- -- --
Measurement function
Measurement-function capable with measurement -- -- --
function Plus
LED display
Electronic release active ✓ ✓ ✓
Alarm ✓ ✓ ✓
ETU fault ✓ ✓ ✓
L-release -- ✓ ✓
S-release -- ✓ ✓
I-release -- ✓ ✓
N-release -- -- ✓
NSE00890
G-release -- -- ✓
G-alarm -- -- --
Release through extended protection function -- -- --
Communication -- -- --
Signals from signaling switches with external CubicleBUS modules (relays)
Overload warning -- -- --
Load shedding, load receiving -- -- --
Leading signal overload trip 200 ms -- -- --
Temperature alarm -- -- --
Phase unbalance -- -- --
Instantaneous short-circuit release -- -- --
Short-time delayed short-circuit release -- -- --
Overload trip -- -- --
Neutral conductor release -- -- --
NSE00891
Ground-fault protection release -- -- --
Ground-fault alarm -- -- --
Auxiliary relay -- -- --
ETU fault -- -- --
Delay time figures given in ms. D & S = Rotary coding and slide switch ✓ Available.
M = Motor protection, corresponds to 20 ms. K = communication -- Not available.
D = Rotary coding switch M/K = menu/communication ❑ Optional.
For the setting range of the operating current Ig, see page 33.

32 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data

Protection functions ETU45B ETU76B


Parameterization by D& S M/K
Functional overview of the electronic release system
Overload protection ✓ ✓
Function can be switched on/off -- ✓
Setting range IR = In × ... 0.4-0.45-0.5-0.55-0.6- 0.4 ... 1
0.65-0.7-0.8-0.9-1
Switchable overload protection (I2t- or I4t-dependent function) ✓ ✓
Setting range for time-lag class tR at I2t 2-3.5-5.5-8-10-14-17-21-25-30 s 2 ... 30 s
Setting range for time-lag class tR at I4t 1-2-3-4-5 s 1 ... 5 s
Thermal image can be switched on/off ✓ ✓
Phase failure sensitivity At tsd = 20 ms (M) ✓ (on/off)
Neutral conductor protection ✓ ✓
Function can be switched on/off ✓ ✓
N conductor setting range IN = In × ... 0.5 ... 1 0.2 ... 2
Short-time delayed short-circuit protection ✓ ✓
Function can be switched on/off ✓ ✓
Setting range Isd = In × ... 1.25-1.5-2-2.5-3-4-6-8-10-12 1.25 × In ... 0.8 × Icw
Setting range for delay time tsd M-100-200-300-400 ms M-80 ... 4000 ms
Switchable short-time delayed short-circuit protection ✓ ✓
(I2t-dependent function)
Setting range for delay time tsd at I2t 100-200-300-400 ms 100 ... 400 ms
Zone Selective Interlocking function By CubicleBUS-Module By CubicleBUS-Module
Instantaneous short-circuit protection ✓ ✓
Function can be switched on/off ✓ ✓
Setting range Ii = In × ... 1.5-2.2-3-4-6-8-10-12-0.8 x Ics 1.5 × In ... 0.8 × Ics
Ground-fault protection ❑ Module can be retrofitted ❑ Module can be retrofitted
Tripping and alarm function ✓ ✓
Tripping function can be switched on/off ✓ ✓
Alarm function can be switched on/off -- ✓
Detection of the ground-fault current through summation cur- ✓ ✓
rent formation with internal or external N conductor transformer
Detection of ground-fault current through external ✓ ✓
current transformer
Setting range of the operating current Ig A-B-C-D-E A ... E
for tripping
Setting range of the operating current Ig for alarm A-B-C-D-E A ... E
Setting range of the delay time tg 100-200-300-400-500 ms 100 ... 500 ms
Switchable ground-fault protection characteristic curve ✓ ✓
(I2t-dependent function)
2
Setting range for delay time tg at I t 100-200-300-400-500 ms 100 ... 500 ms
Zone Selective Interlocking ground-fault protect. function By CubicleBUS-Module By CubicleBUS-Module
Parameter set switchover
Switchable between parameter set A and B -- ✓
LCD
Alphanumeric LCD (4-line) ❑ --
Graphical LCD (24 V, external power supply required) -- ✓
Communication
CubicleBUS integrated ✓ ✓
Communication-capable through PROFIBUS DP ✓ ✓
Measurement function
Measurement-function capable with measurement function ✓ ✓
Plus
LED display
Electronic release active ✓ ✓
Alarm ✓ ✓
ETU fault ✓ ✓
L-release ✓ ✓
S-release ✓ ✓
I-release ✓ ✓
N-release ✓ ✓
G-release ✓ (only with ground-fault protection module) ✓ (only with ground-fault protection module)
G-alarm ✓ (only with ground-fault protection module) ✓ (only with ground-fault protection module)
Release through extended protection functions ✓ ✓
Communication ✓ ✓
Signals from signaling switches with external CubicleBUS modules (relays)
Overload warning ✓ ✓
Load shedding, load receiving ✓ ✓
Leading signal overload trip 200 ms ✓ ✓
Temperature alarm ✓ ✓
Phase unbalance ✓ ✓
Instantaneous short-circuit release ✓ ✓
Short-time delayed short-circuit release ✓ ✓
Overload trip ✓ ✓
Neutral conductor release ✓ ✓
Ground-fault protection release ✓ (only with ground-fault protection module) ✓ (only with ground-fault protection module)
Ground-fault alarm ✓ (only with ground-fault protection module) ✓ (only with ground-fault protection module)
Auxiliary relay ✓ ✓
ETU fault ✓ ✓
Setting range of the operating current Ig Increment size for settings for ETU76B via menu For legend see page 32.
Size I and size II Size III From ... to Increment From ... to Increment
size size
A 100 A 400 A 0 ... 1 0.1 1000 ... 1600 50
B 300 A 600 A 1 ... 100 1 1600 ... 10000 100
C 600 A 800 A 100 ... 500 5 10000 ... max 1000
D 900 A 1000 A 500 ... 1000 10
E 1200 A 1200 A

Siemens · 2012 33
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids

■ Characteristic curves2)
Every release type and every setting has its own characteristic 10000

NSE0_01527
curve. Only a selection is shown in the following. The character- R min R max
istic curves each show the largest and smallest setting range of

[s]
3WL circuit breakers with 1000 A rated current at 500 V rated 1000 0,5 ... 1,0 x n

Opening time
voltage with various releases. In order to obtain a complete trip-
ping characteristic, the relevant parts of the characteristics have 100
to be combined. The characteristic curves show the behavior of
the release when it is activated by a current that is already flow-
ing before the tripping operation. If the overcurrent tripping oc- 10
curs immediately after switch on and the release is therefore not
yet enabled, the opening time is extended, depending on the 1 i min i max
level of the overcurrent by up to 15 ms. In order to determine the 2 ... 8 x n
break-times of the circuit breakers, approximately 15 ms must
0,1
be added to the opening times shown for the arcing time.
Refer to the following legend for tolerances.
The characteristic curves shown apply to ambient temperatures 0,01
at the circuit breaker between -5 and +55 °C. The release can 0,1 1 10 100
/
be operated at ambient temperatures of -20 to +70°C. n

An extended tolerance band can apply at these temperatures. 3WL circuit breaker with ETU15B release
10000 10000
NSE0_01520

NSE0_01519
R min R max
R min R max
Opening time [s]

0,4 ... 1,0 x

Opening time [s]


1000 n 0,4 ... 1,0 x
1000 n
N

100 100

10 10

1 sd min sd max sd max


1 sd min
1,25 ... 12 x n 1,25 ... 12 x
sd max n sd max
0 ... 0,4 s sd min
0,1 0 ... 0,4 s sd min
i > 20 x n 0,1
i
i i > 20 x n
max. 50 kA max. 50 kA
0,01 0,01
0,1 1 10 100 0,1 1 10 100
/ n / n

3WL circuit breaker with ETU25B release, 3WL circuit breaker with ETU27B release,
LSI characteristic curve LSIN characteristic curve
10000
NSE0_01521

10000

NSE0_01523a
Opening time [s]

[s]

1000 1000 sd
Opening Time

1,25 ... 12 x n
100 100
2
sd = const
g min g max
10 10
100 ... 1200 A1)
1 1 2
g max sd = const
0,1 ... 0,5 s
sd = const 0,1 ... 0,4 s
0,1 g min 0,1
0,02 ... 0,4 s
0,01 0,01
100 1000 10000 100000 0,1 1 10 100
A / n

3WL circuit breaker with ETU27B release, 3WL circuit breaker with ETU45B release,
G characteristic curve S characteristic curve
Tolerances for the set currents 1) Sizes I and II: 100 ... 1200 A
L: Tripping operations between 1.05 and 1.2 x IR Size III: 400 ... 1200 A.
S: –0 %, +20 % 2)
I: –0 %, +20 % With single-pole loading in the lowest rated current range, the response
times of the short-circuit release can be extended by approx. 10 % and
G: –0 %, +20 % the tripping times by approx. 15% compared to the characteristic curve.
Tolerances for the tripping times
L: –20 %, +0 % for I2t characteristic curve
S: –0 %, +60 ms or -0 %, 10 % for tripping times greater than 600 ms
I: <50 ms
G: –0 %, +60 ms or -0 %, 10 % for tripping times greater than 600 ms

34 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Every release type and every setting has its own characteristic 10000

NSE0_01525a
curve. Only a selection is shown in the following. The character-
istic curves each show the largest and smallest setting range of

Opening time [s]


3WL circuit breakers with 1000 A rated current at 500 V rated 1000
voltage with various releases.
100
In order to obtain a complete tripping characteristic, the relevant
g
parts of the characteristics have to be combined. 2 = const
10
The characteristic curves show the behavior of the release when 100 ... 1200 A1)
it is activated by a current that is already flowing before the trip-
ping operation. If the overcurrent tripping occurs immediately af- 1
ter switch on and the release is therefore not yet enabled, the 0,1 ... 0,5 s
g
opening time is extended, depending on the level of the overcur- 0,1
rent by up to 15 ms. In order to determine the total break-times
of the circuit breakers, approximately 15 ms must be added to
the opening times shown for the arcing time. 0,01
100 1000 10000 100000
Refer to the following table for tolerances. A

The characteristic curves shown apply to ambient temperatures 3WL circuit breaker with ETU45B and ETU76B release, G characteristic
at the circuit breaker between -5 and +55 °C. The release can curve
be operated at ambient temperatures of -20 to +70°C (ETU76B
10000
with graphics display up to +55 °C). An extended

NSE0_01526a
tolerance band can apply at these temperatures.

Opening time [s]


1000
sd
10000
NSE0_01522a

R 4 = const
1,25 x n ... 0,8 x cw
100
Opening time [s]

1000 0,4 ... 1,0 x n

2 = const 10
100

2
1 sd = const
R
10
2 ... 30s for 2 sd = const
1 ... 5s for 4 0,1 ... 0,4 s
0,1 0,02 ... 4 s
1

0,01
0,1 0,1 1 10 1
/ n / cw

0,01 3WL circuit breaker with ETU76B release, S characteristic curve


0,1 1 10 100
/ n

3WL circuit breaker with ETU45B and ETU76B release, L characteristic


curve
Further characteristic curves are shown in the manual and the
10000 planning and configuring tool SIMARIS deSign, or ask your
NSE0_01524a

Siemens contact person.


Opening time [s]

1000 Tolerances for the set currents


L: Tripping operations between 1.05 and 1.2 × IR
S: –0 %, +20 %
100 I: –0 %, +20 %
G: –0 %, +20 %
10 Tolerances for the tripping times
L: –20 %, +0 % for I2t characteristic curve
S: –0 %, +60 ms or -0 %, 10 % for tripping times greater than 600 ms
1 I: <50 ms
i G: –0 %, +60 ms or -0 %, 10 % for tripping times greater than 600 ms
0,1 1,5 x n ... 0,8 x cs

0,01
0,1 1 10 1
/ n / cs

3WL circuit breaker with ETU45B and ETU76B release, I characteristic


curve
1)
Sizes I and II: 100 ... 1200 A
Size III: 400 ... 1200 A.

Siemens · 2012 35
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids

■ Dimensional drawings
Voltage transformer for 3WL air circuit breakers External current transformers for N conductor without copper
connection pieces
260
Size I, 3WL9 111-0AA21-0AA0
6 0
1 6

125
8
R 1 3 ,1

8 ,9

N S E 0 _ 0 1 3 7 5
9 6 ,8
NSE0_01103b

2 2
8 1
87 R 2 2
For mounting on

4 0
35 mm standard
mounting rail 1 8 5 1
3 6
7 0
Current transformers for overload protection in the N con- 8 3
ductor
Size II, 3WL9 111-0AA22-0AA0
External current transformers for N conductor with copper con-
nection pieces
Size I, 3WL9 111-0AA31-0AA0 R 2 7

1 1 5
1 3 1
5 4
1 5 4 1

N S E 0 _ 0 1 3 7 6
Ø 1 3 ,5

6 5 ,5
4 4

2 4

8 8 5 1
9 5
1 7 0
1 3 0
6 8

9 1
5 1

1 1 3 3

Size III, 3WL9 111-0AA23-0AA0


N S E 0 _ 0 0 6 0 6 b

5 5 9 7 1 6 1
8 3
R 1 5

1 0 7
1 2 3

N S E 0 _ 0 1 3 7 7
4 5

Size II, 3WL9 111-0AA32-0AA0


3 0 3 0 3 × 1 0
3 1
3

5 0 ,5
1 6 0 5 1
Ø 1 3 ,5 1 8 4
4 4

Door cutout for operator panel


2 4
1 3 0

1 7 0

Door cutout with edge protector


9 1
6 8
5 1

2 9 5 Inner dimensions with mounted


edge protector
N S E 0 _ 0 0 6 0 7 b

9 0 1 3 1
1 1 3
3 4 0

Size III, 3WL9 111-0AA33-0AA0

3 0 3 0 3 0 3 × 1 0 5 2
2 4 0

Ø 1 3 ,5
4 4

2 4

N S E 0 _ 0 0 1 6 4 c
1 3 0

9 1
6 8

1 7 0
5 1

Door cutout for operator panel


using the door sealing frame
Option with/without door interlocking
N S E 0 _ 0 0 6 0 8 b

3 1 4
1 6 0 1 2 3
1 8 4 3 0 0
1 2 0 4 0
Ø 5 ,5 3 )
N S E 0 _ 0 0 6 1 0 c

R 5 R 5
1 8 5
1 4 0

2 )
Ø 5 ,5
3 5 0

1 4 0

1 8 0
1 7 5

4 0 1 2 0

■ Dimensions for option with door interlocking Ø 5 ,5


6 5

1)
Mounting surface
2)
Center 3WL circuit breaker operator panel
1 1 ,5

1 2
3)
8 mounting holes for door sealing frame 1 ) 2 1 4 )
4) 4 0
3 mounting holes for door interlocking

36 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
CubicleBUS modules Breaker Data Adapter (BDA)
3WL9 111-0AT2.-0AA0 3WL9 111-0AT28-0AA0
70 86 3WL9 111-0AT33-0AA0
81,9 38
45,5 19

47,5
94

16(B

153

16(B
30

Siemens · 2012 37
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Door cutout for operator panel using protective cover IP55
Protective cover, IP55
400
NSE0_01029c

395

NSE0_01030b
4 x R5

4 x 5,5

85

340-350
72
295-300
72

435
68
70

Circuit breaker mounting level


341
Mounting surface for circuit breaker Circuit breaker
or guide frame 313 mounting level 148

17
Safety clearance from grounded parts Safety clearances from live parts
Rated operational voltage Above Lateral Rear Rated operational voltage Above Lateral Rear
auxiliary connector (each side) auxiliary connector (each side)
V/AC mm mm mm V/AC mm mm mm
Size I, fixed-mounted version Size I, fixed-mounted version
500 751) 0 0 500 150 20 20
690 751) 0 0 690 300 50 125
1000 5003) 1003) 1403)
Size I, withdrawable version,
without arc chute cover Size I, fixed-mounted version,
500 501) 0 0 with arc chute cover
690 501) 0 0 500 14 504) 14
690 14 2254) 14
Size I, withdrawable version,
with arc chute cover Size I, withdrawable version,
500 0 02) 0 without arc chute cover
690 0 02) 0 500 150 20 14
690 300 50 14
Size II, fixed-mounted version 1000 5003) 1003) 1403)
500 751) 0 0
690 751) 0 0 Size I, withdrawable version,
1000 180 0 0 with arc chute cover
Size II, withdrawable version, 500 14 100 14
690 14 100 14
without arc chute cover
500 501) 0 0 Size II, fixed-mounted version
690 501) 0 0 500 250 50 20
1000 100 0 0 690 600 100 140
1000 430 100 125
Size II, withdrawable version,
with arc chute cover Size II, withdrawable version,
500 0 02) 0 without arc chute cover
690 0 02) 0 500 250 50 14
690 600 100 30
Size III, fixed-mounted version 1000 350 100 14
500 751) 0 0
690 751) 0 0 Size II, withdrawable version,
1000 180 0 0 with arc chute cover
Size III, withdrawable version, 500 14 50 14
690 14 225 14
without arc chute cover
500 501) 0 0 Size III, fixed-mounted version
690 501) 0 0 500 75 20 20
1000 100 0 0 690 500 100 125
1000 430 100 125
Size III, withdrawable version,
with arc chute cover Size III, withdrawable version,
500 0 02) 0 without arc chute cover
690 0 02) 0 500 50 20 14
690 500 100 14
DC non-automatic air circuit breakers 1000 350 100 14
300 45 0 0
600 200 0 0 Size III, withdrawable version,
1000 150 0 0 with arc chute cover
500 14 50 14
All safety clearances above the circuit breaker refer to the upper 690 14 200 14
edge of the auxiliary connector - not to the upper edge of the arc 1)
chute! See dimensional drawings on pages 39 to 47, Parts 4) Value for plate; 0 mm for struts and grids
2)
and 5). 40 mm (size II: 70 mm) for plates, which cover the lateral openings in the
guide frame
3)
Not for switching capacity S.
4)
For switching capacity S: 100 mm.

38 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size I, up to 2000 A, fixed-mounted version, 3 and 4-pole
Standard version Optional connection variants Front connection (single),
Horizontal connection not suitable for circuit breakers with rated current 2000 A

4) 5)

35
NSE0_00611h 4 7 55 55 55 55
Æ 13,5

N S E 0 _ 0 0 6 1 2 c
275
440,5
437,5

3)

NSE00613b
421
11)

e
6
123,5

270 15
300 10

35
26
390 60 90 90 90
c 8 2

d
Front connection (double hole)
19) 1) 2) according to DIN 43673
18) Ø 13,5
9) 47 55 55 55 55

40
14)
60,5
8)

80
33,5

NSE0_00615h
a

3)

NSE00616b
421
451,5
541,5

11)
327,5
516

461,5
621

3)
6
a
275
150

5,5
f

80
76

40
14
NSE0_00614h 45 6) c 7) 60 90 90 90
82
150 106
210
230 127
Vertical connection
90 90 90 60 11) 35 NSE00619 b
35

55 Ø13,5
60

4x M8
11)
30

3)
3) 7)
7) 110 (150)
267,5

4x Ø9
NSE0_00618h
127,5

20
NSE0_00617j

113,5 7)
139 58 13,5
128,5
320 60 90 90 90
410

NSE00620 Rated a b c d e f g
circuit breaker
current
A
3) Up to 1000 10 10 10 11 451 34 541
1250 ... 2000 15 20 15 6 461 39 551

60 90 90 90
9)
——— 4-pole version Key operation (optional accessory).
1) 11)
Mounting space for removal of the arc chutes. Terminal face.
14)
2)
Arc quenching space ≤ 690 V – circuit breaker facing grounded or non- Space for electrical auxiliary circuit connections.
conductive surfaces. 18)
Circuit breaker upper edge, only 690 V (+20 %) and 1000 V circuit
3) breakers.
Rivels (4 mm wide, 5 mm deep) for supporting phase barriers in the
system. 19)
Arc quenching space, circuit breaker facing grounded or non-conduc-
4) tive surfaces, only 690 V (+20 %) and 1000 V circuit breakers.
Auxiliary connector with SIGUT screw terminals.
5)
Auxiliary connector with screwless connection method. For safety clearances to grounded parts and to live parts see
6)
Dimension to inside surface of the closed cabinet door. page 38.
7)
Fixing points for mounting the circuit breaker in the system;
4 × setting nut M8.
8)
"Secure OFF" locking device (optional accessory).

Siemens · 2012 39
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size I, up to 2000 A, withdrawable version, 3 and 4-pole
Standard version Optional connection variants Front connection (single),
Horizontal connection not suitable for circuit breakers with rated current 2000 A

320 62,5 3 5 0
270 2 6 0

NSE00622a
4) 5) 5 5 5 5 5 5 5 5
NSE0_00621j
1 3 ,5

3 5
N S E 0 _ 0 0 6 2 3 b
6
275
468,5

403
465,5

1 1 )

3 7 3
3 )

2 8 7
123,5

6 9
13 30

11
10) c 169,5
210 55
300 1 5 9 0 9 0 9 0

3 5
2 6
382,5 Front connection (double hole)
367,5 according to DIN 43673 350
327 260
19) 55 55 55 55
62,5 13,5
2)

NSE0_00625h

40

80
NSE0_00624g 18)

7) 8)
9)
12)
6
a

493

373

287
11)
518,5
620
519

327,5

3)
460

NSE0_00626h
a
275

31
150

34

69
Ø14
76

10)

40

80
40

27 220 45 10)
14
6)
42 58 c 169,5 15 90 90 90
88,5
121,5
140,5

Vertical connection
350
38

55 55 55 55 260
11) b
38
NSE0_00629h

Ø 13,5 13,5
60

11)
30
NSE00627a

267,5

287

3)
127,5

139 68
270 25 NSE0_00628h 150
69

320 10)
410 165
15 90 90 90
350 ——— 4-pole version
260 2) For guide frame without arc chute cover, arc quenching space ≤ 690 V – circuit
breaker facing grounded or non-conductive surfaces.
3) Rivels (4 mm wide, 5 mm deep) for supporting phase barriers in the system.
4) Auxiliary connector with SIGUT screw terminals.
3) 5) Auxiliary connector with screwless connection method.
6) Dimension to inside surface of the closed cabinet door.
287

7) Circuit breaker in connected position.


8) Circuit breaker in test position.
NSE0_00630h

9) Circuit breaker in disconnected position.


69

10)
Fixing holes 10 mm.
11)
10) 15 10) Terminal face.
55 18)
90 90 90 Circuit breaker upper edge, only 690 V (+20 %)and 1000 V circuit breakers.
19)
Arc quenching space, circuit breaker facing grounded or non-conductive surfaces,
only 690 V (+20 %) and 1000 V circuit breakers.

For safety clearances to grounded parts and to live parts see


Rated circuit breaker current a b c page 38.
A
Up to 1000 10 10 10 Flange connections (see following page)
1250 ... 2000 15 15 15

40 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size I, up to 2000 A, withdrawable version, 3 and 4-pole
Flange connection
350
260
55 55 55 55

NSE0_00632h
14
NSE0_00631h

M 12

33

59
287
26
282,5
3)

59
142,5

69
121
10)
15 90 90 90

3)
Rivels (4 mm wide, 5 mm deep) for supporting phase barriers in the
system.
10)
Fixing holes 10 mm.
For safety clearances to grounded parts and to live parts see
page 38.
For more connection options see previous page.

Siemens · 2012 41
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size II, up to 4000 A, fixed-mounted version, 3 and 4-pole
Standard version Optional connection variants
Horizontal connection Front connection (single)
4 7 90 90 90 90

35
NSE0_00633a
4) 5) 40 40

N S E 0 _ 0 0 6 3 4 d
275

NSE00635c
437,5

440,5
6

421
11)

e
3)

35
123,5

85 10
270 13,5

26
90 130 130 130
440
c 8 2

d
570

13) 1) 2) Front connection (double hole)


according to DIN 43673
90 90 90 90
12)

40
4 7 40 40
14)

80
N S E 0 _ 0 0 6 3 7 d
a
621

3)

NSE00638c
541,5

421
516

327,5

3)
451,5

461,5

6 11)
g
275

14
5,5
150

80
a

76

40
NSE0_00636e 45 90 130 130 130 13,5
150 6)
210 106 c 8 2
230 127

Vertical connection up to 3200 A


Ø 13,5

130 130 130 90 b


35

90 NSE00641
30

30 30
30

11)

Ø13,5 3) 3)
7) 7)
290

98

Ø9
134,5

35
NSE0_00639f

139 128 NSE00640b


460 90 130 130 130
590 113,5
11)
128,5

NSE00642 ——— 4-pole version


1)
Mounting space for removal of the arc chutes.
2)
Arc quenching space "≤ 690 V" – circuit breaker facing grounded or non-conductive
3) surfaces.
3)
Rivels (4 mm wide, 5 mm deep) for supporting phase barriers in the system.
4)
Auxiliary connector with SIGUT screw terminals.
5)
Auxiliary connector with spring-loaded connection.
6)
Dimension to inside surface of the closed cabinet door.
7)
Fixing points for mounting the circuit breaker in the system.
11)
Terminal face.
130 12) Circuit breaker upper edge, only 1000 V and 1150 V circuit breaker.
90 130 130
13) Arc quenching space, 1000 V and 1150 V circuit breaker facing grounded or non-
conductive surfaces.
14) Space for electrical auxiliary circuit connections.

Rated a b c d e f g
circuit breaker
current
A
Up to 2000 10 15 10 11 451 34 541
2500 15 15 20 6 461 39 551
3200 30 30 20 6 461 39 551
For safety clearances to grounded parts and to live parts see
page 38.
Flange connections (see following page)

42 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size II, up to 4000 A, fixed-mounted version, 3 and 4-pole
Vertical connection 4000 A
1)
30

2)
85 Nm
541,5

30
516
345,5

Ø 13,5
79,5

NSE0_01868a
100

10
4011)
20
142
200 130 200
162

1)
Mounting space for removal of the arc chutes.
2)
Arc quenching space "≤ 690 V" – circuit breaker facing grounded or non-
conductive surfaces.
11)
Terminal face.
For safety clearances to grounded parts and to live parts see
page 38.
For more connection options see previous page.

Siemens · 2012 43
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size II, up to 3200 A, withdrawable version, 3 and 4-pole
Standard version Optional connection variants
Horizontal connection Front connection (single)
5 3 0

N S E 0 _ 0 0 6 4 5 c
4) 5) 62,5 4 0 0
NSE0_00643b 9 0 9 0
9 0 9 0

NSE00644b
4 0 4 0

3 5
1 3 ,5

275
6

468,5
465,5

403
3 )
1 1 )

3 7 3

2 8 7
123,5

2 6
c

11
40 169,5

6 9
10) 270 10) 4 5 ,1
350 55

3 5
5 5 1 3 0 1 3 0 1 3 0
480
Front connection (double hole)
382,5 according to DIN 43673
5 3 0

N S E 0 _ 0 0 6 4 8 c
367,5 62,5 4 0 0

1 3 ,5
NSE0_00646f
327 13) 9 0 9 0 9 0 9 0

NSE00647b
2) 4 0 4 0

4 0
12)

8 0
7) 8)
9)
493

9
6
3 )
620

3 7 3
1 1 )

2 8 7
a

518,5
520

327,5

3)
34
460
275

1 4
a

6 9
150

8 0
Ø14 169,5
10)
76

5 5 4 5 1 3 0 1 3 0 1 3 0

4 0
31
40

27 220 45 6)
42 58
88,5
121,5
140,5

——— 4-pole version


30 30
2) For guide frame ≤ 690 V, without arc chute cover, arc quenching space facing
grounded or non-conductive surfaces.
3) Rivels (4 mm wide, 5 mm deep) for supporting phase barriers in the system.
38

Ø 13,5 4)
Auxiliary connector with SIGUT screw terminals.
5)
11) Auxiliary connector with spring-loaded connection.
6) Dimension to inside surface of the closed cabinet door.
NSE00649a

7)
3WL circuit breaker in connected position.
8)
3WL circuit breaker in test position.
9) 3WL circuit breaker in disconnected position.
10)
139 138 Fixing holes, 10 mm in diameter.
270 95 11)
Terminal face.
460 12)
590 Guide frame upper edge – only 1000 V and 1150 V AC version.
13)
Arc quenching space, 1000 V and 1150 V circuit breaker facing grounded or
non-conductive surfaces.
530
400
90 90 90 90
NSE0_00652b

3)
287
69

10) 10)
55 45 130 130 130

For safety clearances to grounded parts and to live parts see


Rated circuit breaker current a b c page 38.
A
For vertical connection and flange connection see following
Up to 2000 10 15 10
page.
2500 15 15 20
3200/4000 30 30 20

44 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size II, up to 4000 A, withdrawable version, 3 and 4-pole
Vertical connection up to 3200 A
5 3 0
11)
NSE00650a

4 0 0
38 b N S E 0 _ 0 0 6 5 1 a
30
30

3 )
290

2 8 7
100
135

6 9
157
172 5 5 4 5 1 3 0 1 3 0 1 3 0

Vertical connection 4000 A


30
100
30
315,5

NSE0_01869
109,5

4011) 4,6 10
20
177
197 55 45
200 130 200

Flange connection
NSE00653

5 3 0
4 0 0
N S E 0 _ 0 0 6 5 4 a

M 1 2 9 0 4 0
3 3
2 6

5 9

3 )
2 8 7
2 8 2 ,5

5 9
1 4 2 ,5

6 9

121
4 5 1 3 0 1 3 0 1 3 0

——— 4-pole version


3) Rivels (4 mm wide, 5 mm deep) for supporting phase barriers in the
system.
11) Terminal face.
For safety clearances to grounded parts and to live parts see
page 38.
For more connection options see previous page.

Siemens · 2012 45
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size III, up to 6300 A, fixed-mounted version, 3 and 4-pole
Standard version Optional connection variants
Horizontal connection Front connection (single)
4) 5) 47 160 160 160 160

35
NSE0_00655a 50 50
13,5

NSE00656c
3)

NSE00657c
275
437,5

440,5
6

421
451
11)

26
123,5

35
270 205 12 20 130 210 210 210

11
680 82
890

Front connection (double hole)


according to DIN 43673
13) 1) 4 7 Ø 1 3 ,5 1 6 0 1 6 0 1 6 0 1 6 0
2) 5 0 5 0 5 0 5 0

4 0
12)
14)

8 0
N S E 0 _ 0 0 6 5 9 d
30

3 )

N S E 0 _ 0 0 6 6 0 c
6
621

5 4 1

4 2 1
1 1 )
541,5
516

327,5

3)
451,5

461,5
275

1 4
3 4

8 0
5,5
150
30

76

2 0 1 3 0 2 1 0 2 1 0 2 1 0

4 0
NSE0_00658e 45 8 2
35 150 6)
210 106
230 127

Vertical connection
107 20
30

10 NSE00663
15

210 210 210


35

30 160 15 130
11)
11) 3)
Ø13,5 40
330,5

7) 3) 7)
120

M10
94,5
NSE0_00661e

85 210 210 210


139 248 40
NSE00662a

704 Ø 13,5
142
914
162

NSE00664a

3)

130 210 210 210 130

13)
——— 4-pole version Arc quenching space, 1000 V circuit breaker and circuit breaker with
1) switching capacity C, facing grounded or non-conductive surfaces.
Mounting space for removal of the arc chutes.
14) Space for electrical auxiliary circuit connections.
2)
Arc quenching space "≤ 690 V" – circuit breaker facing grounded or
non-conductive surfaces. For safety clearances to grounded parts and to live parts see
3)
Rivels (4 mm wide, 5 mm deep) for supporting phase barriers in the page 38.
system.
4)
Auxiliary connector with SIGUT screw terminals.
5)
Auxiliary connector with spring-loaded connection.
6)
Dimension to inside surface of the closed cabinet door.
7)
Fixing points for mounting the circuit breaker in the system.
11)
Terminal face.
12)
Circuit breaker upper edge, only 1000 V circuit breaker and circuit
breaker with switching capacity C.

46 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size III, up to 6300 A, withdrawable version, 3 and 4-pole
Standard version Optional connection variants
Horizontal connection up to 5000 A Front connection (single hole),
up to 4000 A 8 4 0

N S E 0 _ 0 0 6 6 7 c
6 3 0
4) 5) 62,5 1 6 0 1 6 0 1 6 0 1 6 0

1 3 ,5
NSE0_00665b

NSE00666b
5 0 5 0

3 5
275
465,5

468,5
6

403
1 1 )

2 8 7
3 7 3
123,5

10) 270 160


10) 10)

6 9
590
800 57 20

11
8 5 2 1 0 2 1 0 2 1 0

3 5
169,5 5 9 0

2 6
5 7 8 0 0
Front connection (double hole)
382,5 according to DIN 43673, 8 4 0

N S E 0 _ 0 0 6 7 0 c
367,5 up to 4000 A 6 3 0

1 3 ,5
NSE0_00668d
327 13) 62,5 1 6 0 1 6 0 1 6 0 1 6 0
2)

4 0
5 0 5 0

NSE00669b
12)

8 0
7) 8)
9)
9
30

493

6
1 1 )

2 8 7
3 7 3
620

518,5
520

327,5

3)
460

30

1 4
275

6 9
8 0
150

Ø14
10) 20
76

8 5 2 1 0 2 1 0 2 1 0
4 0
34

169,5 5 9 0
5 7 8 0 0
31
40

27 220 45 6)
42 58
88,5
121,5
140,5
Vertical connection, up to 6300 A
30 8 4 0
NSE00672a

30 30 Ø 13,5 38 6 3 0
11) 7 0 4
2 0
30

1 0
38

N S E 0 _ 0 0 6 7 3 b

11)
330,5
NSE00671a

124,5

2 8 7
94,5

139 260 24
270 217 177
6 9

704 Ø 13,5 197


914 a b b 2 1 0
5 7 5 9 0
8 0 0
9 1 4

——— 4-pole version


840 2)
For guide frame ≤ 690 V, without arc chute cover, arc quenching space facing
630
160 160 160 160
grounded or non-conductive surfaces.
3)
Rivels (4 mm wide, 5 mm deep) for supporting phase barriers in the system.
NSE0_00674a

4)
Auxiliary connector with SIGUT screw terminals.
5)
Auxiliary connector with spring-loaded connection.
6)
Dimension to inside surface of the closed cabinet door.
287

7)
3WL circuit breaker in connected position.
8)
3WL circuit breaker in test position.
9)
3WL circuit breaker in disconnected position.
10)
69

Fixing holes, 10 mm in diameter.


11)
57 85 210 210 210 Terminal face.
12)
Guide frame upper edge – only 1000 V and 150/130 kA guide frame.
13)
Arc quenching space, 1000 V circuit breaker and circuit breaker with switching
capacity C, facing grounded or non-conductive surfaces.
For safety clearances to grounded parts and to live parts see
Rated circuit breaker current a b page 38.
A
Flange connections (see following page)
4000 40 210
5000 40 210
6300 5 245

Siemens · 2012 47
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size III, up to 6300 A, withdrawable version, 3 and 4-pole
Flange connection, up to 4000 A
8 4 0
NSE00675

6 3 0
7 0 4

N S E 0 _ 0 0 6 7 6 a
1 6 0 1 6 0 1 6 0 1 6 0

1 2
3 3
M

5 9
2 8 7
2 6
2 8 2 ,5

5 9
1 4 2 ,5
5

6 9
3 0
121 5 7 8 5 2 1 0 2 1 0 2 1 0
5 9 0
8 0 0
9 1 4

For safety clearances to grounded parts and to live parts see


page 38.
For more connection options see previous page.

48 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids

■ Circuit diagrams
Terminal assignment diagram

optional Internal wiring Terminals External wiring


Accessories
(Auxiliary switch S1, S2 = Standard) L+
c
L–

e.g. current transformer in the


14 star point of power transformer
Remote reset bell alarm & tripped indicator F7 or a summation current
13 transformer 1200 A /1A
G transformer S2 12
G transformer S1 11
N sensor S2 10
Short terminals if no N-sensor
N sensor S1 9
ext. voltage transformer Com 8 N
ext. voltage transformer L3 7 L3
ext. voltage transformer L2 6 L2
ext. voltage transformer L1 5 L1
0 V DC 4
24 V DC input
24 V DC 3
BUS + 2 Termination resistor,
BUS 1 if not external CB-module!
Not available with communication connection "F02" or “F12”.

14

F1, 2
– + OUT
Trip signalling switch S24 13 /COM16

1 2 3 4 5 6 7 8 9
Open
(position after tripping) 12 (Option F02/F12)

Y1
COM15/COM16 module is at position "-X7".

11
Close
– +

"Spring charged" signal S21 10


Local electric close S10 9 L+ c
Free
– +

8
DPWrite Free

7
Enable

6
5
Signaling contact at the 1 st auxiliary release
External
Internal
IN

4
3
S23 2
Signaling contact at the 2nd auxiliary release
1

14 L+
1st auxiliary release F1 "ST" c
13 L–
12
S1 "NO"
11
10
S1 "NC"
9
Closing solenoid 8 L–
c
7 L+
6
5
"Ready to close" signal S20
4
S2 "NO"
3
2
S2 "NC"
1

F4 only "quick OFF" 14


EMERGENCY STOP
F4 only "quick OFF" 13 or short terminals
12 L+
2nd auxiliary release: F2 "ST", F3 "UVR", F4 "UVR td" c
11 L–
10
S3 "NO" or S7 "NO"
9
8
S3 "NC" or S7 "NO"
7
6
S4 "NO" or S8 "NO"
5
4
S4 "NC" or S8 "NO"
3
NSE0_00605p

(sw) (br)
Charging motor M 2 L+
c
opt. motor main switch S12 1 L–

Siemens · 2012 49
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Example of an overall circuit diagram for 3WL circuit breaker
(3WL1. ..–.....–4GN4–Z C11+ C22 + K07) signaling switch (optionC22), with LSING release, with "UVR" un-
dervoltage release (F3), with "ST" shunt release (F1), with tripped
Manual/motorized operating mechanism with stored-energy fea- signaling switch (option K07), with auxiliary switch 4 NO + 4 NC.
ture with electrical ON button (option C11), with ready-to-close

L1 L1
(L+) release (L+)
OFF
contact
ON

-X5.10
-X7.14
-X7.12

-X6.10
-X5.12
-X6.14

-X6.12

-X6.2
-X6.6

-X5.8

-X5.4
-X6.4
-X5.2

-X5.6
-X6.7
-X7.9

5
1
3
-A1 ETU
version L
-S10

S
electr. I
ON
N N
G
R
-S11 -F5
-S20

-S24

-Q1 -S1 -S2 -S3 -S4


QS P
-T1
M -F3 U<

-Y1 -T2
mech.
ON
-T3

NSE0_01558b
mech. -S12
-F1
OFF

-X5.9
6
2
4

-X6.1

-X5.7

-X5.3
-X6.9
-X6.13

-X6.3

-X5.5
-X6.11
-X7.13
-X5.11

-X8.9
-X5.1

-X8.10
-X6.8

-X6.5

N N
(L-) (L-)
* Short terminals, if no N sensor

Function diagram of -A1 ETU release


3WL circuit breaker -S1/-S2 1st auxiliary switch block (2 NO + 2 NC)
-S3/-S4 2nd auxiliary switch block (2 NO + 2 NC)
-S7 (optional) 2nd auxiliary switch block, S7 (2 NO) can be used
if there is no S3 - S3 and S7 have
F1 the same terminal assignment/mounting space
-S8 (optional) 2nd auxiliary switch block, S8 (2 NO) can be used
F2 if there is no S4 - S4 and S8 have
the same terminal assignment/mounting space
S20 F3
3WL1. ..-.....-...2 (2 NO + 2 NC) S1+S2
3WL1. ..-.....-...4 (4 NO + 4 NC) S1+S2+S3+S4
F4
3WL1. ..-.....-...7 (6 NO+ 2 NC) S1+S2+S7+S8
M1 3WL1. ..-.....-...8 (5 NO + 3 NC) S1+S2+S3+S8
Q1 S1 & S2
P -S10 Electrical ON button
S3 & S4 -S11 Internal motor shutdown switch (if spring is tensioned)
-S12 Motor shutdown switch
1 (no automatic tensioning of spring)
F5 -S20 Ready-to-close signaling switch
S24 -S24 Tripped signaling switch
Y1
-F1 1st auxiliary release shunt release
2 A1 -F3 2nd auxiliary release undervoltage release
T1 -F5 Tripping solenoid
L
T2 S -M Motor for "charging store"
-P Stored-energy mechanism
T3 I -QS Actuator lever for "stored-energy feature"
N N -Q1 Main contacts
T4 G -T1/-T2/-T3 Current transformers
-X5/-X6/-X7/-X8 Terminals
3 -Y1 Closing solenoid
NSE0_01559c
-R Indicator and reset button for release

-X8.9/-X8.10 Connection option: external neutral conductor trans-


former

50 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Example of the mode of operation of Zone Selective
Interlocking functionality in power distribution

SENTRON 3WL SENTRON 3WL SENTRON 3WL


3 3 3
module

module

module
4 4 4
ZSI

ZSI

ZSI
5 5 5
6 6 6 SENTRON 3WL SENTRON 3WL
3 3

module

module
5
6
1
2
3
4
4 4

ZSI

ZSI
5 ZSI module 5
SENTRON 3WL SENTRON 3WL 6 6
3 3
module

module

4 4
ZSI

ZSI

5 5 NSE0_01898
6 6
SENTRON 3WL
SENTRON 3VL SENTRON 3WL
Circuit diagram for a Zone Selective Interlocking functionality with multi-
3 ple infeed and several outgoing units with 3WL circuit breakers
module

4
ZSI

NSE0_01897
5
6

3VL and 3WL circuit breakers used in various staggered levels

SENTRON 3WL SENTRON 3WL


3 3
module

module
5
6
1
2
3
4
4 4
ZSI

ZSI
5 ZSI module 5
6 6

NSE0_01899

SENTRON 3WL

SENTRON 3WL SENTRON 3WL


3 3
module

module
4 4
ZSI

ZSI
5 5
6 6

Zone Selective Interlocking functionality: Connection using a coupling


switch, use of 3WL circuit breakers

■ More information
Up-to-date information on the Internet at:
www.siemens.com/sentron

Siemens · 2012 51
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
General data

■ Technical specifications
Sizes II
Type 3WL12 10 3WL12 20 3WL12 40
Rated current In at 40 °C
Main conductors A ... 1000 2000 4000
Rated operational voltage Ue V DC ... 600/1000 ... 600/1000 ... 600/1000
(1000 V version, see Catalog LV 10.1, order code "A05")
Rated insulation voltage Ui V DC 1000 1000 1000
Rated impulse withstand voltage Uimp
• Main current paths kV 12 12 12
• Auxiliary circuits kV 4 4 4
• Control circuits kV 2,5 2,5 2,5
Isolating function to EN 60947-2 Yes Yes Yes
Permissible ambient temperature
• Operation °C –25/+70 –25/+70 –25/+70
• Storage °C –40/+70 –40/+70 –40/+70
Permissible load up to 40 °C A 1000 2000 4000
at rear horizontal main circuit up to 55 °C A 1000 2000 3640
connections up to 60 °C A 1000 2000 3500
(Cu painted black) up to 70 °C A 1000 1950 3250
Power loss at In for symmetrical loads
Withdrawable circuit breakers W 280 770 1640
Switching times
• Make-time ms 35 35 35
• Opening time ms 34 34 34
• Electrical make-time (through activation solenoid)1) ms 100 100 100
• Electrical opening time (through shunt release) ms 73 73 73
• Electrical opening time (instantaneous undervoltage release) ms 73 73 73
Endurance3)
• Mechanical (without maintenance) Operating cycles 10000 10000 10000
• Mechanical (with maintenance)2) Operating cycles 15000 15000 15000
• Electrical (without maintenance) Operating cycles 6000 6000 4000
• 1000 V version Operating cycles 1000 1000 1000
• Electrical (with maintenance)2) Operating cycles 15000 15000 15000
Switching frequency
• 600 V version 1/h 60 60 60
• 1000 V version 1/h 20 20 20

h m a x .
Mounting position 3 0 ° 3 0 ° 3 0 ° 3 0 °

= 1 m m
and/
or
N S E 0 _ 0 0 0 6 1 a N S E 0 _ 0 0 0 6 2 a N S E 0 _ 0 0 9 2 7 a

Degree of protection IP20 without cabinet door, IP41 with door sealing
frame, IP55 with cover
Auxiliary conductors (Cu) Standard connection = strain-relief clamp
Max. number of • Without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14)
auxiliary conductors × cross- • With end sleeve acc. to DIN 46228 Part 2 1 × 0.5 mm2 (AWG 20) ... 1 × 1.5 mm2 (AWG 16)
section • With twin end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
(solid/stranded)
Optional connection = tension spring
• Without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 2.5 mm2 (AWG 14)
• With end sleeve acc. to DIN 46228 Part 2 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
Weights 3-pole • Fixed-mounted circuit breakers kg 56 56 64
• Withdrawable circuit breakers kg 60 60 68
• Guide frames kg 31 31 45
4-pole • Fixed-mounted circuit breakers kg 67 67 77
• Withdrawable circuit breakers kg 72 72 82
• Guide frames kg 37 37 54
1) Make-time through activation solenoid for synchronization purposes 2) Maintenance means: replace main contact elements and arc chutes
(short-time excited) 50 ms. (see Operating Manual).
3) Further technical specifications on request.

Sizes II
Type 3WL12
Switching capacity class DC
Short-circuit breaking capacity
Up to 220 V DC Icc kA 35
Up to 300 V DC Icc kA 30
Up to 600 V DC Icc kA 25
Up to 1000 V DC Icc kA 20
Rated short-time withstand current Icw
0.5 s kA --
1s kA 351)/302)/253)/204)
2s kA --
3s kA --
1) 3)
At Ue = 220 V DC. At Ue = 600 V DC.
2) 4)
At Ue = 300 V DC. At Ue = 1000 V DC.

52 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Project planning aids

■ Characteristic curves
10000
R= 0.4 ... 1.0 n
R= 2 ... 10 s at 6 R
[s]

1000 R = 0.4 n R = 1.0 n I = 1.25 R ... 4 n

R= 10 s [B]
100 B
2 s [A]
B
A
A
10

1
MIN MAX
I= 1.5
I=1.25 I=
4 n
R
R

NSE0_01578
0,1

0,01
0,1 1 10
/ n

DIGmat S100 characteristic curve

■ Dimensional drawings
DIGmat S100

257
DIG S100 3,5
250
AUTO
ON
_
136

R2 + MENUE
NSE0_01576

R1
115
122

NSE0_01575
AUTO MAIN
MAN PEAK DIAG

271

DIGmat S100 DIGmat S100 drilling pattern

Siemens · 2012 53
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Project planning aids
Size II, up to 4000 A, fixed-mounted version, 3 and 4-pole
Standard version Optional connection variants
Horizontal connection Front connection (single)
4 7 90 90 90 90

35
NSE0_00633a
4) 5) 40 40

N S E 0 _ 0 0 6 3 4 d
275

NSE00635c
437,5

440,5
6

421
11)

e
3)

35
123,5

85 10
270 13,5

26
90 130 130 130
440
c 8 2

d
570
Front connection (double hole)
16) 17) 1) 2) according to DIN 43673
12) 90 90 90 90

40
15) 4 7 40 40
14)

80
N S E 0 _ 0 0 6 3 7 d
a
602

3)

NSE00638c
541,5

421
516

327,5

3)
451,5

461,5

11)
447

6
g
275

14
5,5
150

80
a

76

40
NSE0_02003 45 90 130 130 130 13,5
150 6)
210 106 c 8 2
230 127

Vertical connection
Ø 13,5

130 130 130 90 b


35

90 NSE00641
30

30 30
30

11)

Ø13,5 3) 3)
7) 7)
290

98

Ø9
134,5

35
NSE0_00639f

139 128 NSE00640b


460 90 130 130 130
590 113,5
11)
128,5
——— 4-pole version
NSE00642
1) Mounting space for removal of the arc chutes.
2)
Arc quenching space "≤ 690 V" – circuit breaker facing grounded or non-conductive
surfaces.
3) 3)
Rivels (4 mm wide, 5 mm deep) for supporting phase barriers in the system.
4) Auxiliary connector with SIGUT screw terminals.
5)
Auxiliary connector with spring-loaded connection.
6)
Dimension to inside surface of the closed cabinet door.
7) Fixing points for mounting the circuit breaker in the system.
11)
Terminal face.
12)
Circuit breaker upper edge, only 1000 V circuit breaker.
14)
90 130 130 130 Space for electrical auxiliary circuit connections.
15)
Arc quenching space, 300 V circuit breaker facing grounded or non-conductive sur-
faces.
16) Arc quenching space, 600 V circuit breaker facing grounded or non-conductive sur-
faces.
17)
Arc quenching space, 1000 V circuit breaker (with high arc chute) facing grounded or
non-conductive surfaces.
For safety clearances to grounded parts and to live parts see
Rated a b c d e f g page 38.
circuit breaker
current
A
Up to 2000 10 15 10 11 451 34 541
4000 30 30 20 6 461 39 551

54 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Project planning aids
Size II, up to 4000 A, draw-out technology, 3 and 4-pole
Standard version Optional connection variants
Horizontal connection Front connection (single)
5 3 0

N S E 0 _ 0 0 6 4 5 c
4) 5) 62,5 4 0 0
NSE0_00643b 9 0 9 0
9 0 9 0

NSE00644b
4 0 4 0

3 5
1 3 ,5

275 6
468,5
465,5

403
3 )
1 1 )

3 7 3

2 8 7
123,5

2 6
c

11
40 169,5

6 9
10) 270 10) 4 5 ,1
350 55

3 5
5 5 1 3 0 1 3 0 1 3 0
480
Front connection (double hole)
382,5 according to DIN 43673
5 3 0

N S E 0 _ 0 0 6 4 8 c
367,5 62,5 4 0 0

1 3 ,5
327 16) 17) 9 0 9 0 9 0 9 0

NSE00647b
NSE0_02084 2) 4 0
4 0

4 0
15)

8 0
12)
7) 8)
493

6
9) 3 )
9

3 7 3
1 1 )

2 8 7
651

34
518,5
a
520

327,5
496

3)
460

1 4
c

6 9
275

8 0
a

169,5
150

Ø14
5 5 4 5 1 3 0 1 3 0 1 3 0
4 0
10)
76
31
40

27 220 45 6)
42 58
88,5
121,5
140,5
——— 4-pole version
30 30
2)
For guide frame ≤ 690 V, without arc chute cover, arc quenching space facing
grounded or non-conductive surfaces.
3)
Rivels (4 mm wide, 5 mm deep) for supporting phase barriers in the system.
38

4) Auxiliary connector with SIGUT screw terminals.


Ø 13,5
5)
11) Auxiliary connector with spring-loaded connection.
6)
Dimension to inside surface of the closed cabinet door.
NSE00649a

7)
3WL circuit breaker in connected position.
8)
3WL circuit breaker in test position.
9)
3WL circuit breaker in disconnected position.
139 138 10)
Fixing holes, 10 mm in diameter.
270 95 11)
460 Terminal face.
590 12)
Guide frame upper edge – only 1000 V AC version.
15)
Arc quenching space, 300 V circuit breaker facing grounded or non-conductive
530 surfaces.
400 16)
90 90 90 90 Arc quenching space, 600 V circuit breaker facing grounded or non-conductive
surfaces.
NSE0_00652b

17)
Arc quenching space, 1000 V circuit breaker (with high arc chute) facing grounded or
non-conductive surfaces.

3)
287
69

10) 10)
55 45 130 130 130

For safety clearances to grounded parts and to live parts see


Rated circuit breaker current a b c page 38.
A
For vertical connection and flange connection see following page.
Up to 2000 10 10 10
4000 30 30 20

Siemens · 2012 55
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Project planning aids
Size II, up to 4000 A, draw-out technology, 3 and 4-pole
Vertical connection
5 3 0
11) 4 0 0
NSE00650a

38 b N S E 0 _ 0 0 6 5 1 a
30
30

3 )

2 8 7
290

100
135

6 9
157 5 5 4 5 1 3 0 1 3 0 1 3 0
172

Flange connection
NSE00653

5 3 0
4 0 0

N S E 0 _ 0 0 6 5 4 a
M 1 2 9 0 4 0
3 3
2 6

5 9
3 )
2 8 7
2 8 2 ,5

5 9
1 4 2 ,5

6 9

121
4 5 1 3 0 1 3 0 1 3 0

——— 4-pole version


3)
Rivels (4 mm wide, 5 mm deep) for supporting phase barriers in the
system.
11) Terminal face.
For safety clearances to grounded parts and to live parts see
page 38.
For more connection options see previous page.

56 Siemens · 2012
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Project planning aids

■ Circuit diagrams
L1
AC230
+
N
PE -
DC24
AC230

X1.2 X1.1 X5.2 X5.1


DIGmat S100
Auxiliary power
„Emergency STOP”
+ X4.i1+ X2.1 +
+
Shunt
- X4.i1- (60mV)
DC24 Digital input -
X2.3 -
X4.i2+
X4.i2-
„Automatic RESET”
Digital output
X4.01 X4.01 X4.02 X4.02 X4.03 X4.03 X4.04 X4.04

+ - + - + - + -

12
14
-K1 11 -Q01 1 3 5
Excitation / Alarm

Automatic / Reset

-X6.14 -X5.12
12 14
SENTRON
3WL
-K2 11 -F1 -F3
NSE0_01577a

-X6.13 -X5.11
-Q01 2 4 6

Circuit diagram of the DIGmat S100 and the 3WL non-automatic air circuit
breaker
Application examples
Rated operational Required, For 3-pole non-automatic air circuit For 4-pole non-automatic air circuit breakers
voltage series-connected breakers (operational currents up to 4000 A/conducting path)
breaks at (operational currents up to 4000 A/conduct-
rated voltage ing path)
Up to 300 V + 10 %

1-pole, 2-pole 1-pole, 2-pole


2 parallel conducting 3 parallel conducting paths, 2 parallel conducting
paths, only with grounded-neutral paths
only with grounded- system
neutral system
Over 300 V + 10 %
Up to 600 V + 10 %

2-pole, 1-pole, 2-pole


only with grounded- 2 parallel conducting paths,
neutral system only with grounded-neutral
system
Over 600 V + 10 %
Up to 1000 V + 10 %
(version for 1000 V
required, order with "-Z"
and order code A05)
1-pole, 2-pole, 1-pole,
only with grounded- only with grounded-neutral only with grounded-
neutral system system neutral system

The connection to the circuit breakers is not dependent on direc- current. If the parallel or series connection is made at a distance
tion and polarity; the circuit diagrams can be adapted accord- of 1 m from the connecting bars, the circuit breaker can be used
ingly. at full operational current load.
If the parallel or series connections are made directly at the
connecting bars, for thermal reasons the continuous load on the
] Grounded-neutral system

circuit breakers must only be 80 % of the permissible operational ‡ Load

Siemens · 2012 57
© Siemens AG 2011

3WL Air Circuit Breakers


3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Project planning aids

■ More information
Up-to-date information on the Internet at:
www.siemens.com/sentron

58 Siemens · 2012
© Siemens AG 2011
© Siemens AG 2011

The information provided in this Configuration Manual contains


descriptions or characteristics of performance which in case of actual
Siemens AG Subject to change without prior notice
use do not always apply as described or which may change as a result
Infrastructure & Cities Sector PDF only of further development of the products. An obligation to provide
Low and Medium Voltage Division MP.R3.LV.0000.00.2.92 the respective characteristics shall only exist if expressly agreed in the
Low Voltage Distribution PH 1111 58 En terms of contract. Availability and technical specifications are subject to