SENTRON
Answers for infrastructure.
© Siemens AG 2011
© Siemens AG 2011
2 Introduction
© Siemens AG 2011
All dimensions in mm.
Siemens · 2012
© Siemens AG 2011
Introduction
■ Overview
Degree of protection
With cover IP55 IP55
Without cover IP41 IP41
(with door sealing frame)
Dimensions 3-/4-pole W mm 320/410 460/590 704/914 460/590
W D Fixed H mm 434 434 434 434
mounting D mm 291 291 291 291
H
NSE0_01111a
Rating Plug
2 Siemens · 2012
© Siemens AG 2011
Introduction
Switching capacity
Sizes I II III
Type 3WL11 3WL12 3WL13
Switching capacity class N S H N S H H C C
N S H N S H H 3-pole C 4-pole C
Sizes II
DC
Type 3WL12
Switching capacity class DC
Short-circuit breaking capacity
Up to 220 V DC Icc kA 35
Up to 300 V DC Icc kA 30
Up to 600 V DC Icc kA 25
Up to 1000 V DC Icc kA 20
Rated short-time withstand current Icw
0.5 s kA --
1s kA 355)/306)/257)/208)
2s kA --
3s kA --
S
Circuit breaker with standard switching capacity S L = Long Time Delay = Overload protection
S = Short Time Delay = Short-circuit protection
H
Circuit breaker with high switching capacity H (short-time delayed)
I = Instantaneous = Short-circuit protection
C
Circuit breakers with very high switching capacity C (instantaneous)
N = Neutral Protection Neutral conductor protec-
DC
Non-automatic air circuit breakers with DC switching tion
capacity G = Ground Fault Ground-fault protection
These switching capacities are indicated in the corre-
sponding tables by the symbols shown on orange back-
grounds. L, S, I, N, G: Designation according to IEC 60947-2, Appendix K.
6)
1) Size II with In max ≤ 2500 A. At Ue = 300 V DC.
2) 7) At Ue = 600 V DC.
Size II with In max = 3200 A and In max = 4000 A.
8)
3) At a rated voltage of ≥ 690 V the Icw value of the circuit breaker cannot be At Ue = 1000 V DC.
greater than the Icu or Ics value at 690 V. 9)
Values also apply to version 690 V + 20 % with Z option "A16".
4) Rated operational voltage Ue = 1150 V.
5) At Ue = 220 V DC.
Siemens · 2012 3
© Siemens AG 2011
Introduction
3WL air circuit breakers:
Superior individual products integrated into uniform power dis-
tribution systems - up to and including industry-specific indus-
trial and infrastructure solutions
7
2
3 8
5
4
9
1
25
21
10
19
22 11
23
12
24 18 13
17
14
NSE0_01887c
20
16
15
4 Siemens · 2012
© Siemens AG 2011
Introduction
Communication-capable circuit breakers (with ETU45B or ETU76B electronic release)
18
Ethernet
16
17
PROFIBUS
4 4 19 11 12 13 14 15 5
ab Release 2
CubicleBUS
7
8 6
1 1
9
10
NSE0_01105k
2 3
Features
• Coordinated communication concept using the Communication:
PROFIBUS DP or MODBUS, ranging from 16 A to 6300 A with • For air circuit breakers with optional communication function
3VL compact circuit breakers and 3WL air circuit breakers (ETU45B or ETU76B electronic release)
• The high level of modularity of circuit breakers and accesso- see Catalog LV 10.1.
ries allows easy retrofitting of all communication components • For accessories see Catalog LV 10.1.
• Significant additional benefits for the switchboard due to the • For more information see also Catalog LV 10.1, chapter "Mea-
possibility of linking up external input and output modules to suring Devices and energy management" and "Software".
the circuit breaker-internal CubicleBUS of the 3WL air circuit
breaker
• Innovative software products for parameterization, operation,
monitoring, and diagnostics of circuit breakers, both locally or
via PROFIBUS DP, MODBUS or Ethernet/Intranet/Internet
• Complete integration of the circuit breakers into the Totally
Integrated Power and Totally Integrated Automation solutions
Siemens · 2012 5
© Siemens AG 2011
■ Design
Circuit breaker Breaking capacity Dimensions
rated current n max (A) With-
cu at 500 V AC (kA) or Fixed-mounted, drawable
cc at 300 V DC (kA) 3- /4-pole 3- /4-pole
4000
2500
2000
Size II
1250 30 66 80 100
800
1250
Size I
800
55 66 85
630
291 / 291 385 / 385 Depth
The dimension for the depth of the circuit breaker is from the circuit breaker rear to the inner surface of the closed switchgear door. NSE0_00887p
6 Siemens · 2012
© Siemens AG 2011
N S E 0 _ 0 0 9 6 9 b
N S E 0 _ 0 0 9 7 9 a
N S E 0 _ 0 0 9 6 7 b
N S E 0 _ 0 0 9 7 3 b
N S E 0 _ 0 0 9 7 2 b
Standard versions
Horizontal Front connection with single Vertical Flange 3WL circuit breakers are equipped with the following features as
connection hole or double hole connection connection standard:
• Mechanical ON pushbutton and mechanical OFF pushbutton
Main circuit connections – connection types
• Manual operating mechanism with mechanical closing
Main circuit connections
• Switch position indication
All circuit breakers are equipped with horizontal main circuit • Ready-to-close indicator
connections on the rear for up to 5000 A as standard (horizontal
connection to busbars). Exception: Circuit breakers of size II • Memory status indicator
with max. rated current 4000 A. • Auxiliary switch 2 NO + 2 NC
Circuit breaker with a maximum rated current of 6300 A and • Rear horizontal main connectors for fixed mounting and for
circuit breaker of the size II with a maximum rated current of withdrawable version up to 5000 A, and rear vertical main con-
4000 A are equipped with vertical main connections (for upright nections at 6300 A and size II with 4000 A
busbars).
• For 4-pole circuit breakers, the fourth pole (N) is installed on
The following options are available, with all combinations of the left and is 100 % loadable with the rated current
top and bottom connections possible: • Contact erosion indicator for the main contacts
• Accessible from the front, single hole (for vertically installed
busbars) • Auxiliary circuit plug-in system with SIGUT screw terminals
• Accessible from the front, double hole (holes according to Delivery inclusive of all auxiliary circuit connectors to internal
DIN 43673) (for vertically installed busbars) features including coding device for the prevention of incor-
• At the rear, vertical (for vertically installed busbars) rect installation of auxiliary supply connectors for fixed-
• Connecting flange (for direct connection to guide frame up to mounted circuit breakers
4000 A). • Mechanical "tripped" indicator for electronic release system
• Mechanical reclosing lockout after tripping operation
Connection using Screwless
N S E 0 _ 0 0 9 7 6 b
Siemens · 2012 7
© Siemens AG 2011
8 Siemens · 2012
© Siemens AG 2011
Guide frames
(1 2 )
(9 )
(1 1 )
(1 0 ) N S E 0 _ 0 0 9 6 6 b
Siemens · 2012 9
© Siemens AG 2011
If the circuit breaker is replaced, closing is no longer prevented The interlocking set contains covering caps which can be
unless the new circuit breaker is also protected against unau- sealed.
thorized closing. Sealing device for electronic releases
To activate the locking device, the circuit breaker must be The transparent cover can be sealed. The parameter setting
opened. The locking device is disabled when the circuit breaker ranges are covered to prevent unauthorized access. Openings
is closed. The lock is only activated when the key is removed. allow access to the query and test button.
The safety key can be removed only in the "OFF" position.
Locking mechanisms
Locking device for "Electrical ON"
(see graphic "Circuit breakers") Locking device against movement for withdrawable circuit
breakers when the control cabinet door is open
This prevents unauthorized electrical closing from the operator
panel. Mechanical closing and remote closing remain possible. The crank handle is blocked when the control cabinet door is
The lock is only activated when the key is removed. open and cannot be removed. The withdrawable circuit breaker
cannot be moved. The lock only affects the inserted crank han-
Locking device for "Mechanical ON" dle.
(see graphic "Circuit breakers")
Interlocking of the control cabinet door
This prevents unauthorized mechanical closing. The mechanical
ON button can only be activated if the key is inserted (key oper- The control cabinet door cannot be opened if
ation). Closing with the "Electrical ON" button and remote closing • The fixed-mounted circuit breaker is closed (the blocking sig-
remain possible. The lock is only activated when the key is re- nal is transmitted via the Bowden wire) or
moved. • The withdrawable circuit breaker is in the connected position.
"Secure OFF" circuit breaker-independent locking device Blocking mechanism using "Mechanical ON" and "OFF" buttons
against unauthorized closing
The "Mechanical ON" and "OFF" buttons are covered with a cap
This special switch-independent function for withdrawable cir- which only allows actuation with a tool. These covering caps are
cuit breakers prevents closing and fulfills the specifications for part of the interlocking set.
main switches to EN 60204 (VDE 0113) – disconnector unit. Un-
authorized closing remains impossible even after the circuit Accessories for guide frames
breaker has been exchanged.
Shutters
To activate the lock, the circuit breaker must be opened. The
locking device is disabled when the circuit breaker is closed. The sealing strips of the shutter seal the laminated contacts of
The lock is only activated when the key is removed. The safety the guide frame when the withdrawable circuit breaker is re-
key can be removed only in the "OFF" position. moved and therefore implement touch protection.
Locking device for crank handle The sealing strips can be manually opened using the strip le-
vers.
Prevents removal of the crank. The circuit breaker is protected
against movement. The lock is only activated when the key is re- The position of the sealing strips can be locked in various posi-
moved. tions using padlocks for securing against tampering.
10 Siemens · 2012
© Siemens AG 2011
N S E 0 _ 0 1 0 3 2 a
switches. These can be used to determine the position of the cir-
cuit breaker in the guide frame.
(1 )
Two versions are available:
(4 ) • Option 1
Connected position 1 CO contact,
(2 )
Test position 1 CO contact,
Disconnected position 1 CO contact;
(3 ) (5 )
• Option 2
(1) Guide frame, interior of l/h side; interior of r/h side similar Connected position 3 CO contacts,
(2) Coding pin on racking rail in guide frame Test position 2 CO contacts,
(3) Racking rail
Disconnected position 1 CO contact.
(4) Withdrawable circuit breaker, r/h side; l/h side similar
(5) Coding pin on guide frame
Rated current coding unit between circuit breaker and guide frame
(4 )
DISCON
N S E 0 _ 0 1 0 3 3 a
NSE01037
DISCON
N S E 0 _ 0 1 0 3 4 a
NSE01038
TEST
DISCON
N S E 0 _ 0 1 0 3 5 a
NSE01039
TEST
DISCON
N S E 0 0 1 0 3 6 a NSE01040
(1) Auxiliary circuit (2) Main circuit (3) Control cabinet door (4) Shutter
Siemens · 2012 11
© Siemens AG 2011
■ Function
NSE0_00882b
NSE0_00881b
NSE0_00880b
R
R R
s d
s d
t
i t s d
s d
g
t g
N S E 0 _ 0 0 9 5 0 c N S E 0 _ 0 0 9 5 1 b N S E 0 _ 0 0 9 5 2 b
Additional functions
N-conductor protection can be switched on/off -- -- ✔
N-conductor protection adjustable -- -- --
Short-time delayed short-circuit protection can be switched on/off -- -- --
Instantaneous short-circuit protection can be switched on/off -- -- --
Thermal image can be switched on/off -- -- --
Load monitoring -- -- --
Short-time delayed short-circuit protection switchable to I2t -- -- --
Instantaneous short-circuit protection adjustable ✔ -- --
Overload protection switchable to I4t -- -- --
Overload protection can be switched on/off -- -- --
Selectable parameter sets -- -- --
Measurement function
Measurement function Plus -- -- --
Communication
CubicleBUS -- -- --
Communication through PROFIBUS DP -- -- --
Communication through MODBUS -- -- --
Communication through Ethernet -- -- --
✔ Standard -- Not available ❑ Optional
Detailed information about the functions of the electronic releases is given in the following.
12 Siemens · 2012
© Siemens AG 2011
ETU76B
Rating Plug
=
12
NSE0_00886c
NSE0_00883b
IR IR
tR tR
Isd Isd
t sd t sd
Ig Ig
Ii Ii
tg tg
ETU45B ETU76B
✔ ✔
✔ ✔
✔ ✔
✔ ✔
❑ ❑
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
✔ ✔
-- ✔
-- ✔
✔ --
-- ✔
-- ✔
❑ ❑
❑ --
-- ✔
❑ ❑
✔ ✔
❑ ❑
❑ ❑
❑ ❑
Siemens · 2012 13
© Siemens AG 2011
14 Siemens · 2012
© Siemens AG 2011
Siemens · 2012 15
© Siemens AG 2011
NSE0_00956c
Features:
The same as ETU25B but also
Indicator: overcurrent • Reversible neutral conductor
ETU27B N-conductor protection
release activated
on/off
protection
Indicator: overload alarm OFF ON
Query pushbutton
Test pushbutton Clear pushbutton
Test socket
Rotary switch for setting short-circuit release • Thermal image as restart protection for
value, short-circuit
protection
Indicator: cause of release tripped motor outgoing feeders
Sealing ring
Selector for
Option: earth-fault module
• Reversible and adjustable neutral conduc-
earth-fault protection SI tor protection
Indicator: earth-fault alarm
Rotary switch for setting g
16 Siemens · 2012
© Siemens AG 2011
Ground-fault protection
Selector for Ground-fault releases "G" sense fault currents that flow to ground
Indicators: Ground-fault
ground-fault
alarm
and that can cause fire in the plant. Multiple circuit breakers con-
detection nected in series can have their delay times adjusted so as to pro-
GFM AT 45B Ground-fault
Rotary switch I vide graduated discrimination.
tripped
for setting g TRIP ALARM t
ALARM (s) I 2t g
value,
G A
g
.5 .1
When setting the parameters for the electronic release it is pos-
ground-fault sible to choose between "alarm" and "trip" in the event that the
B .4 .2
protection
C TRIP .3 .3 set current value is exceeded. The reason for tripping is indi-
D .2 .4
OFF E .1 .5
Rotary switch cated by means of an LED when the query button is activated.
for setting
NSE0_00962a
Rotary switch value, ground- The ETU45B and ETU76B electronic release versions can be ret-
for setting value fault protection delay
ground-fault alarm 2
rofitted with a ground-fault protection module. This ground fault
t g/I t g protection function is integrated in ETU27B electronic releases.
GFM AT 45B ground-fault module
TRIP TRIP I 2t
I g= A t g= ms
Fields for Fields for
noting setting NSE0_00964a
noting setting
values values
Siemens · 2012 17
© Siemens AG 2011
A standard current transformer with the following data is used for With the exception of the ETU27B electronic release, all
measurement of the ground-fault current: versions of the ground-fault modules are supplied with an I2t
1200 A/1 A, Class 1 (the internal load of the 3WL circuit breaker characteristic curve which can be activated.
is 0.11 Ω). The current transformer can be installed directly in the Selection criteria for 3WL circuit breakers
grounded neutral point of a transformer.
Basic criteria for selecting circuit breakers are:
• Max. short-circuit current at place of installation of circuit
L1 breaker I ″k max .
L2 This value determines the short-circuit breaking capacity or
SENTRON WL
L3 short-circuit current carrying capacity of the circuit breaker.
N • It is compared with the value Icu, Ics, Icw of the circuit breaker
T5 PE and essentially determines the size of the circuit breaker.
NSE 00946 See illustration "Overview of 3WL Circuit Breakers/Non-Auto-
matic Air Circuit Breakers".
• Rated current In which is to flow through the branch circuit.
3-pole circuit breakers, current transformers in the N conductor This value must not be greater than the maximum rated circuit
breaker current of the circuit breaker.
L1 The rated current for the 3WL circuit breaker is specified using
L2 the rated current module. See illustration "Overview of 3WL
SENTRON WL
L3 Circuit Breakers/Non-Automatic Air Circuit Breakers" in "De-
N sign".
• Ambient temperature
T6 for the circuit breaker.
PE This is usually the control cabinet internal temperature.
T6: 1200 A/1 A NSE 00947
• Design of the circuit breaker
3-pole circuit breakers, current transformers in the grounded neutral • Minimum short-circuit current
point of the transformer. which flows through the switching device. The release must
still detect this value as a short-circuit and must respond by
L1 tripping.
L2
Protection functions of the circuit breaker.
SENTRON WL L3
These are determined by the selection of the
N
corresponding electronic release, see the table
"Functions of the Electronic Releases" under "Functions".
T6
PE
NSE 00948
T6: 1200 A/1 A
18 Siemens · 2012
© Siemens AG 2011
The DIGmat S100 tripping unit monitors the image of the primary
current thus supplied and compares it with the tripping charac- • Short-circuit protection:
teristic curve set on the device. The parameter settings on the Setting range Ii = 1.25 × IR up to max. 4 × In
DIGmat S100 apply also for DC feedbacks. If the set value is exceeded, tripping occurs in less than
Reversing duty is possible therefore. 50 ms.
The tripping characteristic curve is determined and described In = Rated current of the circuit breaker
by the following IR = Set current value of the adjustable overload release
variables: tR = Assigned tripping time of the overload trip
• Overload protection: Ii = Instantaneous tripping current of the adjustable short-cir-
Setting range IR = 0.4 ... 1.0 In cuit releases
The characteristic curve has an I2t characteristic.
The components are available only from the company
The tripping time tR can be selected between 2 and 10 s,
mat – Maschinen- und Anlagentechnik:
although tR for 6 × IR is defined.
mat – Maschinen- und Anlagentechnik
Dr. Becker GmbH
Rudolf-Diesel-Straße 22
D-22941 Bargteheide
Tel.: +49 (4532) 20 21-01
Fax: +49 (4532) 20 21-21
E-mail: info@m-a-t.de
Internet: www.m-a-t.de
■ Configuration
Mutual mechanical circuit breaker interlocking • The bending radii of the Bowden wire must be > 500 mm.
The module for mutual mechanical interlocking can be used for • The sum of all bending angles along the Bowden cable must
one or two 3WL circuit breakers and can be adapted easily to not exceed 640°.
the corresponding versions. The fixed-mounted and withdraw- • In a vertical arrangement of circuit breakers to be interlocked,
able circuit breaker versions are fully compatible and can there- the interlocking mechanisms must be in line.
fore be used in a mixed configuration in an installation. This also • Circuit breakers to be interlocked must be arranged so that
applies to 3WN6 circuit breakers. Bowden cables can be optimally installed in compliance with
The circuit breakers can be mounted alongside each other or the conditions mentioned in the above points.
one above the other, whereby the distance of the circuit breakers • The installed Bowden cable must be fixed (with cable ties or
is determined solely by the length of the Bowden wire (lengths: the like) before the interlock is adjusted.
2 m/3 m/4.5 m). Interlock signals are looped through using the
Bowden cables. Interlocking is only effective in the connected • Select the width of switchgear cubicle to allow enough free-
position in the case of withdrawable circuit breakers. The me- dom of movement for adjusting the interlock!
chanical endurance of the Bowden cables is 10000 operating • Openings and cut-outs in system elements must be designed
cycles. so that Bowden cables are not changed in direction or ob-
structed when they are passed through.
Minimum requirements must be fulfilled in the switchgear for the
interlocking to function:
• Bowden cables must be installed as far as possible in a
straight line with minimum bending.
Mutual mechanical interlocking of circuit breakers – examples
Mutual interlocking of two Interlocking between three Mutual interlocking of three Interlocking of three circuit
circuit breakers circuit breakers circuit breakers breakers, two of them mutual
G G G
S1 S2 S1 S3 S1 S3
S1 S2 S3
S2 S1 S2 S3 S2
Siemens · 2012 19
© Siemens AG 2011
Output device
Ethernet/ e.g. notebook
Intranet/ with browser
Zone Selective
Interlocking module
Digital output module
Relay
Digital output module
Relay, configurable
NSE0_01820b
Communication with PROFIBUS DP
MODBUS
Output device
Ethernet/ e.g. notebook
Intranet/ with browser
Zone Selective
Interlocking module
Digital output module
Relay
Digital output module
Relay, configurable
BDAPlus
20 Siemens · 2012
© Siemens AG 2011
Siemens · 2012 21
© Siemens AG 2011
22 Siemens · 2012
© Siemens AG 2011
All the digital output modules are available as a version with re- Digital input module
lay outputs (CO contacts, up to 12 A). Up to two modules of this With the digital input module, up to 6 additional binary signals
type can be connected to one 3WL circuit breaker. (24 V DC) in the circuit breaker environment can be connected
to the system. It is thus possible for example to send messages
concerning the state of a switch disconnector or a control cabi-
net door to the PROFIBUS DP/MODBUS.
With the digital input module on the CubicleBUS it is also possi-
ble for the two different protection parameter sets held in the
ETU76B electronic releases to be switched over automatically in
a few milliseconds. It is thus possible, for example, to automati-
cally change the parameters of a coupling switch should the
transformer infeed fail.
One module each of this type can be used for holding the six
items of digital information and for automatically switching over
Digital output modules with rotary coding switch the parameters.
Digital output modules, configurable
The configurable output module is available for higher-perfor-
mance solutions. With this module, random events on the
CubicleBUS can be switched directly to one of six available out-
puts or three of these outputs can be assigned with up to six
events. In other words, up to six events can be placed on one
physical output with "OR" operation. Either BDA/BDA Plus or
Switch ES Power is used for configuring.
A relay variant is also available here the same as for the output
modules with rotary coding switch. Only one module of this type
is possible per 3WL circuit breaker.
Digital input module
ZSI modules (short-time grading control)
The use of ZSI modules is recommended when Siemens circuit
breakers are arranged in several staggered levels but full grad-
ing with the smallest possible delay is to be assured neverthe-
less.
The circuit breakers are interconnected by these modules. In
case of a short-circuit, each affected circuit breaker asks the cir-
cuit breakers directly downstream whether the short-circuit has
also occurred in the next, lower level. The short-circuit is exactly
localized as the result, and only the next upstream circuit
Digital output modules, configurable breaker in the energy flow direction is switched off.
Analog output modules
The analog output module can be used to output the following
measured values to analog indicators in the control cabinet
door:
• IL1, IL2, IL3, IN or
• UL12, UL23, UL31, UL1N or
• PL1, PL2, PL3, Stot or
• p.f. 1, p.f. 2, p.f. 3, ΔI % or
• favg, ULLavg, Ptot, p.f.avg
Four 4-20-mA/0-10-V interfaces are available for this. The mea-
sured values to be output are selected with a rotary coding
switch. By using the analog output module it is possible to do ZSI modules (short-time grading control)
without additional converters and their conventional installa-
tion/wiring in the main current path. Up to two modules of this
type can be connected to one 3WL circuit breaker.
Siemens · 2012 23
© Siemens AG 2011
■ Technical specifications
Switching capacity
Sizes I II III
Type 3WL11 3WL12 3WL13
Switching capacity class N S H N S H H C C
N S H N S H H C C
3-pole 4-pole
Short-circuit breaking capacity
Rated operational voltage Ue up to 415 V AC
Icu kA 55 66 85 66 80 100 100 150 130
Ics kA 55 66 85 66 80 100 100 150 130
Icm kA 121 145 187 145 176 220 220 330 286
Rated operational voltage Ue up to 500 V AC
Icu kA 55 66 85 66 80 100 100 150 130
Ics kA 55 66 85 66 80 100 100 150 130
Icm kA 121 145 187 145 176 220 220 330 286
Rated operational voltage Ue up to 690 V AC
Icu kA 42 50 66 50 75 85 85 150 130
Ics kA 42 50 66 50 75 85 85 150 130
Icm kA 88 105 145 105 165 187 187 330 286
Rated operational voltage Ue
up to 1000 V/1150 V AC
Icu kA -- -- 509) -- -- 50 50 704) 704)
Ics kA -- -- 509) -- -- 50 50 704) 704)
Icm kA -- -- 1059) -- -- 105 105 1544) 1544)
Rated short-time withstand current Icw
of the circuit breakers3)
0.5 s kA 55 66 75 66 80 100 100 100 100
1s kA 42 50 66 55 66 80 100 100 100
2s kA 29.5 35 46 39 46 651)/702) 80 80 80
3s kA 24 29 37 32 44 501)/652) 65 65 65
Short-circuit breaking capacity Icc
of the non-automatic air circuit breakers
Up to 500 V AC kA 55 66 75 66 80 100 100 100 100
Up to 690 V AC kA 42 50 66 50 75 85 85 100 100
Up to 1000 V /1150 V AC kA -- -- 509) -- -- 504) 504) 704) 704)
Sizes II
DC
Type 3WL12
Switching capacity class DC
Short-circuit breaking capacity
Up to 220 V DC Icc kA 35
Up to 300 V DC Icc kA 30
Up to 600 V DC Icc kA 25
Up to 1000 V DC Icc kA 20
Rated short-time withstand current Icw
0.5 s kA --
1s kA 355)/306)/257)/208)
2s kA --
3s kA --
S
Circuit breaker with standard switching capacity S L = Long Time Delay = Overload protection
S = Short Time Delay = Short-circuit protection
H
Circuit breaker with high switching capacity H (short-time delayed)
I = Instantaneous = Short-circuit protection
C
Circuit breakers with very high switching capacity C (instantaneous)
N = Neutral Protection Neutral conductor protec-
DC
Non-automatic air circuit breakers with DC switching ca- tion
pacity G = Ground Fault Ground-fault protection
These switching capacities are indicated in the corre-
sponding tables by the symbols shown on orange back-
grounds. L, S, I, N, G: Designation according to IEC 60947-2, Appendix K.
6)
1)
Size II with In max ≤ 2500 A. At Ue = 300 V DC.
2) 7)
Size II with In max = 3200 A and In max = 4000 A. At Ue = 600 V DC.
8)
3)
At a rated voltage of ≥ 690 V the Icw value of the circuit breaker cannot be At Ue = 1000 V DC.
greater than the Icu or Ics value at 690 V. 9) Values also apply to version 690 V + 20 % with Z option "A16".
4)
Rated operational voltage Ue = 1150 V.
5)
At Ue = 220 V DC.
24 Siemens · 2012
© Siemens AG 2011
Sizes I II
Type ... 3WL11 10 3WL11 12 3WL11 16 3WL11 20 3WL12 08 3WL12 10 3WL12 12 3WL12 16
Rated current In at 40 °C, at 50/60 Hz
Main conductors A ... 1000 1250 1600 2000 800 1000 1250 1600
N conductor (only on 4-pole versions) A ... 1000 1250 1600 2000 800 1000 1250 1600
Rated operational voltage Ue at 50/60 Hz V AC ... ... ... ... ... ... ... ...
(1000 V version, see Catalog LV 10.1, "Options") 690/1000 690/1000 690/1000 690/1000 690/1000 690/1000 690/1000 690/1000
Rated insulation voltage Ui V AC 1000 1000 1000 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp
• Main current paths kV 12 12 12 12 12 12 12 12
• Auxiliary circuits kV 4 4 4 4 4 4 4 4
• Control circuits kV 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
Isolating function to EN 60 947-2 Yes Yes Yes Yes Yes Yes Yes Yes
Utilization category B
Permissible ambient temperature
• During operation (in operation with LCD max. 55 °C)4) °C –25/+70 –25/+70 –25/+70 –25/+70 –25/+70 –25/+70 –25/+70 –25/+70
• During storage (special conditions for LCDs must be °C –40/+70 –40/+70 –40/+70 –40/+70 –40/+70 –40/+70 –40/+70 –40/+70
observed)
Permissible load • Up to 55 °C (Cu bare) A 1000 1250 1600 2000 800 1000 1250 1600
At rear horizontal main con- • Up to 60 °C (Cu bare)5) A 1000 1250 1600 1930 800 1000 1250 1600
nections • Up to 70 °C (Cu black A 1000 1210 14908) 1780 800 1000 1250 1600
painted)5)
Rated rotor operational voltage Uer V 2000 2000 2000 2000 2000 2000 2000 2000
Power loss at In
with 3-phase symmetrical load
• Fixed-mounted circuit breakers W 100 105 150 240 40 45 80 85
• Withdrawable circuit breakers W 195 205 350 440 85 95 165 175
Switching times
• Make-time ms 35 35 35 35 35 35 35 35
• Opening time ms 38 38 38 38 34 34 34 34
• Electrical make-time (through closing solenoid)2) ms 80 80 80 80 100 100 100 100
• Electrical opening time (through shunt release) ms 73 73 73 73 73 73 73 73
• Electrical opening time (instantaneous undervoltage ms 73 73 73 73 73 73 73 73
release)
1) 1) 1) 1) 1) 1) 1)
• Opening time due to ETU, instantaneous short-circuit ms 50 50 50 50 50 50 50 501)
release
Endurance: Switching capacity N and S. 3/4-pole
• Mechanical (without maintenance) Operating cycles 10 000 10 000 10 000 10 000 10 000 10 000 10 000 10 000
• Mechanical (with maintenance)3) Operating cycles 20 000 20 000 20 000 15 000 15 000 15 000 15 000 15 000
• Electrical (without maintenance) Operating cycles 10 000 10 000 10 000 7500 7500 7500 7500 7500
• 1000 V version, electrical Operating cycles -- -- -- 1000 1000 1000 1000 1000
(without maintenance)
• 1150 V version, electrical Operating cycles -- -- -- -- 500 500 500 500
(without maintenance)
• Electrical (with maintenance)3) Operating cycles 20 000 20 000 20 000 15 000 15 000 15 000 15 000 15 000
Endurance: Switching capacity H, 3-pole
• Mechanical (without maintenance) Operating cycles 10 000 10 000 10 000 10 000 10 000 10 000 10 000 10 000
• Mechanical (with maintenance)3) Operating cycles 15 000 15 000 15 000 15 000 15 000 15 000 15 000 15 000
• Electrical (without maintenance) Operating cycles 7 500 7 500 7 500 7500 7500 7500 7500 7500
• 1000 V version, electrical Operating cycles 1000 1000 1000 1000 1000 1000 1000 1000
(without maintenance)
• 1150 V version, electrical Operating cycles -- -- -- -- 500 500 500 500
(without maintenance)
• Electrical (with maintenance) 3)9) Operating cycles 15 000 15 000 15 000 15 000 15 000 15 000 15 000 15 000
Endurance: Switching capacity H, 4-pole
• Mechanical (without maintenance) Operating cycles 10 000 10 000 10 000 10 000 10 000 10 000 10 000 10 000
• Mechanical (with maintenance)3) Operating cycles 15 000 15 000 15 000 15 000 15 000 15 000 15 000 15 000
• Electrical (without maintenance) Operating cycles 7 500 7 500 7 500 7500 7500 7500 7500 7500
• 1000 V version, electrical Operating cycles 1000 1000 1000 1000 1000 1000 1000 1000
(without maintenance)
• 1150 V version, electrical Operating cycles -- -- -- -- 500 500 500 500
(without maintenance)
3)9)
• Electrical (with maintenance) Operating cycles 10 000 10 000 10 000 10 000 15 000 15 000 15 000 15 000
Switching frequency6)
• 690 V version 1/h 607) 607) 607) 60 607) 607) 607) 607)
• 1000 V version 1/h -- -- -- 20 20 20 20 20
• 1150 V version 1/h -- -- -- -- 20 20 20 20
Minimum interval between tripping operation by elec- ms 80 80 80 80 80 80 80 80
tronic release and next making operation of the circuit
breaker (only with autom. mechanical resetting of the
lockout device).
Minimum interval between ON/OFF or OFF/ON switching
operations.
1) 5)
Opening time on instantaneous short-circuit release with ETU76B with graphics display can be used up to max. 55 °C.
ETU15B = 85 ms. 6)
Minimum interval between 2 switching operations.
2)
Make-time through closing solenoid for synchronization purposes 7)
3-pole switching with switching capacity N and S: 45/h.
(short-time excited) 50 ms. 8)
3) For switching capacity H: 1600 A to 70 °C.
Maintenance means: replace main contact elements and arc chutes (see 9)
Operating Manual). The main contacts of size I circuit breakers with switching capacity H can
4) only be replaced at the factory.
Use of releases from –20 °C
Siemens · 2012 25
© Siemens AG 2011
Sizes I II
Type ... 3WL11 10 3WL11 12 3WL11 16 3WL11 20 3WL12 08 3WL12 10 3WL12 12 3WL12 16
Mounting position 3 0 ° 3 0 ° 3 0 ° 3 0 °
h m a x .
= 1 m m
and/or
N S E 0 _ 0 0 0 6 1 a N S E 0 _ 0 0 0 6 2 a N S E 0 _ 0 0 9 2 7 a
Degree of protection IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover
Main conductor • Copper bars, Unit(s) 1× 2× 2× 3× 1× 1× 2× 2×
minimum bare mm2 60 × 10 40 × 10 50 × 10 50 × 10 50 × 10 60 × 10 40 × 10 50 × 10
cross-sections • Copper bars, Unit(s) 1× 2× 2× 3× 1× 1× 2× 2×
painted black mm2 60 × 10 40 × 10 50 × 10 50 × 10 50 × 10 60 × 10 40 × 10 50 × 10
Auxiliary conductors (Cu) Standard connection = strain-
Max. number of relief clamp
auxiliary conductors × cross- • Without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14)
section • With end sleeve according to 1 × 0.5 mm2 (AWG 20) ... 1 × 1.5 mm2 (AWG 16)
(solid/stranded) DIN 46228 Part 2
• With twin end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
Optional connection = tension
spring
• Without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 2.5 mm2 (AWG 14)
• With end sleeve according to 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
DIN 46228 Part 2
Position signaling switches Tension spring terminals 1 × 0.5 mm2 (AWG 20) ... 1 × 2.5 mm2 (AWG 14)
Weights 3-pole • Fixed-mounted CBs kg 43 43 43 43 56 56 56 56
• Withdrawable CBs kg 45 45 45 45 60 60 60 60
• Guide frames kg 25 25 25 25 31 31 31 31
4-pole • Fixed-mounted CBs kg 50 50 50 50 67 67 67 67
• Withdrawable CBs kg 54 54 54 54 72 72 72 72
• Guide frames kg 30 30 30 30 37 37 37 37
26 Siemens · 2012
© Siemens AG 2011
Sizes II III
Type 3WL12 20 3WL12 25 3WL12 32 3WL12 40 3WL13 40 3WL13 50 3WL13 63
Rated current In at 40 °C, at 50/60 Hz
Main conductors A 2000 2500 3200 4000 4000 5000 6300
N conductor (only on 4-pole versions) A 2000 2500 3200 4000 4000 5000 6300
Rated operational voltage Ue at 50/60 Hz V AC ... ... ... ... 690 ... ... ...
(1000 V version, see Catalog LV 10.1, "Options") 690/1000 690/1000 690/1000 690/1000 690/1000 690/1000
Rated insulation voltage Ui V AC 1000 1000 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp
• Main current paths kV 12 12 12 12 12 12 12
• Auxiliary circuits kV 4 4 4 4 4 4 4
• Control circuits kV 2.5 2.5 2.5 2.5 2.5 2.5 2.5
Isolating function to EN 60947-2 Yes Yes Yes Yes Yes Yes Yes
Utilization category B (except switching capacity class DC)
Permissible ambient temperature
• During operation (in operation with LCD max. 55 °C)4) °C –25/+70 –25/+70 –25/+70 –25/+70 –25/+70 –25/+70 –25/+70
• During storage (special conditions for LCDs must be observed) °C –40/+70 –40/+70 –40/+70 –40/+70 –40/+70 –40/+70 –40/+70
Permissible load6) • Up to 55 °C (Cu bare) A 2000 2500 3200 3950 4000 5000 5920
• Up to 60 °C (Cu bare)5) A 2000 2500 3020 3810 4000 5000 5810
• Up to 70 °C (Cu black painted)5) A 2000 2280 2870 3600 4000 5000 5500
Rated rotor operational voltage Uer V 2000 2000 2000 2000 2000 2000 2000
Power loss at In
with 3-phase symmetrical load
• Fixed-mounted circuit breakers W 180 270 410 750 520 630 900
• Withdrawable circuit breakers W 320 520 710 925 810 1050 1600
Switching times
• Make-time ms 35 35 35 35 35 35 35
• Opening time ms 34 34 34 34 34 34 34
• Electrical make-time (through closing solenoid)2) ms 100 100 100 100 100 100 100
• Electrical opening time (through shunt release) ms 73 73 73 73 73 73 73
• Electrical opening time (instantaneous undervoltage release) ms 73 73 73 73 73 73 73
• Opening time due to ETU, instantaneous short-circuit release ms 501) 501) 501) 501) 50 50 50
Endurance
• Mechanical (without maintenance) Operating cycles 10000 10000 10000 10000 5000 5000 5000
• Mechanical (with maintenance)3) Operating cycles 15000 15000 15000 15000 10000 10000 10000
• Electrical (without maintenance) up to 690 V Operating cycles 7500 7500 4000 2000 2000 2000 2000
• 1000 V version, electrical (without maintenance) Operating cycles 1000 1000 1000 1000 1000 1000 1000
• 1150 V version, electrical7) (without maintenance) Operating cycles 500 500 500 500 500 500 500
• Switching capacity C: Electrical Operating cycles -- -- -- -- 1000 1000 1000
(without maintenance) up to 690 V
• Switching capacity C: Electrical Operating cycles -- -- -- -- 500 500 500
(without maintenance) up to 1150 V
• Electrical (with maintenance)3) Operating cycles 15000 15000 15000 15000 10000 10000 10000
Switching frequency8)
• 690 V version 1/h 609) 609) 609) 609) 60 60 60
• 1000 V version 1/h 20 20 20 20 20 20 20
• 1150 V version7) 1/h 20 20 20 20 20 20 20
Minimum interval between tripping operation by electronic ms 80 80 80 80 80 80 80
release and next making operation of the
circuit breaker (only with automatic
mechanical resetting of the lockout device)
Minimum interval between ON/OFF or OFF/ON switching opera-
tions.
1) 5)
Opening time on instantaneous short-circuit release with ETU76B with graphics display can be used up to max. 55 °C.
ETU15B = 85 ms. 6)
4000 A, size II in fixed-mounted version, 3-pole.
2)
Make-time through closing solenoid for synchronization purposes 7)
Size II with order code "A15" and size III:
(short-time excited) 50 ms. Data for very high switching capacity.
3)
Maintenance means: replace main contact elements and arc chutes 8)
Minimum interval between 2 switching operations.
(see Operating Manual). 9)
4) 3-pole switching with switching capacity N and S: 45/h.
Use of releases from –20 °C
Siemens · 2012 27
© Siemens AG 2011
Sizes II III
Type 3WL12 20 3WL12 25 3WL12 32 3WL12 40 3WL13 40 3WL13 50 3WL13 63
3 0 ° 3 0 °
h m a x .
Mounting position 3 0 ° 3 0 °
= 1 m m
and/
or
N S E 0 _ 0 0 0 6 1 a N S E 0 _ 0 0 0 6 2 a N S E 0 _ 0 0 9 2 7 a
Degree of protection IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover
Main conductor • Copper bars, Unit(s) 3 × 2× 3× 4× 4x 6x 6x
minimum bare mm2 50 × 10 100 × 10 100 × 10 120 × 10 100 x 10 100 x 10 120 x 10
cross-sections • Copper bars, Unit(s) 3 × 2× 3× 4× 4× 6× 6×
painted black mm2 50 × 10 100 × 10 100 × 10 100 × 101) 100 × 10 100 × 10 120 × 10
Auxiliary conductors Standard connection = strain-relief clamp
(Cu) • Without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14)
Max. no. of • With end sleeve according to 1 × 0.5 mm2 (AWG 20) ... 1 × 1.5 mm2 (AWG 16)
auxiliary conductors × DIN 46228 Part 2
cross-section • With twin end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
(solid/stranded)
Optional connection = tension spring
• Without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 2.5 mm2 (AWG 14)
• With end sleeve according to 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
DIN 46228 Part 2
Position signaling Tension spring terminals 1 × 0.5 mm2 (AWG 20) ... 1 × 2.5 mm2 (AWG 14)
switches
Weights 3-pole • Fixed-mounted circuit breakers kg 56 59 64 85 82 82 90
• Withdrawable circuit breakers kg 60 63 68 121 88 88 96
• Guide frames kg 31 39 45 52 60 60 70
4-pole • Fixed-mounted circuit breakers kg 67 71 77 103 99 99 108
• Withdrawable circuit breakers kg 72 76 82 146 106 106 108
• Guide frames kg 37 47 54 62 84 84 119
1) Minimum main conductor cross-sections for 4-pole withdrawable circuit
breakers: 4 x 120 x 10 mm
28 Siemens · 2012
© Siemens AG 2011
Sizes I to III
Type 3WL1
Manual operating mechanism with mechanical closing
Closing/ Max. force required to operate the hand lever N ≤ 230
Charging stored- Required number of strokes on the hand lever 9
energy feature
Manual operating mechanism with mechanical and electrical closing
Charging stored-
energy feature
Closing solenoid • Primary operating range 0.85 ... 1.1 × Us
(CC)
• Extended operating range for battery operation At 24 V DC, 48 V DC 0.7 ... 1.26 × Us
60 V DC, 110 V DC
220 V DC
• Rated control supply voltage Us 50/60 Hz AC V 110 ... 127; 208 ... 240
DC V 24; 30; 48; 60; 110 ... 125; 220 ... 250
• Power consumption AC/DC VA/W 15/15
• Minimum command duration at Us for the closing solenoid ms 60
• Short-circuit protection 1 A TDz (slow)/1 A
Smallest permissible DIAZED fuse (gL operational class)/
miniature circuit breaker with C characteristic
Manual/motorized operating mechanism with mechanical and electrical closing
Manual operating For data see above.
mechanism
Motor • Primary operating range 0.85 ... 1.1 × Us
• Extended operating range for battery operation At 24 V DC, 48 V DC 0.7 ... 1.26 × Us
60 V DC, 110 V DC
220 V DC
• Power consumption of motor AC/DC VA/W 135/135
• Time required to charge the stored-energy mechanism at 1 × Us s ≤ 10
Closing solenoid For data see above.
For motor and • Short-circuit protection 6 A TDz (slow)/2 A
closing solenoid Smallest permissible DIAZED fuse (gL operational class)/miniature circuit breaker with
C characteristic; Motor and closing solenoid for identical rated control supply voltages
• Smallest permissible DIAZED fuse (gL operational class)/ At Us = 24 ... 30 V 6A
miniature circuit breaker with C characteristic (for different At Us = 48 ... 60 V 6A
rated control supply voltages) At Us = 110 ... 125 V DC/ 2A
110 ... 127 V AC
At Us = 220 ... 250 V DC/ 2A
208 ... 240 V AC
Electronic release signals
Measuring accuracy of the electronic release Protection functions acc. to
EN 60947; current indication ≤ 10 %;
Measurement function
Base electrical quantities ≤ 1 %;
Measurement function
derived variables ≤ 4 %
Auxiliary releases
Undervoltage • Response values Pick-up ≥ 0.85 × Us (circuit breaker can
releases be closed)
UVR (F3) and Dropout 0.35 ... 0.7× Us
UVR-td (F4) (circuit breaker is tripped)
• Primary operating range 0.85 ... 1.1
• Extended operating range for battery operation At 24 V DC, 30 V DC, 0.85 ... 1.26
48 V DC, 110 V DC, 220 V DC
• Rated control supply voltage Us Instantaneous
50/60 Hz AC V 110 ... 127/208 ... 240/380 ... 415
DC V 24/30/48/60/110 ... 125/220 ... 2501)
Delayed
50/60 Hz AC V 110 ... 127; 208 ... 240; 380 ... 415
DC V 48; 110 ... 125; 220 ... 250
• Power consumption (pickup/uninterrupted duty) AC VA 20/5
DC W 20/5
• Opening time of circuit breaker at Us = 0 ms 200
- Version UVR (F3)
Instantaneous ms 80
With delay ms 200
- Version UVR-td (F8)
with delay, td = 0.2 to 3.2 s s 0.2 ... 3.2
Reset via additional NC contact – direct switching off ms ≤ 100
• Short-circuit protection 1 A TDz (slow)/1 A
Smallest permissible DIAZED fuse (gL operational class)/
miniature circuit breaker with C characteristic
1)
24 V and 30 V only with undervoltage release UVR (F3).
Siemens · 2012 29
© Siemens AG 2011
Sizes I to III
Type 3WL1
Auxiliary releases
Shunt release (ST) • For continuous command - Response value Pick-up > 0.7 × Us
(F1, F2) (100 % ON period), locks (circuit breaker is tripped)
out on momentary-con- - Primary operating range 0.85 ... 1.1 × Us
tact commands
- Extended operating range At 24 V DC, 48 V DC 0.7 ... 1.26 × Us
for battery operation 60 V DC, 110 V DC
220 V DC
- Rated control supply voltage Us 50/60 Hz AC V 110 ... 127; 208 ... 240
DC V 24; 30; 48; 60; 110 ... 125;
220 ... 250
- Power consumption AC/DC VA/W 15/15
- Minimum command duration at Us ms 60
- Opening time of circuit breaker at AC/DC ms 80
Us = 100 %
- Short-circuit protection 1 A TDz (slow)/1 A
Smallest permissible DIAZED fuse (gL operational
class)/miniature circuit breaker with C characteristic
5 % OP - Response value Pick-up > 0.7 × Us
(circuit breaker is tripped)
- Primary operating range 0.85 ... 1.1 × Us
- Extended operating range At 24 V DC, 48 V DC 0.7 ... 1.26 × Us
for battery operation 60 V DC, 110 V DC
220 V DC
- Rated control supply voltage Us 50/60 Hz AC V 110 ... 127; 208 ... 240
DC V 24; 48; 110 ... 125; 220 ... 250
- Power consumption AC/DC VA/W 15/15
- Minimum command duration at Us ms 25
- Opening time of circuit breaker at AC/DC ms 50
Us = 100 %
- Short-circuit protection 1 A TDz (slow)/1 A
Smallest permissible DIAZED fuse (gL operational
class)/miniature circuit breaker with C characteristic
• With stored energy fea- - Rated control supply voltage Us 50/60 Hz AC V 110; 230
ture DC V 110; 220
consisting of shunt re- - Primary operating range 0.85 ... 1.1 × Us
lease and capacitor stor-
age device - Power consumption AC/DC VA/W 1/1
- Storage time at Us/ max. 5 min/min. 5 s
recharging time at Us
- Opening time of circuit breaker, short-circuit protec- As with "for continuous com-
tion mand"
Remote reset solenoid for mechanical tripped indicator (F7)
Remote reset solenoid for - Primary operating range 0.85 ... 1.1 × Us
mechanical tripped indica- - Extended operating range At 24 V DC, 48 V DC 0.7 ... 1.26 × Us
tor (F7) for battery operation 110 V DC
220 V DC
- Power consumption AC/DC VA/W 50/50
- Minimum command duration at Us for the remote re- ms 60
set solenoid
- Short-circuit protection
Smallest permissible DIAZED fuse (gL operational class)/ 2 A TDz (slow)/1 A at 24 V DC
miniature circuit breaker with C characteristic and 48 V DC,
1 A TDz (slow)/1 A at 110 V and
208 ... 250 V
Contact position-driven auxiliary switches (S1, S2, S3, S4, S7, S8)
Rated insulation voltage Ui V AC/DC 500
Rated operational voltage Ue V AC/DC 500
Rated impulse withstand voltage Uimp kV 4
Switching capacity • Alternating current - Rated operational voltage Ue V 24 ... 230 380/400 500
50/60 Hz - rated operational current
Ie /AC-12 A 10 10 10
Ie/AC-15 A 4 3 2
• Direct current - Rated operational voltage Ue V 24 48 110 220
- rated operational current
Ie/DC-12 A 10 8 3.5 1
Ie/DC-13 A 8 4 1.2 0.4
Short-circuit protection • Largest permissible DIAZED fuse (gL operational class) 10 A TDz, 10 A Dz
• Largest permissible miniature circuit breaker with C characteristic 10 A
30 Siemens · 2012
© Siemens AG 2011
Sizes I to III
Type 3WL1
Ready-to-close signaling switch (S20) (according to DIN VDE 0630)
Switching capacity • Alternating current - Rated operational voltage Ue V 250
- Rated operational current Ie A 8
• Direct current - Rated operational voltage Ue V 125 250
- Rated operational current Ie A 0.4 0.2
Short-circuit protection Largest permissible DIAZED fuse (gL operational class) 2 A Dz (quick)
Tripped signaling switch (S24) and signaling switch for auxiliary releases (S22, S23)
(according to DIN VDE 0630)
Switching capacity • Alternating current - Rated operational voltage Ue V 250
- Rated operational current Ie/AC-12 A 8
• Direct current - Rated operational voltage Ue V 24 125 250
- Rated operational current Ie/DC-12 A 6 0.4 0.2
Short-circuit protection Largest permissible DIAZED fuse (gL operational class) 6 A Dz (quick)
Tripped signaling switch Signal duration after tripping Until manual or electrical
remote reset (option)
Position signaling switch on guide frame
Type of contact • Signal: - "Circuit breaker in connected posi- 3 CO 1 CO
tion" 2 CO or 1 CO
- "Circuit breaker in test position" 1 CO 1 CO
- "Circuit breaker in disconnected
position"
Rated insulation voltage Ui 50/60 Hz AC V 440
DC V 250
Rated operational voltage Ue V 250
Rated impulse withstand voltage Uimp kV 4
Switching capacity • Rated operational - Ie/AC-12 24 V 10 A, 110/127 V 10 A,
current Ie 220/240 V 10 A, 320/440 V 10 A
- Ie/AC-15 220/240 V 4 A,
320/440 V 3 A,
- Ie/DC-12 24 V 10 A, 48 V 2.5 A,
220/240 V 0.2 A,
- Ie/DC-13 24 V 3.0 A, 220/240 V 0.1 A
Siemens · 2012 31
© Siemens AG 2011
g
G current transformer
Setting range of the operating current Ig for tripping -- -- A-B-C-D-E
N S E 0 _ 0 0 8 8 9 a Setting range of the operating current Ig for alarm -- -- --
Setting range of the delay time tg -- -- 100-200-300-400-500 ms
Switchable ground-fault protection characteristic -- -- --
2
curve (I t-dependent function)
Setting range for delay time tg at I2t -- -- --
Zone Selective Interlocking ground-fault protect. -- -- --
function
Parameter set switchover
Switchable between parameter set A and B -- -- --
LCD
Alphanumeric LCD (4-line) -- -- --
Graphical LCD (24 V, external power supply required) -- -- --
Communication
CubicleBUS integrated -- -- --
Communication-capable through PROFIBUS DP -- -- --
Measurement function
Measurement-function capable with measurement -- -- --
function Plus
LED display
Electronic release active ✓ ✓ ✓
Alarm ✓ ✓ ✓
ETU fault ✓ ✓ ✓
L-release -- ✓ ✓
S-release -- ✓ ✓
I-release -- ✓ ✓
N-release -- -- ✓
NSE00890
G-release -- -- ✓
G-alarm -- -- --
Release through extended protection function -- -- --
Communication -- -- --
Signals from signaling switches with external CubicleBUS modules (relays)
Overload warning -- -- --
Load shedding, load receiving -- -- --
Leading signal overload trip 200 ms -- -- --
Temperature alarm -- -- --
Phase unbalance -- -- --
Instantaneous short-circuit release -- -- --
Short-time delayed short-circuit release -- -- --
Overload trip -- -- --
Neutral conductor release -- -- --
NSE00891
Ground-fault protection release -- -- --
Ground-fault alarm -- -- --
Auxiliary relay -- -- --
ETU fault -- -- --
Delay time figures given in ms. D & S = Rotary coding and slide switch ✓ Available.
M = Motor protection, corresponds to 20 ms. K = communication -- Not available.
D = Rotary coding switch M/K = menu/communication ❑ Optional.
For the setting range of the operating current Ig, see page 33.
32 Siemens · 2012
© Siemens AG 2011
Siemens · 2012 33
© Siemens AG 2011
■ Characteristic curves2)
Every release type and every setting has its own characteristic 10000
NSE0_01527
curve. Only a selection is shown in the following. The character- R min R max
istic curves each show the largest and smallest setting range of
[s]
3WL circuit breakers with 1000 A rated current at 500 V rated 1000 0,5 ... 1,0 x n
Opening time
voltage with various releases. In order to obtain a complete trip-
ping characteristic, the relevant parts of the characteristics have 100
to be combined. The characteristic curves show the behavior of
the release when it is activated by a current that is already flow-
ing before the tripping operation. If the overcurrent tripping oc- 10
curs immediately after switch on and the release is therefore not
yet enabled, the opening time is extended, depending on the 1 i min i max
level of the overcurrent by up to 15 ms. In order to determine the 2 ... 8 x n
break-times of the circuit breakers, approximately 15 ms must
0,1
be added to the opening times shown for the arcing time.
Refer to the following legend for tolerances.
The characteristic curves shown apply to ambient temperatures 0,01
at the circuit breaker between -5 and +55 °C. The release can 0,1 1 10 100
/
be operated at ambient temperatures of -20 to +70°C. n
An extended tolerance band can apply at these temperatures. 3WL circuit breaker with ETU15B release
10000 10000
NSE0_01520
NSE0_01519
R min R max
R min R max
Opening time [s]
100 100
10 10
3WL circuit breaker with ETU25B release, 3WL circuit breaker with ETU27B release,
LSI characteristic curve LSIN characteristic curve
10000
NSE0_01521
10000
NSE0_01523a
Opening time [s]
[s]
1000 1000 sd
Opening Time
1,25 ... 12 x n
100 100
2
sd = const
g min g max
10 10
100 ... 1200 A1)
1 1 2
g max sd = const
0,1 ... 0,5 s
sd = const 0,1 ... 0,4 s
0,1 g min 0,1
0,02 ... 0,4 s
0,01 0,01
100 1000 10000 100000 0,1 1 10 100
A / n
3WL circuit breaker with ETU27B release, 3WL circuit breaker with ETU45B release,
G characteristic curve S characteristic curve
Tolerances for the set currents 1) Sizes I and II: 100 ... 1200 A
L: Tripping operations between 1.05 and 1.2 x IR Size III: 400 ... 1200 A.
S: –0 %, +20 % 2)
I: –0 %, +20 % With single-pole loading in the lowest rated current range, the response
times of the short-circuit release can be extended by approx. 10 % and
G: –0 %, +20 % the tripping times by approx. 15% compared to the characteristic curve.
Tolerances for the tripping times
L: –20 %, +0 % for I2t characteristic curve
S: –0 %, +60 ms or -0 %, 10 % for tripping times greater than 600 ms
I: <50 ms
G: –0 %, +60 ms or -0 %, 10 % for tripping times greater than 600 ms
34 Siemens · 2012
© Siemens AG 2011
NSE0_01525a
curve. Only a selection is shown in the following. The character-
istic curves each show the largest and smallest setting range of
The characteristic curves shown apply to ambient temperatures 3WL circuit breaker with ETU45B and ETU76B release, G characteristic
at the circuit breaker between -5 and +55 °C. The release can curve
be operated at ambient temperatures of -20 to +70°C (ETU76B
10000
with graphics display up to +55 °C). An extended
NSE0_01526a
tolerance band can apply at these temperatures.
R 4 = const
1,25 x n ... 0,8 x cw
100
Opening time [s]
2 = const 10
100
2
1 sd = const
R
10
2 ... 30s for 2 sd = const
1 ... 5s for 4 0,1 ... 0,4 s
0,1 0,02 ... 4 s
1
0,01
0,1 0,1 1 10 1
/ n / cw
0,01
0,1 1 10 1
/ n / cs
Siemens · 2012 35
© Siemens AG 2011
■ Dimensional drawings
Voltage transformer for 3WL air circuit breakers External current transformers for N conductor without copper
connection pieces
260
Size I, 3WL9 111-0AA21-0AA0
6 0
1 6
125
8
R 1 3 ,1
8 ,9
N S E 0 _ 0 1 3 7 5
9 6 ,8
NSE0_01103b
2 2
8 1
87 R 2 2
For mounting on
4 0
35 mm standard
mounting rail 1 8 5 1
3 6
7 0
Current transformers for overload protection in the N con- 8 3
ductor
Size II, 3WL9 111-0AA22-0AA0
External current transformers for N conductor with copper con-
nection pieces
Size I, 3WL9 111-0AA31-0AA0 R 2 7
1 1 5
1 3 1
5 4
1 5 4 1
N S E 0 _ 0 1 3 7 6
Ø 1 3 ,5
6 5 ,5
4 4
2 4
8 8 5 1
9 5
1 7 0
1 3 0
6 8
9 1
5 1
1 1 3 3
5 5 9 7 1 6 1
8 3
R 1 5
1 0 7
1 2 3
N S E 0 _ 0 1 3 7 7
4 5
5 0 ,5
1 6 0 5 1
Ø 1 3 ,5 1 8 4
4 4
1 7 0
9 0 1 3 1
1 1 3
3 4 0
3 0 3 0 3 0 3 × 1 0 5 2
2 4 0
Ø 1 3 ,5
4 4
2 4
N S E 0 _ 0 0 1 6 4 c
1 3 0
9 1
6 8
1 7 0
5 1
3 1 4
1 6 0 1 2 3
1 8 4 3 0 0
1 2 0 4 0
Ø 5 ,5 3 )
N S E 0 _ 0 0 6 1 0 c
R 5 R 5
1 8 5
1 4 0
2 )
Ø 5 ,5
3 5 0
1 4 0
1 8 0
1 7 5
4 0 1 2 0
1)
Mounting surface
2)
Center 3WL circuit breaker operator panel
1 1 ,5
1 2
3)
8 mounting holes for door sealing frame 1 ) 2 1 4 )
4) 4 0
3 mounting holes for door interlocking
36 Siemens · 2012
© Siemens AG 2011
47,5
94
16(B
153
16(B
30
Siemens · 2012 37
© Siemens AG 2011
395
NSE0_01030b
4 x R5
4 x 5,5
85
340-350
72
295-300
72
435
68
70
17
Safety clearance from grounded parts Safety clearances from live parts
Rated operational voltage Above Lateral Rear Rated operational voltage Above Lateral Rear
auxiliary connector (each side) auxiliary connector (each side)
V/AC mm mm mm V/AC mm mm mm
Size I, fixed-mounted version Size I, fixed-mounted version
500 751) 0 0 500 150 20 20
690 751) 0 0 690 300 50 125
1000 5003) 1003) 1403)
Size I, withdrawable version,
without arc chute cover Size I, fixed-mounted version,
500 501) 0 0 with arc chute cover
690 501) 0 0 500 14 504) 14
690 14 2254) 14
Size I, withdrawable version,
with arc chute cover Size I, withdrawable version,
500 0 02) 0 without arc chute cover
690 0 02) 0 500 150 20 14
690 300 50 14
Size II, fixed-mounted version 1000 5003) 1003) 1403)
500 751) 0 0
690 751) 0 0 Size I, withdrawable version,
1000 180 0 0 with arc chute cover
Size II, withdrawable version, 500 14 100 14
690 14 100 14
without arc chute cover
500 501) 0 0 Size II, fixed-mounted version
690 501) 0 0 500 250 50 20
1000 100 0 0 690 600 100 140
1000 430 100 125
Size II, withdrawable version,
with arc chute cover Size II, withdrawable version,
500 0 02) 0 without arc chute cover
690 0 02) 0 500 250 50 14
690 600 100 30
Size III, fixed-mounted version 1000 350 100 14
500 751) 0 0
690 751) 0 0 Size II, withdrawable version,
1000 180 0 0 with arc chute cover
Size III, withdrawable version, 500 14 50 14
690 14 225 14
without arc chute cover
500 501) 0 0 Size III, fixed-mounted version
690 501) 0 0 500 75 20 20
1000 100 0 0 690 500 100 125
1000 430 100 125
Size III, withdrawable version,
with arc chute cover Size III, withdrawable version,
500 0 02) 0 without arc chute cover
690 0 02) 0 500 50 20 14
690 500 100 14
DC non-automatic air circuit breakers 1000 350 100 14
300 45 0 0
600 200 0 0 Size III, withdrawable version,
1000 150 0 0 with arc chute cover
500 14 50 14
All safety clearances above the circuit breaker refer to the upper 690 14 200 14
edge of the auxiliary connector - not to the upper edge of the arc 1)
chute! See dimensional drawings on pages 39 to 47, Parts 4) Value for plate; 0 mm for struts and grids
2)
and 5). 40 mm (size II: 70 mm) for plates, which cover the lateral openings in the
guide frame
3)
Not for switching capacity S.
4)
For switching capacity S: 100 mm.
38 Siemens · 2012
© Siemens AG 2011
4) 5)
35
NSE0_00611h 4 7 55 55 55 55
Æ 13,5
N S E 0 _ 0 0 6 1 2 c
275
440,5
437,5
3)
NSE00613b
421
11)
e
6
123,5
270 15
300 10
35
26
390 60 90 90 90
c 8 2
d
Front connection (double hole)
19) 1) 2) according to DIN 43673
18) Ø 13,5
9) 47 55 55 55 55
40
14)
60,5
8)
80
33,5
NSE0_00615h
a
3)
NSE00616b
421
451,5
541,5
11)
327,5
516
461,5
621
3)
6
a
275
150
5,5
f
80
76
40
14
NSE0_00614h 45 6) c 7) 60 90 90 90
82
150 106
210
230 127
Vertical connection
90 90 90 60 11) 35 NSE00619 b
35
55 Ø13,5
60
4x M8
11)
30
3)
3) 7)
7) 110 (150)
267,5
4x Ø9
NSE0_00618h
127,5
20
NSE0_00617j
113,5 7)
139 58 13,5
128,5
320 60 90 90 90
410
NSE00620 Rated a b c d e f g
circuit breaker
current
A
3) Up to 1000 10 10 10 11 451 34 541
1250 ... 2000 15 20 15 6 461 39 551
60 90 90 90
9)
——— 4-pole version Key operation (optional accessory).
1) 11)
Mounting space for removal of the arc chutes. Terminal face.
14)
2)
Arc quenching space ≤ 690 V – circuit breaker facing grounded or non- Space for electrical auxiliary circuit connections.
conductive surfaces. 18)
Circuit breaker upper edge, only 690 V (+20 %) and 1000 V circuit
3) breakers.
Rivels (4 mm wide, 5 mm deep) for supporting phase barriers in the
system. 19)
Arc quenching space, circuit breaker facing grounded or non-conduc-
4) tive surfaces, only 690 V (+20 %) and 1000 V circuit breakers.
Auxiliary connector with SIGUT screw terminals.
5)
Auxiliary connector with screwless connection method. For safety clearances to grounded parts and to live parts see
6)
Dimension to inside surface of the closed cabinet door. page 38.
7)
Fixing points for mounting the circuit breaker in the system;
4 × setting nut M8.
8)
"Secure OFF" locking device (optional accessory).
Siemens · 2012 39
© Siemens AG 2011
320 62,5 3 5 0
270 2 6 0
NSE00622a
4) 5) 5 5 5 5 5 5 5 5
NSE0_00621j
1 3 ,5
3 5
N S E 0 _ 0 0 6 2 3 b
6
275
468,5
403
465,5
1 1 )
3 7 3
3 )
2 8 7
123,5
6 9
13 30
11
10) c 169,5
210 55
300 1 5 9 0 9 0 9 0
3 5
2 6
382,5 Front connection (double hole)
367,5 according to DIN 43673 350
327 260
19) 55 55 55 55
62,5 13,5
2)
NSE0_00625h
40
80
NSE0_00624g 18)
7) 8)
9)
12)
6
a
493
373
287
11)
518,5
620
519
327,5
3)
460
NSE0_00626h
a
275
31
150
34
69
Ø14
76
10)
40
80
40
27 220 45 10)
14
6)
42 58 c 169,5 15 90 90 90
88,5
121,5
140,5
Vertical connection
350
38
55 55 55 55 260
11) b
38
NSE0_00629h
Ø 13,5 13,5
60
11)
30
NSE00627a
267,5
287
3)
127,5
139 68
270 25 NSE0_00628h 150
69
320 10)
410 165
15 90 90 90
350 ——— 4-pole version
260 2) For guide frame without arc chute cover, arc quenching space ≤ 690 V – circuit
breaker facing grounded or non-conductive surfaces.
3) Rivels (4 mm wide, 5 mm deep) for supporting phase barriers in the system.
4) Auxiliary connector with SIGUT screw terminals.
3) 5) Auxiliary connector with screwless connection method.
6) Dimension to inside surface of the closed cabinet door.
287
10)
Fixing holes 10 mm.
11)
10) 15 10) Terminal face.
55 18)
90 90 90 Circuit breaker upper edge, only 690 V (+20 %)and 1000 V circuit breakers.
19)
Arc quenching space, circuit breaker facing grounded or non-conductive surfaces,
only 690 V (+20 %) and 1000 V circuit breakers.
40 Siemens · 2012
© Siemens AG 2011
NSE0_00632h
14
NSE0_00631h
M 12
33
59
287
26
282,5
3)
59
142,5
69
121
10)
15 90 90 90
3)
Rivels (4 mm wide, 5 mm deep) for supporting phase barriers in the
system.
10)
Fixing holes 10 mm.
For safety clearances to grounded parts and to live parts see
page 38.
For more connection options see previous page.
Siemens · 2012 41
© Siemens AG 2011
35
NSE0_00633a
4) 5) 40 40
N S E 0 _ 0 0 6 3 4 d
275
NSE00635c
437,5
440,5
6
421
11)
e
3)
35
123,5
85 10
270 13,5
26
90 130 130 130
440
c 8 2
d
570
40
4 7 40 40
14)
80
N S E 0 _ 0 0 6 3 7 d
a
621
3)
NSE00638c
541,5
421
516
327,5
3)
451,5
461,5
6 11)
g
275
14
5,5
150
80
a
76
40
NSE0_00636e 45 90 130 130 130 13,5
150 6)
210 106 c 8 2
230 127
90 NSE00641
30
30 30
30
11)
Ø13,5 3) 3)
7) 7)
290
98
Ø9
134,5
35
NSE0_00639f
Rated a b c d e f g
circuit breaker
current
A
Up to 2000 10 15 10 11 451 34 541
2500 15 15 20 6 461 39 551
3200 30 30 20 6 461 39 551
For safety clearances to grounded parts and to live parts see
page 38.
Flange connections (see following page)
42 Siemens · 2012
© Siemens AG 2011
2)
85 Nm
541,5
30
516
345,5
Ø 13,5
79,5
NSE0_01868a
100
10
4011)
20
142
200 130 200
162
1)
Mounting space for removal of the arc chutes.
2)
Arc quenching space "≤ 690 V" – circuit breaker facing grounded or non-
conductive surfaces.
11)
Terminal face.
For safety clearances to grounded parts and to live parts see
page 38.
For more connection options see previous page.
Siemens · 2012 43
© Siemens AG 2011
N S E 0 _ 0 0 6 4 5 c
4) 5) 62,5 4 0 0
NSE0_00643b 9 0 9 0
9 0 9 0
NSE00644b
4 0 4 0
3 5
1 3 ,5
275
6
468,5
465,5
403
3 )
1 1 )
3 7 3
2 8 7
123,5
2 6
c
11
40 169,5
6 9
10) 270 10) 4 5 ,1
350 55
3 5
5 5 1 3 0 1 3 0 1 3 0
480
Front connection (double hole)
382,5 according to DIN 43673
5 3 0
N S E 0 _ 0 0 6 4 8 c
367,5 62,5 4 0 0
1 3 ,5
NSE0_00646f
327 13) 9 0 9 0 9 0 9 0
NSE00647b
2) 4 0 4 0
4 0
12)
8 0
7) 8)
9)
493
9
6
3 )
620
3 7 3
1 1 )
2 8 7
a
518,5
520
327,5
3)
34
460
275
1 4
a
6 9
150
8 0
Ø14 169,5
10)
76
5 5 4 5 1 3 0 1 3 0 1 3 0
4 0
31
40
27 220 45 6)
42 58
88,5
121,5
140,5
Ø 13,5 4)
Auxiliary connector with SIGUT screw terminals.
5)
11) Auxiliary connector with spring-loaded connection.
6) Dimension to inside surface of the closed cabinet door.
NSE00649a
7)
3WL circuit breaker in connected position.
8)
3WL circuit breaker in test position.
9) 3WL circuit breaker in disconnected position.
10)
139 138 Fixing holes, 10 mm in diameter.
270 95 11)
Terminal face.
460 12)
590 Guide frame upper edge – only 1000 V and 1150 V AC version.
13)
Arc quenching space, 1000 V and 1150 V circuit breaker facing grounded or
non-conductive surfaces.
530
400
90 90 90 90
NSE0_00652b
3)
287
69
10) 10)
55 45 130 130 130
44 Siemens · 2012
© Siemens AG 2011
4 0 0
38 b N S E 0 _ 0 0 6 5 1 a
30
30
3 )
290
2 8 7
100
135
6 9
157
172 5 5 4 5 1 3 0 1 3 0 1 3 0
NSE0_01869
109,5
4011) 4,6 10
20
177
197 55 45
200 130 200
Flange connection
NSE00653
5 3 0
4 0 0
N S E 0 _ 0 0 6 5 4 a
M 1 2 9 0 4 0
3 3
2 6
5 9
3 )
2 8 7
2 8 2 ,5
5 9
1 4 2 ,5
6 9
121
4 5 1 3 0 1 3 0 1 3 0
Siemens · 2012 45
© Siemens AG 2011
35
NSE0_00655a 50 50
13,5
NSE00656c
3)
NSE00657c
275
437,5
440,5
6
421
451
11)
26
123,5
35
270 205 12 20 130 210 210 210
11
680 82
890
4 0
12)
14)
8 0
N S E 0 _ 0 0 6 5 9 d
30
3 )
N S E 0 _ 0 0 6 6 0 c
6
621
5 4 1
4 2 1
1 1 )
541,5
516
327,5
3)
451,5
461,5
275
1 4
3 4
8 0
5,5
150
30
76
2 0 1 3 0 2 1 0 2 1 0 2 1 0
4 0
NSE0_00658e 45 8 2
35 150 6)
210 106
230 127
Vertical connection
107 20
30
10 NSE00663
15
30 160 15 130
11)
11) 3)
Ø13,5 40
330,5
7) 3) 7)
120
M10
94,5
NSE0_00661e
704 Ø 13,5
142
914
162
NSE00664a
3)
13)
——— 4-pole version Arc quenching space, 1000 V circuit breaker and circuit breaker with
1) switching capacity C, facing grounded or non-conductive surfaces.
Mounting space for removal of the arc chutes.
14) Space for electrical auxiliary circuit connections.
2)
Arc quenching space "≤ 690 V" – circuit breaker facing grounded or
non-conductive surfaces. For safety clearances to grounded parts and to live parts see
3)
Rivels (4 mm wide, 5 mm deep) for supporting phase barriers in the page 38.
system.
4)
Auxiliary connector with SIGUT screw terminals.
5)
Auxiliary connector with spring-loaded connection.
6)
Dimension to inside surface of the closed cabinet door.
7)
Fixing points for mounting the circuit breaker in the system.
11)
Terminal face.
12)
Circuit breaker upper edge, only 1000 V circuit breaker and circuit
breaker with switching capacity C.
46 Siemens · 2012
© Siemens AG 2011
N S E 0 _ 0 0 6 6 7 c
6 3 0
4) 5) 62,5 1 6 0 1 6 0 1 6 0 1 6 0
1 3 ,5
NSE0_00665b
NSE00666b
5 0 5 0
3 5
275
465,5
468,5
6
403
1 1 )
2 8 7
3 7 3
123,5
6 9
590
800 57 20
11
8 5 2 1 0 2 1 0 2 1 0
3 5
169,5 5 9 0
2 6
5 7 8 0 0
Front connection (double hole)
382,5 according to DIN 43673, 8 4 0
N S E 0 _ 0 0 6 7 0 c
367,5 up to 4000 A 6 3 0
1 3 ,5
NSE0_00668d
327 13) 62,5 1 6 0 1 6 0 1 6 0 1 6 0
2)
4 0
5 0 5 0
NSE00669b
12)
8 0
7) 8)
9)
9
30
493
6
1 1 )
2 8 7
3 7 3
620
518,5
520
327,5
3)
460
30
1 4
275
6 9
8 0
150
Ø14
10) 20
76
8 5 2 1 0 2 1 0 2 1 0
4 0
34
169,5 5 9 0
5 7 8 0 0
31
40
27 220 45 6)
42 58
88,5
121,5
140,5
Vertical connection, up to 6300 A
30 8 4 0
NSE00672a
30 30 Ø 13,5 38 6 3 0
11) 7 0 4
2 0
30
1 0
38
N S E 0 _ 0 0 6 7 3 b
11)
330,5
NSE00671a
124,5
2 8 7
94,5
139 260 24
270 217 177
6 9
4)
Auxiliary connector with SIGUT screw terminals.
5)
Auxiliary connector with spring-loaded connection.
6)
Dimension to inside surface of the closed cabinet door.
287
7)
3WL circuit breaker in connected position.
8)
3WL circuit breaker in test position.
9)
3WL circuit breaker in disconnected position.
10)
69
Siemens · 2012 47
© Siemens AG 2011
6 3 0
7 0 4
N S E 0 _ 0 0 6 7 6 a
1 6 0 1 6 0 1 6 0 1 6 0
1 2
3 3
M
5 9
2 8 7
2 6
2 8 2 ,5
5 9
1 4 2 ,5
5
6 9
3 0
121 5 7 8 5 2 1 0 2 1 0 2 1 0
5 9 0
8 0 0
9 1 4
48 Siemens · 2012
© Siemens AG 2011
■ Circuit diagrams
Terminal assignment diagram
14
F1, 2
– + OUT
Trip signalling switch S24 13 /COM16
1 2 3 4 5 6 7 8 9
Open
(position after tripping) 12 (Option F02/F12)
Y1
COM15/COM16 module is at position "-X7".
11
Close
– +
8
DPWrite Free
7
Enable
6
5
Signaling contact at the 1 st auxiliary release
External
Internal
IN
4
3
S23 2
Signaling contact at the 2nd auxiliary release
1
14 L+
1st auxiliary release F1 "ST" c
13 L–
12
S1 "NO"
11
10
S1 "NC"
9
Closing solenoid 8 L–
c
7 L+
6
5
"Ready to close" signal S20
4
S2 "NO"
3
2
S2 "NC"
1
(sw) (br)
Charging motor M 2 L+
c
opt. motor main switch S12 1 L–
Siemens · 2012 49
© Siemens AG 2011
L1 L1
(L+) release (L+)
OFF
contact
ON
-X5.10
-X7.14
-X7.12
-X6.10
-X5.12
-X6.14
-X6.12
-X6.2
-X6.6
-X5.8
-X5.4
-X6.4
-X5.2
-X5.6
-X6.7
-X7.9
5
1
3
-A1 ETU
version L
-S10
S
electr. I
ON
N N
G
R
-S11 -F5
-S20
-S24
-Y1 -T2
mech.
ON
-T3
NSE0_01558b
mech. -S12
-F1
OFF
-X5.9
6
2
4
-X6.1
-X5.7
-X5.3
-X6.9
-X6.13
-X6.3
-X5.5
-X6.11
-X7.13
-X5.11
-X8.9
-X5.1
-X8.10
-X6.8
-X6.5
N N
(L-) (L-)
* Short terminals, if no N sensor
50 Siemens · 2012
© Siemens AG 2011
module
module
4 4 4
ZSI
ZSI
ZSI
5 5 5
6 6 6 SENTRON 3WL SENTRON 3WL
3 3
module
module
5
6
1
2
3
4
4 4
ZSI
ZSI
5 ZSI module 5
SENTRON 3WL SENTRON 3WL 6 6
3 3
module
module
4 4
ZSI
ZSI
5 5 NSE0_01898
6 6
SENTRON 3WL
SENTRON 3VL SENTRON 3WL
Circuit diagram for a Zone Selective Interlocking functionality with multi-
3 ple infeed and several outgoing units with 3WL circuit breakers
module
4
ZSI
NSE0_01897
5
6
module
5
6
1
2
3
4
4 4
ZSI
ZSI
5 ZSI module 5
6 6
NSE0_01899
SENTRON 3WL
module
4 4
ZSI
ZSI
5 5
6 6
■ More information
Up-to-date information on the Internet at:
www.siemens.com/sentron
Siemens · 2012 51
© Siemens AG 2011
■ Technical specifications
Sizes II
Type 3WL12 10 3WL12 20 3WL12 40
Rated current In at 40 °C
Main conductors A ... 1000 2000 4000
Rated operational voltage Ue V DC ... 600/1000 ... 600/1000 ... 600/1000
(1000 V version, see Catalog LV 10.1, order code "A05")
Rated insulation voltage Ui V DC 1000 1000 1000
Rated impulse withstand voltage Uimp
• Main current paths kV 12 12 12
• Auxiliary circuits kV 4 4 4
• Control circuits kV 2,5 2,5 2,5
Isolating function to EN 60947-2 Yes Yes Yes
Permissible ambient temperature
• Operation °C –25/+70 –25/+70 –25/+70
• Storage °C –40/+70 –40/+70 –40/+70
Permissible load up to 40 °C A 1000 2000 4000
at rear horizontal main circuit up to 55 °C A 1000 2000 3640
connections up to 60 °C A 1000 2000 3500
(Cu painted black) up to 70 °C A 1000 1950 3250
Power loss at In for symmetrical loads
Withdrawable circuit breakers W 280 770 1640
Switching times
• Make-time ms 35 35 35
• Opening time ms 34 34 34
• Electrical make-time (through activation solenoid)1) ms 100 100 100
• Electrical opening time (through shunt release) ms 73 73 73
• Electrical opening time (instantaneous undervoltage release) ms 73 73 73
Endurance3)
• Mechanical (without maintenance) Operating cycles 10000 10000 10000
• Mechanical (with maintenance)2) Operating cycles 15000 15000 15000
• Electrical (without maintenance) Operating cycles 6000 6000 4000
• 1000 V version Operating cycles 1000 1000 1000
• Electrical (with maintenance)2) Operating cycles 15000 15000 15000
Switching frequency
• 600 V version 1/h 60 60 60
• 1000 V version 1/h 20 20 20
h m a x .
Mounting position 3 0 ° 3 0 ° 3 0 ° 3 0 °
= 1 m m
and/
or
N S E 0 _ 0 0 0 6 1 a N S E 0 _ 0 0 0 6 2 a N S E 0 _ 0 0 9 2 7 a
Degree of protection IP20 without cabinet door, IP41 with door sealing
frame, IP55 with cover
Auxiliary conductors (Cu) Standard connection = strain-relief clamp
Max. number of • Without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14)
auxiliary conductors × cross- • With end sleeve acc. to DIN 46228 Part 2 1 × 0.5 mm2 (AWG 20) ... 1 × 1.5 mm2 (AWG 16)
section • With twin end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
(solid/stranded)
Optional connection = tension spring
• Without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 2.5 mm2 (AWG 14)
• With end sleeve acc. to DIN 46228 Part 2 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
Weights 3-pole • Fixed-mounted circuit breakers kg 56 56 64
• Withdrawable circuit breakers kg 60 60 68
• Guide frames kg 31 31 45
4-pole • Fixed-mounted circuit breakers kg 67 67 77
• Withdrawable circuit breakers kg 72 72 82
• Guide frames kg 37 37 54
1) Make-time through activation solenoid for synchronization purposes 2) Maintenance means: replace main contact elements and arc chutes
(short-time excited) 50 ms. (see Operating Manual).
3) Further technical specifications on request.
Sizes II
Type 3WL12
Switching capacity class DC
Short-circuit breaking capacity
Up to 220 V DC Icc kA 35
Up to 300 V DC Icc kA 30
Up to 600 V DC Icc kA 25
Up to 1000 V DC Icc kA 20
Rated short-time withstand current Icw
0.5 s kA --
1s kA 351)/302)/253)/204)
2s kA --
3s kA --
1) 3)
At Ue = 220 V DC. At Ue = 600 V DC.
2) 4)
At Ue = 300 V DC. At Ue = 1000 V DC.
52 Siemens · 2012
© Siemens AG 2011
■ Characteristic curves
10000
R= 0.4 ... 1.0 n
R= 2 ... 10 s at 6 R
[s]
R= 10 s [B]
100 B
2 s [A]
B
A
A
10
1
MIN MAX
I= 1.5
I=1.25 I=
4 n
R
R
NSE0_01578
0,1
0,01
0,1 1 10
/ n
■ Dimensional drawings
DIGmat S100
257
DIG S100 3,5
250
AUTO
ON
_
136
R2 + MENUE
NSE0_01576
R1
115
122
NSE0_01575
AUTO MAIN
MAN PEAK DIAG
271
Siemens · 2012 53
© Siemens AG 2011
35
NSE0_00633a
4) 5) 40 40
N S E 0 _ 0 0 6 3 4 d
275
NSE00635c
437,5
440,5
6
421
11)
e
3)
35
123,5
85 10
270 13,5
26
90 130 130 130
440
c 8 2
d
570
Front connection (double hole)
16) 17) 1) 2) according to DIN 43673
12) 90 90 90 90
40
15) 4 7 40 40
14)
80
N S E 0 _ 0 0 6 3 7 d
a
602
3)
NSE00638c
541,5
421
516
327,5
3)
451,5
461,5
11)
447
6
g
275
14
5,5
150
80
a
76
40
NSE0_02003 45 90 130 130 130 13,5
150 6)
210 106 c 8 2
230 127
Vertical connection
Ø 13,5
90 NSE00641
30
30 30
30
11)
Ø13,5 3) 3)
7) 7)
290
98
Ø9
134,5
35
NSE0_00639f
54 Siemens · 2012
© Siemens AG 2011
N S E 0 _ 0 0 6 4 5 c
4) 5) 62,5 4 0 0
NSE0_00643b 9 0 9 0
9 0 9 0
NSE00644b
4 0 4 0
3 5
1 3 ,5
275 6
468,5
465,5
403
3 )
1 1 )
3 7 3
2 8 7
123,5
2 6
c
11
40 169,5
6 9
10) 270 10) 4 5 ,1
350 55
3 5
5 5 1 3 0 1 3 0 1 3 0
480
Front connection (double hole)
382,5 according to DIN 43673
5 3 0
N S E 0 _ 0 0 6 4 8 c
367,5 62,5 4 0 0
1 3 ,5
327 16) 17) 9 0 9 0 9 0 9 0
NSE00647b
NSE0_02084 2) 4 0
4 0
4 0
15)
8 0
12)
7) 8)
493
6
9) 3 )
9
3 7 3
1 1 )
2 8 7
651
34
518,5
a
520
327,5
496
3)
460
1 4
c
6 9
275
8 0
a
169,5
150
Ø14
5 5 4 5 1 3 0 1 3 0 1 3 0
4 0
10)
76
31
40
27 220 45 6)
42 58
88,5
121,5
140,5
——— 4-pole version
30 30
2)
For guide frame ≤ 690 V, without arc chute cover, arc quenching space facing
grounded or non-conductive surfaces.
3)
Rivels (4 mm wide, 5 mm deep) for supporting phase barriers in the system.
38
7)
3WL circuit breaker in connected position.
8)
3WL circuit breaker in test position.
9)
3WL circuit breaker in disconnected position.
139 138 10)
Fixing holes, 10 mm in diameter.
270 95 11)
460 Terminal face.
590 12)
Guide frame upper edge – only 1000 V AC version.
15)
Arc quenching space, 300 V circuit breaker facing grounded or non-conductive
530 surfaces.
400 16)
90 90 90 90 Arc quenching space, 600 V circuit breaker facing grounded or non-conductive
surfaces.
NSE0_00652b
17)
Arc quenching space, 1000 V circuit breaker (with high arc chute) facing grounded or
non-conductive surfaces.
3)
287
69
10) 10)
55 45 130 130 130
Siemens · 2012 55
© Siemens AG 2011
38 b N S E 0 _ 0 0 6 5 1 a
30
30
3 )
2 8 7
290
100
135
6 9
157 5 5 4 5 1 3 0 1 3 0 1 3 0
172
Flange connection
NSE00653
5 3 0
4 0 0
N S E 0 _ 0 0 6 5 4 a
M 1 2 9 0 4 0
3 3
2 6
5 9
3 )
2 8 7
2 8 2 ,5
5 9
1 4 2 ,5
6 9
121
4 5 1 3 0 1 3 0 1 3 0
56 Siemens · 2012
© Siemens AG 2011
■ Circuit diagrams
L1
AC230
+
N
PE -
DC24
AC230
+ - + - + - + -
12
14
-K1 11 -Q01 1 3 5
Excitation / Alarm
Automatic / Reset
-X6.14 -X5.12
12 14
SENTRON
3WL
-K2 11 -F1 -F3
NSE0_01577a
-X6.13 -X5.11
-Q01 2 4 6
Circuit diagram of the DIGmat S100 and the 3WL non-automatic air circuit
breaker
Application examples
Rated operational Required, For 3-pole non-automatic air circuit For 4-pole non-automatic air circuit breakers
voltage series-connected breakers (operational currents up to 4000 A/conducting path)
breaks at (operational currents up to 4000 A/conduct-
rated voltage ing path)
Up to 300 V + 10 %
The connection to the circuit breakers is not dependent on direc- current. If the parallel or series connection is made at a distance
tion and polarity; the circuit diagrams can be adapted accord- of 1 m from the connecting bars, the circuit breaker can be used
ingly. at full operational current load.
If the parallel or series connections are made directly at the
connecting bars, for thermal reasons the continuous load on the
] Grounded-neutral system
Siemens · 2012 57
© Siemens AG 2011
■ More information
Up-to-date information on the Internet at:
www.siemens.com/sentron