Professional Documents
Culture Documents
Home / Technical Articles / Close and charging motor control circuits for a power circuit breaker explained in
detail
CB Control Schematics
This technical article deals with schematics of close and charging motor
control circuits for a medium-voltage circuit breaker. The proper functioning
of MV switchgear depends on control circuits. For the switchgear to operate
properly, the integrity of these control circuits is crucial, hence records of
commissioning and maintenance activities are crucial for troubleshooting
procedures.
Close and charging motor control circuits for a power circuit breaker
explained in detail (on photo: Operating mechanism of Siemens's medium-
voltage vacuum circuit breaker)
In order to gain the skills of troubleshooting and following the sequence of
operations, one must also be able to understand and interpret control
circuits.
Despite having numerous control circuits, all of them ultimately boil down to
the CB close/trip coils. It’s worth mentioning that switchgear designs must
incorporate interlock systems in order to prevent unintentional closures that
could compromise the security of both people and equipment.
Protection relays for medium-voltage circuit breakers are not built within the
circuit breaker like those for low-voltage breakers, nor are they powered by
the primary circuit’s current. The safety relays are offered externally.
Because of this, medium voltage circuit breakers rely on control power to
precisely and consistently trip or open the breaker in the case of a
malfunction.
Since the availability of control power is critical to the protective function of
a medium-voltage circuit breaker , the control power source is extremely
reliable.
The most reliable source in a utility electric generation station is a DC
source from a station battery system. Even on a loss of all AC power in
the power plant, the battery voltage is maintained and the breakers are able
to provide their circuit protective functions.
While the protective relay in medium voltage applications requires control
power, the typical medium voltage breaker is closed and opened via
mechanical springs in the breaker and there is a manual close and trip
button on the face of the breaker along with a flag indicating breaker status.
The operating mechanism is a stored-energy mechanism. The closing spring
is charged either electrically or manually. It latches tight at the end of the
charging process and serves as an energy store. The force is transmitted
from the operating mechanism to the pole assemblies via operating levers.
Where:
1. Closing Spring
2. Latch Check Switch (To Rear of Motor Cutoff Switch)
3. Motor Cutoff Switch
4. Closing cam
5. Spring Release Assembly
6. Shunt Trip Assembly
7. Closing Spring
8. Reset/Opening Spring
9. Manual Charge Socket
10. Ratchet Wheel
11. Operations Counter
12. Charging Motor
Figure 2 shows the typical close and charging motor control circuit for a
power circuit breaker. Table 1 defines some of the functions of the contacts
in the control schematics of Figures 2 and 3 (see below).
With the breaker open, the contact 52/b is closed. The 52/b contact is an
auxiliary contact that simply mirrors breaker status. When the breaker is
open, the 52/b contact is closed, and when the breaker is closed, the 52/b
contact is open. The normally open spring-charged limit switch (LS) contact
below the 52/b contact is closed when the closing spring is charged.
This is a normally open contact off the LS mechanism. In order to ensure that
there is mechanical force available to close the breaker, this contact is only
closed when the closing spring is charged.
Downstream of the 52/b contact is the latch check switch (LCS). The circuit
breaker can be used for instantaneous reclosing thanks to the latch check
switch. Before allowing the instantaneous re-closure, the switch makes sure
that the mechanical mechanism has been reset and is prepared for a reclose
following a breaker trip.
Downstream of the latch check switch (LCS) is a normally closed contact
from the anti-pump relay (Y). The anti-pump relay (Y) acts as a one-shot
device.
Looking at Figure 2, you can see that the anti-pump relay is driven by the
close signal on stab pin 11 and the position of the charging spring limit
switch normally closed contact.
Notice that the red light is not only fed from two 52/a contacts in series but is
also fed through the breaker trip coil between the two 52/a contacts.
This is done for the following reason: When the breaker is closed (via the
52/a contact) AND there is continuity through the trip coil, the red light will be
activated. If you approach this breaker and notice that the green light is on
and the red light is off, you will know that it is open and that you have the
power to close it.
If you approach this breaker and observe the red light on and the green
light off, you will know it is closed, have control power available to trip it, and
continuity through the trip coil, which confirms the trip coil’s integrity.
If you approach the breaker and neither the red nor the green light is on,
what does that mean?
One of two things is implied by this. Either the breaker is closed but the
trip coil has failed and is open, or we have opened our fuse to the breaker’s
trip circuit. It is crucial to be alert to this condition and raise the alarm so that
the problem can be fixed. A contact closure from the protective relay (PR) or
the control switch trip contact (CS/T) will NOT open or trip the breaker if the
breaker is closed and the trip coil is open.
This indicates that we have lost any overcurrent, differential, or other
protection that this breaker may have been providing, and this issue needs
to be fixed right away.
Suggested Reading – Tricks in designing and analyzing schematics and
diagrams of HV substations
This is a good moment to explain a word of caution about the location of
the red light! Notice that when the breaker is closed, the red light is
illuminated by allowing current to flow through the trip coil. To
prevent nuisance tripping of the breaker , the resistance that the red light
presents must be much higher than the resistance that the trip coil presents
to prevent this current from activating the trip coil.
Said in another way, the current required to illuminate the red light must be
substantially lesser than the minimum current required to activate the trip
coil. The same discussion pertains to any device connected in parallel with
the trip contacts. One common application of modern distributed control
systems (DCS) is to parallel a voltage input to the DCS with the trip
contacts.
To stop the breaker from accidentally tripping, the input resistance of this
DCS input must be significantly higher than the resistance of the trip coil.
Additionally, it is standard procedure to connect two DCS voltage inputs that
are in series with one another in parallel with the trip contact when the
breaker is essential to the proper operation of the plant.
This is done so that, in the event one of the two cards fails shorted, it does
not cause a nuisance trip of the breaker.
Figure 4 – ABB UniGear ZS1 vacuum circuit breakers (VCB) – photo credit:
slaters-electricals.com
For metal-enclosed interrupter IEEE C37.20.3 applies. Unless the customer
specifies other arrangements, the phase arrangement on a three-phase
assembled switchgear bus and connection are set up as phase A, phase B,
and phase C from front to back, or top to bottom, or left to right as viewed
from the front of the switchgear.
When viewed from the front of the switchgear, the polarities on the buses
and connections of DC assembled switchgear are set up as positive, neutral,
or negative from front to back, or from top to bottom, or from left to right.
Even though this is the IEEE standard, switchgear is always built
specifically for a customer needs, so the user should always refer to
specific switchgear construction drawings for information on the phase
orientation of the switchgear. The IEEE standard phase configuration is
frequently deviated from in older generation stations. In some older
stations, A-B-C phase rotation was west to east and south to
north instead of left to right and top to bottom.
Below is a description of some of the auxiliary contacts in a breaker, starter,
or cubicle. A form “a” contact is a normally open contact while a form
“b” contact is a normally closed contact. A form “c” contact has a normally
open and normally closed contact with one side being common.
Below are some specific standard nomenclatures for auxiliary contacts along
with their description.