You are on page 1of 2

A Preferred Power Solutions Strategic Business Partner

Galleon Pro 11
3P Series
lOKVA - 200KVA
Online Double Conversion
3 Phase In/ 3 Phase Out UPS

• True double-conversion sinewave UPS


• DSP technology guarantees high performance
• Output power factor 0.9 for 100K-200KVA, Pf=1.0 for 10K-80KVA
• Active power factor correction in all phases
• 50Hz/60Hz frequency converter mode
• ECO mode operation for energy saving
• Emergency Power Off (EPO) feature available
• Adjustable battery quantities Design
• Adjustable charging current, up to 12A for 10K-40KVA, 24A for 60- 80KVA
• 10" touch colored LCD for 100KVA and higher model
• 4.3" touch LCD for 10KVA - 80KVA
• Parallel Capability up to 3 units for 10K-80KVA, 2 units for 100KVA and above
• Maintenance bypass available
• Dual Inputs for flexible configuration for 10K-80KVA (100KVA and above are Optional)
• Generator Compatible
• Cold Start Capability
Mode 10K/KS 15K/KS 20K/KS 30K/KS 40K/KS 60KS 80KS 100KS 120KS 160KS 200KS
Power (KVA) 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA 80KVA 100KVA 120KVA 160KVA 200KVA
Power (KW) 10KW 15KW 20KW 30KW 40KW 60KW 80KW 90KW 108KW 144KW 180KW
INPUT
Nominal Voltage Three Phase 3 x 380V, 3 x400V, 3 x 415V ( 4 Wires, 3 phases + N + E)
190 – 520 VAC (3-Phase) @ 50% load 208 – 478 VAC (3-Phase) @ 70% load
Input Voltage Range
305 – 478 VAC (3-Phase) @ 100% load 305 – 478 VAC (3-Phase) @ 100% load
Frequency Range 46 - 54Hz or 56 - 64Hz 40 ~ 70Hz
Power Factor ≥ 0.99 @ 100% Load
Output
Nominal Voltage Three Phase 3 x 380V, 3 x400V, 3 x 415V ( 4 Wires, 3 phases + N + E)
Regulation +/-1%,
Frequency (Synchronized) 46 ~ 54 Hz or 56 ~ 64Hz
Frequency (Batt. mode) 50Hz / 60Hz +/- 0.1Hz , Slew Rate @+/- 1 Hz/s
Waveform Pure Sine wave
≤ 2% THD (Linear Load), ≤ 2% THD (Linear Load),
Harmonic Distortion
≤ 5% THD (Non-Linear Load) ≤ 4% THD (Non-Linear Load)
100~110%: 60 mins; 111~125%: 10 mins ;
AC mode 100~110%: 60 mins; 111~125%: 10 mins ; >150%: Immediately
126~150%: 1 min; >150%:200 ms
Overload
100~110%: 60 mins; 111~125%: 10 mins ;
Battery Mode 100~110%: 60 mins; 111~125%: 10 mins ; >150%: Immediately
126~150%: 1 min; >150%:200 ms
Crest factor 3.0 to 1 (max)
EFFICIENCY
AC Mode 95.5% 94.5%
Econ Mode 98.5% 98.0%
Battery Mode 94.5% 93.0%
BATTERY
Capacity 12V9Ah 12V7Ah 12V9Ah 12V7Ah 12V9Ah
(10+10)
Numbers (16+16) pcs (16+16) pcs x 2 strings
pcs
Standard
Recharge 9 hours recover to 90% capacity (default) Not Applicable
Model
Charging, A 1A – 12A (Adjustable)
Charging, Vdc +/- 218 Vdc +/-10%
Capacity Depending on the Battery Capacity and application
(10+10)
Extended Numbers 32 (16+16) – 40 (20+20) pcs , Adjustable
pcs
Model
Charging, A 1A – 12A (Adjustable) 2A – 24A (Adjustable) 24A 32A 40A 48A
Charging, Vdc +/- 13.65 x N ( N=16-20) +/- 13.7 x N ( N=16-20)
Display
LCD Display UPS Status, Load level, Battery level, Input/Output Voltage, Discharge time & Fault 10” Color LCD with Touch Screen Features
PHYSICAL
Enclosure Protection IP 20
Dimension,
Standard 250 x 626 x 750 300 x 815 x 1000
WxDxH (mm) Not Applicable
Model
Weight, Kg 135 139 225 250
Dimension,
Extended 250 x 626 x 750 300 x 815 x 1000 360 x 790 x 1010 567 x 940 x 1015 567 x 1040 x 1442
WxDxH (mm)
Model
Weight, Kg 28 43 60 61 108 113 194 229 306 340
ENVIRONMENT
Temperature and Humidity 0°C to 40°C, and 0-95% without Condensation
< 55 dB < 60 dB < 75 dB
Noise level, dB < 58 dB @ 1.0 M < 70 dB @ 1.0 M < 70 dB @ 1.0 M < 73 dB @ 1.0 M
@ 1.0 M @ 1.0 M @ 1.0 M
Management
Smart RS232/USB Support Windows 2000/2003/XP/Vista/2008, Windows 7/8/1, Linux and MAC
Optional SNMP Card for Remote Monitoring via Network , ModBus Card for BMS System
STANDARDS
Safety EN-62040-1-2, EN 60950-1
Electromagnetic
EN-61000-2, EN-61000-4
Compatibility (EMC)
Operating VFI-SS-111 in accordance with EN 62040-3
Design CE
Note: Specification subject to change without prior notice