DETAIL 1160

Cover expansion joint with a


strip of Duro-Last membrane
Batt insulation or
polyethylene sponge tube
Field weld
(Note 1, typ.)

Wood nailer Approved cover


(Note 2) board (Note 3)
Approved
insulation
(Note 3)

3-Inch Square Metal Plates or Approved vapor


Cleat Plates fastened a maximum barrier (Note 3)
of 18 inches on center with Any thickness Duro-Last
approved Duro-Last fasteners (typ.) membrane to support
insulation or sponge tube

Note 1: All field welds shall be a minimum of 1-1/2 inches wide.


Note 2: A wood nailer is required if 1 inch of insulation or greater is used. The top of the
wood nailer is to be flush with the top of the insulation. Wood nailers must
withstand a minimum force of 180 pounds per lineal foot (per building code). Any
pull values greater than 270 pounds will allow for a fastener spacing of 18 inches
on center. Pull values less than 270 pounds will require additional fasteners. The
installing contractor is responsible for meeting building codes.
Note 3: Refer to specifications for vapor barrier, insulation and cover board requirements.

REVISED: 01/31/2017 GENERAL DETAIL FOR MECHANICALLY FASTENED SYSTEMS


PREVIOUS: 01/01/2009 DECK-LEVEL EXPANSION JOINT
SCALE: NONE NEW CONSTRUCTION OR RE-ROOF