AQV24UGBN AQV24UGBX
Air Conditioner
Mode
Mode can help you sleep quickly and
soundly and wake up refreshed.
AQV18PSBN
Silence Mod
AQV24PSBN When you use the "Silence Mode", you can
experience extremely quiet operation of your
air conditioner.
AQV18PSBX
AQV24PSBX
Operating Instructions and Installation
Contents
11. Precautions ........................................................................................................................................ 1-1
1-1 Installing the air conditioner .......................................................................................................... 1-1
1-2 Power supply and circuit breaker .................................................................................................. 1-1
1-3 During operation .............................................................................................................................. 1-1
1-4 Disposing of the unit ....................................................................................................................... 1-2
1-5 Others ................................................................................................................................................. 1-2
Samsung Electronics 1
Operating Instructions and Installation
Contents
9. Circuit Descriptions ...................................................................................................................... 9-1
9-1 PCB Circuit Descriptions .................................................................................................................. 9-1
9-2 Refrigerating Cycle Diagram .......................................................................................................... 9-3
2 Samsung Electronics
1SPEVDU4QFDJGJDBUJPOT
5IF'FBUVSFPG1SPEVDU
QCatechin Filter
QDeodorizing Filter
4BNTVOH&MFDUSPOJDT
AQV24PSB
2.2/6.8/8
Heating 1.9/7.8/10
15/68/88
Heating 15/66/100
50 50
Heating 60 60
3.21
Heating 3.61
2.6/9.5/12.5
Heating 2.3/10/16.5
70/90/95
H e a tin g 7 0 /9 0 /9 5
mm 1065x230x298 8 8 0 x7 9 8 x3 1 0
Weight(Net) kg 13 59.2
UG4T200FUAE4-SS
1650
AQV18PSB
1.6/5.0/6.0
Heating 1.2/6.0/7.5
15/63/76
Heating 15/71/93
2
16/14/12 -
16/14/12 -
46 46
Heating 57 57
3.40
Heating 3.61
310/1470/1800
Heating 260/1660/2300
1.6/6.8/8.3
Heating 1.6/7.7/10.5
75/90/95
H e a tin g 7 5 /9 0 /9 5
mm 1065x230x298 7 9 0 x5 4 5 x2 8 5
Weight(Net) kg 13 36
φ
φ12.7
φ20x550
UG4T150FUAJQ-SS
24
1300
6
2-3 The Comparative Specifications of Product
Development Model
Item
AQV24PSB
Indoor Unit
Design
Outdoor Unit
Evaporator
Air Purifying System Filter Catechin Filter
Deodorizing Fiter
Development Model
Item
AQV18PSB
Indoor Unit
Design
Outdoor Unit
In d o o r U n it 1 3 kg
Net Weight
O u td o o r U n it 36kg
In d o o r U n it 46d B ↓
Noise
O u td o o r U n it 57d B ↓
DB93-11115K
DB98-32436A
Operating Instructions and Install ation
4-3
Parts List
30-2
30-1
3
Exploded Views and Parts List
Parts List
Qty
No. Code No. Description Specification SA/SNA
AQV18PSBX
1 DB90-05752A ASSY CABI FRONT ASSY 1 SA
2 DB63-02588A GUARD FAN PP 1 SA
3 DB90-05746A ASSY BASE OUT ASSY 1 SA
4 DB61-04339A BRACKET-VALVE SGCC-M(PAINTED) 1 SA
5 DB31-00564A MOTOR FAN ASSY 1 SA
6 DB67-01042A FAN-PROPELLER PP-(GF+PD)40, 410 1 SA
7 6009-001369 SCREW-HEX M4, L12 3 SA
8 DB60-30020A SCREW-MACHINE M6,ZPC(WHT) 1 SA
9 DB61-04320A BRACKET MOTOR SGCC-M 1 SA
10 DB90-05736A ASSY CABINET-UPPER ASSY 1 SA
11 DB94-02998A ASSY-PARTITION ASSY 1 SA
12 DB27-00042B COIL CHOKE-REACTOR 5mH,15A 1 SA
13 DB96-15137A ASSY COND ASSY 1 SA
14 DB64-02444A SCREEN-COND BAR ASSY 1 SA
15 DB90-05751A ASSY CABINET-SIDE RH ASSY 1 SA
16 DB90-05740A ASSY COVER VALVE ASSY 1 SA
17 DB90-05749A ASSY CABINET-SIDE LF ASSY 1 SA
18 UG4T150FUAJQSS COMPRESSOR ROTARY 1 SA
19 6021-001142 NUT-HEXAGON FLANGE M5,ZPC(YEL) 1 SA
20 DB60-30028A SCREW-HEX M8,ZPC(WHT) 3 SA
21 DB63-02296A GROMMET ISOLATOR ASSY 3 SA
22 DB63-02310A COVER TERMINAL NORYL 1 SA
23 DB63-00817B GASKET EPDM RUBBER 1 SA
24 DB63-02865A FELT-COMP UPPER OUT FELT+PVC 1 SA
25 DB63-02862A FELT-COMP SIDE FELT 1 SA
26 DB63-02866A FELT-COMP SIDE OUT FELT+PVC 1 SA
27 DB63-02864A FELT-COMP BASE FELT 1 SA
28 DB93-10960B ASSY CONTROL OUT ASSY 1 SNA
28-1 DB93-10952A ASSY PCB MAIN OUT ASSY 1 SA
29 DB96-15136A ASSY-VALVE 4WAY ASSY 1 SA
30 DB96-15135A ASSY-EEV ASSY 1 SA
30-1 DB62-04065A VALVE EXPANSION BODY FUJIKOKI 1.65 1 SA
30-2 DB62-05932B VALVE EXPANSION COIL FUJIKOKI 6-PIN 1 SA
TERMINAL
MPI WIRE
5-4 Ass'y Control Out
Model
KCaution:
The terminal is locking type.
So, when you separate terminals,
pull pressing the button.
Button
KCaution:
When you separate the connector,
pull pressing the locking button.
KCaution:
When you separate the connector,
pull pressing the locking button.
KCaution:
When you separate the connector,
pull pressing the locking button.
KCaution:
When you separate the connector,
pull pressing the locking button.
$PNNPO8PSL
-PPTFOGJYJOHTDSFX $$8
PGUIF$PWFS
$POUSPMBOEEFUBDIUIF$PWFS$POUSPM
-PPTFOGJYJOHTDSFXT $$8
BOEEFUBDIUIF
$BCJOFU6QQFS
-PPTFOTDSFX $$8
GJYFEUPBTTFNCMF$POUSPM
#PYXJUI$BCJOFU4JEF3)
-PPTFOGJYJOHTDSFXT $$8
BOEEFUBDIUIF
$BCJOFU4JEF3)
-PPTFOGJYJOHTDSFXT $$8
PGUIF$BCJOFU
'SPOU
-PPTFOTDSFXT $$8
GJYFEPOUIF(VJEF
$POEFOTFS
'BO
%FUBDIUIF/VU'MBOHFMJLFUIFQJDUVSFPO
UIFSJHIUTJEF 5VSODMPDLXJTFCFDBVTFUIF
.PUPS TDSFXJTMFGUIBOEFE
%FUBDIUIF'BO1SPQFMMFS
-PPTFOGJYJOHTDSFXT $$8
UPEFUBDI
UIF.PUPS
%JTDPOOFDUUIFXJSFCFUXFFO"TTZ$POUSPM
0VUBOE.PUPS
-PPTFOGJYJOHTDSFXT $$8
BOEEFUBDIUIF
#SBDLFU.PUPS
"TTZ$POUSPM0VU
%FUBDITFWFSBMDPOOFDUPSTGSPNUIF
"TTZ$POUSPM0VU
%FUBDITFWFSBMDPOOFDUPSTGSPNUIF1$#PG
"TTZ$POUSPM0VU
1VMMVQUIF"TTZ$POUSPM0VU
)FBU&YDIBOHFS
3FMFBTFUIFSFGSJHFSBOUBUGJSTU
-PPTFOGJYJOHTDSFX $$8
BOEEFUBDIUIFTUFFM
CBS
%JTBTTFNCMFUIFQJQFTJOCPUIJOMFUBOEPVUMFU
XJUIXFMEJOHUPSDL
#FGPSFZPVEJTBTTFNCMFUIFQJQFTBOE
$POEFOTFS
CFTVSFUIBUUIFSFTIPVMECF
OPSFGSJHFSBOUSFNBJOFEJOUIFVOJU
-PPTFOGJYJOHTDSFX $$8
BOEEFUBDIUIF)FBU
&YDIBOHFS
$PNQSFTTPS
%JTBTTFNCMFUIF'FMU$PNQ4PVOE
-PPTFOUIFGJYJOHOVU $$8
BOEEFUBDIUIF
$PNQSFTTPS-FBE8JSF
-PPTFOUIFCPMUT $$8
BUUIFCPUUPNPG
$PNQSFTTPSMJLFUIFQJDUVSFPOUIFSJHIUTJEF
*UFNTUPCFDIFDLFEGJSTU
5IFJOQVUWPMUBHFTIPVMECFSBUJOHWPMUBHFSBOHF
5IFBJSDPOEJUJPOFSNBZOPUPQFSBUFQSPQFSMZJGUIFWPMUBHFJTPVUPGUIJTSBOHF
*TUIFMJOLDBCMFMJOLJOHUIFJOEPPSVOJUBOEUIFPVUEPPSVOJUMJOLFEQSPQFSMZ
5IFJOEPPSVOJUBOEUIFPVUEPPSVOJUTIBMMCFMJOLFECZDBCMFT
$IFDLUIFUFSNJOBMTJGUIFJOEPPSVOJUBOEPVUEPPSVOJUBSFQSPQFSMZMJOLFECZUIFTBNFOVNCFSPGDBCMFT
0UIFSXJTFUIFBJSDPOEJUJPOFSNBZOPUPQFSBUFQSPQFSMZ
8IFOBQSPCMFNPDDVSTEVFUPUIFDPOUFOUTJMMVTUSBUFEJOUIFUBCMFCFMPXJUJTBTZNQUPNOPUSFMBUFEUPUIFNBMGVODUJPOPGUIF
BJSDPOEJUJPOFS
/P 0QFSBUJPOPGBJSDPOEJUJPOFS &YQMBOBUJPO
5IF01&3"5*0/JOEJDBUJPO-&% #-6&
CMJOLTXIFOBQPXFS *UJOEJDBUFTQPXFSJTPO5IF-&%TUPQTCMJOLJOHJGUIFPQFSBUJPO
QMVHPGUIFJOEPPSVOJUJTQMVHHFEJOGPSUIFGJSTUUJNF 0/0''CVUUPOPOUIFSFNPUFDPOUSPMVOJUJTQVTIFE
'BOTQFFETFUUJOHJTOPUBMMPXFEJO%3:
NPEF 5IFTQFFEPGUIFJOEPPSGBOJTTFUUP--JO%3:NPEF
'BOTQFFEJTTFMFDUFEBVUPNBUJDBMMZJO"650NPEF
$PNQSFTTPSTUPQTPQFSBUJPOJOUFSNJUUFOUMZJO%3:
$PNQSFTTPSPQFSBUJPOJTDPOUSPMMFEBVUPNBUJDBMMZJO%3:NPEF
NPEF EFQFOEJOHPOUIFSPPNUFNQFSBUVSFBOEIVNJEJUZ
5JNFS-&% 03"/(&
PGUIFJOEPPSVOJUMJHIUTVQBOEUIF 5JNFSJTCFJOHBDUJWBUFEBOEUIFVOJUJTJOSFBEZNPEF
BJSDPOEJUJPOFSEPFTOPUPQFSBUF 5IFVOJUPQFSBUFTOPSNBMMZJGUIFUJNFSPQFSBUJPOJTDBODFMMFE
5IFDPNQSFTTPSTUPQTJOUFSNJUUFOUMZJOB$00-NPEFPS 5IFDPNQSFTTPSTUPQTJOUFSNJUUFOUMZPSUIFGBOTQFFEPGUIF
%3:NPEF
BOEGBOTQFFEPGUIFJOEPPSVOJUEFDSFBTFT JOEPPSVOJUEFDSFBTFTUPQSFWFOUJOTJEFPVUTJEFBJSGSP[FO
EFQFOEJOHPOUIFJOTJEFPVUTJEFBJSUFNQFSBUVSF
<*ODBTFPGIFBUQVNQNPEFM> 5IFDPNQSFTTPSBOEJOEPPSGBOTUPQJOUFSNJUUFOUMZJGSPPN
5IFDPNQSFTTPSBOEJOEPPSGBOTUPQJOUFSNJUUFOUMZJO)&"5 UFNQFSBUVSFFYDFFETBTFUUJOHUFNQFSBUVSFJOPSEFSUPQSPUFDU
NPEF UIFDPNQSFTTPSGSPNPWFSIFBUFEBJSJOB)&"5NPEF
<*ODBTFPGIFBUQVNQNPEFM> 5IFDPNQSFTTPSPQFSBUFTJOBSFWFSTFDZDMFUPSFNPWF
*OEPPSGBOBOEPVUEPPSGBOTUPQPQFSBUJPOJOUFSNJUUFOUMZ FYUFSJPSJDFJOB)&"5NPEF
BOEJOEPPSGBOBOEPVUEPPS
JOB)&"5NPEF GBOEPOPUPQFSBUFJOUFSNJUUFOUMZGPSXJUIJOPGUIFUPUBM
IFBUFSPQFSBUJPO
4BNTVOH&MFDUSPOJDT
12-2-1.Communication error
Indoor display ○ ⊙ ⊙ Communication error
1.Checklist :
1) Is the cable between the indoor unit and outdoor unit connected correctly?
2) Isn't the power cable and communication cable cross?
2. Troubleshooting procedure
Restart after power off.
YES
NO
Is the connection of power cable
Correct the wrong cable.
and communication cable normal?
YES
NO
Is the power is normal?
Exchange the PBA of no power unit
(check the LED Lamp)
YES
NO
Is the communication error Terminate the service.
occurred again?
YES
1.Checklist :
1) Is the indoor units temperature sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
Sensor Replace
Is the sensor resistance value #1-#2
NO Sensor resistance value : 20℃ - 12.09kohm
10kohm±3% at the room
30℃ - 8.31kohm
temperature
35℃ - 6.94kohm
of 25℃
40℃ - 5.83kohm
YES
YES
Below 0.5V or Over 4.5V? Exchange the indoor PBA
NO
YES
12-3
12-2-3.Indoor Eva-in temperature sensor error
Indoor Eva-in temp sensor
Indoor display ⊙ ⊙ ○
error
1.Checklist :
1) Is the indoor units temperature sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
Sensor Replace
Isthe sensor resistance value
-#4 #3
NO Sensorresistance value ℃
: -12.09kohm
20
10kohm ±3% at the room
30℃ -8.31kohm
temperature
35℃ -6.94kohm
of 25℃
40℃ -5.83kohm
YES
YES
Below 0.5V or Over 4.5V? Exchangethe indoor PBA
NO
YES
12-4
12-2-4.When the Up/Down louver motor does not operate (Initial Diagnosis)
(Not displayed)
1.Checklist :
1) Is the input power voltage normal?
2) Is the Up/Down louver motor properly connected with the connector? (CN61)
2. Troubleshooting procedure
Unplug the power cord and plug it after 30seconds
later.
YES
NO
Is the connected louver wire? Connect the wire PBA to louver motor
YES
NO
YES
12-5
12-2-5.When the remote control is not receiving
1.Checklist :
1) Check if the connector was normally assembled.
2) Check the battery in remote control
3) All the lights out and check again : Change electronic typed to a fluorescent light
4) Put the set in operation and check the voltage of display PBA
5) Replace the display PBA
12-6
12-2-6.Indoor fan motor speed detecting error (BLDC fan)
1.Checklist :
1) Is the indoor units fan motor properly connected with the connector(CN72)?
2) Is the AC voltage correct?
2. Troubleshooting procedure
Restart after
power off.
YES
NO Terminate the NO
Isthe fan error appeared again?
service
YES
NO
Isthe voltage of CN72-#3
#1 over Followthe check procedure of Indoor unit power
250Vdc supply error check
YES
YES
12-7
12-2-7.Outdoor temperature sensor error
Indoor display ⊙ ○ ⊙ Outdoor error
1.Checklist :
1) Is the sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull-up correct?
Isthe sensor connector(CN251) NO
2-1. Troubleshooting procedure (ASV18P**)
connected correctly in accordance Reconnect the sensor connector.
with a color(BLU,6PIN)?
YES
Sensor Replace
Isthe sensor resistance value
-#2 #1
NO Sensorresistance value ℃
: -12.09kohm
20
10kohm ±3% at the room
30℃ -8.31kohm
temperature
35℃ -6.94kohm
of 25℃
40℃ -5.83kohm
YES
YES
Below 0.5V or Over 4.5V? Exchangethe Outdoor PBA
NO
YES
YES
Sensor Replace
2-2. Troubleshooting procedure
Isthe sensor resistance value (ASV24P**)
-#2 #1 NO Sensorresistance value ℃
: -12.09kohm
20
10kohm ±3% at the room 30℃ -8.31kohm
temperature of ℃
25 35℃ -6.94kohm
40℃ -5.83kohm
YES
YES
Below 0.5V or Over 4.5V? Exchangethe Outdoor PBA
NO
YES
12-8
12-2-8.Outdoor Coil temperature sensor error
Indoor display ⊙ ○ ⊙ Outdoor error
1.Checklist :
1) Is the sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull-up correct?
YES
Sensor Replace
Isthe sensor resistance value
-#6 #5
NO Sensorresistance value ℃
: -12.09kohm
20
10kohm ±3% at the room
30℃ -8.31kohm
temperature
35℃ -6.94kohm
of 25℃
40℃ -5.83kohm
YES
YES
Below 0.5V or Over 4.5V? Exchangethe Outdoor PBA
NO
YES
YES
Sensor Replace
2-2. Troubleshooting procedure
Isthe sensor resistance value (ASV24P**)
-#4 #3 NO Sensorresistance value ℃
: -12.09kohm
20
(CN501) 10kohm±3% at the room 30℃ -8.31kohm
temperature of ℃
25 35℃ -6.94kohm
40℃ -5.83kohm
YES
YES
Below 0.5V or Over 4.5V? Exchangethe Outdoor PBA
NO
YES
12-9
12-2-9.Outdoor Discharge temperature sensor error
Indoor display ⊙ ○ ⊙ Outdoor error
1.Checklist :
1) Is the sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull-up correct?
Isthe sensor connector(CN251) NO
2-1. Troubleshooting procedure
connected correctly (ASV18P**)
in accordance Reconnect the sensor connector.
with a color(BLU,6PIN)?
YES
Sensor Replace
Isthe sensor resistance value
-#4 #3
NO Sensorresistance value ℃
: -20242kohm
200kohm ±3% at the room
30℃ - 166ohm
temperature
35℃ - 138ohm
of 25℃
40℃ - 115kohm
YES
YES
Below 0.5V or Over 4.5V? Exchangethe Outdoor PBA
NO
YES
YES
Sensor Replace
Isthe sensor resistance value
-#4 #3
2-2. Troubleshooting Sensorresistance value ℃
: -20242kohm
3% at procedure
200kohm ± the room (ASV24P**) NO
30℃ - 166ohm
temperature
35℃ - 138ohm
of 25℃
40℃ - 115kohm
YES
YES
Below 0.5V or Over 4.5V? Exchangethe Outdoor PBA
NO
YES
12-10
12-2-10.Outdoor Discharge over temperature error
1.Checklist :
1) Check the discharge temperature in the outdoor unit
2) Check the compressor locking or gas leak
3) Download the EEPROM data
2. Troubleshooting procedure
Restart after
power off.
after 30min
~ 1Hr
YES
The condition is too poor for air conditioner to
operate
Wait until discharge temperature is decreased
Restart after power off
NO
Isthe discharge over temperature
sensor error appeared again? Terminate the service
YES
NO
Isthe discharge over temperature
Terminate the service
sensor error appeared again?
YES
Exchangedthe Compressor
12-11
12-2-11.Outdoor Fan motor error
1.Checklist :
1) Are the input power voltage and the power connection correct?
2) Is the motor wire connected to the outdoor PBA correctly?
3) Is there no assembly error or none-assembly in the terminal of motor wire connector?
4) Is there no obstacle at the surrounding of motor and propeller?
2. Troubleshooting procedure
Restart after
power off.
YES
NO Terminate the NO
Isthe fan error appeared again?
service
YES
NO
Isthe voltage of CN901-#3
#1 over Followthe check procedure of outdoor unit power
250Vdc supply error check
YES
YES
12-12
12-2-12.Compressor starting error
1.Checklist :
1) Is the connection of cable for the compressor?
2) Is the compressor wire is connected clockwise? U(RED)-V(BLU)-W(YEL)
3) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after
power off.
NO
Is the restart error occurred
again? Terminatethe service
YES
NO
Isthe connection of compressor
wire is normal? Connectthe comp wire normally
YES
NO
Is the restart error occurred
again? Terminate the service
YES
YES
Is the compressor body and
Exchange the Outdoor PBA
interphase resistance insulated?
NO
Exchangethe compressor
12-13
12-2-13.Compressor wire missing error/rotation error
1.Checklist :
1) Is the connection of cable for the compressor?
2) Is the compressor wire is connected clockwise? U(RED)-V(BLU)-W(YEL)
3) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after
power off.
NO
Is the restart error occurred
again? Terminatethe service
YES
YES
NO
Is the restart error occurred
again? Terminate the service
YES
YES
Is the compressor body and
Exchange the Outdoor PBA
interphase resistance insulated?
NO
Exchangethe compressor
12-14
12-2-14. O.C(Over Current) error
Indoor display ⊙ ○ ⊙ Outdoor error
1.Checklist :
1) Is the IPM Shunt(ASV18P**:R451,R452,R453,ASV24P**:R413,R414,R415) resistance value correct? Check the resistor is opened
2) Is the condition of surrounding temperature abnormal overload?
3) Is there any problem as like the temperature sensor separation or measurement value error?
4) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after
power off.
NO
Is the O.C
error occurred? Terminatethe service
YES
NO
Isthe connection of compressor
wire is normal? Connectthe comp wire normally
YES
NO
Is the O.C error occurred
again? Terminate the service
YES
Is the condition
of indoor/outdoor NO
Restart after returning to the normal load
temperature normal load?
YES
YES Is the O.C error NO Terminatethe
occurred again? service
YES
NO
Exchangethe compressor
12-15
12-2-15. DC_link voltage sensor error
1.Checklist :
1) Is the input voltage of outdoor terminal block is normal?
2) Is the reactor wire connected?
3) Is the DC_link capacitor(ASV18P**:CE101,CE102,CE103,ASV24P**:CE001,CE002,CE003,CE004)) assembled in
accordance the specification? (Outdoor PBA)
4) Is the DC_link resistor(ASV18P**:R104,R106,R107,R108,ASV24P**:R004,R005,R006,R007) value is normal? (Outdoor PBA)
YES
Restart after
power off.
Start the operation (cooling mode or heating mode)
YES
YES
NO
Is the reactor
insulation damaged? Exchange the Outdoor PBA
YES
Exchangethe Reactor
12-16
12-2-16. DC_link voltage under/over error, Over voltage protection error/PFC
over load
Indoor display ⊙ ○ ⊙ Outdoor error
YES
Restart after
power off.
YES
Restart after
power off.
Start the operation (cooling mode or heating mode)
YES
YES
NO
Is the reactor
insulation damaged? Exchange the Outdoor PBA
YES
Exchangethe Reactor
12-17
12-2-17.I_trip error, PFC over current
1.Checklist :
1) Is the PFC Shunt(ASV18P**:R062,R063,ASV24P**:R807,R808,R809) resistance value correct? Check the resistor is opened
2) Is the condition of surrounding temperature abnormal overload?
3) Is there any problem as like the temperature sensor separation or measurement value error?
4) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after
power off.
Is the condition
of indoor/outdoor NO
Restart after returning to the normal load
temperature normal load?
YES
Is the I_trip error NO Terminatethe
YES occurred again? service
YES
YES
12-18
12-2-18.Current sensor error/Input current sensor error
1.Checklist :
1) Is the PFC Shunt(ASV18P**:R062,R063,ASV24P**:R807,R808,R809) resistance value correct? Check the resistor is opened
2) Is the IPM Shunt(ASV18P**:R451,R452,R453,ASV24P**:R413,R414,R415) resistance value correct? Check the resistor is opened
3) Is there no short or open around IC451(ASV18P**) or IC451,IC452(ASV24P**)?
2. Troubleshooting procedure
Restart after
power off.
Is the PFC
shunt and IPM shunt NO Exchangethe Outdoor PBA
resistance value correct?
YES
YES
12-19
12-2-19.Heatsink sensor error/Heatsink over heat
1.Checklist :
1) Are there screws assembly in PBA-heatsink?
2) Is the gap PBA-heatsink
3) Is the fan operation normal?
4) Is the cover assembly in conrol-box normal?
Restart after
2. Troubleshooting power off.
procedure
NO
Are there screws in -heatsink?
PBA
Fasteningthe screw
(4 screws)
YES
NO
Check the fan connection
Is the fan
operation normal?
Change the Fan motor
YES
12-20
12-2-20.Comp Vlimit error/Comp current limit error
Indoor display ⊙ ○ ⊙ Outdoor error
1.Checklist :
1) Is the IPM Shunt(ASV18P**:R451,R452,R453,ASV24P**:R413,R414,R415) resistance value correct? Check the resistor is opened
2) Is the condition of surrounding temperature abnormal overload?
3) Is there any problem as like the temperature sensor separation or measurement value error?
4) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after
power off.
NO
Is the O.C
error occurred? Terminatethe service
YES
NO
Isthe connection of compressor
wire is normal? Connectthe comp wire normally
YES
NO
Is the O.C error occurred
again? Terminate the service
YES
Is the condition
of indoor/outdoor NO
Restart after returning to the normal load
temperature normal load?
YES
YES Is the O.C error NO Terminatethe
occurred again? service
YES
NO
Exchangethe compressor
12-21
12-2-21.EEPROM error/OTP error
1.Checklist :
1) Is there a short around micom?
2) Is there a short around IC202(ASV18P**) or IC701(ASV24P**)?
3) Did you download or insert EEPROM IC, after changing outdoor PBA?
YES
12-22
12-2-22.AC zero cross signal error
1.Checklist :
1) Check the power condition at customer's house (Is there any power noise?)
2) Have been there power failure?
2. Troubleshooting procedure
Restart after power off
YES
12-23
12-2-23.Operation condition secession error
1.Checklist :
1) Check the temperature around the outdoor unit.
2. Troubleshooting procedure
Restart after power off
YES
YES
12-23
12-2-24.Capacity miss match error
1.Checklist :
1) Check the Btu between indoor and outdoor unit
2) Check the indoor unit option and outdoor unit EEPROM data
2. Troubleshooting procedure NO
Isthe rated Btu between indoor Exchange the one of them according to the exact
unit and outdoor unit? model spec
YES
YES
YES
12-23
12-2-25.Gas leak error
1.Checklist :
1) Is the position of indoor Eva_in sensor normal?
2) Check the pipe crack
3) Check the EEV valve connection in Outdoor unit
4) Check the refrigerant was charged
2. Troubleshooting
Isthe position procedure
of indoor eva_in NO
Indoor sensor take the normal position
sensor normal?
YES
after 20minutes
later
Is the gas
leak error
appeared NO
Terminate the service.
again?
YES
YES
YES
YES
12-23
12-2-26.No power indoor (Initial Diagnosis) (Not displayed)
1.Checklist :
1) Is input power normal?
2) Is AC power linked correctly?
3) Is input voltage of DC_link capacitor normal?
4) Is the voltage of DC regulator normal?
2. Troubleshooting procedure
Unplug the power cord
YES
YES
YES
Is the DC_link
voltage normal? NO
Exchange the PBA
C102(+)-C101(-) :270Vdc~320Vdc
YES
YES
12-23
12-3-1 Pre-inspection Notices
1. Check if you pulled out the AC power plug when you eliminate the PCB or front panel
2. Don't hold the PCB side not impose excessive force on it to eliminate the PCB
3. Don’t pull the lead wire but hold the whole housing to connect or disconnect a connector to the PCB
4. In case of outdoor PCB disassembly, check first the complete discharge of condenser after 1 minute power off
12-26
"MJHONFOUBOE"EKVTUNFOUT
5FTU.PEF
Q)PXUP"QQSPBDI5FTU.PEF
:PVDBOBQQSPBDIUIF5FTU.PEFCZQSFTTJOHUIFPOPGGTXJUDIPG
JOEPPSVOJUGPSTFDPOET
POPGGTXJUDI
QZ5FTU.PEF0QFSBUJPO0QUJPO
"GUFSJOTUBMMJOHUIFBJSDPOEJUJPOFS
DIFDLXIFUIFSFBDITVCPSEJOBUFJTOPSNBMMZPQFSBUFEPSOPUCZPQFSBUJOHUIF5FTU.PEF
t8IFOBOFSSPSPDDVST
EJTQMBZUIF&SSPS.PEF
t0QFSBUJPO.PEF$PPMNPEF0QFSBUFUIFDPPMNPEFCZPQFSBUJOHUIFDPNQSFTTPSCZGPSDFXJUIPVUUIFDPNQSFTTPS0/0''
BDDPSEJOHUPUIFTFUUFNQFSBUVSFJOEPPSUFNQFSBUVSF %POPUGPMMPXUIFBOUJGSFF[FDPOUSPM
t6QEPXOMPVWFS6QEPXOTXJOHNPEF
t*OEPPS'BO)JHI
t#FDBVTFUIF5FTU.PEFPQFSBUFUIFDPPMNPEFCZGPSDFOPUSFMBUFEUPUIFTFUUFNQFSBUVSFJOEPPSUFNQFSBUVSF
DIFDL
XIFUIFSFBDITVCPSEJOBUFJTPQFSBUFEOPSNBMMZPSOPUBGUFSDPNQMFUJOHJOTUBMMBUJPOBOENVTUUVSOPGGUIFQPXFSPGUIF
BJSDPOEJUJPOFS
4BNTVOH&MFDUSPOJDT
GOOD
OPERA
TION
TIMER SLEEP DESCRIPTION
/SPI
○ ◎ ○ Indoor Room Temp Sensor Error
◎ ◎ ○ Evap In Temp Sensor Error
○ ○ ◎ Fan Error (Indoor)
◎ ○ ◎ Outdoor Error
○ ◎ ◎ Communication Error
◎ ◎ ◎ EEPROM Error
◎ ◎ ◎ Option Error
● LED ON
◎ LED BLINKING
○ LED OFF
3-3 Setting Option Setup Method
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
0 1 2 3 0 5 1 7 4 2 7 B 2 7 4 4 4 E
SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 SEG25 SEG26 SEG27 SEG28 SEG29 SEG30 SEG31 SEG32 SEG33 SEG34 SEG35 SEG36
3 7 8 2 0 0 0 3 4 C 4 B 1 0 4 4 4 2
SEG 1-6 SEG 7-12 SEG 13-18 SEG 19-24 SEG 25-30 SEG 31-36
0 1 2 3 0 5 1 7 4 2 1 D 2 7 3 2 3 C 3 7 2 6 0 0 0 3 4 7 4 3 1 1 3 F 4 7
AQV24PSB
SEG 1-6 SEG 7-12 SEG 13-18 SEG 19-24 SEG 25-30 SEG 31-36
0 1 2 3 0 5 1 7 4 2 7 B 2 7 4 4 4 E 3 7 8 2 0 0 0 3 4 C 4 B 1 0 4 4 4 2
3-4 EEPROM Downloading Method
13-2
9-2-1
AQV18PSB
3 2
6
7
8
9
AQV24PSB
10-3
Electrical Part List
9
Electrical Part List
1$#$JSDVJU%FTDSJQUJPOT
*OEPPS6OJU
4.141"35 #6;;&31"35
*/%003'"/$0/530- 46#1$#$0//&$503
;&30$3044*/(1"35 %*41-":1"35
*/%0035&.1&3"563&4&/403 45&1.0503*0/
.1*1"35 )6.*%1"35
5IJT%PDVNFOUDBOOPUCFVTFEXJUIPVU4BNTVOHTBVUIPSJ[BUJPO
4BNTVOH&MFDUSPOJDT
Circuit Descriptions Circuit Descriptions
*OEPPS6OJU 0VUEPPS6OJU
XBZWBMWF
&YQBOTJPOWBMWF
-JRVJETJEF
)FBU
&YDIBOHFS
&WBQPSBUPS
1SPQFMMFS'BO
)FBU
&YDIBOHFS
$POEFOTFS
$SPTT'BO
(BTTJEF
XBZWBMWF XBZWBMWF
$PNQSFTTPS $PPMJOH
)FBUJOH
(BT-FBL$IFDL1PJOU
4BNTVOH&MFDUSPOJDT
Main parts
Room
temperature
sensor
Air intake
indicator
Operation indicator
Power button
Smart Saver
Mode
Less energy usage makes your space
Set one of the 5 operating modes
cool between the temperature range
(see pages 10-11 for instructions).
of 24°C~30°C.
Auto Clean
Turbo Auto clean function – Dry inside of the indoor
Operate in auto fan speed to unit to get rid of odor.
cool quickly.
Quiet Air swing
Reduce noise generated from an indoor
unit during operation. automatically up and down.
Fan
h
h
Temp + -
Increase/Decrease the temperature by 1˚C.
such as Auto/Low/Medium/High.
Set the mode on.
Set
On Timer
Set the timer/ mode.
Set the On Timer on.
Cancel
Cancel the timer/ mode.
Time Up/Time Down
Adjust the time for timer/
mode.
This button doesn't have any function.
A S V 1 8 H B A X
Ex.) Maldives (Grille – White) Heat Pump12k Btu/h Model Indoor Unit
A Q V 1 2 P W A N
(1), (2) Product Division (6) Project (7) Grille Color (8) Version
A Mont Blanc (Premium) B Black A-K SSEC
AS Cooling Only B Cry stal - Temporary
S Silver L-S TSE
AQ Heat Pump Max(including Smart)
C W White
- Temporary
D Mont Blanc (Deluxe) F La Fleur (9) Unit
(3) Inverter E Cry stal (V ivaldi Deluxe) U Blue N Indoor Unit
V Inverter F Forte
G Grey X Outdoor unit
G GP
None Non Inverter H HB
J W W Premium
(4), (5) Capacity K Jungfrau-PRM
L Forte Deluxe
09 9,000 Btu
M Moderato
12 12,000 Btu N Neo Forte
18 18,000 Btu P Maldives
R Max Smart (V ivaldi Std)
24 24,000 Btu
S Forte Smart (SSEC)
T Boracay
U Max (V ivaldi Standard)
V V ivace
W WW
X Forte Smart (TSE)
Y Jungfrau-DLX
14-2 Low Refrigerant Pressure Distribution
Note : Please measure the refrigerant pressure after the air conditioner operates on testing cooling mode during more than
10 minutes.
AQV24PSB
Outdoor Temperature[ ]
Q1PXFS)FBU
8 DBMT LDBMI #UVI )1 LH NT *C NT
4BNTVOH&MFDUSPOJDT
2"GPS/POUSPVCMF
2 5IFDPPMJOHJTXFBL
" 8
IFOJUJTIPUPVUTJEF
JUTDPPMJOHDBQBDJUZEFDSFBTFTEVFUPUIFJODSFBTFPGUIFBNCJFOUUFNQFSBUVSF8IFO
UIFEVTUGJMUFSHFUTCMPDLFEPSXBSNPVUTJEFBJSHFUTJO
UIFDPPMJOHDBQBDJUZXJMMEFDSFBTF4P
NBLFTVSFUP
DMFBOUIFEVTUGJMUFSGSFRVFOUMZ
QSFWFOUIFBUMPTTCZDMPTJOHUIFEPPSTBOEJOTVMBUFUIFDPPMJOHBSFBCZVTJOH
DVSUBJOT
CMJOET
TIBEFTPSXJOEPXUJOUJOH
2 5IFDPPMJOHJTHPPEHFOFSBMMZ#VU JUHFUTXFBLXIFOJUJTDPOTJEFSBCMZIPU
2 *UGBJMTUPEPDPPMJOH
" 8
IFOUIFBJSDPOEJUJPOFSJTTFUUP7FOUJMBUJPOPSUIFEFTJSFEUFNQFSBUVSFJTTFUIJHIFSUIBOUIF
DVSSFOUUFNQFSBUVSF
JUGBJMTUPEPDPPMJOH*OUIJTDBTF
TFMFDU$PPMJOHPSTFUUIFEFTJSFEUFNQFSBUVSFMPXFS
2 *UGMPPETUIFGMPPS
2 8BUFSESJQTBUUIFESBJODPOOFDUJPO TFSWJDFWBMWF
PGUIFPVUEPPSVOJU
" 8
IFOBHMBTTCPUUMFJTUBLFOPVUPGUIFSFGSJHFSBUPS
NPJTUVSFHFUTDPOEFOTFEPOJUTTVSGBDFEVFUPUIF
UFNQFSBUVSFEJGGFSFODFT5IFTBNFQSJODJQMFBQQMJFTUPUIFBJSDPOEJUJPOFS8IFODPMESFGSJHFSBOUHPFT
UISPVHIUIFDPQQFSUVCF
NPJTUVSFHFUTDPOEFOTFEPOUIFTVSGBDFPGUIFUVCFBOEUIFDPOOFDUJPOBSFBT
-FBLBHF 5PQSFWFOUUIFXBUFSDPOEFOTBUJPO
UIFQJQFTBSFJOTVMBUFE#VU
UIFDPOOFDUJPOBSFBTPGUIFPVUEPPSVOJUBSF
OPUJOTVMBUFEGPSUIFQVSQPTFPGNBJOUFOBODFPSSFQBJS
BOEXBUFSHFUTDPOEFOTFEEVFUPUIFUFNQFSBUVSF
EJGGFSFODFTBOEESJQTEPXO(FOFSBMMZ
JUFWBQPSBUFTSJHIUBXBZ#VU
XIFOJUESJQTNVDIEVSJOHNVHHZEBZT
QVUBXBUFSQBOPOUIFGMPPS
2 *UMFBLTFWFOUIPVHIBESBJOQVNQJTVTFE
" * UPDDVSTXIFOUIFESBJOQVNQJTQMVHHFEPVUPSJUJTPVUPGPSEFS$IFDLUIFQPXFSPGUIFESBJOQVNQBOE
UIFQPTJUJPOPGUIFESBJOIPTF
BOEXIFOUIFQVNQJTGBVMUZ
DPOUBDUUIFESBJOQVNQNBOVGBDUVSFS4BNTVOH
&MFDUSPOJDTEPOPUNBOVGBDUVSFESBJOQVNQT4P
XFBSFOPUBCMFUPDPSSFDUUIFESBJOQVNQQSPCMFNT
2 8IFOFWFSUIFBJSDPOEJUJPOFSJTUVSOFEPO JUJSSJUBUFTNZFZFTBOEHJWFTNFBIFBEBDIF
" 5 IFSFBSFOPDPNQPOFOUTJOUIFBJSDPOEJUJPOFSJSSJUBUJOHUIFFZFTBOETFOEJOHPVUDIFNJDBMTNFMMT
#VU
XIFOUIFBJSDPOEJUJPOFSJTUVSOFEPO
PUIFSTNFMMTPVSDFTBSFTVDLFEJOUPUIFBJSDPOEJUJPOFSBOE
4NFMMT HFUPVUPGJU4P
GJOEBOESPPUPVUUIFTNFMMTPVSDFT(FOFSBMMZ
JUPDDVSTBUBJOUFSJPSSFOPWBUFEQMBDF
B
QIBSNBDZ
BHBTPMJOFIBOEMJOHQMBDF
BUJSFTIPQ
BTFDPOEIBOECPPLTIPQPSBOFMFDUSPOJDDPNQPOFOU
IBOEMJOHQMBDFXIFOJUTDIFNJDBMPSNVTUZTNFMMTBSFTVDLFEJOBOETFOUPVU
JUDBOCFNJTMFEUIBUUIFBJS
DPOEJUJPOFSHFOFSBUFTUIFN4P
GJOEBOESPPUPVUUIFQSPCMFNPSSFGSFTIUIFSPPNGSFRVFOUMZ
4BNTVOH&MFDUSPOJDT
3FGFSFODF4IFFU
2 8IFOFWFSUIFBJSDPOEJUJPOFSJTUVSOFEPO JUTUJOLT
2 8IFOFWFSUIFBJSDPOEJUJPOFSJTUVSOFEPO JUTNFMMTTPVS
2 8IFOFWFSUIFBJSDPOEJUJPOFSJTUVSOFEPO JUTFOETPVUCBETNFMMTTVDIBTTUBMFTNFMMT
2 *UTFOETPVUCBETNFMMT
2 *UXPOhUTUBSU
2 *UHPFTPGGEVSJOHPQFSBUJPO
2 5IFSFNPUFDPOUSPMMFSXPOhUPQFSBUF
" 8IFOUIFCBUUFSJFTSVOPVUPSUIFUSBOTNJUUFSPSSFDFJWFSPGUIFSFNPUFDPOUSPMMFSJTCMPDLFECZPCTUBDMFT
DIBOHFUIFCBUUFSJFTPSLFFQUIFPCTUBDMFTBXBZGSPNUIFDPOUSPMMJOHBSFB"MTP
UIFSFNPUFDPOUSPMMFSNBZ
OPUXPSLVOEFSJOUFOTJWFMJHIUGSPNBXBWFMFOHUIMBNQPSBOFPOTJHOEVFUPUIF&.**OUIJTDBTF
UBLF
UIFSFNPUFDPOUSPMMFSDMPTFSUPUIFSFDFJWFS
4BNTVOH&MFDUSPOJDT
3FGFSFODF4IFFU
2 8IPJOTUBMMTUIFBJSDPOEJUJPOFS 3FMPDBUJPO3FJOTUBMMBUJPO
" 8
IFOSFMPDBUJOHPSSFJOTUBMMJOHUIFBJSDPOEJUJPOFS
NBLFTVSFUPDPOUBDU4BNTVOH&MFDUSPOJDT4FSWJDF
$FOUFSPS"VUIPSJ[FE4FSWJDF"HFOUBOEIBWFUIFNUPEPUIFKPC *GOPU
JUDPVMEDBVTFQFSTPOBMJOKVSZPS
QSPEVDUEBNBHF
5IFDPTUGPSUIFSFMPDBUJPOSFJOTUBMMBUJPOPGUIFBJSDPOEJUJPOFSJTTVCKFDUUPUIFDVTUPNFShTFYQFOTF
5IFSFJTBDPTUUBCMF#VU
PVSTFSWJDFFOHJOFFSOFFETUPWJTJUUPUPUBMVQUIFDPTUDPSSFDUMZ
8IFOZPVNPWFJO
NBLFTVSFUPDPOUBDU4BNTVOH&MFDUSPOJDT4FSWJDF$FOUFSPS"VUIPSJ[FE4FSWJDF"HFOUJO
BEWBODFUPTUSFBNMJOFUIFQSPDFTT
2 *TJUQPTTJCMFUPJOTUBMMUIFPVUEPPSVOJUPVUTJEF
" * UJTQPTTJCMFUPJOTUBMMJUBUBEFTJHOBUFEQMBDFJOUIFBQBSUNFOUPSPOUIFSPPGUPQOFBSCZ
#VU
JUhTJMMFHBMIBOHJOHBOBOHMFJSPODBTFXJUIUIFPVUEPPSVOJUJOJUPVUTJEFUIFBQBSUNFOU
*OTUBMMBUJPO "MTP
JUJTJMMFHBMPCTUSVDUJOHQBTTFSTCZXJUIUIFPVUEPPSVOJUJOTUBMMFEPVUTJEF
2 8IBUDBOCFEPOFUPJOTUBMMUIFPVUEPPSVOJUGBDJOHUIFSPBECFDBVTFJUJTBDPNNFSDJBMCVJMEJOH
" 5 IFGPMMPXJOHJTBOFYDFSQUGSPN#VJMEJOH$PEFHPJOHJOUPFGGFDUGSPN+6/&TU5IFFYIBVTUQJQFPGB
DPPMJOHPSWFOUJMBUJPOGBDJMJUZJOTUBMMFEJOBCVJMEJOHBEKBDFOUUPUIFTUSFFUTPGDPNNFSDJBMPSSFTJEFOUJBMBSFBT
TIBMMCFJOTUBMMFEIJHIFSUIBONUPQSFWFOUUIFFYIBVTUBJSGSPNCMPXJOHEJSFDUMZUPQBTTFSTCZBOEUIF
DVSSFOUGBDJMJUJFTTIBMMCFDPSSFDUFECZ.":TU4P
QMFBTFJOTUBMMJUIJHIFSUIBONPSOPUUPCMPXUIF
IPUFYIBVTUJOHBJSEJSFDUMZUPQBTTFSTCZ
2 8IBUBCPVUJOTUBMMJOHBXJOETDSFFOEVSJOHJOTUBMMBUJPOOPUUPCMPXIPUBJSEJSFDUMZUPQBTTFSTCZ
4BNTVOH&MFDUSPOJDT
Opening the panel
Tightly grab top of the front panel and pull it down to open.
Then slightly lift the panel up.
Open the panel and put the Air filter out. Clean the Air filter with a vacuum cleaner or soft brush.
If dust is too heavy, rinse it with running water.
Insert the Air filter back in its original position Dry the Air filter in a ventilated area.
and close the front panel.
on the usage and environmental conditions. In dusty area, clean it once a week.
Power
well-ventilated area.
3FGFSFODF4IFFU
$MFBOJOH%FPEPSJ[JOHBOE#JPGJMUFS 0QUJPO
5PSFNPWFNJOVUFEVTUQBSUJDMFTBOEPEPST
EFPEPSJ[JOHBOE#JPGJMUFSBSFJOTUBMMFEJOUIFBJSDPOEJUJPOFS
:PVTIPVMEDMFBOUIFGJMUFSTFWFSZNPOUIT
0QFOUIFVQQFSGSPOUHSJMMFCZQVMMJOHUIFMPXFSSJHIUBOEMFGUUBCTPGUIFHSJMMF
%FPEPSJ[JOH'JMUFS
1VMMPVUUIFEFPEPSJ[JOHBOE#JPGJMUFS
#JP'JMUFS
*OTFSUUIFGJMUFSTJOUPUIFPSJHJOBMQPTJUJPO
/PUFt:PVDBODIBOHFUIFQPTJUJPOPGGJMUFSTXJUIFBDIPUIFS
$MPTFUIFGSPOUHSJMMF
4BNTVOH&MFDUSPOJDT
*OTUBMMBUJPO
#FGPSF*OTUBMMBUJPO
,FFQUIFBJSDPOEJUJPOFSPVUMFUBOEJOMFUGSFFGSPNJUTTVSSPVOEJOHT
*ODBTFPGJOTUBMMBUJPO
LFFQUIFTZNNFUSZBOEGJYJUUPQSFWFOUWJCSBUJPO
5IFQJQFMFOHUITIBMMNFFUUIFTUBOEBSEBTGBSBTQPTTJCMF
*OTUBMMBUJPO1SPDFEVSF
Q -PDBUJPO
*OTUBMMUIFQSPEVDUJOBOBSFBUPHVBSBOUFFUIFCFTUDPPMJOHFGGFDU
DPOWFOJFODFPGQJQJOHBOEFMFDUSJDXPSL
BOEJOFYJTUFODFPG
WJCSBUJPOPSXJOE
Q 8BMM%SJMMJOH
%SJMMUIFXBMMEPXOXBSEJOBEJBNFUFSPGUPNN
Q 'JYJOH*OEPPS6OJU0VUEPPS6OJU
'JYUIFBJSDPOEJUJPOFSJOEPPSVOJUTFDVSFMZUPUIFXBMM4FDVSFUIFPVUEPPSVOJUJOBTVJUBCMFQPTJUJPO
Q 1JQF4QPPMJOH$POOFDUJOH
:PVTIBMMDVUUIFQJQFXJUIBQJQFDVUUFSBOEHSJOEBMMUIFCVSSTPGUIFDVUTVSGBDF
1JQFFYQBOTJPONBZDPOUJOVFVOUJMUIFQJQFTVSGBDFCFDPNFTVOFWFOPSUPSOBQBSU
#FTVSFUPVTFBUPSRVFXSFODIUPUJHIUFOQJQFTPSGMBSFOVUT
5PSRVF%FQUI
0VUFS%JBNFUFS %
5PSRVF LHGrDN
%FQUI "
NN
_ NN
NN
_ NN
NN
_ NN
NN
_ NN
NN
_
NN
Q -FBL5FTU
1 VUBOJOFSUHBTMJLFOJUSPHFOJOUIFPVUEPPSVOJUQJQFBOEQVUTPBQCVCCMFTPSPUIFSUFTUMJRVJETPOUIFQJQFTVSGBDFGPSUIF
MFBLUFTU
Q %SBJO)PTF$POOFDUJOH
*OTUBMMUIFESBJOIPTFEPXOXBSEUPESBJOXBUFSOBUVSBMMZ#FTVSFUPQPVSXBUFSJOUPUIFIPTFUPDIFDLJGJUESBJOTXFMM
Q &MFDUSJD&BSUI8PSL
& MFDUSJDBOEFBSUIXPSLTIBMMNFFUUIF&MFDUSJD'BDJMJUZ5FDIOPMPHZ4UBOEBSEBOEUIF*OUFSOBM8JSF3FHVMBUJPOPGUIF&MFDUSJD
#VTJOFTT-BXT
Q *OTQFDUJPO5SJBM3VO
6QPODPNQMFUJPOPGUIFUFTUT
ZPVTIBMMNBLFBUSJBMSVOXIJMFZPVFYQMBJOUIFNBJOGVODUJPOTPGUIFBJSDPOEJUJPOFSUPGJOJTIUIF
JOTUBMMBUJPO
4BNTVOH&MFDUSPOJDT
*OTUBMMBUJPO%JBHSBNPG*OEPPS6OJUBOE0VUEPPS6OJU
"JS1VSHF1SPDFEVSF
0VUEPPSVOJU *OEPPSVOJU
$POOFDUFBDIBTTFNCMZQJQFUPUIFBQQSPQSJBUFWBMWF
POUIFPVUEPPSVOJUBOEUJHIUFOUIFGMBSFOVU (BTQJQFTJEF
-JRVJEQJQFTJEF
$POOFDUUIFDIBSHJOHIPTFPGMPXQSFTTVSFTJEFPG
NBOJGPMEHBVHFUPUIFQBDLFEWBMWFIBWJOHBTFSWJDF
QPSUBTTIPXOBUUIFGJHVSF
0QFOUIFWBMWFPGUIFMPXQSFTTVSFTJEFPG
NBOJGPMEHBVHFDPVOUFSDMPDLXJTF
1VSHFUIFBJSGSPNUIFTZTUFNVTJOHWBDVVNQVNQ
GPSBCPVUNJOVUFT
o.BLFTVSFUIBUQSFTTVSFHBVHFTIPX
.1B DN)H
BGUFSBCPVUNJOVUFT
o5IJTQSPDFEVSFJTWFSZJNQPSUBOUJOPSEFSUPBWPJE
HBTMFBL
o5VSOPGGUIFWBDVVNQVNQ
o$MPTFUIFWBMWFPGUIFMPXQSFTTVSFTJEFPG
NBOJGPMEHBVHFDMPDLXJTF
o3FNPWFUIFIPTFPGUIFMPXQSFTTVSFTJEF
PGNBOJGPMEHBVHF
7BDVVN1VNQ
4FUWBMWFDPSLPGCPUIMJRVJETJEFBOEHBTTJEFPG
QBDLFEWBMWFUPUIFPQFOQPTJUJPO
7BMWFTUFN
.PVOUUIFWBMWFTUFNOVUTBOEUIFTFSWJDFQPSUDBQ
4UFNDBQ
UPUIFWBMWF
BOEUJHIUFOUIFNBUUIFUPSRVFPG
LHGtDNXJUIBUPSRVFXSFODI "
HBT
#
MJRVJE
$IFDLGPSHBTMFBLBHF
"UUIJTUJNF
FTQFDJBMMZDIFDLGPSHBTMFBLBHFGSPN
UIFXBZWBMWFTTUFNOVUT
BOEGSPNUIFTFSWJDF
QPSUDBQ
4BNTVOH&MFDUSPOJDT
3FGFSFODF4IFFU
i1VNQEPXOw1SPDFEVSF
1VNQEPXOXJMMCFDBSSJFEPVUXIFOBOFWBQPSBUPSJTSFQMBDFEPSXIFOUIFVOJUJTSFMPDBUFEJOBOPUIFSBSFB
3FNPWFUIFDBQTGSPNUIFXBZWBMWFBOEUIF
8BZWBMWF
5VSOUIF8BZWBMWFDMPDLXJTFUPDMPTFBOE
DPOOFDUBQSFTTVSFHBVHF MPXQSFTTVSFTJEF
XBZ7BMWF
UPUIFTFSWJDFWBMWF
BOEPQFOUIFXBZWBMWF
BHBJO
XBZ7BMWF
4FUUIFVOJUUPDPPMPQFSBUJPONPEF
$IFDLJGUIFDPNQSFTTPSJTPQFSBUJOH
5VSOUIF8BZWBMWFDMPDLXJTFUPDMPTF
8IFOUIFQSFTTVSFHBVHFJOEJDBUFTUVSOUIF
8BZWBMWFDMPDLXJTFUPDMPTF
4UPQPQFSBUJPOPGUIFBJSDPOEJUJPOFS
$MPTFUIFDBQPGFBDIWBMWF
3FMPDBUJPOPGUIFBJSDPOEJUJPOFS
t3FGFSUPUIJTQSPDFEVSFXIFOUIFVOJUJTSFMPDBUFE
t$BSSZPVUUIFQVNQEPXOQSPDFEVSF SFGFSUPUIFEFUBJMTPGhQVNQEPXOh
t3FNPWFUIFQPXFSDPSE
t%JTDPOOFDUUIFBTTFNCMZDBCMFGSPNUIFJOEPPSBOEPVUEPPSVOJUT
t3FNPWFUIFGMBSFOVUDPOOFDUJOHUIFJOEPPSVOJUBOEUIFQJQF
t"UUIJTUJNF
DPWFSUIFQJQFPGUIFJOEPPSVOJUBOEUIFPUIFSQJQFVTJOHBDBQPSWJOZMQMVHUPBWPJEGPSFJHO
NBUFSJBMFOUFSJOH
t%JTDPOOFDUUIFQJQFDPOOFDUFEUPUIFPVUEPPSVOJU
"UUIJTUJNF
DPWFSUIFWBMWFPGUIFPVUEPPSVOJUBOEUIFPUIFSQJQFVTJOHBDBQPSWJOZMQMVHUPBWPJEGPSFJHONBUFSJBM
FOUFSJOH
t.BLFTVSFZPVEPOPUCFOEUIFDPOOFDUJPOQJQFTJOUIFNJEEMFBOETUPSFUPHFUIFSXJUIUIFDBCMFT
t.PWFUIFJOEPPSBOEPVUEPPSVOJUTUPBOFXMPDBUJPO
t3FNPWFUIFNPVOUJOHQMBUFGPSUIFJOEPPSVOJUBOENPWFJUUPBOFXMPDBUJPO
4BNTVOH&MFDUSPOJDT
15-1. POWER SUPPLY
Working Voltage 198V ~ 264V
Within a 3% Deviation from Each Voltage at the Main Terminal of
Voltage Imbalance
Outdoor Unit
Starting Voltage Higher than 85% of the Rated Voltage
15-2-1. MULTIZONE/MONOZONE/SUMMIT
Applicable models:
MULTIZONE MONOZONE SUMMIT
RAM-40QH5 RAC-25NH5 RAC-25WX8 RAC-25YH5 RAC-18YH6
RAM-55QH5 RAC-35NH5 RAC-35WX8 RAC-35YH5 RAC-25YH6
RAM-65QH5 RAC-50NH5 RAC-50WX8 RAC-50YH6 RAC-35YH6
RAM-72HQ5 RAC-65NH5 RAC-25FX8 RAC-60YH5 RAC-50DH7
RAM-90QH5 RAC-35FX8 RAC-70YH5 RAC-60DH7
RAM-130QH5 RAC-50FX8 RAC-80YH5 RAC-70DH7
Cooling Heating
working range min (oC) max (oC) rated (oC) working range min (oC) max (oC) rated (oC)
outdoor -10 43 35 outdoor -15 21 7
indoor 16 32 27 indoor 16 27 20
30 30
20 20
10 10
0 0
-10 -10
-20 -20
-10 -5 0 5 10 15 20 25 30 35 40 -10 -5 0 5 10 15 20 25 30 35 40
Indoor temperature Indoor temperature
Cooling Heating
o o o o o o
working range min ( C) max ( C) rated ( C) working range min ( C) max ( C) rated ( C)
outdoor 10 43 35 outdoor -15 21 7
indoor 16 32 27 indoor 16 27 20
Ambient temperature
Ambient temperature
30 30
20 20
10 10
0 0
-10 -10
-20 -20
-10 -5 0 5 10 15 20 25 30 35 40 -10 -5 0 5 10 15 20 25 30 35 40
Indoor temperature Indoor temperature
15-2-2. BIGFLOW
Cooling Heating
working range min (oC) max (oC) rated (oC) working range min (oC) max (oC) rated (oC)
outdoor 21 43 35 outdoor -10 21 7
indoor 16 32 27 indoor 16 27 20
30 30
20 20
10 10
0 0
-10 -10
-20 -20
-10 -5 0 5 10 15 20 25 30 35 40 -10 -5 0 5 10 15 20 25 30 35 40
Indoor temperature Indoor temperature