You are on page 1of 5

Application of Synchrophasor Data

for Fault Detection during Power Swing


J. Ganeswara Rao and A.K. Pradhan, Senior Member, IEEE

negative sequence vector to detect symmetrical and


Abstract—Distance relays are blocked during power swing. asymmetrical faults is available in [7]. The superimposed
However, if a fault occurs during power swing, it should be current component calculated by comparing the present cycle
detected and unblocking function should be invoked to clear the with previous cycle samples is proposed in [8]. The method is
fault as soon as possible. Detection of fault during power swing is
simple and faster. It is difficult to set the threshold value for
a challenging task. The technology of synchronized phasor
measurements has come of age and simplified the differential the method as the superimposed current component is
protection scheme. Differential protection scheme using significantly high during power swing. It fails to identify
synchrophasor data are applied in this paper to supplement the symmetrical faults occurring at load angle close to 180⁰.
available fault detection techniques to distance relay for fault Phasor measurement units are increasingly being applied in
during power swing. power systems for improved control, protection and
monitoring [9]-[10]. As the available techniques for fault
Index Terms—Distance relay, Power swing, Phasor
Measurement Unit, Synchrophasor, Transmission line faults. detection during power swing take around two cycles to detect
the faults, with a PMU reporting rate of 50/60 frames per
I. INTRODUCTION second and a dedicated communication system, it would be
feasible to use synchrophasor data for fault detection during
T HE apparent impedance computed by the distance relay
may fall within the operating zone due to large variations
in voltage and current during power swing. It causes undesired
power swing. In many systems PMUs may be placed at
different buses for various applications such as monitoring,
diagnosis and control. It is the aim of this work to exploit such
tripping of transmission lines which may further lead to
a resource for possible protection applications. In this work
subsequent outages and power blackout. Power Swing
the synchrophasor data supplements the protection decision by
Blocking (PSB) function is used to prevent unwanted distance
a distance relay during critical situations like power swing
relay operation during swing and facilitates the power system
when the relay is already blocked. The proposed scheme
to maintain reliability. However, if a fault occurs during the
detects the fault for the line during power swing by comparing
power swing, it should be detected and unblocking function
the synchronized current phasors obtained through PMUs
should be invoked to clear the fault as soon as possible.
available at both the ends of a line. Otherwise, the PMU data
For such purpose various fault detection techniques have
can independently decide the fault in the line which can be
been applied to identify faults during power swing. A method
used as a backup protection to the existing distance relay. It is
based on the sudden reduction of absolute value of the change
to be noted that the latency issue with PMU data (system of
in rate of power swing-centre-voltage (PSCV) is available in
Fig. 1) does not permit for primary differential protection for
[3]. This method is able to detect the symmetrical faults
the line and the distance relay is supplemented by such data.
during swing but takes around two cycles. In [4] a
This is demonstrated for a power system simulated in
multiresolution analysis based on wavelet transform is applied
PSCAD/EMTDC.
to detect symmetrical faults during power swing. A method
based on DC component of fault current is proposed to detect
II. PROPOSED METHOD
fault quickly during power swing [5]. A method using the
difference between the derivative of the three-phase active With PMU reporting rate of 50/60 frames per sec for 50/60
power and reactive power is applied to identify symmetrical Hz power system, at every cycle synchrophasors can be
faults during power swing [6]. This method requires around obtained through dedicated communication system, which
one and half a cycle for detection. As the nature of the power would be compatible to slower protection decision like fault
swing is symmetrical, the symmetrical component techniques detection during power swing. A power system is considered
are simultaneously used to identify unsymmetrical faults as shown in Fig. 1, where the distance relay R1 at bus M
during power swing. Using swing-centre-voltage and synthetic observes swing following a clearance of fault in line-2. Any
fault in line-1 during swing is to be detected by R1. The
The authors are with the Department of Electrical Engineering, Indian positive sequence current phasors at both the ends are
Institute of Technology, Kharagpur, India-721302. obtained and the difference in phasors is calculated.
(email: ganeshjada@gmail.com; akpradhan@ee.iitkgp.ernet.in)

ID IM IN (1)
978-1-4673-0136-7/11/$26.00 ©2011 IEEE
Where, IM is the positive sequence current flowing through negligible during power swing and significantly high at the
line-1 at bus M and IN is the positive sequence current flowing time of fault. The rate of change in swing-center-voltage is
through line-1 at bus N. The magnitude of differential current significant during power swing and it is zero during the fault
ID is negligible during power swing and significantly high period. The differential current phasors during the swing is
for any fault in line-1. If the difference in positive sequence also negligible and significantly high throughout the fault
current magnitudes of both the ends of the line becomes more period. All three methods are able to identify the fault
than a threshold value then the proposed algorithm declares a correctly for this case.
fault in the line. The algorithm can able to detect both

Superimp current (A)


symmetrical and high resistance asymmetrical faults during 20

power swing. The technique being based on differential


principle is not affected by load angle variation and fault type. 10

The proposed method compared with superimposed current


component fault detection method and rate of change in swing 0
1.67 1.68 1.69 1.7 1.71 1.72 1.73 1.74 1.75 1.76
center voltage. The superimposed current component is

Rate of change SCV (V/s)


20
calculated by comparing present cycle with previous cycle
samples as mentioned in [8]. The swing center voltage will 0
vary with respect to angle between bus voltages (δ) during
-20
power swing and it is constant during fault period [1]. So, the
rate of change in swing center voltage will be zero during the -40
1.67 1.68 1.69 1.7 1.71 1.72 1.73 1.74 1.75 1.76
fault period.
20

Diff current (A)


III. SIMULATION RESULTS OF DOUBLE CIRCUIT LINE
10
In order to verify the proposed method a system with a
double circuit line shown in Fig. 1 is considered. The system
is simulated using PSCAD/EMTDC software. Phasor 0
1.67 1.68 1.69 1.7 1.71 1.72 1.73 1.74 1.75 1.76
Measurement Units are placed at the buses M and N. A Time (s)

disturbance is created by a three phase fault on Line-2 at point Fig. 2. Three-phase fault at 1.72 s at 50 km in line-1
F at 0.5 s which is cleared after 0.1 s by the opening of B. 3-phase fault at δ=130⁰ during fast swing
breakers B3 and B4. As a result, line-1 experiences a power A three-phase fault is simulated at 4.5 s at 70 km from
swing. To test the method different faults are simulated at
relay R1 in line-1 during a swing (at δ=130⁰) and the
different swing conditions in line-1 during power swing. Data
corresponding results are provided in Fig. 3.
are collected at a sampling frequency of 1 kHz. The
performance of the proposed method is compared with the
Superimp current (A)

superimposed current component method and rate of change 20

in swing center voltage. Results for two critical cases of fault 15

detection during power swing are provided below following a 10

general case. 5
0
4.36 4.38 4.4 4.42 4.44 4.46
Rate of change SCV (V/s)

2000
Communication Link
0
PMU 1 PMU 2
-2000
B1 Line1 B2
-4000
4.36 4.38 4.4 4.42 4.44 4.46

~ R1
15
Diff current (A)

Line2 10

B3 B4 5
M F N
0
Fig. 1. The 280 km Double circuit Transmission System 4.36 4.38 4.4 4.42 4.44 4.46

A. 3-phase fault at δ=70⁰ during slow swing


Time (s)
Fig. 3. Three-phase fault at 4.45 s at 70 km in line-1
A three-phase fault is simulated at 1.72 s at 50 km from
relay R1 in line-1 during a swing (at δ=70⁰). The two It is observed that the superimposed current component has
conventional methods and the proposed method are applied significant value during power swing as compared with
and the corresponding results are provided in Fig. 2. It is previous case in Fig. 2. Further, the values before and during
observed that the superimposed current component is the fault are comparable. Fig. 3 is clearly shows that the index
value of the superimposed current component is significantly experiences a power swing. For the purpose of simulating this
less and fails to identify the fault. The rate of change in swing- method, two PMUs are assumed to available at bus 9 and bus
center-voltage method is also takes significant time to identify 6 (may be for different applications). Any fault in line 9-6
the fault. Whereas the differential current method is able to during the power swing is to be detected using synchronized
identifies the fault correctly with one phasor data. Of course, current phasors obtained through PMUs. To test the proposed
the dynamic plot for current differential does not include method different type of faults are simulated in line 9-6 during
communication delay. This example clearly demonstrates the power swing. Data are collected at sampling frequency 1.2
accuracy of the proposed method over conventional kHz. The performance of the proposed method is compared
techniques. with the superimposed current component method and rate of
change in swing center voltage.
C. Line-to-ground fault at δ=170⁰ during fast swing
A line-to-ground fault is simulated at 4.3 s near 120 km Bus-2 Bus-7 Bus-8 Bus-9 Bus-3
from relay location with a fault resistance of 100 Ω during
swing (at δ=170⁰). The results for the case are provided in Fig.
4. The current flowing through the line is increases, as the
˜ ˜
angle between two buses increases. If a fault occurs at that
instant the increase in current due to fault is less. From the
Bus-5 Bus-6
figure it is observed that the index value of superimposed
current is marginally high only for short duration in the initial
period of fault. The rate of change in swing-center-voltage
does not provide a high index value to conclude the fault. On
Bus-4
the other hand, the proposed current differential approach
detects the fault with few phasors of fault data as evident from
the result.
Bus-1

˜
10
Superimp current (A)

Fig. 5. WSCC 9 bus system


5
A. 3-phase fault at δ=100⁰ during slow swing
0
A three-phase fault is simulated at 2.45 s at middle of the
4.15
x 10
4
4.2 4.25 4.3 4.35 4.4
line 9-6 during a slow power swing of frequency 2 Hz at a
Rate of change SCV (V/s)

1
separation angle δ=100⁰. The results for the case are provided
0.5
in Fig. 6. It is observed from the figure that the superimposed
0
current component is significant at the time fault and able to
-0.5 detect the fault correctly. The rate of change in swing-center-
-1
4.15 4.2 4.25 4.3 4.35 4.4
voltage is zero for fault duration and identifies the fault
30 correctly. The difference in current phasors is negligible
during power swing and significantly high during the fault
Diff current (A)

20
period.
10
25
Superimposed current (A)

20
0
4.15 4.2 4.25 4.3 4.35 4.4
Time (s) 15

Fig. 4. High resistance line-to-ground fault at 4.3 s at 120 km in line-1 10

IV. SIMULATION RESULTS OF WSCC 9 BUS SYSTEM 0


2.2
x 10
6
2.25 2.3 2.35 2.4 2.45 2.5 2.55 2.6
Rate of change in SCV (V/s)

In order to verify the proposed technique WSCC 9 bus 2

system is considered. Single line diagram of the system is 0

shown in Fig. 5. The system is simulated using


-2
PSCAD/EMTDC software. Transmission lines are modeled
with distributed parameters in the simulation. Generators are -4
2.2 2.25 2.3 2.35 2.4 2.45 2.5 2.55 2.6

modeled with one axis flux decay dynamics and exciters are 50
Differential current (A)

modeled as IEEE type-1 exciter. For this study a distance


40

30
relay considered at bus-9 of the line 9-6. For the purpose of 20
simulating power swing, a three-phase fault is assumed to 10

occur in line 5-4 at middle of the line. The fault is cleared in 0

0.3 seconds by opening the line breakers at both ends of the


2.2 2.25 2.3 2.35 2.4 2.45 2.5 2.55 2.6
Time (s)

line 4-5. As a result, the distance relay at bus 9 in line 9-6 Fig. 6. Three-phase fault at 2.45 s at middle of the line 9-6.
B. Line-ground fault at δ=150⁰ during fast swing It is observed that the superimposed current component is
A line-ground fault is simulated at 3.97 s at middle of the less than 10 A, which is less than the index value of
line 9-6 at δ=150⁰ during a fast swing and the corresponding superimposed current during power swing in previous case as
results are provided in Fig. 7. The current will increase as the shown in Fig. 7. It clearly shows the problem in setting the
angle between two areas increases during power swing. It is threshold value for the superimposed current component
observed from the figure that the superimposed current is method to detect fault during power swing. The rate of change
significant during power swing and it is high for small in swing-center-voltage takes two cycles to conclude the fault.
duration at the instant of fault. This method may fail to detect On the other hand, the differential current is negligible during
the fault. The rate of change in SCV is zero throughout the power swing and significantly high though out the fault
fault period and able to detect the fault correctly. The period.
proposed method identifies the fault with few phasors of fault
data as evident from the result (of course communication V. CONCLUSION
delay has to be added to detection time). It is noticed that available fault detection methods for
distance relays have limitation during power swing.
Superimposed currnet (A)

20

15 Synchrophasor data of the two ends of a line are applied for


10 detection of fault during power swing using current
5
differential principle. The method assumes that PMUs are
available at both the ends of a line for other purposes. The
0
3.6
x 10
5
3.65 3.7 3.75 3.8 3.85 3.9 3.95 4 4.05 4.1
proposed method tested for a double circuit line and WSCC 9
1
bus system at different fault scenarios during power swing. It
Differential current (A) Rate of change in SCV (V/s)

-1
is found that the technique is accurate and can supplement the
-2 distance relay for fault detection during power swing. Of
-3 course such PMU data can be used as backup protection to the
-4
3.6 3.65 3.7 3.75 3.8 3.85 3.9 3.95 4 4.05 4.1
existing relaying schemes. The constraint for the method is the
40 latency compatibility with PMU data transfer.
30

20 APPENDIX
10 The parameters of the 400 kV system.
0
3.6 3.65 3.7 3.75 3.8 3.85 3.9 3.95 4 4.05 4.1
Equivalent Generator G:
Time (s) 600MVA, 22 kV, 50 Hz, inertia constant = 4.4 MW/MVA.
Fig. 7. Line-ground fault at 3.97 s at middle of the line 9-6. Xd = 1.81 p.u., X"d = 0.3 p.u., X"d = 0.23 p.u., T"do = 8 s.,
T"do = 0.03 s., Xq = 1.76 p.u., X"q = 0.25p.u., T"q0 = 0.03 s.,
C. 3-phase fault at δ=150⁰ during slow swing Ra = 0.003 p.u., Xp (Potier reactance) = 0.15 p.u.
A three-phase fault is simulated at 1.8 s at middle of the Transformer:
line 9-6 during a slow power swing of frequency 2 Hz at a 600MVA, 22/400 kV, 50 Hz, Δ /Υ, X = 0.163 p.u.,
separation angle δ=150⁰ and the corresponding results are Xcore = 0.33 p.u., Rcore = 0.0 p.u., Pcopper = 0.00177 p.u.
provided in Fig. 8. Transmission lines:
5 Line length (each) = 280 km
Superimposed current (A)

4 Positive sequence impedance (Z1) = 0.12 + j 0.88 Ω/km


3 Zero sequence impedance (Z0) = 0.309 + j 1.297 Ω/km
2
Positive sequence capacitance (C1) = 1.0876 x 10-8 F/km
1
Zero sequence capacitance (C0) = 0.768 x 10-8 F/km
0
CT ratio = 600/5A
1.7 1.72 1.74 1.76 1.78 1.8 1.82 1.84 1.86 1.88 1.9
PT ratio = 400kV/110V
Rate of change SCV (V/s)

1000

0 ACKNOWLWDGEMENT
-1000 The authors are thankful to Department of Science and
-2000 Technology, New Delhi for sponsoring the project-
-3000
“Protecting power system using wide area measurements
1.7
30
1.72 1.74 1.76 1.78 1.8 1.82 1.84 1.86 1.88 1.9
(WAM)”, No. 100/IFD/631/2009-2010 through which the
research was conducted
Differential Current (A)

20

REFERENCES
10
[1] IEEE Power System Relaying Committee of the IEEE Power Eng. Soc.,
0
“Power swing and out-of-step considerations on transmission line,” Rep.
1.7 1.72 1.74 1.76 1.78 1.8 1.82 1.84 1.86 1.88 1.9
PSRC WG D6., Jul. 2005. [Online]. Available: http://www.pes-psrc.org
Time (s)

Fig. 8. Three-phase fault at 1.8 s at middle of the line 9-6.


[2] G. Benmouyal, D. Hou and D. Tziouvaras, “Zero-setting power swing [9] J. De La Ree, V. Centeno, J. S. Thorp, A. G. Phadke, “Synchronized
blocking protection,” The 31st Annual Western Protective Relay phasor measurement applications in power systems,” IEEE Trans. Smart
Conference, Washington, 2004. Grid, Vol. 1, Issue 1, pp. 20-27, 2010.
[3] B. Su,. X. Z. Dong, Z. Q. Bo, Y. Z. Sun, B.R.J Caunce, D. Tholomier [10] P. V. Navalkar, S. A. Soman, “Secure remote backup protection of
and A. Apostolov, “Fast detector of symmetrical fault during power transmission lines using synchrophasors,” IEEE Trans. Power Del., Vol.
swing for distance relay,” IEEE Power Eng. Soc. Gen. Meet., Vol. 2, 26, Issue 1, pp. 87-96, 2011.
pp.1836 – 1841, 2005.
[4] Chengzong Pang and Mladen Kezunovic, “Fast distance relay scheme BIOGRAPHIES
for detecting symmetrical fault during power swing,” IEEE Trans.
Power Deliver, Vol. 25, Issue 4, pp. 2205-2212, Oct 2010. J Ganeswara Rao obtained his B. Tech degree in Electrical Engineering from
[5] H. Kazemi Karegar and B. Mohamedi, “A new method for fault Institution of Engineers (India), Kolkata in 2008 and obtained his M. Tech
detection during power swing in distance protection,” IEEE ECTI-CON degree in Power System Engineering from Indian Institute of Technology
2009, Vol. 01, pp. 230-233, 2009. Kharagpur, India in 2011. Presently he is pursuing for Ph.D. degree at Indian
[6] L. Xiangning, Z. Qing, L. Wenjun, W. Kecheng and W. Hanli, “A fast Institute of Technology Kharagpur. His research area is Power System
unblocking scheme for distance protection to identify symmetrical fault Protection.
occurring during power swings,” IEEE Power Eng. Soc. Gen. Meet.,
pp.1-8, 2006. Ashok Kumar Pradhan (SM’10, M’94) received Ph.D. in Electrical
[7] S. Jiao, Z. Bo, W. Liu and Q. Yang, “New principles to detect faults Engineering from Sambalpur University, India in 2001. He has been with the
during power swing,” Developments in Power System Protection Department of Electrical Engineering, Indian Institute of Technology,
Conference, IEEE, pp. 515-518, 2001. Kharagpur, India since 2002. He has served at the Department of Electrical
[8] A. P. Apostolov, D. Tholomier, S. H. Richards, “Superimposed Engineering, University College of Engineering Burla, India from 1992-
components based sub-cycle protection of transmission lines,” Power 2002. Dr Pradhan is a recipient of the Young Engineer Award, Indian
Systems Conference and Exposition, IEEE PES, vol.1, pp. 592 – 597, National Academy of Engineering, India in 2001. His research interest
2004. includes Power System Relaying and Monitoring.

You might also like