Type Selection
Mounting Output Measuring range Supply: 24 to 48 VAC/DC Supply: 115/230 VAC
DIN-rail SPDT 0.1 to 10 V AC/DC DUB 01 C D48 10V DUB 01 C B23 10V
2 to 500 V AC/DC DUB 01 C D48 500V DUB 01 C B23 500V
Plug-in SPDT 0.1 to 10 V AC/DC PUB 01 C D48 10V PUB 01 C B23 10V
2 to 500 V AC/DC PUB 01 C D48 500V PUB 01 C B23 500V
Input Specifications
Input (voltage level) Contact input
DUB01 Terminals Y1, Y2 DUB01 Terminals Z1, Y1
PUB01 Terminals 5, 7 PUB01 Terminals 8, 9
Measuring ranges Disabled > 10 kΩ
Direct Int. resist. Max. volt. Enabled < 500 Ω
Selectable by DIP-switches Latch disable > 500 ms
..10V: 0.1 to 1 V AC/DC >200 kΩ 100 V
0.2 to 2 V AC/DC >200 kΩ 100 V
0.5 to 5 V AC/DC >200 kΩ 100 V
1 to 10 V AC/DC >200 kΩ 100 V
Max. voltage for 1 s 200 V
..500V: 2 to 20 V AC/DC >500 kΩ 350 V
5 to 50 V AC/DC >500 kΩ 350 V
20 to 200 V AC/DC >500 kΩ 600 V
50 to 500 V AC/DC >500 kΩ 600 V
Max. voltage for 1 s 1000 V
Note:
The input voltage cannot
raise over 300 VAC/DC
with respect to ground
(PUB01 only)
Mode of Operation
DUB01 and PUB01 monitor drops below (or exceeds) the set delay time. Note
both AC and DC over or the set level (see hysteresis Provided that the voltage When the inhibit contact is
under voltage. setting), or when power sup- has dropped below (or has opened, if the input signal is
ply is interrupted. exceeded) the set point (see already in alarm position, the
Example 1 hysteresis setting) the relay delay time needs to elapse
(no connection between ter- Example 2 releases when the intercon- before relay activation.
minals Z1, Y1 or 8, 9 - latch (connection between termi- nection between terminals
function disabled) nals Z1, Y1 or 8, 9 - latch Z1, Y1 or 8, 9 is interrupted,
function enabled) or power supply is interrupt-
The relay operates when the ed as well.
measured value exceeds (or The relay operates and The red LED flashes until the
drops below) the set level for latches in operating position delay time has expired or
more than the set delay when the measured value the measured value has
time. exceeds (or drops below) dropped below the set point
It releases when the voltage the set level for more than (see hysteresis setting).
Operation Diagrams
Over voltage - N.D. relay Under voltage - Latch function - N.D. relay
Under voltage - N.D. relay Over voltage - Inhibit function - N.D. relay
Wiring Diagrams
24÷48 VAC/DC
230 VAC 115VAC
24÷48 VAC/DC
230 VAC 115VAC
24÷48 VAC/DC
230 VAC 115VAC
Latch/inhibit
Enable
24÷48 VAC/DC
230 VAC 115VAC
DUB01 PUB01
Dimensions
DIN-rail Plug-in
22.5 94
99.5
36 90
83.5
80
63
63
80
28.5 28.5