Mechanical drawing

Horizontal line parallel to the ceiling BSR-5136 Addressable manual call point
with integrated isolator

TECHNICAL CHARACTERISTICS
COMMUNICATION PROTOCOL Olympia A Protocol
MAIN VOLTAGE 11-30V
STANDBY CONSUMPTION 90μΑ
ALARM CONSUMPTION 2.5mA (with activation LED)
TYPE Type A
USE Indoors
MAXIMUM LOOP CURRENT (Ic max, -L in/out) 1A
MAXIMUM SWITCH CURRENT (Is max, -L in/out) 5A
MAXIMUM SERIES RESISTANCE (Zc max, -L in-out) 50mΩ
MAXIMUM LEAKAGE CURRENT (IL max, -L in/out) 25mA pulses (6ms duration every 2sec)
ISOLATION VOLTAGE (Vso min-max) 9.3 - 10.6
RECONNECT VOLTAGE (Vsc min-max) 10.7 - 12.7
DEGREES OF COVER PROTECTION IP20
PRODUCED IN ACCORDANCE WITH EN 54-11, EN 54-17
ο
OPERATION TEMPERATURE RANGE -40 to 70 C
RELATIVE HUMIDITY Up to 95%
CONSTRUCTION MATERIALS ABS/PC
EXTERNAL DIMENSIONS 94 x 98 x 56 mm
TYPICAL WEIGHT 185 gr.
GUARANTEE 2 years
Mounting holes

Thank you for your trust in our products


Olympia Electronics - European manufacturer
Description
BSR-5136 is an addressable manual call point which activates the fire detection panel.
BSR-5136 works with any panel supports Olympia A Protocol. It is essential to be placed in
every fire detection system in co-operation with fire detection. At least one manual call
point has to be placed in every fire detection system, close to the main control panel.

Pushing the clear plastic cover of the manual call point activates the alarm system. The
clear plastic cover does not break but can be reset to its original position using the special
plastic key which is included in the package. Periodic fire detection system testing can be
carried out by activating a manual call point. It should be mounted in a clearly visible spot,
near to the exit or ladder and at a height of 1.5 meters.

A red LED that blinks periodically in standby mode indicates a good link between manual
call point and main panel. The LED lights up and remains lit in case this manual call point
triggers an alarm on the panel. The LED remains lit during siren silence periods to indicate
the manual call point which triggered the alarm. The LED goes off when we RESET the
panel.

Page 4 from 4 921513600_09_002 Page 1 from 4 921513600_09_002


Each button has a unique address with which it is recognized from the panel. It is forbidden Loop
for two devices with same address to be connect to the same loop. The "Point change Loop Loop
address" and "Detect-AUTOADDRESS" functions as described in the user manual can be
used to set the address. The panel references the buttons with the name POINTS.

BSR-5136 features an intergrated short-circuit isolator which is automatically activated to N


N

I
isolate the faulty node from the rest of the loop. This feature allows to locate installation

+
-

IN

IN
/OU

/OU
T

T
faults directly from the main panel.

-R
-

-R
O -
UT O
UT

Additional specifications of the device :

PRE
ALAR M
ALAR

CN2
- Resettable operating element with easy front access

M
- 160° viewable LED
- Semi flush or surface mounting

PE +L -L +L -L
- Configurable as alarm or pre-alarm call point

CN2

IN
N

PE +L -L +L -L
I

+
-

IN

IN OUT
/OU
T

OUT
-R
-
O
UT

Protocol values
Quiescence state 10
Alarm 128
Pre-alarm 64 N N

+
I

-
-

IN
IN

/OU
/OU

T
T
-R

-R
- -
O O
UT UT

UID:
In every device there is a double sticker with the UID (Unique Identifier) number. This number is
unique for each device. Loop

WARRANTY
Indicator LED
Blinks periodically in standby mode. Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty
The LED lits constantly when the device trigger an alarm. is specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which
The LED goes off when RESET command is received from the panel. accompanies each product. This warranty ceases to exist if the buyer does not follow the technical
instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods
provided or has any repairs or re-setting done by a third party, unless Olympia Electronics has fully
agreed to them in writing. Products that have been damaged can be returned to the premises of our
company for repair or replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the
CN2
Selects the signal that the manual call point sends to the panel. M A
buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the
ALAR M
In position (Α) the manual call point sends an alarm signal. PREA
LAR B buyer the transportation cost.
In position (B) the manual call point sends a pre-alarm signal. HEAD OFFICE
(Programming is also required in the panel) 72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
IN OUT www.olympia-electronics.gr
info@olympia-electronics.gr
PE +L -L +L -L

Terminal block for connecting to the loop.

Page 2 from 4 921513600_09_002 Page 3 from 4 921513600_09_002

You might also like