System Architecture

SLC 1

S H
MM CM
SLC 8

S H
MM CM

RS-485

R/D 1 R/D n R/D 64

N-NET

N-NCS

y Advanced history filters. Manual/ Automatic; Lamp Inspection/ Self-test;


y Autoprogramming and Walk Test. System Reset.
y Field–programmable on panel or offline on PC with - Operation Keys: Menu; Help; Escape; Enter;
N-VFT programming software tools. Navigation Keys.
y Powerful Boolean logic equations – 1,000! - LCD Display: 1060 characters (20 × 53), with
y Support RS-485 annunciators. 320 × 240 Pixel LCD
y Supports integral printer on panel.
Specification
y 1060-character display features:
y Primary input power, MPS-350W:
- Backlit, 1060-character display.
- 220VAC, 50/60 Hz, 1.5 Amps;
- Program keypad: full QWERTY keypad.
110VAC, 50/60 Hz, 3.0 Amps
- Up to three access levels, each with its own
- Total output 24V power: 14.6 A in alarm
password
- General purpose power: 1.0A
- 11 LED Indicators: Power; Fire Alarm; Pre-Alarm; - Battery charger ranges: 25AH – 55AH, use
Trouble; Self-Test; CBE; Delay; Signals Silenced; separate cabinet for batteries over 25AH
Point Disabled; Supervisory; CPU Failure. - Float Rate: 27.6V
- Membrane Switch Controls: Acknowledge; Signal y Temperature and humidity ranges:
Silence; Fire Alarm/ Pre-Alarm; Trouble/ Horn/ - Temperature: 0 to 50 ºC
Strobe; Supervision/ Feedback; CBE/ Delay; - Humidity: 5% to 95% non-condensing
Manual/ Automatic; Lamp Inspection/ Self-test;
This document is not intended to be used for installation purposes. We try to keep our product
information up-to-date and accurate. We cannot cover all specific applications or anticipate all
requirements. All specifications are subject to change without notice. For more information, please
contact NOTIFIER. Phone: +886 (2) 22487171 Fax: +886 (2) 22450927

Page 2 of 3 – N-6000 Rev. D • 9/6/08

You might also like