VOLTAGE DROP CALCULATIONS

Cable or Busbar Duct Current


Max. Voltage Drop allowed (v)
Write "C" for Cable or "B" for
Cable Size Sqmm or Busbar

% Voltage Drop Allowed (%)


Type (e.g. XLPE for Cable &

Check for Current Capacity


Voltage Drop Winthin Limit
CU or AL for Busbar Duct)

Installation Type. G/A/D


Act. % Voltage Drop (v)
Voltage Drop/A/M (mV)
Operating Voltage (V)

Act. Voltage Drop (v)


Runs per Phase

Derating Factor
Load Current A
Current Rating

MCCB Rating

MCCB Rating
Load Current
ADMD in KW

Power factor
Busbar Duct

Dearated Ct.
Mt

TCL in KW
Cable Ref.

TOTAL VD

Rating
Cores
FROM
Cable From Connected To

Length
SOURCE
TO CKT

INCOMER
A Transformer-1 MFP-1 1 3,5 120 C XLPE 415 30 96.99 96.99 160 0.55 5 20.75 0.8 169 2.8 0.67 A 1.00 OK 225 169 160 225 OK 4

OUTGOING
1 MFP-1 FP-1 2 3,5 70 C XLPE 415 322 28.67 28.67 63 0.93 5 20.75 0.9 44 6.6 1.60 A 1.00 OK 340 44 63 340 OK 4 2.27
2 MFP-1 FP-2 2 3,5 70 C XLPE 415 165 68.32 68.32 125 0.93 5 20.75 0.9 106 8.1 1.95 A 1.00 OK 340 106 125 340 OK 4 2.62

OUTGOING
1 FP-1 C1 1 4 25 C XLPE 415 834 4.48 4.48 16 2.5 5 20.75 0.9 7 14.4 3.48 A 1.00 OK 95 7 16 95 OK 4 5.75
2 FP-1 C2 1 4 25 C XLPE 415 647 5.38 5.38 16 2.5 5 20.75 0.9 8 13.4 3.24 A 1.00 OK 95 8 16 95 OK 4 5.51
3 FP-1 C3 1 4 16 C XLPE 415 407 5.38 5.38 16 3.97 5 20.75 0.9 8 13.4 3.24 A 1.00 OK 78 8 16 78 OK 4 5.51
4 FP-1 C4 1 4 25 C XLPE 415 963 4.48 4.48 16 2.5 5 20.75 0.9 7 16.7 4.02 A 1.00 OK 95 7 16 95 OK 4 4.69

5 FP-1 C5 1 4 25 C XLPE 415 665 4.48 4.48 16 2.5 5 20.75 0.9 7 11.5 2.77 A 1.00 OK 95 7 16 95 OK 4 5.04
6 FP-1 C6 1 4 16 C XLPE 415 425 4.48 4.48 16 3.97 5 20.75 0.9 7 11.7 2.82 A 1.00 OK 78 7 16 78 OK 4 5.09

OUTGOING
1 FP-2 C1 1 4 16 C XLPE 415 435 4.48 4.48 16 3.97 5 20.75 0.9 7 12.0 2.88 A 1.00 OK 78 7 16 78 OK 4 5.51
2 FP-2 C2 1 4 25 C XLPE 415 639 4.48 4.48 16 2.5 5 20.75 0.9 7 11.1 2.67 A 1.00 OK 95 7 16 95 OK 4 5.29
3 FP-2 C3 1 4 25 C XLPE 415 790 3.64 3.64 16 2.5 5 20.75 0.9 6 11.1 2.68 A 1.00 OK 95 6 16 95 OK 4 5.30
4 FP-2 C4 1 4 16 C XLPE 415 532 3.64 3.64 16 3.97 5 20.75 0.9 6 11.9 2.86 A 1.00 OK 78 6 16 78 OK 4 5.49
5 FP-2 C5 1 4 16 C XLPE 415 519 3.64 3.64 16 3.97 5 20.75 0.9 6 11.6 2.79 A 1.00 OK 78 6 16 78 OK 4 5.42
6 FP-2 C6 1 4 25 C XLPE 415 701 4.48 4.48 16 2.5 5 20.75 0.9 7 12.1 2.92 A 1.00 OK 95 7 16 95 OK 4 5.55
7 FP-2 C7 1 4 16 C XLPE 415 759 1.40 1.40 16 3.97 5 20.75 0.9 2 6.5 1.57 A 1.00 OK 78 2 16 78 OK 4 4.19
8 FP-2 C8 1 4 16 C XLPE 415 629 1.40 1.40 16 3.97 5 20.75 0.9 2 5.4 1.30 A 1.00 OK 78 2 16 78 OK 4 3.93
9 FP-2 C9 1 4 16 C XLPE 415 455 4.48 4.48 16 3.97 5 20.75 0.9 7 12.5 3.01 A 1.00 OK 78 7 16 78 OK 4 5.64
10 FP-2 C10 1 4 16 C XLPE 415 426 4.48 4.48 16 3.97 5 20.75 0.9 7 11.7 2.82 A 1.00 OK 78 7 16 78 OK 4 5.45
11 FP-2 C11 1 4 25 C XLPE 415 481 4.93 4.93 16 2.5 5 20.75 0.9 8 9.2 2.21 A 1.00 OK 95 8 16 95 OK 4 4.83
12 FP-2 C12 1 4 16 C XLPE 415 319 4.48 4.48 16 3.97 5 20.75 0.9 7 8.8 2.11 A 1.00 OK 78 7 16 78 OK 4 4.74
13 FP-2 C13 1 4 16 C XLPE 415 397 4.48 4.48 16 3.97 5 20.75 0.9 7 10.9 2.63 A 1.00 OK 78 7 16 78 OK 4 5.25
14 FP-2 C14 1 4 16 C XLPE 415 514 1.68 1.68 16 3.97 5 20.75 0.9 3 5.3 1.28 A 1.00 OK 78 3 16 78 OK 4 3.90
15 FP-2 C15 1 4 16 C XLPE 415 357 1.68 1.68 16 3.97 5 20.75 0.9 3 3.7 0.89 A 1.00 OK 78 3 16 78 OK 4 3.51
16 FP-2 C16 1 4 16 C XLPE 415 236 1.40 1.40 16 3.97 5 20.75 0.9 2 2.0 0.49 A 1.00 OK 78 2 16 78 OK 4 3.11
17 FP-2 C17 1 4 16 C XLPE 415 302 1.40 1.40 16 3.97 5 20.75 0.9 2 2.6 0.63 A 1.00 OK 78 2 16 78 OK 4 3.25
18 FP-2 C18 1 4 16 C XLPE 415 418 1.40 1.40 16 3.97 5 20.75 0.9 2 3.6 0.87 A 1.00 OK 78 2 16 78 OK 4 3.49
19 FP-2 C19 1 4 35 C XLPE 415 692 5.38 5.38 16 1.81 5 20.75 0.9 8 10.4 2.51 A 1.00 OK 116 8 16 116 OK 4 5.13
20 FP-2 C20 1 4 35 C XLPE 415 754 5.38 5.38 16 1.81 5 20.75 0.9 8 11.3 2.73 A 1.00 OK 116 8 16 116 OK 4 5.36

VD Calculation 1 of 9 23/09/2008
VOLTAGE DROP CALCULATIONS

Max. Voltage Drop allowed (v)

Cable or Busbar Duct Current


Write "C" for Cable or "B" for

% Voltage Drop Allowed (%)


Cable Size Sqmm or Busbar

Type (e.g. XLPE for Cable &

Check for Current Capacity


Voltage Drop Winthin Limit
CU or AL for Busbar Duct)

Installation Type. G/A/D


Act. % Voltage Drop (v)
Voltage Drop/A/M (mV)
Operating Voltage (V)

Act. Voltage Drop (v)


Runs per Phase

Derating Factor
Load Current A
Current Rating

MCCB Rating

MCCB Rating
Load Current
ADMD in KW

Power factor
Busbar Duct

Dearated Ct.
Mt

TCL in KW
Cable Ref.

TOTAL VD

Rating
Cores
FROM
Cable From Connected To

Length
SOURCE
TO CKT

INCOMER
A Transformer-2 MFP-2 1 3,5 70 C XLPE 415 30 65.86 65.86 125 0.93 5 20.75 0.8 115 3.2 0.77 A 1.00 OK 170 115 125 170 OK 4

OUTGOING
1 MFP-2 FP-3 1 4 35 C XLPE 415 13 40.94 40.94 80 1.81 5 20.75 0.9 63 1.5 0.36 A 1.00 OK 116 63 80 116 OK 4 1.13
2 MFP-2 FP-4 1 3,5 70 C XLPE 415 344 24.92 24.92 50 0.93 5 20.75 0.9 39 12.3 2.97 A 1.00 OK 170 39 50 170 OK 4 3.74

OUTGOING
1 FP-3 C1 1 4 16 C XLPE 415 744 2.52 2.52 16 3.97 5 20.75 0.9 4 11.5 2.77 A 1.00 OK 78 4 16 78 OK 4 3.90
2 FP-3 C2 1 4 16 C XLPE 415 544 2.24 2.24 16 3.97 5 20.75 0.9 3 7.5 1.80 A 1.00 OK 78 3 16 78 OK 4 2.93
3 FP-3 C3 1 4 16 C XLPE 415 568 2.24 2.24 16 3.97 5 20.75 0.9 3 7.8 1.88 A 1.00 OK 78 3 16 78 OK 4 3.01
4 FP-3 C4 1 3,5 50 C XLPE 415 1438 5.38 5.38 16 1.33 5 20.75 0.9 8 15.9 3.83 A 1.00 OK 140 8 16 140 OK 4 4.96
5 FP-3 C5 1 4 35 C XLPE 415 1172 5.38 5.38 16 1.81 5 20.75 0.9 8 17.6 4.25 A 1.00 OK 116 8 16 116 OK 4 5.38
6 FP-3 C6 1 4 25 C XLPE 415 908 5.38 5.38 16 2.5 5 20.75 0.9 8 18.9 4.55 A 1.00 OK 95 8 16 95 OK 4 5.67
7 FP-3 C7 1 4 25 C XLPE 415 620 5.38 5.38 16 2.5 5 20.75 0.9 8 12.9 3.10 A 1.00 OK 95 8 16 95 OK 4 4.23
8 FP-3 C8 1 4 25 C XLPE 415 607 6.27 6.27 16 2.5 5 20.75 0.9 10 14.7 3.55 A 1.00 OK 95 10 16 95 OK 4 4.67
9 FP-3 C9 1 4 16 C XLPE 415 624 3.08 3.08 16 3.97 5 20.75 0.9 5 11.8 2.84 A 1.00 OK 78 5 16 78 OK 4 3.97
10 FP-3 C10 1 4 16 C XLPE 415 403 3.08 3.08 16 3.97 5 20.75 0.9 5 7.6 1.84 A 1.00 OK 78 5 16 78 OK 4 2.96

1 OUTGOING 4
1 FP-4 C1 1 4 35 C XLPE 415 721 3.64 3.64 16 1.81 5 20.75 0.9 6 7.3 1.77 A 1.00 OK 116 6 16 116 OK 4 5.51
2 FP-4 C2 1 4 35 C XLPE 415 721 3.64 3.64 16 1.81 5 20.75 0.9 6 7.3 1.77 A 1.00 OK 116 6 16 116 OK 4 5.51
3 FP-4 C3 1 4 25 C XLPE 415 722 2.80 2.80 16 2.5 5 20.75 0.9 4 7.8 1.88 A 1.00 OK 95 4 16 95 OK 4 5.62
4 FP-4 C4 1 4 16 C XLPE 415 522 2.80 2.80 16 3.97 5 20.75 0.9 4 9.0 2.16 A 1.00 OK 78 4 16 78 OK 4 5.90
5 FP-4 C5 1 4 16 C XLPE 415 383 2.80 2.80 16 3.97 5 20.75 0.9 4 6.6 1.59 A 1.00 OK 78 4 16 78 OK 4 5.33
6 FP-4 C6 1 4 16 C XLPE 415 459 2.80 2.80 16 3.97 5 20.75 0.9 4 7.9 1.90 A 1.00 OK 78 4 16 78 OK 4 5.64
7 FP-4 C7 1 4 25 C XLPE 415 689 3.36 3.36 16 2.5 5 20.75 0.9 5 8.9 2.16 A 1.00 OK 95 5 16 95 OK 4 5.90
8 FP-4 C8 1 4 16 C XLPE 415 410 3.08 3.08 16 3.97 5 20.75 0.9 5 7.7 1.87 A 1.00 OK 78 5 16 78 OK 4 5.61

VD Calculation 2 of 9 23/09/2008
VOLTAGE DROP CALCULATIONS

Max. Voltage Drop allowed (v)

Cable or Busbar Duct Current


Write "C" for Cable or "B" for

% Voltage Drop Allowed (%)


Cable Size Sqmm or Busbar

Type (e.g. XLPE for Cable &

Check for Current Capacity


Voltage Drop Winthin Limit
CU or AL for Busbar Duct)

Installation Type. G/A/D


Act. % Voltage Drop (v)
Voltage Drop/A/M (mV)
Operating Voltage (V)

Act. Voltage Drop (v)


Runs per Phase

Derating Factor
Load Current A
Current Rating

MCCB Rating

MCCB Rating
Load Current
ADMD in KW

Power factor
Busbar Duct

Dearated Ct.
Mt

TCL in KW
Cable Ref.

TOTAL VD

Rating
Cores

FROM
Cable From Connected To

Length
SOURCE TO
CKT

INCOMER
A Transformer-3 MFP-3 1 4 25 C XLPE 415 30 13.86 13.86 63 2.5 55 228.25 0.8 24 1.8 0.44 A 1.00 OK 95 24 63 95 OK 4

OUTGOING
1 MFP-3 C1 1 4 16 C XLPE 415 336 5.38 5.38 16 3.97 5 20.75 0.9 8 11.1 2.67 A 1.00 OK 78 8 16 78 OK 4 3.11
1 MFP-3 C2 1 4 16 C XLPE 415 356 5.38 5.38 16 3.97 5 20.75 0.9 8 11.7 2.83 A 1.00 OK 78 8 16 78 OK 4 3.27
1 MFP-3 C3 1 4 16 C XLPE 415 454 2.80 2.80 16 3.97 5 20.75 0.9 4 7.8 1.88 A 1.00 OK 78 4 16 78 OK 4 2.32
2 MFP-3 FP-5 1 4 16 C XLPE 415 1932 0.31 0.31 32 3.97 5 20.75 0.9 0.5 3.7 0.89 A 1.00 OK 78 0 32 78 OK 4 1.32

OUTGOING
1 FP-5 C1 1 4 16 C XLPE 415 35.5 0.16 0.16 16 3.97 5 20.75 0.9 0.2 0.0 0.01 A 1.00 OK 78 0 16 78 OK 4 0.89
1 FP-5 C2 1 4 16 C XLPE 415 22.5 0.16 0.16 16 3.97 5 20.75 0.9 0.2 0.0 0.01 A 1.00 OK 78 0 16 78 OK 4 1.33

VD Calculation 3 of 9 23/09/2008
VOLTAGE DROP CALCULATIONS

Max. Voltage Drop allowed (v)

Cable or Busbar Duct Current


Write "C" for Cable or "B" for

% Voltage Drop Allowed (%)


Cable Size Sqmm or Busbar

Type (e.g. XLPE for Cable &

Check for Current Capacity


Voltage Drop Winthin Limit
CU or AL for Busbar Duct)

Installation Type. G/A/D


Act. % Voltage Drop (v)
Voltage Drop/A/M (mV)
Operating Voltage (V)

Act. Voltage Drop (v)


Runs per Phase

Derating Factor
Load Current A
Current Rating

MCCB Rating

MCCB Rating
Load Current
ADMD in KW

Power factor
Busbar Duct

Dearated Ct.
Mt

TCL in KW
Cable Ref.

TOTAL VD

Rating
Cores
FROM
Cable From Connected To

Length
SOURCE
TO CKT

INCOMER
A Transformer-4 MFP-4 1 3,5 50 C XLPE 415 30 54.58 54.58 125 1.33 5 20.75 0.8 95 3.8 0.91 A 1.00 OK 140 95 125 140 OK 4

OUTGOING
1 MFP-4 C1 1 4 16 C XLPE 415 168 1.01 1.01 16 3.97 5 20.75 0.9 2 1.0 0.25 A 1.00 OK 78 2 16 78 OK 4 1.16
2 MFP-4 C2 2 4 35 C XLPE 415 2001 6.16 6.16 16 1.81 5 20.75 0.9 10 17.2 4.16 A 1.00 OK 232 10 16 232 OK 4 5.07
3 MFP-4 C3 1 4 25 C XLPE 415 743 7.17 7.17 16 2.5 5 20.75 0.9 11 20.6 4.96 A 1.00 OK 95 11 16 95 OK 4 5.87
4 MFP-4 FP-6 1 4 25 C XLPE 415 13 22.40 22.40 63 2.5 5 20.75 0.9 35 1.1 0.27 A 1.00 OK 95 35 63 95 OK 4 1.18
5 MFP-4 FP-7 2 3.5 50 C XLPE 415 1384 11.96 11.96 40 1.33 5 20.75 0.9 18 17.0 4.10 A 1.00 OK 280 18 40 280 OK 4 5.01
6 MFP-4 C4 2 4 25 C XLPE 415 1354 5.88 5.88 16 2.5 5 20.75 0.9 9 15.4 3.71 A 1.00 OK 190 9 16 190 OK 4 4.62

OUTGOING

1 FP-6 C1 1 4 25 C XLPE 415 928 5.38 5.38 16 2.5 5 20.75 0.9 8 19.3 4.65 A 1.00 OK 95 8 16 95 OK 4 5.83

2 FP-6 C2 1 4 25 C XLPE 415 664 5.38 5.38 16 2.5 5 20.75 0.9 8 13.8 3.32 A 1.00 OK 95 8 16 95 OK 4 4.51
3 FP-6 C3 1 4 16 C XLPE 415 387 4.48 4.48 16 3.97 5 20.75 0.9 7 10.6 2.56 A 1.00 OK 78 7 16 78 OK 4 3.75
4 FP-6 C4 1 4 16 C XLPE 415 246 3.58 3.58 16 3.97 5 20.75 0.9 6 5.4 1.30 A 1.00 OK 78 6 16 78 OK 4 2.49
5 FP-6 C5 1 4 16 C XLPE 415 422 3.58 3.58 16 3.97 5 20.75 0.9 6 9.3 2.24 A 1.00 OK 78 6 16 78 OK 4 3.42

1 OUTGOING
1 FP-7 C1 1 4 16 C XLPE 415 82 0.31 0.31 63 3.97 5 20.75 0.9 0.5 0.2 0.04 A 1.00 OK 78 0 63 78 OK 4 0.95
2 FP-7 C2 1 4 25 C XLPE 415 684 3.58 3.58 63 2.5 5 20.75 0.9 6 9.5 2.28 A 1.00 OK 95 6 63 95 OK 4 3.20
3 FP-7 C3 1 4 25 C XLPE 415 917 4.48 4.48 63 2.5 5 20.75 0.9 7 15.9 3.83 A 1.00 OK 95 7 63 95 OK 4 4.74
4 FP-7 C4 1 4 25 C XLPE 415 1079 3.58 3.58 63 2.5 5 20.75 0.9 6 14.9 3.60 A 1.00 OK 95 6 63 95 OK 4 4.51

4C 16

VD Calculation 4 of 9 23/09/2008
VOLTAGE DROP CALCULATIONS

Max. Voltage Drop allowed (v)

Cable or Busbar Duct Current


Write "C" for Cable or "B" for

% Voltage Drop Allowed (%)


Cable Size Sqmm or Busbar

Type (e.g. XLPE for Cable &

Check for Current Capacity


Voltage Drop Winthin Limit
CU or AL for Busbar Duct)

Installation Type. G/A/D


Act. % Voltage Drop (v)
Voltage Drop/A/M (mV)
Operating Voltage (V)

Act. Voltage Drop (v)


Runs per Phase

Derating Factor
Load Current A
Current Rating

MCCB Rating

MCCB Rating
Load Current
ADMD in KW

Power factor
Busbar Duct

Dearated Ct.
Mt

TCL in KW
Cable Ref.

TOTAL VD

Rating
Cores FROM
Cable From Connected To

Length
SOURCE
TO CKT

INCOMER
A TOLL PLAZA (1) MAIN LT P MFP-5 1 3,5 120 C XLPE 415 150 64.51 64.51 100 0.55 5 20.75 0.8 112 9.3 2.23 A 1.00 OK 225 112 100 225 OK 4

OUTGOING
1 MFP-5 C-1 1 4 25 C XLPE 415 351 10.75 10.75 32 2.5 5 20.75 0.9 17 14.6 3.51 A 1.00 OK 95 17 32 95 OK 4 5.74
2 MFP-5 C-2 1 4 16 C XLPE 415 150 10.75 10.75 32 3.97 5 20.75 0.9 17 9.9 2.38 A 1.00 OK 78 17 32 78 OK 4 4.62
1 MFP-5 C-3 1 4 16 C XLPE 415 107 10.75 10.75 32 3.97 5 20.75 0.9 17 7.1 1.70 A 1.00 OK 78 17 32 78 OK 4 3.93
2 MFP-5 C-4 1 4 16 C XLPE 415 141 10.75 10.75 32 3.97 5 20.75 0.9 17 9.3 2.24 A 1.00 OK 78 17 32 78 OK 4 4.47
1 MFP-5 C-5 1 4 25 C XLPE 415 678 5.38 5.38 16 2.5 5 20.75 0.9 8 14.1 3.39 A 1.00 OK 95 8 16 95 OK 4 5.62
1 MFP-5 C-6 1 4 35 C XLPE 415 940 5.38 5.38 16 1.81 5 20.75 0.9 8 14.1 3.41 A 1.00 OK 116 8 16 116 OK 4 5.64
1 MFP-5 C-7 1 4 25 C XLPE 415 562 5.38 5.38 16 2.5 5 20.75 0.9 8 11.7 2.81 A 1.00 OK 95 8 16 95 OK 4 5.04
2 MFP-5 C-8 1 4 35 C XLPE 415 825 5.38 5.38 16 1.81 5 20.75 0.9 8 12.4 2.99 A 1.00 OK 116 8 16 116 OK 4 5.22

VD Calculation 5 of 9 23/09/2008
VOLTAGE DROP CALCULATIONS

Max. Voltage Drop allowed (v)

Cable or Busbar Duct Current


Write "C" for Cable or "B" for

% Voltage Drop Allowed (%)


Cable Size Sqmm or Busbar

Type (e.g. XLPE for Cable &

Check for Current Capacity


Voltage Drop Winthin Limit
CU or AL for Busbar Duct)

Installation Type. G/A/D


Act. % Voltage Drop (v)
Voltage Drop/A/M (mV)
Operating Voltage (V)

Act. Voltage Drop (v)


Runs per Phase

Derating Factor
Load Current A
Current Rating

MCCB Rating

MCCB Rating
Load Current
ADMD in KW

Power factor
Busbar Duct

Dearated Ct.
Mt

TCL in KW
Cable Ref.

TOTAL VD

Rating
Cores
FROM
Cable From Connected To

Length
SOURCE
TO CKT

INCOMER
A TOLL PLAZA (2) MAIN LT P MFP-6 1 3,5 70 C XLPE 415 50 64.51 64.51 125 0.93 5 20.75 0.8 112 5.2 1.26 A 1.00 OK 170 112 125 170 OK 4

OUTGOING
1 MFP-6 C1 1 4 16 C XLPE 415 238 10.75 10.75 32 3.97 5 20.75 0.9 17 15.7 3.78 A 1.00 OK 78 17 32 78 OK 4 5.04
2 MFP-6 C2 1 4 16 C XLPE 415 191 10.75 10.75 32 3.97 5 20.75 0.9 17 12.6 3.04 A 1.00 OK 78 17 32 78 OK 4 4.29
2 MFP-6 C3 1 4 16 C XLPE 415 138 10.75 10.75 32 3.97 5 20.75 0.9 17 9.1 2.19 A 1.00 OK 78 17 32 78 OK 4 3.45
2 MFP-6 C4 1 4 25 C XLPE 415 365 10.75 10.75 32 2.5 5 20.75 0.9 17 15.2 3.65 A 1.00 OK 95 17 32 95 OK 4 4.91
2 MFP-6 C5 1 4 25 C XLPE 415 668 5.38 5.38 16 2.5 5 20.75 0.9 8 13.9 3.34 A 1.00 OK 95 8 16 95 OK 4 4.60
2 MFP-6 C6 1 4 35 C XLPE 415 933 5.38 5.38 16 1.81 5 20.75 0.9 8 14.0 3.38 A 1.00 OK 116 8 16 116 OK 4 4.64
2 MFP-6 FP-8 1 3,5 50 C XLPE 415 630 10.75 10.75 32 1.33 5 20.75 0.9 17 13.9 3.36 A 1.00 OK 140 17 32 140 OK 4 4.61
OUTGOING
1 FP-8 C1 1 4 16 C XLPE 415 218 3.58 3.58 16 3.97 5 20.75 0.9 6 4.8 1.16 A 1.00 OK 78 6 16 78 OK 4 5.77
2 FP-8 C2 1 4 25 C XLPE 415 290 3.58 3.58 16 2.5 5 20.75 0.9 6 4.0 0.97 A 1.00 OK 95 6 16 95 OK 4 5.58
3 FP-8 C3 1 4 35 C XLPE 415 468 3.58 3.20 16 1.81 5 20.75 0.9 6 4.7 1.13 A 1.00 OK 116 6 16 116 OK 4 5.74

VD Calculation 6 of 9 23/09/2008
VOLTAGE DROP CALCULATIONS

Max. Voltage Drop allowed (v)

Cable or Busbar Duct Current


Write "C" for Cable or "B" for

% Voltage Drop Allowed (%)


Cable Size Sqmm or Busbar

Type (e.g. XLPE for Cable &

Check for Current Capacity


Voltage Drop Winthin Limit
CU or AL for Busbar Duct)

Installation Type. G/A/D


Act. % Voltage Drop (v)
Voltage Drop/A/M (mV)
Operating Voltage (V)

Act. Voltage Drop (v)


Runs per Phase

Derating Factor
Load Current A
Current Rating

MCCB Rating

MCCB Rating
Load Current
ADMD in KW

Power factor
Busbar Duct

Dearated Ct.
Mt

TCL in KW
Cable Ref.

TOTAL VD

Rating
Cores
FROM
Cable From Connected To

Length
SOURCE
TO CKT

INCOMER
A Transformer-5 MFP-7 1 4 35 C XLPE 415 150 15.00 15.00 100 1.81 5 20.75 0.85 25 6.7 1.61 A 1.00 OK 116 25 100 116 OK 4

OUTGOING
1 MFP-7 FP-9 2 3,5 70 C XLPE 415 414 29.12 29.12 50 0.93 5 20.75 0.9 45 8.7 2.09 A 1.00 OK 340 45 50 340 OK 4 3.69
2 MFP-7 FP-10 1 3,5 70 C XLPE 415 246 21.55 21.55 40 0.93 5 20.75 0.9 33 7.6 1.84 A 1.00 OK 170 33 40 170 OK 4 3.44

OUTGOING
1 FP-9 C1 1 4 35 C XLPE 415 591 6.27 6.27 16 1.81 5 20.75 0.9 10 10.4 2.50 A 1.00 OK 116 10 16 116 OK 4 6.19
2 FP-9 C2 1 4 25 C XLPE 415 361 6.27 6.27 16 2.5 5 20.75 0.9 10 8.8 2.11 A 1.00 OK 95 10 16 95 OK 4 5.80
3 FP-9 C3 1 4 25 C XLPE 415 448 6.27 6.27 16 2.5 5 20.75 0.9 10 10.9 2.62 A 1.00 OK 95 10 16 95 OK 4 6.31
4 FP-9 C4 1 4 16 C XLPE 415 408 1.34 1.34 16 3.97 5 20.75 0.9 2 3.4 0.81 A 1.00 OK 78 2 16 78 OK 4 4.51
5 FP-9 C5 1 4 16 C XLPE 415 420 1.34 1.34 16 3.97 5 20.75 0.9 2 3.5 0.83 A 1.00 OK 78 2 16 78 OK 4 4.53
5 FP-9 C6 1 4 16 C XLPE 415 443 1.34 1.34 16 3.97 5 20.75 0.9 2 3.7 0.88 A 1.00 OK 78 2 16 78 OK 4 4.57
5 FP-9 C7 1 4 16 C XLPE 415 459 1.34 2.20 16 3.97 5 20.75 0.9 2 3.8 0.91 A 1.00 OK 78 2 16 78 OK 4 4.61
5 FP-9 C8 1 4 35 C XLPE 415 838 4.93 2.20 16 1.81 5 20.75 0.9 8 11.6 2.79 A 1.00 OK 116 8 16 116 OK 4 6.48

OUTGOING
1 FP-10 C1 1 4 16 C XLPE 415 290 5.38 5.38 16 3.97 5 20.75 0.9 8 9.6 2.31 A 1.00 OK 78 8 16 78 OK 4 5.75
2 FP-10 C2 1 4 16 C XLPE 415 392 5.38 5.38 16 3.97 5 20.75 0.9 8 12.9 3.12 A 1.00 OK 78 8 16 78 OK 4 6.56
3 FP-10 C3 1 4 16 C XLPE 415 524 3.58 3.58 16 3.97 5 20.75 0.9 6 11.5 2.78 A 1.00 OK 78 6 16 78 OK 4 6.22
4 FP-10 C4 1 4 16 C XLPE 415 841 2.68 2.68 16 3.97 5 20.75 0.9 4 13.8 3.33 A 1.00 OK 78 4 16 78 OK 4 6.78
5 FP-10 C5 1 4 16 C XLPE 415 755 2.52 2.52 16 3.97 5 20.75 0.9 4 11.7 2.81 A 1.00 OK 78 4 16 78 OK 4 6.26
5 FP-10 C6 1 4 16 C XLPE 415 311 2.01 2.01 16 3.97 5 20.75 0.9 3 3.8 0.92 A 1.00 OK 78 3 16 78 OK 4 4.37

VD Calculation 7 of 9 23/09/2008
Bus bar
Area of Area of
VD/A/M AIR GROUND Duct Ct. @ VD/A/M CSA MCCB
Condr. Condr.
35oC
2.5 25.150 18 21 17.5 800 0.057 185x105 10 1.5 1
4 15.400 23 28 23 1000 0.044 185x120 16 2.5 2
6 9.580 30 35 29 1200 0.036 185x135 20 4 3
10 6.400 53 57 39 1350 0.030 185x150 32 6 4
16 3.970 70 78 94 1600 0.024 185x180 40 10 5
25 2.500 99 95 125 2000 0.019 185x215 50 10 6
35 1.810 117 116 150 2500 0.016 185x255 63 16 7
50 1.330 140 140 175 3200 0.012 185x310 80 25 8
70 0.930 176 170 215 4000 0.010 185x380 100 35 9
95 0.680 221 200 260 5000 0.008 185x460 125 50 10
120 0.550 258 225 300 160 70 11
150 0.460 294 255 335 200 95 12
185 0.370 339 285 380 225 120 13
240 0.300 402 325 440 250 150 14
300 0.260 461 370 495 300 185 15
400 0.220 542 435 570 350 240 16
500 0.180 918 770 620 400 300 17
630 0.170 1027 840 670 630 400 18
800 0.170 1119 888 692 800 500 19
1000 0.160 1214 942 735 1000 630 20
1600 630 21
* Single Core Cables 2000 630 22
3200 630 23
Incomer Breaker Ratings 4000 630 24
1 =< 7 kw 40 A 5000 630 25
7.1 to
63 A 26
2 11kw
11. 1 to 14
80 A 27
3 kw
14.1 to
100 A 28
4 17.5 kw
17.6 to 22
125 A 29
5 kw
22.1 to 28
160 A 30
6 kw
28.1 to 35
200 A 31
7 kw