wind loads. Calculating wind loads is important in design of the wind force-resisting
system, including structural members, components, and cladding, against shear, sliding,
The National Structural Code of the Philippines requires that buildings are
designed to withstand the winds that they are likely to be subjected to. During Wind
Analysis, we are able to determine the wind forces that the structure must be able to
endure.
The design falls under occupancy category III since school building is describe as
Special Occupancy Structure and therefore its importance factor is 1.15. The proposed
factor is 0.85 since the structural type is Building Main Wind Forces Resisting System.
q h=47.3 x 10−6 K z K zt K d V 2 I w
Where in:
V = 200 kPa – Basic Wind Speed (refer to NSCP 2010, Vol.1, Ed. 6 Table 207-1)
Iw = 1.15 – Importance Factor (refer to NSCP 2010, Vol.1, Ed. 6 Table 207-3)
KZT = 1.00 – Topographic Factor (refer to NSCP 2010, Vol.1, Ed. 6 Section 207.5.7.2)
Kd = 0.85 – Wind Directionality Factor (refer to NSCP 2010, Vol.1 Ed. 6 Table 207-
2)
K Z – Velocity Pressure Exposure Coefficients (refer to NSCP 2010, Vol.1, Ed. 6 Table
207-4)
Roof Level
H = 15 m
K z=1.09
Second Floor
H = 8 m ; K Z =0.95
9−7.5 9−8
=
0.98−0.94 0.98−K z
K z=0.953
First floor
H=4m
K z=0.85
Velocity Pressure, q h
q h=47.3 x 10−6 K z K zt K d V 2 I w qh
P=qh (G C pf −GC pi )
Using:
Roof Level
P=qh (G C pf −GC pi ) P
WINDWAD P = 2.015 (0.40 – 0.18) 443.493314 Pa
LEEWARD P = 2.105 (-0.29 – (-0.18)) -221.746657 Pa
Second Floor
First Floor
Transversal Section
Roof Level
F = PA F
F = PA F
First Floor
F = PA F
Longitudinal Section
F = PA F
Second Floor
F = PA F
F = PA F