You are on page 1of 9

Applied Thermal Engineering 114 (2017) 1073–1081

Contents lists available at ScienceDirect

Applied Thermal Engineering


journal homepage: www.elsevier.com/locate/apthermeng

Research Paper

Sizing effects on the energy performance of reversible air-source heat


pumps for office buildings
Matteo Dongellini ⇑, Claudia Naldi, Gian Luca Morini
Department of Industrial Engineering (DIN), Alma Mater Studiorum – University of Bologna, Viale Risorgimento 2, 40136 Bologna, Italy

h i g h l i g h t s

 A study on the annual performance of air-to-water heat pumps is presented.


 The influence of HP modulating capability, climate and system sizing is shown.
 Mono-compressor, multi-compressor and inverter-driven heat pumps are considered.
 SCOP is maximum when HP capacity is tuned on building peak load.
 Best SEER is obtained for HPs slightly oversized with respect to design peak load.

a r t i c l e i n f o a b s t r a c t

Article history: This paper deals with the numerical analysis of the energy performance of HVAC systems for heating and
Received 17 August 2016 cooling, based on a reversible electrical air-source heat pump. The aim of this study is to highlight in
Revised 24 October 2016 which way the energy consumption of these systems is influenced by the heat pump modulating capa-
Accepted 4 December 2016
bility, the heat pump sizing and the climate. A numerical model based on the bin method and the energy
Available online 5 December 2016
signature procedure, able to take into account the performance of the heat pump at partial load, has been
followed in order to calculate the seasonal and annual performance of the HVAC system coupled to a typ-
Keywords:
ical office building, located in three different European locations (Frankfurt, Istanbul, Lisbon). Different
Air-source heat pump
Reversible heat pump
kinds of heat pumps (mono-compressor on-off, multi-compressor and inverter-driven heat pumps) have
Seasonal performance factor been considered. The numerical results presented in this paper point out that the heat pump sizing
Annual performance factor strongly affects seasonal and annual HVAC energy consumption: the ratio between the full thermal
Heat pump oversizing capacity of the heat pump and the building peak load strongly influences the energy performance of
Energy efficiency the system. It has been demonstrated that, depending on the season, the seasonal performance of the
above-mentioned kinds of heat pumps are influenced in a different way by their sizing.
Ó 2016 Elsevier Ltd. All rights reserved.

1. Introduction In 2013 about 56% of the total heat pumps sold in Europe were
reversible units, and about 91% of them were air-source systems
During the last decade, the European Union (EU) has made a [4]. It has been demonstrated that air-source heat pumps can con-
strong effort in order to achieve a significant reduction of both tribute to reduce the primary energy consumption of a building
new and old building energy consumptions. A series of specific with respect to traditional systems [5]; however, the potential
Directives [1–3], aimed to promote the use of renewable energies energy saving linked to the use of air-source heat pumps depends
and to improve the energy efficiency in buildings and HVAC sys- on the correct selection of the heat pump size, on the basis of the
tems, have been published and their application is deeply changing building seasonal energy needs and on outdoor conditions [6]. In
the national regulations. The Directive 2009/28/EC (RES Directive) the last years, many researchers have investigated which parame-
[1], in particular, highlights the potential of technologies based on ters mainly influence the seasonal energy performance of air-
renewable energy sources and promotes this new generation of source heat pumps [7–10] and specific numerical models have
high-efficiency HVAC systems to provide heating, cooling and air been proposed in order to estimate the Seasonal Energy Efficiency
ventilation in buildings. Heat pump systems are one of the most Ratio (SEER) and the Seasonal Coefficient Of Performance (SCOP) of
suitable solutions for energy efficiency improvement in buildings. these devices coupled to a building. As an example, Kinab et al. [11]
presented a numerical model of a modulating reversible air-source
⇑ Corresponding author. heat pump, by means of which the optimal design of the system
E-mail address: matteo.dongellini@unibo.it (M. Dongellini). can be obtained. The interaction between the heat pump character-

http://dx.doi.org/10.1016/j.applthermaleng.2016.12.010
1359-4311/Ó 2016 Elsevier Ltd. All rights reserved.
1074 M. Dongellini et al. / Applied Thermal Engineering 114 (2017) 1073–1081

Nomenclature

APF Annual Performance Factor [–] D extra infrared radiation (external surface-sky) [W/m2]
BES Building Energy Signature [–] e absorptance coefficient of external surface [–]
Cc degradation coefficient for on-off cycles [–]
COP Coefficient Of Performance [–] Subscripts
DD Degree Days [–] avg average value
EER Energy Efficiency Ratio [–] base reference value
E energy [kW h] BU delivered by back-up
I total solar irradiation [W/m2] c cooling value
h heat transfer coefficient [W/m2 K] des design value
N HVAC system operating hours [h] fc full capacity value
P heat pump thermal capacity [kW] el electric value
PLF Part Load Factor [–] ext outdoor value
PLR Part Load Ratio [–] h heating value
SCOP Seasonal Coefficient Of Performance [–] HP delivered by heat pump
SEER Seasonal Energy Efficiency Ratio [–] month monthly value
T temperature [°C] o at outer surface
sa sol-air
Greek symbols supply delivered value
a downsizing/oversizing parameter [–]
b unbalanced loads indicator [–]

istics and the building heating/cooling loads has been investigated of the HVAC system coupled to the office building reflects its occu-
numerically by Madonna and Bazzocchi [12]. The authors pointed pancy profile: during workdays (from Monday to Friday) the heat-
out that the ratio between heating and cooling peak loads strongly ing/cooling plant is switched on from 6.00 to 20.00, on Saturday
affects the annual performance of air-source heat pumps; in build- the HVAC system is activated from 6.00 to 14.00 while on Sunday
ings with unbalanced loads the heat pump seasonal efficiency the system is turned off.
could experience a marked decrease, down to 25%, due to the
excess of on-off cycles. 2.2. Climatic data and choice of the sites
Busato et al. [13] reported a SCOP comparison between single-
stage electrical and gas-driven air-to-water heat pumps, installed In order to take into account the influence of different climates
in residential buildings, by considering three different Italian sites. on the annual performance of the heating/cooling system, the
The study shows that heat pumps have a huge potential to reduce office building has been placed in three different locations: Frank-
primary energy consumption and CO2 emissions, but they are char- furt (50.6°N, 8.4°E), Istanbul (41.0°N, 41.6°E) and Lisbon (38.4°N,
acterized by a greater investment cost with respect to traditional 9.7°E), which can be considered representative, according to the
systems. goal of this work, of Colder, Average and Warmer heating reference
The analysis of the literature in this field puts in evidence that climates indicated by the standard EN 14825 [14] (even if different
the evaluation of the energy saving potentiality of HVAC systems from Helsinki, Strasburg and Athens, cited by the standard).
based on different kinds of electric-driven heat pumps (i.e. The local outdoor temperature bin trend can be calculated by
mono-compressor, multi-compressor, inverter-driven), with means of the hourly outside temperature distribution of the Typi-
respect to traditional heating and cooling systems, is still incom- cal Meteorological Year (TMY) defined for the specific location, as
plete. Some authors focused their research on the optimization of pointed out by Naldi et al. [15]. In this paper, bins of both heating
mono-compressor [8–9,13] or inverter-driven [7,10,12] heat and cooling season have been calculated by using the TMYs of the
pumps, but a complete comparison between the seasonal perfor- Meteonorm database (version 5.0.13) included in TRNSYS 17 [16].
mance obtainable by adopting these heat pumps as a function of In Table 2 the duration of the heating and cooling season is
the design thermal loads of the building is still missing. In this reported together with the typical value of the Heating Degree
paper, the estimation of the seasonal performance, both in heating Days (DDh) and Cooling Degree Days (DDc) of each location. The
and cooling mode, of different models of electric-driven air-to- calculation of DDc has been performed by using the sol-air temper-
water heat pumps, located in different European climates, is ature Tsa [17], by taking into account the effect of incident solar
shown. The aim of the work is the assessment of the optimal sizing radiation on building envelope. Sol-air temperature is an indicator
rules for this kind of heat pumps, in order to obtain the best Annual more useful than external air temperature to consider the severity
Performance Factor (APF) as a function of climate, building thermal of the cooling season and it is defined as:
loads and heat pump characteristics. The relationship between
eI  D
outdoor conditions, heating and cooling loads, modulating capabil- T sa ¼ T ext þ ð1Þ
ho
ity and the system efficiency is presented in order to provide a
complete set of information to HVAC designers. where e is the surface solar absorptance of the building envelope, I
is the global solar irradiance on the envelope, ho is the heat transfer
coefficient for long-wave radiation and convection at the outer sur-
2. The case study face and D is the extra infrared radiation due to difference between
the external air temperature and the apparent sky temperature (cal-
2.1. Building characteristics culated by means of UNI TS 11300-1:2014 [18]).
To evaluate the effect of defrosting cycles during the heating
A typical three-story office building having the characteristics season, the percentage of the heating season in which the outdoor
summarized in Table 1 has been considered. The working profile conditions fall within the frosting region [19] (i.e. air temperature
M. Dongellini et al. / Applied Thermal Engineering 114 (2017) 1073–1081 1075

Table 1
Geometrical and thermal characteristics of the selected office building.

Net floor area Total surface area Total windows area Net volume S/V ratio External wall U-value Floor U-value Windows U-value
(m2) (m2) (m2) (m3) (m1) (W/m2 K) (W/m2 K) (W/m2 K)
787 1416 139 2125 0.52 0.37 0.46 1.70

Table 2
Main climatic data of the selected sites.

Frankfurt Istanbul Lisbon


Heating season
Length of the season From 1st October to 30th April From 1st November to 15th April From 1st December to 31st March
DDh (Tbase,h = 20 °C) 3233 1973 863
Frosting period 60% 36% 3%
Cooling season
Length of the season From 1st June to 31st August From 1st June to 30th September From 1st May to 30th September
DDc (Tbase,c = 26 °C) 405 1079 1251

below 6 °C and relative humidity above 50%), is shown in Table 2 milder heating season, with Tdes,h equal to 3 °C and 4 °C,
for each location. A penalty coefficient has been applied on the heat respectively, and Tavg,h equal to 8.3 °C and 11.6 °C, respectively.
pump performance during the hours falling in the frosting region, The hot seasons of the selected locations are more similar to one
by following the simplified model by Vocale et al. [20]. With the another, as evidenced by Fig. 1b. The most severe condition for the
method suggested in [20], the number of defrost cycles can be esti- heat pump is set in Lisbon, with a value of the design temperature
mated by considering both the external conditions and the heat Tdes,c of 32 °C and with an average outdoor temperature Tavg,c equal
pump characteristics; in this way it becomes possible to link the to 20.7 °C. Istanbul cooling season is characterized by similar
penalty coefficient to the heat pump modulating capability. values (Tdes,c equal to 30 °C and Tavg,c equal to 22.4 °C) but the
The bin distributions of the selected locations present different length of the season is one month shorter than in Lisbon. Finally,
trends, as evidenced in Fig. 1. Fig. 1a highlights that the heating Frankfurt presents a cooling design temperature of 29 °C and an
season in Frankfurt is the coldest among the selected climates: it average air temperature equal to 18.1 °C; in this location bins are
presents a design temperature Tdes,h of 10 °C with an average shifted towards lower outdoor temperature values.
value Tavg,h of 4.9 °C. Istanbul and Lisbon are characterized by a
2.3. Heating and cooling loads calculation

250 The calculation of building net thermal energy needs for space
Bin (hours)

Frankfurt heating and cooling has been performed on a monthly basis


200 Istanbul according to the standard EN ISO 13790:2008 [21]. As a result,
the monthly net thermal energy required by the building for
Lisbon
heating and cooling (Emonth,h and Emonth,c, respectively) has been
150
obtained.
Considering an operating time for the HVAC system that follows
100 the activation profiles described previously, both during the heat-
ing and cooling season, it is possible to calculate the monthly mean
50 thermal power that the heat pump (Pmonth,h/c) has to supply to the
building by dividing the thermal energy needs for the number of
0 operating hours (Nmonth).
-10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 The monthly values of Pmonth,h/c can be correlated to the monthly
Outdoor air temperature (°C) average values of the outdoor air temperature (or sol-air tempera-
(a) ture in summer) via the Building Energy Signature (BES) method
(Fels [22], UNI EN 15603 [23]), which considers the outdoor tem-
200
Bin (hours)

perature (or the sol-air temperature during the hot season) as


Frankfurt the only forcing term of building thermal needs.
Istanbul In Fig. 2 Pmonth,h/c values are represented as functions of the out-
150
Lisbon door monthly average temperature in winter and sol-air tempera-
ture in summer; the linear interpolation of these data represents
100 the BES, both for heating and cooling season, associated to the
office building in the three selected sites. BESs obtained for the
same building located in Frankfurt, Istanbul and Lisbon are repre-
50 sented in Fig. 2a–c, respectively.
By observing Fig. 2, it is evident that in Frankfurt the heating
peak load (Pdes,h = 31.3 kW) is larger than the cooling peak load
0
(Pdes,c = 13.6 kW); on the other hand, in Istanbul seasonal peak
5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35
Outdoor air temperature (°C)
loads are more balanced (Pdes,h = 20.1 kW, Pdes,c = 15.8 kW) like in
(b) Lisbon, where the maximum peak load is associated to the cooling
season (Pdes,h = 14.1 kW, Pdes,c = 16.3 kW). Frankfurt is representa-
Fig. 1. Bin trend for the selected locations during heating (a) and cooling season (b). tive of typical situations in which the maximum thermal load is
1076 M. Dongellini et al. / Applied Thermal Engineering 114 (2017) 1073–1081

40
Thermal power (kW) Building heating load

Building cooling load


30
Pdes,h

20

Pdes,c
10

Tdes,h Tdes,c
0
-10 -5 0 5 10 15 20 25 30 35 40
Outdoor air temperature (°C) (a)

40
Thermal power (kW) Building heating load

Building cooling load


30

20 Pdes,h
Pdes,c

10

Tdes,h Tdes,c
0
-10 -5 0 5 10 15 20 25 30 35 40
Outdoor air temperature (°C) (b)

40
Thermal power (kW) Building heating load

Building cooling load


30

20
Pdes,c
Pdes,h
10

Tdes,h Tdes,c
0
-10 -5 0 5 10 15 20 25 30 35 40
Outdoor air temperature (°C) (c)

Fig. 2. Building energy signature for heating and cooling season: Frankfurt (a), Istanbul (b) and Lisbon (c).

reached during winter and strongly unbalanced loads are present Pdes;c
b¼ ð2Þ
moving from the heating to the cooling season. Istanbul is repre- Pdes;h
sentative of sites in which maximum thermal loads are always
reached during winter, but loads moving from the cold to the hot
season are only slightly unbalanced. Lisbon is representative of when b = 1 the absolute value of the design thermal power is the
locations in which the cooling season is more severe than the heat- same both for heating and cooling; when b > 1 the building thermal
ing one, but loads are balanced from one season to the other. loads during summer are larger than the winter loads and the oppo-
An indicator of the existence of seasonal unbalanced loads can site occurs for b < 1. The three examples in this paper are character-
be introduced by the ratio b: ized by b = 0.43 (Frankfurt), b = 0.79 (Istanbul) and b = 1.16 (Lisbon).
M. Dongellini et al. / Applied Thermal Engineering 114 (2017) 1073–1081 1077

2.4. Description of heat pumps characteristics At partial loads, the simplest solution to fit the heat pump
capacity to the building load is to perform a series of on-off cycles,
The HVAC system coupled to the office building is based on a which, however, have a strong impact on heat pump efficiency and
single reversible electric heat pump, which satisfies both heating consequently on the overall seasonal energy performance of the
and cooling loads; electric heaters have been considered as back- unit [25]. In fact, for each restart, the compressor restores the pres-
up system during the cold season, whereas no back-up systems sure difference between condenser and evaporator and, during off
are considered for the hot season. The building terminal units con- periods, energy consumption due to auxiliary appliances is still
sist of two-pipe fan-coils, sized with a supply water temperature of active. The capability of multi-compressor and inverter-driven
45 °C during winter and 7 °C in summer. heat pumps to reduce the use of on-off cycles is one of the reasons
Three different heat pump typologies are considered: mono- of their better performance compared with mono-compressor on-
compressor ON-OFF Heat Pumps (ON-OFF HPs), Multi- off heat pumps. In addition, it is important to take into account that
Compressor Heat Pumps (MCHPs) and Inverter-Driven Heat Pumps at partial loads the heat exchanger surfaces become oversized and
(IDHPs). the pressure ratio between condensation and evaporation is
For each heat pump typology, different units, which differ for reduced; all these effects improve the performance of these heat
their nominal thermal capacity, have been selected: the most pow- pump typologies at partial loads.
erful heat pump model for each typology has been chosen in order To take into account the above-mentioned degradation of COP
to match the peak load during the most severe season. Then, other or EER at partial loads, several researchers [6,8,10–12,15] and stan-
smaller units have been considered, in order to evaluate the influ- dards [14] have proposed to correct the full load COP/EER by means
ence of heat pump sizing on the seasonal and annual performance. of a part load factor (PLF), defined as follows:
For Frankfurt and Istanbul climates (b < 1), the choice of the small-
PLR
est nominal thermal power is based on the cooling peak load. For PLF ¼ ð3Þ
Lisbon (b > 1), the heating and cooling loads are almost balanced ð1  C C Þ þ C c PLR
but the cooling season is slightly more severe; therefore, the heat where Cc is a parameter that takes into account on-off losses and
pump sizing is based on the cooling peak load. In fact, even if smal- the part load ratio (PLR) is defined as the percentage of the full load
ler heat pumps would be more suitable during the cold season, capacity delivered by the heat pump at partial load. As highlighted
then the cooling demand would not be satisfied during the whole by Madonna and Bazzocchi [12], the value of Cc strongly influences
hot season, since no back-up system for cooling is present in the on-off losses: for Cc = 1 no degradation effects are considered, while
HVAC system. cycling losses increase if Cc decreases. The value of Cc suggested by
Eleven different commercial reversible air-to-water heat pumps UNI EN 14285 [14] is 0.9, but experimental tests have highlighted
have been considered; technical data at full capacity given by the that values from 0.7 to 0.9 can be in some cases more realistic: as
manufacturer are reported in Tables 3–5 for ON-OFF HPs, MCHPs an example, Madonna and Bazzocchi [12] have used for their
and IDHPs, respectively. Each heat pump is identified by a progres- variable-speed air-to-water heat pump values of the degradation
sive number (# HP unit). coefficient equal to 0.73 and 0.83 for heating and cooling modes
The calculation of the seasonal energy performance of the respectively.
above-mentioned heat pumps, coupled to the office building For MCHPs and IDHPs, the model used in this paper [24] allows
described before, has been performed by following the numerical to take into account the modulation range of these devices: within
method proposed by Dongellini et al. [24], which takes into this range, the model calculates heat pump performance at partial
account the different modulating capability of the heat pump load by evaluating the characteristic curves of the unit on the basis
typologies and calculates the heat pump efficiency at partial loads. of the number of compressors switched on (MCHPs) or the effec-
This aspect is crucial for a correct analysis of the seasonal and tive inverter frequency (IDHPs). Outside the modulation range,
annual energy performance of the system, because heat pumps heat pump COP/EER is corrected by means of PLF from Eq. (3), by
work at full load only for a limited period of the whole heating/- assuming Cc = 0.9.
cooling season. More in detail, the evaluation of SCOP and SEER
for the proposed case study has been carried out according to the
‘‘fixed outlet” approach reported by the standard EN 14825 [14]; 3. Discussion of the results
in the present analysis, the supply water temperature has been
fixed at 45 °C during the heating season and at 7 °C during the The seasonal energy performance of a HVAC system character-
cooling season. ized by a single reversible unit, is heavily affected by the device siz-
ing. In the case of strongly unbalanced seasonal peak loads, as

Table 3
Thermal/cooling capacity and COP/EER at full load of the selected on-off heat pumps.

# HP unit 1 2 3 4
HP typology ON-OFF HP ON-OFF HP ON-OFF HP ON-OFF HP
Heating mode (Tsupply,h = 45°C)
Text (°C) Ph (kW) COP Ph (kW) COP Ph (kW) COP Ph (kW) COP
7 17.8 2.55 20.0 2.56 21.9 2.58 26.4 2.59
2 20.6 2.94 23.6 2.96 25.9 2.97 31.6 2.95
7 22.9 3.31 27.0 3.33 29.8 3.36 36.3 3.37
12 25.7 3.74 31.0 3.76 34.3 3.81 41.1 3.78
Cooling mode (Tsupply,c = 7°C)
Text (°C) Pc (kW) EER Pc (kW) EER Pc (kW) EER Pc (kW) EER
20 22.3 4.28 27.2 4.30 31.0 4.31 35.9 4.33
25 21.2 3.73 26.1 3.80 29.5 3.76 34.3 3.82
30 20.2 3.30 24.7 3.32 27.8 3.26 32.7 3.35
35 19.2 2.82 23.3 2.88 26.1 2.79 30.9 2.86
1078 M. Dongellini et al. / Applied Thermal Engineering 114 (2017) 1073–1081

Table 4
Thermal/cooling capacity and COP/EER at full load of the selected multi-compressor heat pumps.

# HP unit 5 6 7 8
HP typology MCHP MCHP MCHP MCHP
Compressors 2 2 2 2
Heating mode (Tsupply,h = 45°C)
Text (°C) Ph (kW) COP Ph (kW) COP Ph (kW) COP Ph (kW) COP
7 14.6 2.47 16.7 2.42 20.0 2.48 24.6 2.44
2 19.1 3.04 21.8 2.97 26.0 3.00 32.1 2.99
7 22.2 3.36 25.1 3.31 30.1 3.35 37.3 3.33
12 25.6 3.67 29.1 3.71 34.8 3.75 43.0 3.72
Cooling mode (Tsupply,c = 7°C)
Text (°C) Pc (kW) EER Pc (kW) EER Pc (kW) EER Pc (kW) EER
20 21.8 4.62 25.3 4.68 30.7 4.64 37.1 4.67
25 20.8 4.13 24.2 4.18 29.3 4.08 35.6 4.15
30 19.9 3.59 22.8 3.62 27.9 3.57 34.0 3.66
35 18.8 3.15 21.6 3.18 26.4 3.11 32.4 3.20

Table 5
Thermal/cooling capacity and COP/EER at full load of the selected inverter-driven heat pumps (data evaluated for inverter frequency equal to 120 Hz).

# HP unit 9 10 11
HP typology IDHP IDHP IDHP
Frequency range (Hz) 20–120 20–120 20–120
Heating mode (Tsupply,h = 45°C)
Text (°C) Ph (kW) COP Ph (kW) COP Ph (kW) COP
7 15.1 2.11 21.3 2.10 24.4 2.14
2 18.6 2.52 26.1 2.54 30.1 2.55
7 21.2 2.82 29.6 2.76 33.2 2.78
12 24.6 3.22 33.8 3.18 38.6 3.19
Cooling mode (Tsupply,c = 7°C)
Text (°C) Pc (kW) EER Pc (kW) EER Pc (kW) EER
20 21.9 3.89 30.7 3.85 34.4 3.81
25 20.9 3.37 29.4 3.33 32.9 3.31
30 19.7 2.89 28.0 2.85 31.3 2.86
35 18.5 2.46 26.6 2.42 29.6 2.45

obtained for Frankfurt, the heat pump can fit exactly only one of P fc;c  Pdes;c
ac ¼ ð5Þ
these two peak loads. Pdes;c
In Table 6 the heating and cooling full capacity (Pfc,h, Pfc,c) of the
A value of a equal to 0 means that the selected heat pump is
selected heat pumps, evaluated at the design outdoor temperature,
able to deliver exactly the building design thermal load; for a < 0
are shown and compared with the heating and cooling peak loads
the heat pump is downsized with respect to the building loads,
of the office building situated in the three considered locations. It is
while a > 0 indicates an oversized heat pump.
possible to check the heat pump oversizing/downsizing with
By fixing a heat pump, its downsizing/oversizing depends on
respect to the design loads by introducing the heating and cooling
the location of the building. For example, the MCHP #6 is strongly
oversizing parameters (ah, ac) defined as:
oversized during the cooling season, with respect to the cooling
Pfc;h  Pdes;h peak loads of the office building situated in Frankfurt and Istanbul
ah ¼ ð4Þ
Pdes;h (ac = 70% and ac = 45%, respectively). On the other hand, the heat
pump #6 is downsized with respect to the heating loads in Frank-

Table 6
Full heating and cooling capacity (Pfc,h Pfc,c) at the design temperature of the selected heat pumps and percentage of their oversizing (or downsizing) in heating and cooling mode
for the typical office building as a function of its location.

Location Frankfurt Istanbul Lisbon


Unit full Down/Oversizing Unit full Down/Oversizing Unit full Down/Oversizing
capacity at Tdes parameter capacity at Tdes parameter capacity at Tdes parameter
(kW) (kW) (kW)
# HP unit Pfc,h Pfc,c ah ac Pfc,h Pfc,c ah ac Pfc,h Pfc,c ah ac
1 (ON-OFF) 16.3 20.4 48% +50% 18.5 20.2 8% +28% 21.5 19.8 +53% +22%
2 (ON-OFF) 18.2 25.0 42% +84% 20.9 24.7 +4% +57% – – – –
3 (ON-OFF) 19.9 28.2 36% +107% 22.9 27.8 +14% +76% – – – –
4 (ON-OFF) 23.2 33.0 26% +143% – – – – – – – –
5 (MCHP) 13.4 20.1 57% +48% 16.5 19.9 18% +26% 20.3 19.4 +44% +19%
6 (MCHP) 15.4 23.1 51% +70% 18.8 22.9 6% +45% – – – –
7 (MCHP) 18.4 28.2 41% +107% 22.4 27.9 +12% +77% – – – –
8 (MCHP) 22.6 34.3 28% +153% – – – – – – – –
9 (IDHP) 14.4 20.0 54% +47% 16.4 19.7 18% +25% 19.6 19.2 +39% +18%
10 (IDHP) 20.2 28.3 35% +108% 23.2 28.0 +16% +77% – – – –
11 (IDHP) 23.3 31.6 26% +133% – – – – – – – –
M. Dongellini et al. / Applied Thermal Engineering 114 (2017) 1073–1081 1079

furt (ah = 51%) but in Istanbul it is only slightly downsized the smallest units, i.e. models #1 (ah = 8%), #5 (ah = 18%) and
(ah = 6%). The value of ah and ac is reported in Table 6 for each #9 (ah = 18%) for ON-OFF HPs, MCHPs and IDHPs, respectively.
heat pump and climate. In Lisbon the cooling season is more severe than the hot season
For each case, the thermal energy delivered by the heat pump and the heat pump selection is based on the cooling peak load.
and by the electric back-up (if needed), as well as the electrical Hence, only the smallest units (#1: ac = 22%, #5: ac = 19%, #9:
energy overall consumptions of the system have been calculated, ac = 18%) have been considered in simulations. The HVAC system
both for heating and cooling modes. The seasonal performance in Lisbon gives the best annual performance among the considered
indexes linked to the heating season (SCOP) and to the cooling sea- sites.
son (SEER) have been evaluated: In order to outline general rules for the optimal sizing of HVAC
systems based on reversible heat pumps, in Fig. 3 the SCOP trend
EHP;h þ EBU;h
SCOP ¼ ð6Þ calculated with different heat pumps is represented as a function
Eel;HP;h þ Eel;BU;h of ah.
For downsized heat pumps (negative ah), the SCOP decreases
EHP;c rapidly because it is negatively influenced by the electric heaters
SEER ¼ ð7Þ
Eel;HP;c used as back-up system. When the heat pump capacity is tuned
on the building thermal needs (ah between 20% and 20%), the
where EHP and EBU are the thermal energy delivered by the heat SCOP reaches its maximum value for ON-OFF HPs; this value is gen-
pump and by the back-up system, respectively, and Eel,HP and Eel,BU erally lower than those obtained with MCHPs and IDHPs, due to
are the electric energy consumptions of the heat pump and of the their enhanced capability to reduce the number of on-off cycles
back-up system, respectively. by modulating the thermal power delivered. By adopting MCHPs
The Annual Performance Factor (APF), able to describe the and IDHPs it is possible to obtain higher SCOP values even for
annual energy performance of the system (by taking into account ah > 20% with respect to ON-OFF HPs.
both the heating and cooling behavior in a while) and defined as: In Fig. 4 the SEER trend is represented as a function of ac; results
EHP;h þ EBU;h þ EHP;c point out that, by scaling from larger to smaller units, the SEER
APF ¼ ð8Þ increases because the chillers reduce their need of on-off cycles.
Eel;HP;h þ Eel;BU;h þ Eel;HP;c
The maximum SEER is obtained for values of ac close to zero; the
is also calculated for all the cases investigated in this work. values of SEER for ON-OFF HPs are lower than those obtained for
In Table 7 the values assumed by the indexes of Eqs. (6)–(8) are IDHPs and MCHPs; in addition, Fig. 4 highlights that the influence
shown for each case. These performance values can be useful in of ac on the value of SEER is larger for ON-OFF HPs with respect to
order to evidence the influence of the heat pump typology, climate IDHPs and MCHPs due to the enhanced modulating capability of
and unit sizing on the seasonal and annual energy performance of the latter two heat pump typologies.
the system.
In a site like Frankfurt characterized by a heating season more 3,4
severe than the cooling season (b = 0.43), the heat pump size is
generally chosen accordingly to the heating peak load. In this case, 3,2
units #4, #8 and #11 are the closest to the heating peak load, with
downsized full capacity at design outdoor temperature (#4: 3,0
ah = 26%, #8: ah = 28%, #11: ah = 26%). Since in Frankfurt the
2,8
SCOP

cooling peak load is lower than the heating one, units #4, #8 and
#11 result largely oversized with respect to the cooling peak load, 2,6
up to 153% for unit #8 (see Table 6). Therefore, during the cooling
season the chillers have to deliver only a small fraction of their full ON-OFF HP
2,4
cooling capacity by using their modulation capability. MCHP
In Istanbul heating and cooling peak loads are similar (b = 0.73), 2,2 IDHP
but the cold season is still more severe than the hot season; conse-
quently, heat pump sizing is usually based on the heating design 2,0
-80% -60% -40% -20% 0% 20% 40% 60%
load. Owing to a lower value of heating peak load, units #4, #8
h
and #11 have not been considered for Istanbul simulations due
to their large cooling and heating capacity. The results point out Fig. 3. SCOP as a function of the heating heat pump downsizing/oversizing
that the best annual performance is achievable by considering parameter (ah).

Table 7
Seasonal and annual performance indexes as functions of the considered heat pump and of the location.

Location Frankfurt Istanbul Lisbon


# HP unit SCOP SEER APF SCOP SEER APF SCOP SEER APF
1 (ON-OFF) 2.49 3.09 2.54 2.77 3.27 2.95 2.72 3.13 2.94
2 (ON-OFF) 2.57 2.91 2.60 2.69 3.14 2.85 – – –
3 (ON-OFF) 2.62 2.76 2.63 2.65 3.01 2.78 – – –
4 (ON-OFF) 2.59 2.63 2.60 – – – – – –
5 (MCHP) 2.53 4.29 2.64 3.15 4.34 3.52 3.31 4.22 3.79
6 (MCHP) 2.71 4.08 2.80 3.19 4.17 3.51 – – –
7 (MCHP) 2.89 3.85 2.96 3.16 4.05 3.45 – – –
8 (MCHP) 2.93 3.61 2.99 – – – – – –
9 (IDHP) 2.29 4.35 2.40 2.93 4.33 3.35 3.23 4.25 3.75
10 (IDHP) 2.59 4.07 2.69 2.89 4.13 3.27 – – –
11 (IDHP) 2.66 4.02 2.75 – – – – – –
1080 M. Dongellini et al. / Applied Thermal Engineering 114 (2017) 1073–1081

4,5 fact, the enhanced modulating capability of these devices strongly


cuts down the difference between heat pump capacity and build-
ing thermal loads, avoiding on-off cycles penalization.
4,0
Furthermore, Fig. 5 highlights the influence of unbalanced
building loads on the annual system performance: APF is lower
3,5 in correspondence of lower values of b. In fact, a thermal load
SEER

strongly unbalanced during winter (i.e. a low b value) leads to a


higher use of electric back-up heaters.
3,0
These results suggest, for an optimal exploitation of the energy
ON-OFF HP
saving potential of heat pumps, a building design able to obtain
2,5 MCHP balanced heating and cooling loads (b ffi 1), so the heat pump can
IDHP cover both heating and cooling loads by reducing the use of
2,0 back-up systems. MCHPs and IDHPs must be preferred to ON-OFF
0% 20% 40% 60% 80% 100% 120% 140% 160% 180% HPs due to their enhanced modulating capability, which reduces
c the use of on-off cycles during the year; nevertheless, their use
in buildings with low b (b < 0.5) markedly reduces the energy
Fig. 4. SEER as a function of the cooling heat pump downsizing/oversizing
savings.
parameter (ac).
As a rule for HVAC designers, the best energy performance of
HVAC systems based on a single reversible electric heat pump is
reached if a multi-compressor or an inverter-driven heat pump is
4,0 selected with a slight oversizing with respect to the annual build-
ON-OFF HP
ing thermal loads, according to the overall parameter atot intro-
duced in this paper.
3,6 MCHP =1.16

IDHP

3,2
4. Conclusions
APF

2,8 In this work the behavior of a HVAC system based on a reversi-


ble air-to-water heat pump coupled to a typical office building dur-
2,4 ing both heating and cooling season has been analyzed. Electric
=0.79 resistances have been considered as back-up system during winter.
=0.43 The main seasonal and annual energy performance indexes have
2,0 been calculated by means of a model based on the bin-method
-60% -40% -20% 0% 20% 40% 60%
and the building energy signature. Mono-compressor on-off,
tot
multi-compressor and inverter driven heat pumps have been con-
Fig. 5. APF as a function of the overall heat pump downsizing/oversizing parameter sidered to take into account the different capability of thermal
(atot). power modulation of these devices.
The obtained results evidence that downsizing/oversizing
degree of the considered heat pump with respect to the thermal
loads of the building is a crucial parameter that influences the
In order to analyze the annual energy performance of the HVAC energy performance of the HVAC system. It has been demonstrated
system, an overall indicator of the downsizing/oversizing degree of that during winter, when the full thermal capacity delivered by the
the system (atot) has been defined: selected heat pump at design conditions ranges from 20% to +20%
of the building design thermal load, the SCOP value becomes max-
DDh ah þ DDc ac
atot ¼ ð9Þ imum, especially for buildings characterized by balanced loads
DDh þ DDc
between winter and summer. Inverter driven and multi-
compressor heat pumps are able to guarantee larger SCOP than
where ah and ac are weighted on the degree days linked to the heat-
those obtainable by adopting on-off heat pumps (+20%). The lar-
ing (DDh) and cooling (DDc) seasons.
gest values of SEER are reached if the heat pump oversizing is lower
In Fig. 5 APF is shown as a function of atot. Values of the unbal-
than 40% of the design building cooling load.
ance indicator b (see Eq. (2)) are also reported for each case. It is
In addition, it has been demonstrated that the Annual Perfor-
evident that the best annual performance is obtained by adopting
mance Factor (APF) of the system is a function of the unbalance
MCHPs or IDHPs slightly oversized (0% < atot < 40%) with respect to
indicator b and of the overall index of the downsizing/oversizing
building design energy needs.
degree of the system atot. The variation of APF with b and atot is
ON-OFF HPs are less influenced by the overall oversizing per-
strongly dependent on the kind of heat pump considered (on-off,
centage than the other heat pump typologies: from atot = 30% to
multi-compressor, inverter driven), which means that the rules
atot = 20–40%, APF increases of about 10% for on-off units and of
for the optimal sizing of a heat pump change with the typology
about 20% for other heat pump typologies. This result highlights
of the selected heat pump.
the influence of heat pump sizing on the annual energy perfor-
mance of the HVAC system.
Fig. 5 confirms that ON-OFF HPs are able to reach lower APF val-
ues (16%) with respect to MCHPs and IDHPs. Reported data high- Acknowledgements
lights also that the more accurate control of the thermal power
delivered by multi-compressor and inverter-driven heat pumps The authors acknowledge the support provided by the manu-
can guarantee larger enhancements on APF, especially with unbal- facturer Galletti Group Spa (Italy) which made the technical data
anced loads (b < 1 or b > 1) and a strong heat pump oversizing. In sheets of their electric heat pumps available for this analysis.
M. Dongellini et al. / Applied Thermal Engineering 114 (2017) 1073–1081 1081

References [13] F. Busato, R.M. Lazzarin, M. Noro, Energy and economic analysis of different
heat pump systems for space heating, Int. J. Low-Carbon Technol. 7 (2012)
104–112.
[1] European Commission, Directive 2009/28/EC of the European Parliament and
[14] European standard EN 14825:2013, Air conditioners, liquid chilling packages
of the Council of 23 April 2009 on the Promotion of the use of energy from
and heat pumps, with electrically driven compressors, for space heating and
renewable sources, 2009.
cooling – Testing and rating at part load conditions and calculation of seasonal
[2] European Commission, Directive 2010/31/EU of the European Parliament and
performance, 2013.
of the Council of 19 May 2010 on the Energy Performance of Buildings, 2010.
[15] C. Naldi, M. Dongellini, G.L. Morini, E. Zanchini, Comparison between hourly
[3] European Commission, Directive 2012/27/EU of the European Parliament and
simulation and bin-method for the seasonal performance evaluation of electric
of the Council of 25 October 2012 on Energy Efficiency, amending Directives
air-source heat pumps for heating, in: Proceedings of Building Simulation
2009/125/EC and 2010/30/EU and repealing Directives 2004/8/EC and 2006/
Applications 2015–2nd IBPSA Italy, Bolzano, Italy, 2015.
32/EC, 2012.
[16] S.A. Klein et al., TRNSYS 17: A Transient System Simulation Program, Solar
[4] T. Nowak, P. Westring, Heat pump market development in Europe, in:
Energy Laboratory, University of Winsconsin, Madison, USA, 2010.
Proceedings of 7th EHPA European Heat Pump Forum, Berlin, Germany, 2014.
[17] Handbook, ASHRAE fundamentals, Non-residential cooling and heating load
[5] R. Chargui, H. Sammouda, Modeling of a residential house coupled with a dual
calculation procedures, American Society of Heating, Refrigerating and
source heat pump using TRNSYS software, Energy Convers. Manage. 81 (2014)
AirConditioning Engineers, Atlanta, USA, 2001.
384–399.
[18] Italian standard UNI TS 11300-1:2014, Energy performance of buildings – Part
[6] W. Wu, W. Shi, B. Wang, X. Li, Annual performance investigation and economic
1: Evaluation of energy need for space heating and cooling, 2014.
analysis of heating systems with a compression-assisted air source absorption
[19] J.H. Zhu, Y.Y. Sun, W. Wang, S.M. Deng, Y.J. Ge, L.T. Li, Developing a new
heat pump, Energy Convers. Manage. 98 (2015) 290–302.
frosting map to guide defrosting control for air-source heat pump units, Appl.
[7] S. In, K. Cho, B. Lim, C. Lee, Partial load performance test of residential heat
Therm. Eng. 90 (2015) 782–791.
pump system with low-GWP refrigerants, Appl. Therm. Eng. 85 (2015) 179–
[20] P. Vocale, G.L. Morini, M. Spiga, Influence of outdoor air conditions on the air
187.
source heat pumps performance, Energy Proc. 45 (2014) 653–662.
[8] W. Chen, A comparative study on the performance and environmental
[21] European standard ISO 13790:2008, Energy performance of buildings –
characteristics of R410A and R22 residential air conditioners, Appl. Therm.
Calculation of energy use for space heating and cooling, 2008.
Eng. 28 (2008) 1–7.
[22] M.F. Fels, PRISM: an introduction, Energy Build. 9 (1986) 5–18.
[9] L. Palmiter, J.-H. Kim, B. Larson, P.W. Francisco, E.A. Groll, J.E. Braun, Measured
[23] European standard UNI EN 15603, Energy performance of buildings — Overall
effect of airflow and refrigerant charge on the seasonal performance of an air-
energy use and definition of energy ratings. 2008.
source heat pump using R-410A, Energy Build. 43 (2011) 1802–1810.
[24] M. Dongellini, C. Naldi, G.L. Morini, Seasonal performance evaluation of
[10] L. Junghans, Evaluation of the economic and environmental feasibility of heat
electric air-to-water heat pump systems, Appl. Therm. Eng. 90 (2015) 1072–
pump systems in residential buildings, with varying qualities of the building
1081.
envelope, Renew. Energy 76 (2015) 699–705.
[25] H.I. Henderson, D. Parker, Y.J. Huang, Improving DOE-2’s RESYS routine: user
[11] E. Kinab, D. Marchio, P. Riviere, A. Zoughaib, Reversible heat pump model for
defined functions to provide more accurate part load energy use humidity
seasonal performance optimization, Energy Build. 42 (2010) 2269–2280.
predictions, in: 2000 ACEEE Summer Study Proceedings, 2000.
[12] F. Madonna, F. Bazzocchi, Annual performances of reversible air-to-water heat
pumps in small residential buildings, Energy Build. 65 (2013) 299–309.

You might also like