Professional Documents
Culture Documents
2. Introduction
Wall wetting sprinkler systems are utilised where the proximity of new or existing structures to a fire
source feature are inadequate to satisfy the requirements of the Building Code of Australia, Part C3
or where inferior walls (ie, those not meeting the FRL requirements of the regulations) are installed.
Wall wetting systems provide a deemed to comply fire resistance level on an inferior wall required to
be fire rated by the regulations. The inferior wall may be constructed of any material, however, wall
wetting systems incorporating glazed construction are the most commonly installed. The fire
resistance level is achieved by the action of water delivered onto the inferior wall so as to provide a
constant flow of water across the surface of the wall.
The Building Code of Australia Part C3 requires such openings to be protected by internal or
external wall wetting sprinklers. The protection of inferior walls is normally part of a modificaion or
dispensation process. The Building Code of Australia does not specify any details of wall wetting
sprinklers and the application of AS 2118.2 for these systems is inappropriate. As a result, there has
not previously been a consistent approach to the installation of these systems.
3. Objectives
The principal objective of this guideline is to provide a practical reference document for designers
and regulators for use in the design and installation of wall wetting systems. This specification does
not replace the process of obtaining regulatory approval for the provision of wall wetting systems. In
addition, this paper aims to ensure that the primary fire protection systems to which the wall wetting
system is connected are not compromised by the design.
Where modification or dispensation has been granted requiring the use of wall wetting systems, the
Building Control Branch of the City of Melbourne and the Fire Safety Department of the
Metropolitan Fire Brigade will support the use of systems designed and installed in accordance with
this document.
4. Background
Many papers exist which indicate the suitability of glass wall wetting systems, however a proven
method of construction or test has not been developed. Appendix A contains a bibliography of the
papers researched for this guideline in an effort to standardise some of the systems used in these
tests.
When exposed in a fire, glass characteristically fails due to either:
a) Radiant heat induced failure; or
b) Direct flame contact induced failure.
© Metropolitan Fire & Emergency Services Boards Structural Fire Safety Ph. (03) 9420 3874
GL-010
During radiant heat exposure, differing radiation levels cause internal stresses and differing thermal
expansion of the glass surface. Failure can occur when temperature differences are as low as
approximately 40oC. In wall wetting systems, sprinkler heads are designed to activate and fully wet
the surface before radiation effects cause glass failure. Water flow then maintains the glass at a
constant temperature thus maintaining the smoke and heat barrier.
However, where direct flame contact is made with the glass, thermal shock causing stresses between
the hot and cool side of the glass occurs. This causes rapid cracking and failure of the glass
irrespective of whether or not general heating has taken place. Increased glass thickness may
accelerate this type of failure. In this instance, heat build up will not be sufficient to activate the
sprinkler head and the smoke and heat barrier integrity is immediately compromised. This
characteristic has been highlighted in a number of tests.
Glass wall wetting systems are not suitable for all applications and a proven reliable method of
constructing a satisfactory glass wall wetting system has not been developed. In particular, the fire
load adjacent to the glass wall has a substantial impact on the effectiveness of this type of system to
achieve its objectives. The Metropolitan Fire Brigade and City of Melbourne therefore make no
representations or otherwise as to the effectiveness of glass wall wetting systems to withstand the
effects of fire for the required period of time.
2
GL-010
6. Specification
6.1 Introduction
Wall wetting systems may be installed internally or externally. It is therefore important for the
sprinklers to be located on the correct side of the glazing; ie. on the side from which protection is
required. Internal protection is intended to prevent the fire transferring from the subject building or
compartment, while external protection is intended to protect the building from fire from another
source. The appropriate design choice is dependent upon each application and should be discussed
with the relevant Regulatory Authority.
The wall wetting system may be designed in accordance with the following options:
a) As part of an installed AS 2118.1 automatic fire sprinkler system;
b) As part of the installed fire hydrant system;
c) With a dedicated pipe reticulation system incorporating a separate tapping;
d) Utilising a combined domestic and wall wetting tapping.
The water supply requirements for each system configuration is detailed within Section 7.
6.2 General
Section 6.2 applies to all wall wetting systems. The provisions contained herein are designed on the
basis of linear flooding rates which allow for water run down on the vertical surface of the wall.
Where the height of the inferior wall exceeds one (1) storey, sprinkler heads are required to be
located at every storey.
6.2.1 Sprinkler heads shall be positioned not greater than 300 mm from the wall requiring
protection. The wall wetting system shall be designed to achieve the following discharge rates:
a) 5 l/min per lineal metre of wall for an internal wall wetting system where an automatic fire
sprinkler system in accordance with AS 2118.1 is installed throughout the building; or
b) 10 l/min per lineal metre where the building is not protected by an AS 2118.1 sprinkler system,
or where the wall wetting sprinklers are located externally.
6.2.2 Two (2) types of sprinkler heads are permitted:
a) Conventional pendant sprinkler heads, where it shall be assumed that 45% of the sprinkler
discharge is directed at the wall. The sprinkler heads shall be positioned 2 m to 3 m apart.
b) Pendant sidewall sprinkler heads, where it shall be assumed that 90% of the sprinkler
discharge is directed at the wall. The sidewall sprinkler heads shall be positioned 2 m to 4 m
apart.
Sprinkler heads shall be nominal 15 mm orifice and shall be mounted such that the deflector is level
or a maximum of 100 mm below the top of the wall or glazing.
4
GL-010
2. The minimum capability of the water supply must allow for the simultaneous operation of
the wall wetting system as determined in the relevant section of this document and the
hydrant demand required in accordance with AS 2419.1.
5
GL-010
8. Approval Requirements
Building approval via the modification or dispensation process is necessary for the use of wall
wetting systems in lieu of walls with the required fire resistance level. The following details shall be
submitted for the approval of the relevant Regulatory Authority prior to installation:
6
GL-010
9. BIBLIOGRAPHY
The use of conventional pendant pattern sprinkler heads as wall wetting sprinklers;
J.F. Kennedy, M.P. Delany
The effect of water flow rate on the protection of fire rated window assemblies;
G.D. Lougheed, A.K. Kim, G.P. Crampton
The effects of sprinkler location and activation time on the protection of glazing systems;
A.K. Kim, B.C. Taber