ASpectrum Designs Plus Engineering Services Project Title: Proposed Two Store Residential Building
Address: 8487 Sandoval Avenue, Pinagbuhatan, Pasig City 1602 Project Location: Villa Cuana Phase 1, Pinagbuhata, Pasig City 1602
Contact: 09982028893 Structural Engineer: Engr. Andro S Rebuyas, RCE, ME-1, RMP, M.Eng-SE
Gmail add: asrebuyas.wvc@gmail.com Membership: M.PICE, M.ASCE, M.PAMEA, M.FPEA, M.PSUMP, M.NAMPAP, M.SEAD
DATA INPUT
Profile= W4x13 Beam A36 Beams Framing Angles thickness = 0.75 inch/inches
tw= 7.112 mm A36 Framing Angles Shear Force Demand = 242.11 kN
D= 105.664 Ø Bolt= 0.75 inch = 20mm
n bolts= 4 PCS
Fastener Length of Weld= 240 mm
m
ex= 2.25 inches (eccentricity)
f= 0.75 (reduction factor)
Beams
(Y.S.) Fy= 36 (T.S.) Fu= 58 max t= All Fnv = 60 ksi
SPECIFICATIONS
1 A325 bolts, threads are not exluded from shear plane Fy Fu Max t
2 A325 bolts, threads are exluded from shear plane 1 A36 36 60 <8
3 A490 bolts, threads are not exluded from shear plane 2 A53 Grade B 35 60 All
4 A490 bolts, threads are exluded from shear plane 3 A242 50 70 3/4
4 A510 36 58 All
5 A514 100 110 2.5
1 Single Shear Cell Link: 3 6 A570 Grade 4040 55 All
2 Double Shear 7 A570 Grade 4545 60 All
Cell Link: 2 8 A570 Grade 5050 65 All
9 A572 Grade 4242 60 6
Fnt Fnv 3 angles beams 10 A572 Grade 5050 65 4
1 90 48 3 5 4 11 A572 Grade 6060 75 1.25
2 90 60 3 12 A572 Grade 6565 80 1.25
3 113 60 3 13 A992 50 65 All
4 113 75 5.5
DESIGN STRENGTH fRn PER BOLT FOR THE CONNECTION TO THE WEB OF THE BEAM / GIRDER
(a) Design strengths fRn per bolt for the connection to the web of the Beam/Girder,
the design strength in double shear (m=2)
fRn = fFnvmAb
fRn = 39.761 kips/bolt or 176.86 kN/bolt
Nominal Strength in bearing on the tw of web, for bolt spacing exceeds 3db
fRn = f2.4dtFu
fRn = 21.924 kips/bolt or 97.52281 kN/bolt
Pu (TOTAL CONNECTION FACTORED LOAD Pu CAPACITY BASED ON THE WEB CONNECTION TO THE BEAM)
(b) Pu (Total connection factored load Pu capacity based on the web connection to the beam)
Pu = nfRn Maximum
Pu = 87.70 kips or 390.0912 kN Maximum
(c) Design strength fRn per bolt for the connection to the flange of the column. The design strength
in single shear (m=1) is
TOTAL CONNECTION FACTTORED LOAD Pu CAPACITY ON THE CONNECTION TO THE FLANGE / END PLATE.
(d) Total connection factored Load Pu capacity based on the connection to the flange/End Plate.
Neglecting Eccentricity.
IF THE COMBINED SHEAR AND CONNECTION IS CONSIDERED, AND THE ELASTIC VECTOR METHOD IS USED
(e) If the combined shear & tension effect is considered, and the elastic vector method is used, the
factored Tension Tu at the most heavily loaded bolt
Tu= Mc/I x A
Tu= Puec/I x A
Tu= 0.075 Pu
Using AISC-Formulas (J3-2) and (J3-3a), nominal Load F'nt in tension permitted in the presence of shear
2 E60 70
E70
E80
E90
Fv=0.27xFt
Fv= 130.41 MPa
t= 7.07 mm
fy= 71.34 MPa
fx= 81.54 MPa
fv= 108.35 MPa
L
CAPACITY SUMMARY
1.1)Vcap= 390.09 kN
1.2)D/C Ratio= 0.621 Adequate!
2.1)Vcap= 556.75 kN
2.2)D/C Ratio= 0.43 Adequate!
7.) Weld:
7.1)Weld Capacity= 130.41 MPa
7.2)D/C Ratio= 0.831 Adequate!
This Spreadsheets is licensed only to Engr. Andro S. Rebuyas, RCE, ME-1, RMP, M.Eng-SE