You are on page 1of 2

Energy Division

BCAC
Bushing Connection Animal Cover

Our hot-stickable insulating cover is Fast and Versatile Installation The cover incorporates a gripper attach-
designed to prevent animal caused out- The BCAC cover uses a scissor action ment that can be locked in two ­different
ages on pole-top transformer equipment design to allow for live installations on locations on the cover. This ­allows for
ranging from 15 to 35 kV. bushing skirts ranging in size from installations from a pole or from a bucket.
1.7" (43mm) through 2.7" (68mm) in
Reliable Outage Protection core diameter and 3.0" (75mm) through A step latching mechanism is incorporated
Tyco Electronics’ Raychem insulating 4.75" (120mm) in shed diameter. for a more craft friendly installation.
­covers have been successfully eliminating
outages from all types of animals for The scissor action translates the force High Performance Material
years. This cover has been designed to on contact with the bushing core to a Superior high-voltage outdoor materials are
­provide the same great protection with ­rotating action that closes the cover used in the BCAC cover design. The rugged,
enhanced features. around the bushing. non-tracking, UV-resistant polymer ensures
long-term performance even in the most
extreme environmental conditions.
Product Performance

Product Test Requirement


AC Wet Withstand 20 kV minimum
Wind Tunnel (70 MPH for 10 minutes) No dislodging of BCAC
from bushing

Key Material Properties Test Method Requirement


Physical
Tensile Strength ASTM D638 17 Mpa minimum (2450 psi min.)
Ultimate Elongation ASTM D638 25% minimum

Electrical
Tracking and Erosion Resistance ASTM D2303 No tracking or erosion to top
surface or flame failure after:
Step Voltage Method 1hr.@ 2.5 kV, 2.75 kV, 3.00 kV
(initiate@ 2.5 kV) 20 min.@ 3.25 kV

Product Selection

Product Type Standard Pack Insulator Core Range Insulator Shed Range Cover Size
BCAC-G-5D/8 (B12) 12 1.7"–2.7" (43mm–68mm) 3.00"–4.75" (75mm–120mm) 5" (125mm) dia, 8" (200mm) ht

Technical Report
EDR-5339—Bushing Connection Animal Cover (BCAC 5D/8) Mechanical/Electrical Evaluation
UVR 8209—Material Test Report

Hot-Stick Installation

Tyco Electronics Corporation All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding
8000 Purfoy Road and is to the best of our knowledge and belief correct and reliable. Users, however, should independently evaluate the
Fuquay Varina, NC 27526-9349 suitability of each product for the desired application. Under no circumstances does this constitute an assurance of
Tel: 800.327.6996 any particular quality or performance. Such an assurance is only provided in the context of our product specifications
Fax: 800.527.8350 or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions
E-mail: naenergy@tycoelectronics.com of sale. Raychem,TE logo, and Tyco Electronics are trademarks.
http://energy.tycoelectronics.com/raysulate
www.tycoelectronics.com Energy Division – a pioneer in the development of economical solutions for the electrical power industry. Our
Copyright 2005, 2007, 2009 product range includes: Cable accessories, connectors & fittings, electrical equipment, instruments, lighting
Tyco Electronics Corporation. All rights reserved. controls, insulators & insulation enhancement and surge arresters.
1309020 E155 03/09