Manufacturer PFISTERER
Catalogue name CONNEX Surge Arrester Earthing cable not in scope of delivery
Size 2 Cross section min. 16 mm2
Type designation plug-in dry type MO separable arrester Material of earthing cable copper
Art.-No. 827 52X XXX Material of cable lug tinned copper
Applicable standard IEC 60099-4, EN 50180/50181
Dimension of the surge arrester
Environment Conditions Installation position any position
Working place indoor; outdoor; offshore Total length 490 -635 mm
Altitude above sea level up to 5000 m Length outside GIS/ transformer 350 -500 mm
Environment temperature -25 .. +40°C Diameter 66 -98 mm
Weight 3.5 –4.4 kg
Electrical characteristics
Rated frequency 16.7; 50; 60 Hz Packing
Line discharge class 1 Type cardboard box
Energy absorption capability 2 kJ/kVUr Installation instruction for each kit 1 piece
Gross weight 1pc 3.7 -6.3 kg
Current Dimensions 1pc / 1case 720x 125x 180 mm
Nominal discharge current (8/20µs) 10 kA
Rated short circuit current 16 kA Installation
High current impulse (4/10µs) 65 kA Site condition protected against rain and dust
Long duration current impulse (2800µs) 250 A Installation work by experienced fitters
Installation temperature range 0 .. +50°C
Electrical test levels of type test (IEC 60099-4 and internal
standard) Storage
Rated short circuit current (0.2s) 16 kA Guaranteed period after shipment 1 year
Reduced short circuit current (0.2s) 6 kA Storage time 40 years
Reduced short circuit current (0.2s) 3 kA Limitation for assembly set 2 years
Low short circuit current (1s) 600 A Expected service life after installation 30 years
Storage temperature range -5 .. +50°C
Insulation withstand tests on the arrester housing (IEC Storage conditions not outside; dry place
60099-4) Relative humidity max. 60 %, non-condensing
Lightning impulse voltage (1.2/50 µs) 175 kV
Power-frequency voltage 50 Hz (1 min) 70 kV
5 06/2021 20211169
Version-No. Date Change-No.
All information subject to change without prior notice
Power frequency voltage versus time characteristic (TOV) (initial temperature +60°C)
1,20
1,10 1.075
1.0
U/Ur [kV]
1,00
0.925
0,90 continuous operating voltage Uc
0,85
0,80
0,70
0,1 1 10 100 1000 10000
t [s]
5 06/2021 20211169
Version-No. Date Change-No.
All information subject to change without prior notice
Strom Montage
Nenn-Ableitstoßstrom (8/20µs) 10 kA Montagebedingungen Feuchtigkeits- und Staubgeschützt
Bemessungs-Kurzschlussstrom 16 kA Montage durch erfahrenes Fachpersonal
Hochstromimpulse (4/10µs) 65 kA Montagetemperatur 0 .. +50°C
Langzeit Stromimpulse (2800µs) 250 A
Lagerung und Garantie
Elektrische Typprüfwerte (IEC 60099-4 und interner Garantie nach Auslieferung 1 Jahr
Standard) Lagerfähigkeit 40 Jahre
Bemessungs-Kurzschlussstrom (0.2s) 16 kA Limitierung für Montageset 2 Jahre
Verminderter Kurzschlussstrom (0.2s) 6 kA zu erwartende Lebensdauer 30 Jahre
Verminderter Kurzschlussstrom (0.2s) 3 kA Lagertemperatur -5 .. +50°C
Niedriger Kurzschlussstrom (1s) 600 A Lagerbedingungen Innenraum, trocken
Luftfeuchtigkeit max. 60 %, nicht kondensierend
Spannungsfestigkeit der Isolationsstrecke (IEC 60099-4)
Blitzstoßspannung (1.2/50 µs) 175 kV
Wechselspannung 50 Hz (1 min) 70 kV
5 06/2021 20211169
Version-No. Date Change-No.
All information subject to change without prior notice
1,10 1.075
1.0
U/Ur [kV]
1,00
0.925
0,90 Dauerspannung Uc
0,85
0,80
0,70
0,1 1 10 100 1000 10000
t [s]
5 06/2021 20211169
Version-No. Date Change-No.
All information subject to change without prior notice