INSTANTANEOUS ULTRAFAST TRIP

RXR4 RELAY

4 CO CONTACTS INSTANTANEOUS
ULTRA FAST TRIP RELAY

APPLICATIONS MAIN FEATURES


> Ultra fast tripping functions > Designed to allow continuous operation even in
> Galvanic isolation between the control system high temperature ambient, within the whole
and the primary equipment. voltage range..
> Applications where the request is ultrafast > Self-cleaning contacts.
actuation.. > High level of electrical insulation between
> Direct operation on MV/HV primary equipment. circuits.
> Contact multiplication in control systems with > Capable to operate under low duty loads,
minimum delay activate digital inputs, and operate without any
> Low duty loads control, very low delay digital load.
input activation > Very high speed operation
> Digital integration of primary equipment > Sturdy design.
> Includes an internal diode to avoid damaging the
relay when connecting with inverse polarity.
> High protection degree (IP40), with transparent
cover, making them suitable for use in salty and
tropical atmospheres.
> Several auxiliary voltage levels.
> Versatile installation (plug-in relays in a wide
Substations, Power plants and range of sockets with different installation
Industry configurations).

> Critical process surveyance


> Command and Control
> Alarm signaling and multiplication
> Low duty loads.

1 www.arteche.com LATCHING RELAYS


V1.0
TECHNICAL SPECIFICATIONS

Construction Characteristics
Applications Ultrafast instantaneous trip relay
Contacts 4 Changeover contacts

Connections

Weight (g) 126 gr


Dimensions (mm) 53 x 90 x 58 mm.

Electrical Characteristics
Standard voltages 110, 125, 250 Vdc
Voltage range +10% -20% Un
Coil characteristics
Pick-up / release voltage See pick-up/release voltage-temperature curves
Average consumptions <4W
Operating times Pick-up time <3ms
Contact material AgNi
Contacts resistance ≤ 20 mΩ
Contacts Continuous current capacity 8A
Short-time current capacity 15 A 4s
Umax opened contact 250 Vdc / 400 Vac
Dielectric strength
independent 2 kV. 50Hz. 1 min
circuits
Dielectric strength open
1,0 kV. 50Hz. 1 min
contacts
Impulse voltage
independent 5 kV. 0,5 J. 1,2/50 µs
circuits
Impulse voltage 1 vs 2 and
2,5 kV. 0,5 J. 1,2/50 µs
3 vs 4 contact
Impulse voltage
independent 2,0 kV. 0,5 J. 1,2/50 µs
circuits
Insulation resistance 500 Vdc.; > 100MW

2 www.arteche.com LATCHING RELAYS


V1.0
Endurance Characteristics
Mechanical endurance 1*107 operations

Other Standard Compliances


High frequency 1MHz burst Common mode: 2,5kV 1MHz and 100 kHz
EN 60255-22-1
disturbance test Differential mode: 1kV, 1MHz and 100 kHz
Common mode: 4 kV, 5kHz, 1min
Electrical Fast transient EN 61000-4-4
Differential mode: 2 kV, 5kHz, 1min
Emc Immunity.
Common mode: 2kV 1,2/50µs. (voltage) | 8/20µs. (current)
Surge EN 61000-4-5
Differential mode: 1kV 1,2/50µs. (voltage) | 8/20µs. (current)
Magnetic fields at power
EN 61000-4-8 100 A/m 1min. | 1000 A/m 1s.
frequency
Maximum temperature in Maximum ambient T, 8 A through contacts 1 and 3. Time until
EN 61810-1
the relay parts thermal stability
Thermal test
Maximum ambient T, Vmax, 8 A through contacts 1 and 3.
Thermal Endurance EN 61810-7
1.000 hours
Immunity to
Functional Tests capacitive ESI 48-4 EB1: Low burden
discharges

3 www.arteche.com LATCHING RELAYS


V1.0
RELAY DIMENSIONS

SOCKETS AND RETAINING CLIP


This relay is available for DIN rail mounting:

4 www.arteche.com LATCHING RELAYS